- DESIGN-BID-BUILD (DBB), MEDICAL HOMEPORT RENOVATION, B449, NAVSUBBASE NLON, GROTON, CONNECTICUT
- Solicitation number
- N4008518R8715
About this file
Amend0007_-_PPI.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amend_0008.pdf | ||
| Amend0007_18-8715.pdf | ||
| Existing_Air-Handling_Units_Info.pdf | ||
| Amend0006_18-8715.pdf | ||
| Amend0006_-_PPI.pdf | ||
| Amend0005_-_PPI.pdf | ||
| B449-site_visit.pdf | ||
| Amend0005_18-8715.pdf | ||
| Amend0004_-_PPIs.pdf | ||
| Amend0004_-_map.pdf | ||
| Amend0004_18-8715.pdf | ||
| Amend_0003_18-8715.pdf | ||
| Amend0002_18-8715.pdf | ||
| Amend0002_-_sample_ltr.pdf | ||
| Amend0002_-_PPIs.pdf | ||
| Amend_0001_18-8715.pdf | ||
| 180615_Vol_I_Specifications.pdf | ||
| N4008518R8715_RFP.pdf | ||
| Attachments.zip | ZIP file | |
| 180615_Vol_II_Specifications.pdf |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SOLICITATION NO. N4008518R8715
PROJECT TITLE/LOCATION: DBB Medical Homport Reno, NLON, Groton, CT
PRE‐PROPOSAL INQUIRY FORM
Question
No. REFERENCE QUESTION GOVERNMENT RESPONSE Posted on
Amend No.
Page Section Para.
ET 275116 a.Are we to provide a complete, turnkey new
Radio & PA system? If so, is there a approved list of manufactures?
b.If not, what is our scope of work regarding system equipment? Utilizing existing system equipment?
Provide new PA speakers and associated equipment for the renovated areas fed from the existing rack mounted Crown CDi 1000 amplifier as indicated on plans and spec section 27 51 16.
Manufacturer shall meet the requirement of spec section 27 52 24 and shall be compatible with the existing amplifier.
ET 275224 a.Are we to provide a complete, turnkey new
Nurse Call system? If so, is there a approved list of manufactures?
b.If not, what is our scope of work regarding system equipment? Utilizing existing system equipment?
Provide a new, complete nurse call system for the renovated areas as indicated on the floor plans and spec section 27 52 24. Manufacturer shall meet the requirements of spec section 27 52 24.
M‐ 403 Drawing
No.
12770909
Do you have any pictures of the FTR covers?
Also, what are the make and model #’s of the
AHU’s that need new motors, VFD’s, Coils etc.
as indicated on drawing M‐403?
See attachments photos of existing finned‐tube radiation (in Lobby Conference Room) and spreadsheet with manufacturer's model and serial numbers for existing air‐handling units
IF 123570 What is the scope of work with the Healthcare
Casework? If contractor is to provide, please provide the basis of design manufacturer.
Specification section 123570 Healthcare Casework specifically addresses stainless steel countertops and casework included in the construction documents and indicated on the Architectural sheets. Additional healthcare casework not indicated or addressed in the construction documents will be procured and installed by others. Contractor will be required to coordinate final locations of mechanical, plumbing, electrical and telecom hookups associated with these items with the Contracting Officer.
AF601 122413 There is no window elevations or schedule provided to do a take off for window treatments. Please Advise.
Window locations are depicted in the exterior walls of the floor plans shown on sheets AE101A ‐
AE101F. For the purposes of bidding, approximate window heights are listed below. Contractor to verify actual heights in field prior to procuring window treatments.
• 2’‐8” window height in rooms 1314, 1315, 1316, 1317, 1318, 1319, 1320, 1321, 1322, 1324, 1325, 1334, 1343, 1344, 1406, 1408, 1412, 1413, 1414, 1415, 1416
• 8’‐0” window height in rooms 1209, 1210, 1211, 1326, 1328, 1345, 1402, 1409, 1411, 1426
• 2’‐8” window height for half the length and 8’‐0” window height for half the length in room 1407
• 10’‐0” window height in rooms 1300, 1301
• 11’‐6” window height in rooms 1702, 1802
• Window treatments are not required in rooms
1200, 1214, 1305, 1313, 1425, 1700, 1800, ST4‐1