This solicitation is for repair work to the HVAC and electrical systems at Building 3280 aboard Marine Corps Base Quantico in Virginia. The scope of work includes replacing the 300-ton chiller with a 200-ton unit and reconfiguring to a primary/secondary pumping system. Other requirements are replacing chilled water and condenser water pumps, the boiler, all ten air handling units, VAV boxes, and completing renovation of the building automation system and controls. The bid also contains two optional scopes - providing a temporary trailer for displaced occupants, and completing work in occupied areas at night and on weekends with dust control and temporary partitions. The soliciting agency is the Naval Facilities Engineering Command.
View the file
Other files for this federal contract opportunity
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
B-3280 Repair HVAC and Electrical Systems MCB Quantico, VA
SECTION 26 29 23
ADJUSTABLE SPEED DRIVE (ASD) SYSTEMS UNDER 600 VOLTS
02/20
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 519 (2014) Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems
IEEE C62.41.1 (2002; R 2008) Guide on the Surges Environment in Low-Voltage (1000 V and Less) AC Power Circuits
IEEE C62.41.2 (2002) Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and Less) AC Power Circuits
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA 250 (2018) Enclosures for Electrical Equipment (1000 Volts Maximum)
NEMA ICS 1 (2000; R 2015) Standard for Industrial Control and Systems: General Requirements
NEMA ICS 3.1 (2019) Guide for the Application, Handling, Storage, Installation and Maintenance of Medium-Voltage AC Contactors, Controllers and Control Centers
NEMA ICS 6 (1993; R 2016) Industrial Control and Systems: Enclosures
NEMA ICS 7 (2014) Adjustable-Speed Drives
NEMA ICS 7.2 (2015) Application Guide for AC Adjustable Speed Drive Systems
NEMA MG 1 (2018) Motors and Generators
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2020; ERTA 20-1 2020; ERTA 20-2 2020; TIA
20-1; TIA 20-2; TIA 20-3; TIA 20-4)
National Electrical Code
SECTION 26 29 23 Page 1
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
47 CFR 15 Radio Frequency Devices
UNDERWRITERS LABORATORIES (UL)
UL 489 (2016) UL Standard for Safety Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures
UL 508C (2002; Reprint Nov 2010) Power Conversion Equipment
1.2 RELATED REQUIREMENTS
Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM and 26 00 00 BASIC ELECTRICAL MATERIALS AND METHODS applies to this section with additions and modifications specified herein.
1.3 SYSTEM DESCRIPTION
1.3.1 Performance Requirements
1.3.1.1 Electromagnetic Interference Suppression
Computing devices, as defined by 47 CFR 15 and mil-std-461 rules and regulations, must be certified to comply with the requirements for class A computing devices and labeled.
1.3.1.2 Electromechanical and Electrical Components
Ensure electrical and electromechanical components of the Adjustable Speed Drive (ASD) do not cause electromagnetic interference to adjacent electrical or electromechanical equipment while in operation.
1.3.2 Electrical Requirements
1.3.2.1 Power Line Surge Protection
IEEE C62.41.1 and IEEE C62.41.2 , IEEE 519 Control panel must have surge protection, included within the panel to protect the unit from damaging transient voltage surges. Surge protective device must be mounted near the incoming power source and properly wired to all three phases and ground. Fuses must not be used for surge protection.
1.3.2.2 Sensor and Control Wiring Surge Protection
I/O functions as specified must be protected against surges induced on control and sensor wiring installed outdoors and as shown. Test the inputs and outputs in both normal mode and common mode using the following two waveforms:
a. A 10 microsecond by 1000 microsecond waveform with a peak voltage of 1500 volts and a peak current of 60 amperes.
b. An 8 microsecond by 20 microsecond waveform with a peak voltage of 1000 volts and a peak current of 500 amperes.
SECTION 26 29 23 Page 2
1.4 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval.. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Schematic Diagrams; G
Interconnecting Diagrams; G
Installation Drawings; G
Submit drawings for government approval prior to equipment construction or integration. Modifications to original drawings made during installation shall be immediately recorded for inclusion into the as-built drawings.
SD-03 Product Data
Adjustable Speed Drives; G
Wires and Cables
Equipment Schedule
SD-06 Test Reports
ASD Test
Performance Verification Tests
Endurance Test
] SD-08 Manufacturer's Instructions
Installation instructions
SD-09 Manufacturer's Field Reports
ASD Test Plan; G
Factory Test Results
SD-10 Operation and Maintenance Data
Adjustable Speed Drives, Data Package 4
Submit in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA. Provide service and maintenance information including preventive maintenance, assembly, and disassembly procedures. Include electrical drawings from electrical general
SECTION 26 29 23 Page 3 sections. Submit additional information necessary to provide complete operation, repair, and maintenance information, detailed to the smallest replaceable unit. Include copies of as-built submittals. Provide routine preventative maintenance instructions, and equipment required. Provide instructions on how to modify program settings, and modify the control program.
Provide instructions on drive adjustment, trouble-shooting, and configuration. Provide instructions on process tuning and system calibration.
1.5 QUALITY ASSURANCE
1.5.1 Schematic Diagrams
Submit diagrams showing circuits and device elements for each replaceable module. Schematic diagrams of printed circuit boards are permitted to group functional assemblies as devices, provided that sufficient information is provided for government maintenance personnel to verify proper operation of the functional assemblies.
1.5.2 Interconnecting Diagrams
Show interconnections between equipment assemblies, and external interfaces, including power and signal conductors. Include for enclosures and external devices.
1.5.3 Installation Drawings
Show floor plan of each site, with ASD's and motors indicated. Indicate ventilation requirements, adequate clearances, and cable routes. Submit drawings for government approval prior to equipment construction or integration. Immediately record modifications to original drawings made during installation for inclusion into the as-built drawings.
1.5.4 Equipment Schedule
Provide schedule of equipment supplied. Schedule must provide a cross reference between manufacturer data and identifiers indicated in shop drawings. Schedule must include the total quantity of each item of equipment supplied and data indicating compatibility with motors being driven. For complete assemblies, such as ASD's, provide the serial numbers of each assembly, and a sub-schedule of components within the assembly. Provide recommended spare parts listing for each assembly or component.
1.5.5 Installation Instructions
Provide installation instructions issued by the manufacturer of the equipment, including notes and recommendations, prior to shipment to the site. Provide operation instructions prior to acceptance testing.
1.5.6 Factory Test Results
Document test results and submit to government within 7 working days after completion of test.
1.5.7 Standard Products
Provide materials and equipment that are products of manufacturers
SECTION 26 29 23 Page 4 regularly engaged in the production of such products which are of equal material, design and workmanship and:
a. Have been in satisfactory commercial or industrial use for 2 years prior to bid opening including applications of equipment and materials under similar circumstances and of similar size.
b. Have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period.
c. Where two or more items of the same class of equipment are required, provide products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.
1.6 DELIVERY AND STORAGE
Store delivered equipment to protect from the weather, humidity and temperature variations, dirt and dust, or other contaminants.
1.7 WARRANTY
The complete system must be warranted by the manufacturer for a period of one year . Repair or replace any component failing to perform its function as specified and documented at no additional cost to the Government. Items repaired or replaced must be warranted for an additional period of at least one year from the date that it becomes functional again, as specified in FAR 52.246-21 Warranty of Construction.
1.8 MAINTENANCE
1.8.1 Spare Parts
Manufacturers provide spare parts in accordance with recommended spare parts list.
1.8.2 Operation and Maintenance Data
Provide in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA. Provide service and maintenance information including preventive maintenance, assembly, and disassembly procedures. Include electrical drawings from electrical general sections. Provide additional information necessary to provide complete operation, repair, and maintenance information, detailed to the smallest replaceable unit. Include copies of as-built submittals. Provide routine preventative maintenance instructions, and equipment required. Provide instructions on how to modify program settings, and modify the control program. Provide instructions on drive adjustment, trouble-shooting, and configuration.
Provide instructions on process tuning and system calibration.
1.8.3 Maintenance Support
During the warranty period, provide on-site, on-call maintenance services by drive manufacturer's personnel on the following basis: The service must be on a per-call basis with 36 hour response. Contractor is responsible for the maintenance of all hardware and software of the system during the warranty period. Various personnel of different expertise must be sent on-site depending on the nature of the maintenance service required. Costs must include travel, local transportation, living
SECTION 26 29 23 Page 5 expenses, and labor rates of the service personnel while responding to the service request. The provisions of this Section are not in lieu of, nor relieve the Contractor of, warranty responsibilities covered in this specification. Should the result of the service request be the uncovering of a system defect covered under the warranty provisions, all costs for the call, including the labor necessary to identify the defect, must be borne by the Contractor.
1.8.4 Technical Support
Provide the ASDs with manufacturer's technical telephone support in English, readily available during normal working hours.
PART 2 PRODUCTS
2.1 ADJUSTABLE SPEED DRIVES (ASD)
Provide adjustable speed drive to control the speed of induction motor(s). The ASD must include the following minimum functions, features and ratings.
a. Input circuit breaker per UL 489 with a minimum of 10,000 amps symmetrical interrupting capacity and door interlocked external operator.
b. A converter stage per UL 508C must change fixed voltage, fixed frequency, ac line power to a fixed dc voltage. The converter must utilize a full wave bridge design incorporating diode rectifiers.
Silicon Controlled Rectifiers (SCR) are not acceptable. The converter must be insensitive to three phase rotation of the ac line and must not cause displacement power factor of less than .95 lagging under any speed and load condition.
c. An inverter stage must change fixed dc voltage to variable frequency, variable ac voltage for application to a standard NEMA MG 1 Part 30 motor designed for use with adjustable frequency power supplies.
Switch the inverter to produce a sine coded pulse width modulated (PWM) output waveform.
d. The ASD shall be capable of supplying 120 percent of rated full load current for one minute at maximum ambient temperature.
e. The ASD must be designed to operate from a 480 volt, plus or minus 10 percent, three phase, 60 Hz supply, and control motors with a corresponding voltage rating.
f. Acceleration and deceleration time must be independently adjustable from one second to 60 seconds.
g. Adjustable full-time current limiting must limit the current to a preset value which must not exceed 110 percent of the controller rated current. The current limiting action must maintain the V/Hz ratio constant so that variable torque can be maintained. Short time starting override must allow starting current to reach 175 percent of controller rated current to maximum starting torque.
h. The controllers must be capable of producing an output frequency over
SECTION 26 29 23 Page 6 the range of 3 Hz to 60 Hz (20 to one speed range), without low speed cogging. Over frequency protection must be included such that a failure in the controller electronic circuitry must not cause frequency to exceed 110 percent of the maximum controller output frequency selected.
i. Minimum and maximum output frequency must be adjustable over the following ranges: 1) Minimum frequency 3 Hz to 50 percent of maximum selected frequency; 2) Maximum frequency 40 Hz to 60 Hz.
j. The controller efficiency at any speed must not be less than 96 percent.
k. The controllers must be capable of being restarted into a motor coasting in the forward direction without tripping.
l. Protection of power semiconductor components must be accomplished without the use of fast acting semiconductor output fuses. Subjecting the controllers to any of the following conditions must not result in component failure or the need for fuse replacement:
(1) Short circuit at controller output
(2) Ground fault at controller output
(3) Open circuit at controller output
(4) Input undervoltage
(5) Input overvoltage
(6) Loss of input phase
(7) AC line switching transients
(8) Instantaneous overload
(9) Sustained overload exceeding 115 percent of controller rated current
(10) Over temperature
(11) Phase reversal
m. Solid state motor overload protection must be included such that current exceeding an adjustable threshold must activate a 60 second timing circuit. Should current remain above the threshold continuously for the timing period, the controller will automatically shut down.
n. Include slip compensation circuit that will sense changing motor load conditions and adjust output frequency to provide speed regulation of NEMA MG 1 Part 30 designed for use with adjustable frequency power supplies motors to within plus or minus 0.5 percent of maximum speed without the necessity of a tachometer generator.
o. The ASD must be factory set for manual restart after the first protective circuit trip for malfunction (overcurrent, undervoltage, overvoltage or overtemperature) or an interruption of power. The ASD
SECTION 26 29 23 Page 7 must be capable of being set for automatic restart after a selected time delay. If the drive faults again within a specified time period (adjustable 0-60 seconds), a manual restart will be required.
p. The ASD must include external fault reset capability. All the necessary logic to accept an external fault reset contact must be included.
q. Provide critical speed lockout circuitry to prevent operating at frequencies with critical harmonics that cause resonant vibrations.
The ASD must have a minimum of three user selectable bandwidths.
r. Provide preperly sized NEMA rated by-pass and isolation contactors to enable operation of motor in the event of ASD failure. Install mechanical and electrical interlocks between the by-pass and isolation contactors. Provide a selector switch and transfer delay timer.
Motor overload and short circuit protective features must remain in use during the bypass mode.
s. Each individual ASD must meet the following Total Harmonic Distortion (THD) requirements at the input terminals to the factory assembly of the ASD or at the load disconnecting means serving the ASD and filter assembly. These measurements should be taken with the drive set at 90 percent frequency (rpms) and the motor under a minimum of 50 percent demand.
(1) The Voltage THD should not exceed 2.0 percent THD.
(2) The Current THD should not exceed 15.0 percent THD.
(3) If the standard factory ASD does not meet or exceed these requirements the factory must install appropriate equipment (Harmonic Traps, Filters, different Drive technology, etc.) to mitigate the distortion to assure performance of the VFD is within the limits.
(4) These tests should be performed at the Manufacturers Laboratory facilities and submitted as part of the Product Data Submittals, in order to prevent the necessity of adding mitigation equipment in the field. If the requirements listed above are met, IEEE 519 will also be met.
t. Minimum Operating Conditions. Designed and constructed ASD's to operate within the following service conditions:
(1) Ambient Temperature Rating: 0 to 120 degrees F.
(2) Non-condensing relative humidity rating: less than 95 percent.
(3) Ambient rating: Not exceed 3,300 feet.
2.1.1 ASD for Industrial Application
Provide the following operator control and monitoring devices mounted on the front panel of the ASD:
a. Manual speed potentiometer.
b. Hand-Off-Auto (HOA) switch.
SECTION 26 29 23 Page 8
c. Power on light.
d. Drive run power light.
e. Local display.
2.2 ENCLOSURES
Provide equipment enclosures conforming to NEMA 250, NEMA ICS 7 , and NEMA ICS 6 , with a heater if located outdoors.
2.3 WIRES AND CABLES
All wires and cables must conform to NEMA 250, NEMA ICS 7 , NFPA 70 .
2.4 NAMEPLATES
Nameplates external to NEMA enclosures must conform with the requirements of Section 26 00 00 BASIC ELECTRICAL MATERIALS AND METHODS. Provide manufacturer's standard, permanent nameplates for internal areas of enclosures.
2.5 SOURCE QUALITY CONTROL
2.5.1 ASD Test Plan
To ensure quality, each ASD must be subject to a series of in-plant quality control inspections before approval for shipment from the manufacturer's facilities. Provide test plans.
2.5.2 ASD Test Report
To ensure quality, each ASD must be subject to a series of in-plant quality control inspections before approval for shipment from the manufacturer's facilities. Provide test reports.
PART 3 EXECUTION
3.1 INSTALLATION
Per NEMA ICS 3.1 , install equipment in accordance with the approved manufacturer's printed installation drawings, instructions, wiring diagrams, and as indicated on project drawings and the approved shop drawings. A field representative of the drive manufacturer must supervise the installation of all equipment, and wiring.
3.2 GROUNDING
Per NEMA ICS 7.2 , ASD must be solidly grounded to the main distribution.
3.3 FIELD QUALITY CONTROL
Specified products must be tested as a system for conformance to specification requirements prior to scheduling the acceptance tests.
Conduct performance verification tests in the presence of Government representative, observing and documenting complete compliance of the system to the specifications. Submit a signed copy of the test results, certifying proper system operation before scheduling tests.
SECTION 26 29 23 Page 9
3.3.1 ASD Test
A proposed test plan must be submitted to the contracting officer at least 28 calendar days prior to proposed testing for approval. The tests must conform to NEMA ICS 1 , NEMA ICS 7 , and all manufacturer's safety regulations. The Government reserves the right to witness all tests and review any documentation. Inform the Government at least 14 working days prior to the dates of testing.
3.3.2 Performance Verification Tests
"Performance Verification Test" plan must provide the step by step procedure required to establish formal verification of the performance of the ASD. Compliance with the specification requirements must be verified by inspections, review of critical data, demonstrations, and tests. The Government reserves the right to witness all tests, review data, and request other such additional inspections and repeat tests as necessary to ensure that the system and provided services conform to the stated requirements. Inform the Government 14 calendar days prior to the date the test is to be conducted.
3.3.3 Endurance Test
Immediately upon completion of the performance verification test, the endurance test must commence. The system must be operated at varying rates for not less than 192 consecutive hours, at an average effectiveness level of 0.9998, to demonstrate proper functioning of the complete PCS.
Continue the test on a day-to-day basis until performance standard is met. The contractor is not allowed in the building during the endurance test. The system must respond as designed.
3.4 DEMONSTRATION
3.4.1 Training
Coordinate training requirements with the Contracting Officer.
3.4.1.1 Instructions to Government Personnel
Provide the services of competent instructors with minimum two-year field experience with the operation and maintenance of similar ASDs who will give full instruction to designated personnel in operation, maintenance, calibration, configuration, and programming of the complete control system. Orient the training specifically to the system installed.
Instructors must be thoroughly familiar with the subject matter they are to teach. The number of training days of instruction furnished must be as specified. A training day is defined as eight hours of instruction, including two 15-minute breaks and excluding lunch time; Monday through Friday. Provide a training manual for each student at each training phase which describes in detail the material included in each training program.
Provide one additional copy for archiving. Provide equipment and materials required for classroom training. Provide a list of additional related courses, and offers, noting any courses recommended. List each training course individually by name, including duration, approximate cost per person, and location of course. Unused copies of training manuals must be turned over to the Government at the end of last training session.
SECTION 26 29 23 Page 10
3.4.1.2 Operating Personnel Training Program
Provide one 2-hour training session at the site at a time and place mutually agreeable between the Contractor and the Government. Provide session to train 4 operation personnel in the functional operations of the system and the procedures that personnel will follow in system operation.
This training shall include:
a. System overview
b. General theory of operation
c. System operation
d. Alarm formats
e. Failure recovery procedures
f. Troubleshooting
3.4.1.3 Engineering/Maintenance Personnel Training
Accomplish the training program as specified. Training must be conducted on site at a location designated by the Government. Provide a one-day training session to train four (4)engineering personnel in the functional operations of the system. This training must include:
a. System overview
b. General theory of operation
c. System operation
d. System configuration
e. Alarm formats
f. Failure recovery procedures
g. Troubleshooting and repair
h. Maintenance and calibration
i. System programming and configuration
-- End of Section --
SECTION 26 29 23 Page 11
| ADJUSTABLE SPEED DRIVE ASD SYSTEMS UNDER 600 VOLTS |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 RELATED REQUIREMENTS |
| 1.3 SYSTEM DESCRIPTION |
| 1.3.1 Performance Requirements |
| 1.3.1.1 Electromagnetic Interference Suppression |
| 1.3.1.2 Electromechanical and Electrical Components |
| 1.3.2 Electrical Requirements |
| 1.3.2.1 Power Line Surge Protection |
| 1.3.2.2 Sensor and Control Wiring Surge Protection |
| 1.4 SUBMITTALS |
| 1.5 QUALITY ASSURANCE |
| 1.5.1 Schematic Diagrams |
| 1.5.2 Interconnecting Diagrams |
| 1.5.3 Installation Drawings |
| 1.5.4 Equipment Schedule |
| 1.5.5 Installation Instructions |
| 1.5.6 Factory Test Results |
| 1.5.7 Standard Products |
| 1.6 DELIVERY AND STORAGE |
| 1.7 WARRANTY |
| 1.8 MAINTENANCE |
| 1.8.1 Spare Parts |
| 1.8.2 Operation and Maintenance Data |
| 1.8.3 Maintenance Support |
| 1.8.4 Technical Support |
| PART 2 PRODUCTS |
| 2.1 ADJUSTABLE SPEED DRIVES ASD |
| 2.1.1 ASD for Industrial Application |
| 2.2 ENCLOSURES |
| 2.3 WIRES AND CABLES |
| 2.4 NAMEPLATES |
| 2.5 SOURCE QUALITY CONTROL |
| 2.5.1 ASD Test Plan |
| 2.5.2 ASD Test Report |
| PART 3 EXECUTION |
| 3.1 INSTALLATION |
| 3.2 GROUNDING |
| 3.3 FIELD QUALITY CONTROL |
| 3.3.1 ASD Test |
| 3.3.2 Performance Verification Tests |
| 3.3.3 Endurance Test |
| 3.4 DEMONSTRATION |
| 3.4.1 Training |
| 3.4.1.1 Instructions to Government Personnel |
| 3.4.1.2 Operating Personnel Training Program |
| 3.4.1.3 Engineering/Maintenance Personnel Training |