This document contains specifications for a federal contract opportunity to repair HVAC and electrical systems at a building aboard Marine Corps Base Quantico, Virginia. The scope of work includes replacing the existing 300-ton chiller, chilled and condenser water pumps, boiler, and all ten air handling units. It also involves replacing all fan powered and passive VAV boxes, renovating the building automation system, updating controls and sequences of operation, and correcting cooling tower issues. Bid Option 1 provides for a temporary relocatable trailer and associated accommodations for displaced occupants. Bid Option 2 isolates specific occupied areas from construction work to allow continued use. The solicitation number is N4008020R0035 and was issued by the Department of the Navy Naval Facilities Engineering Command.
View the file
Other files for this federal contract opportunity
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MCB Quantico, VA
SECTION 26 00 00
BASIC ELECTRICAL MATERIALS AND METHODS
01/07
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
ASTM INTERNATIONAL(ASTM)
ASTM D 709 (2001; R 2007) Laminated Thermosetting Materials
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.147 Control of Hazardous Energy (Lock Out/Tag Out)
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE Std 100 (2000) The Authoritative Dictionary of IEEE Standards Terms
IEEE C2 (2017; Errata 1-2 2017; INT 1 2017) National Electrical Safety Code
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA C57.12.28 (1999) Pad-Mounted Equipment - Enclosure Integrity (Revision of ANSI C57.12.28-88)
NEMA ICS 6 (1993; R 2016) Industrial Control and Systems: Enclosures
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2;
TIA 17-3) National Electrical Code
1.2 RELATED REQUIREMENTS
This section applies to all sections of Division 26, "Electrical," of this project specification unless specified otherwise in the individual sections.
1.3 DEFINITIONS
a. Unless otherwise specified or indicated, electrical and
SECTION 26 00 00 Page 1 4 Sep 2020
B-3280 Repair HVAC and Electrical Systems electronics terms used in these specifications, and on the drawings, shall be as defined in IEEE Std 100 .
b. The technical sections referred to herein are those specification sections that describe products, installation procedures, and equipment operations and that refer to this section for detailed description of submittal types.
c. The technical paragraphs referred to herein are those paragraphs in PART 2 - PRODUCTS and PART 3 - EXECUTION of the technical sections that describe products, systems, installation procedures, equipment, and test methods.
1.4 ELECTRICAL CHARACTERISTICS
Electrical characteristics for this project shall be 35 kV primary, three phase, three wire, 60 Hz, and 277/480 volts secondary, three phase, four wire.
1.5 SUBMITTALS
Submittals required in the sections which refer to this section shall conform to the requirements of Section 01 33 00, "Submittal Procedures" and to the following addition2al requirements. Submittals shall include the manufacturer's name, trade name, place of manufacture, catalog model or number, nameplate data, size, layout dimensions, capacity, project specification and technical paragraph reference. Submittals shall also include applicable federal, military, industry, and technical society publication references, and years of satisfactory service, and other information necessary to establish contract compliance of each item to be provided. Photographs of existing installations are unacceptable and will be returned without approval.
1.5.1 Manufacturer's Catalog Data
Submittals for each manufactured item shall be current manufacturer's descriptive literature of cataloged products, equipment drawings, diagrams, performance and characteristic curves, and catalog cuts.
Handwritten and typed modifications and other notations not part of the manufacturer's preprinted data will result in the rejection of the submittal. Should manufacturer's data require supplemental information for clarification, the supplemental information shall be submitted as specified for certificates of compliance.
1.5.2 Instructions
Where installation procedures or part of the installation procedures are required to be in accordance with manufacturer's instructions, submit printed copies of those instructions prior to installation. Installation of the item shall not proceed until manufacturer's instructions are received. Failure to submit manufacturer's instructions shall be cause for rejection of the equipment or material.
1.5.3 Certificates
Submit manufacturer's certifications as required for products, materials, finishes, and equipment as specified in the technical sections.
Certificates from material suppliers are not acceptable. Preprinted certifications and copies of previously submitted documents will not be
SECTION 26 00 00 Page 2 acceptable. The manufacturer's certifications shall name the appropriate products, equipment, or materials and the publication specified as controlling the quality of that item. Certification shall not contain statements to imply that the item does not meet requirements specified, such as "as good as"; "achieve the same end use and results as materials formulated in accordance with the referenced publications"; or "equal or exceed the service and performance of the specified material."
Certifications shall simply state that the item conforms to the requirements specified. Certificates shall be printed on the manufacturer's letterhead and shall be signed by the manufacturer's official authorized to sign certificates of compliance.
1.5.3.1 Reference Standard Compliance
Where equipment or materials are specified to conform to industry and technical society reference standards of the organizations such as American National Standards Institute (ANSI), American Society for Testing and Materials (ASTM), National Electrical Manufacturers Association (NEMA), Underwriters Laboratories (UL), and Association of Edison Illuminating Companies (AEIC), submit proof of such compliance. The label or listing by the specified organization will be acceptable evidence of compliance.
1.5.4 Operation and Maintenance Manuals
Comply with the requirements and the technical sections.
1.5.4.1 Operating Instructions
Submit text of posted operating instructions for each system and principal item of equipment as specified in the technical sections.
1.6 QUALITY ASSURANCE
1.6.1 Material and Equipment Qualifications
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship. Products shall have been in satisfactory commercial or industrial use for 2 years prior to bid opening. The 2-year period shall include applications of equipment and materials under similar circumstances and of similar size. The product shall have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period. Where two or more items of the same class of equipment are required, these items shall be products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in the technical section.
1.6.2 Regulatory Requirements
Equipment, materials, installation, and workmanship shall be in accordance with the mandatory and advisory provisions of NFPA 70 .
1.6.3 Alternative Qualifications
Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, SECTION 26 00 00 Page 3 is furnished.
1.6.4 Service Support
The equipment items shall be supported by service organizations which are reasonably convenient to the equipment installation in order to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract.
1.6.5 Manufacturer's Nameplate
Each item of equipment shall have a nameplate bearing the manufacturer's name, address, model number, and serial number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.
1.6.6 Modification of References
In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "shall" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer.
1.6.7 Material and Equipment Manufacturing Date
Products manufactured more than 3 years prior to date of delivery to site shall not be used, unless specified otherwise.
1.7 POSTED OPERATING INSTRUCTIONS
Provide for each system and principal item of equipment as specified in the technical sections for use by operation and maintenance personnel.
The operating instructions shall include the following:
a. Wiring diagrams, control diagrams, and control sequence for each principal system and item of equipment.
b. Start up, proper adjustment, operating, lubrication, and shutdown procedures.
c. Safety precautions.
d. The procedure in the event of equipment failure.
e. Other items of instruction as recommended by the manufacturer of each system or item of equipment.
Print or engrave operating instructions and frame under glass or in approved laminated plastic. Post instructions where directed. For operating instructions exposed to the weather, provide weather-resistant materials or weatherproof enclosures. Operating instructions shall not fade when exposed to sunlight and shall be secured to prevent easy removal or peeling.
1.8 NAMEPLATES
ASTM D 709 . Provide laminated plastic nameplates for each panelboard, equipment enclosure, relay, switch, and device; as specified in the
SECTION 26 00 00 Page 4 technical sections or as indicated on the drawings. Each nameplate inscription shall identify the function and, when applicable, the position. Nameplates shall be melamine plastic, 0.125 inch thick, black with white center core. Surface shall be matte finish. Corners shall be square. Accurately align lettering and engrave into the core. Minimum size of nameplates shall be one by 2.5 inches. Lettering shall be a minimum of 0.25 inch high normal block style.
1.9 WARNING SIGNS
Provide warning signs for the enclosures of electrical equipment including substations, pad-mounted transformers, pad-mounted switches, generators, and switchgear having a nominal rating exceeding 600 volts.
a. When the enclosure integrity of such equipment is specified to be in accordance with NEMA C57.12.28 , such as for pad-mounted transformers and pad-mounted SF6 switches, provide self-adhesive warning signs on the outside of the high voltage compartment door(s). Sign shall be a decal and shall have nominal dimensions of 7 by 10 inches with the legend "DANGER HIGH VOLTAGE" printed in two lines of nominal 2 inch high letters. The word "DANGER" shall be in white letters on a red background and the words "HIGH VOLTAGE" shall be in black letters on a white background. Decal shall be Panduit No. PPSO710D72 or approved equal.
b. When such equipment is guarded by a fence, mount signs on the fence. Provide metal signs having nominal dimensions of 14 by 10 inches with the legend "DANGER HIGH VOLTAGE KEEP OUT" printed in three lines of nominal 3 inch high white letters on a red and black field.
1.10 CABLE TAGS IN MANHOLES, HANDHOLES, AND VAULTS
Provide tags for each cable or wire located in manholes, handholes, and vaults. Tag new wire and cable provided under this contract and existing wire and cable which are indicated to have splices and terminations provided by this contract. The first position on the tag shall denote the voltage. The second through sixth positions on the tag shall identify the circuit. The next to last position shall denote the phase of the circuit and shall include the Greek "phi" symbol. The last position shall denote the cable size. The tags shall be polyethylene. Do not provide handwritten letters. As an example, a tag could have the following designation: "11.5 NAS 1-8(Phase A)500," denoting that the tagged cable is on the 11.5kV system circuit number NAS 1-8, underground, Phase A, sized at 500 kcmil.
1.10.1 Polyethylene Cable Tags
Provide tags of polyethylene that have an average tensile strength of 3250 pounds per square inch; and that are 0.08 inch thick (minimum), non-corrosive non-conductive; resistive to acids, alkalis, organic solvents, and salt water; and distortion resistant to 170 degrees F.
Provide 0.05 inch (minimum) thick black polyethylene tag holder. Provide a one-piece nylon, self-locking tie at each end of the cable tag. Ties shall have a minimum loop tensile strength of 175 pounds. The cable tags shall have black block letters, numbers, and symbols one inch high on a yellow background. Letters, numbers, and symbols shall not fall off or change positions regardless of the cable tags' orientation.
SECTION 26 00 00 Page 5
1.11 ELECTRICAL REQUIREMENTS
Electrical installations shall conform to IEEE C2 , NFPA 70 , and requirements specified herein.
1.11.1 Motors and Equipment
Provide electrical components of mechanical equipment, such as motors, motor starters, control or push-button stations, float or pressure switches, solenoid valves, and other devices functioning to control mechanical equipment, including control wiring and conduit for circuits rated 100 volts or less, to conform with the requirements of the section covering the mechanical equipment. Extended voltage range motors shall not be permitted. The interconnecting power wiring and conduit, control wiring rated 120 volts (nominal) and conduit, and the electrical power circuits shall be provided under Division 26.
Provide motors, controllers, integral disconnects, and contactors with their respective pieces of equipment . Extended voltage range motors shall not be permitted. Control voltage for controllers and contactors shall not exceed 120 volts nominal. When motors and equipment furnished are larger than sizes indicated, the cost of additional electrical service and related work shall be included under the section that specified that motor or equipment. Where fuse protection is specifically recommended by the equipment manufacturer, provide fused switches in lieu of non-fused switches indicated.
1.11.2 Wiring and Conduit
Provide internal wiring for components of packaged equipment as an integral part of the equipment. Control wiring and conduit shall be provided under, and conform to the requirements of the section specifying the associated equipment.
1.11.3 New Work
Provide electrical components of mechanical equipment, such as motors, motor starters , control or push-button stations, float or pressure switches, solenoid valves, integral disconnects, and other devices functioning to control mechanical equipment, as well as control wiring and conduit for circuits rated 100 volts or less, to conform with the requirements of the section covering the mechanical equipment. Extended voltage range motors shall not be permitted. The interconnecting power wiring and conduit, control wiring rated 120 volts (nominal) and conduit, the motor control equipment forming a part of motor control centers, and the electrical power circuits shall be provided under Division 26, except internal wiring for components of packaged equipment shall be provided as an integral part of the equipment. When motors and equipment furnished are larger than sizes indicated, provide any required changes to the electrical service as may be necessary and related work as a part of the work for the section specifying that motor or equipment.
1.11.4 Modifications to Existing Systems
Where existing mechanical systems and motor-operated equipment require modifications, provide electrical components under Division 26.
SECTION 26 00 00 Page 6
1.11.5 Three-Phase Motor Protection
Provide controllers for motors rated 1-hp and above with electronic phase-voltage monitors designed to protect motors from phase-loss, undervoltage, and overvoltage. Provide protection for motors from immediate restart by a time adjustable restart relay.
1.12 LOCKOUT REQUIREMENTS
Provide disconnecting means capable of being locked out for machines and other equipment to prevent unexpected startup or release of stored energy in accordance with 29 CFR 1910.147 . Mechanical isolation of machines and other equipment shall be in accordance with requirements of Division 23, "Mechanical."
1.13 EQUIPMENT INVENTORY UPDATE
Submit information for each piece of equipment removed and supplied for use to update the Maximo equipment inventory. For the purposes of this paragraph, inventoried equipment is defined as equipment listed on the Maximo Equipment Inventory Update form.
1.13.1 Requirements
The contractor shall prepare and submit one Maximo Equipment Inventory Update form for each individual item of inventoried equipment that is demolished, removed, replaced, or installed. (ex: three new condensing units would require the submission of three Equipment Inventory Update forms. The replacement of two existing air handling units with two new air handling units would require the submission of two Equipment Inventory Update forms). The contractor shall prepare and submit a VAV/TAB Room Number List for each VAV/Tab model installed in a single building. Only one Maximo Equipment Inventory Update form is required for each model of VAV or TAB in a single building.
1.13.1.1 Demolition of all equipment in a structure or facility
When all the inventoried equipment in a building or structure is demolished or removed, and not replaced, an Equipment Inventory Update form is not required.
1.13.1.2 Standards
The contractor shall provide accurate, complete, and legible information on all required forms. All required forms shall be completed and delivered to the Contracting Officer on or before the Beneficial Occupancy Date.
All information on Equipment Inventory Update forms shall be obtained by visual inspection of equipment data plate(s).
1.13.1.3 Form Preparation
Each required Maximo Equipment Inventory Update form shall contain the following information:
(1) The name and telephone number of an individual who can be contacted for clarification or additional information pertaining to the data on the form.
(2) The date of data collection
SECTION 26 00 00 Page 7
(3) The building or structure identification number and the specific location of the equipment within the structure (ex: 3d deck mech room)
(4) A check adjacent to the description of the new or replacement item, and a check adjacent to the supplemental description if applicable (ex: circulating pump and HVAC or steam)
(5) The Maximo number or serial number of the demolished or removed item, if applicable
(6) All applicable data from the equipment data plate
Each Room Number List form shall contain the following information:
(1) The name and telephone number of the individual providing the information
(2) The date the form was completed
(3) The building or structure identification number
(4) A check in the box adjacent to each applicable room number
PART 2 PRODUCTS
Not used.
PART 3 EXECUTION
3.1 PAINTING OF EQUIPMENT
3.1.1 Factory Applied
Electrical equipment shall have factory-applied painting systems which shall, as a minimum, meet the requirements of NEMA ICS 6 corrosion-resistance test.
3.1.2 Field Applied
Paint electrical equipment as required to match finish of adjacent surfaces or to meet the indicated or specified safety criteria.
3.2 NAMEPLATE MOUNTING
Provide number, location, and letter designation of nameplates as indicated. Fasten nameplates to the device with a minimum of two sheet-metal screws or two rivets.
3.3 WARNING SIGN MOUNTING
Provide the number of signs required to be readable from each accessible side, but space the signs a maximum of 30 feet apart.
3.4 CABLE TAG INSTALLATION
MAXIMO EQUIPMENT INVENTORY UPDATE
Employee: __________________ Phone: ____________ Date: ____/____/____
SECTION 26 00 00 Page 8
MAXIMO EQUIPMENT INVENTORY UPDATE
Bldg: ____________ Specific Location: ________________________________
__ AC, Computer Room __ Heat Pump, Indoor Unit __ AC, Package __ Heat Pump, Outdoor Unit __ AC, Package Terminal __ Heat Pump, Package __ Assembly, Trap line __ Heat Pump, Package Terminal __ Backflow Preventer __ Pump, Circulating, Chilled Water __ Boiler __ Pump, Circulating, Domestic Water __ Chiller, Air Cooled Recip __ Pump, Circulating, Dual Temp Water __ Chiller, Air Cooled Screw __ Pump, Circulating, Heating Water __ Chiller, Air Cooled Scroll __ Pump, Condensate __ Chiller, Water Cooled Recip __ Pump, Sump __ Chiller, Water Cooled Screw __ Regulator, Temperature __ Compressor, Control Air __ Tank, Hot Water Storage __ Compressor, Industrial Air __ Tower, Cooling __ Dryer, Refrigerated Air __ Unit, Air Handling __ Exchanger, Heat __ Unit, AC Condensing __ Evaporator, Freezer __ Unit, Freezer Condensing __ Evaporator, Refrigerator __ Unit, Refrigerator Condensing __ Fan, Exhaust __ Unit, Fan Coil __ Generator __ Unit, TAB (Attach Room No. List) __ Heater, Space __ Unit, VAV (Attach Room No. List) __ Heater, Unit __ Valve, Pressure Reducing __ Heat Pump, Geo-Thermal __ Valve, Steam Pilot __ Water Heater
Demol i shed/ Removed Equi pment
Maximo no: __________ or Ser no: ___________________________________
New Equi pment
Manufacturer: _____________________________________________________
Model no: ________________________________________________________
Ser no: __________________________________________________________
Type: __Elec __Oil __LP Gas __Nat Gas __Steam __Water __Air
Motor Data: HP____ Volts____ Phase____ RLA_____ RPM____ Frame____
Tons____ No. of Motors____ no. of Belts____ Belt size(s)____ CFM____
KW____ Refrig type______ Refrig Qty_________ Filter Size(s)____________
SECTION 26 00 00 Page 9
-- End of Section --