This solicitation is for HVAC and electrical system repairs at Building 3280 aboard Marine Corps Base Quantico in Virginia. The scope of work includes replacing the existing 300-ton chiller, chilled and condenser water pumps, boiler, and all ten air handling units. It also involves replacing VAV boxes, renovating the building automation system, updating controls, and correcting cooling tower issues. The base bid requires completing all scope items. Bid Option 1 provides a temporary trailer for displaced occupants. Bid Option 2 isolates occupied areas on respective floors for work during nights and weekends only. The Department of the Navy, Naval Facilities Engineering Command is the agency seeking these repairs by the specified response and award dates.
View the file
Other files for this federal contract opportunity
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATTACHMENT E – SALIENT FEATURES FOR HVAC SYSTEM
BRAND NAME OR EQUAL SUPPLEMENTAL:
See Sheet M-601 Water-cooled Chiller Schedule (CH2)
Chiller: Carrier 30HXC206
Reference Sheet M-601 Water Cooled Chiller Schedule CH-2
Nominal Chiller Size: 206 Tons
Semi-hermetic Twin-screw
No. of Compressors: 3
Nominal capacity (tons) per Compressor: 66/39/80
No. of capacity steps: 8
Overall maximum dimension: 153 inches
AHRI RATINGS
Capacity Tons: 211.7
Input Power: 146.1
Evap flow: 507.5 gpm
Evap Pressure Drop: 14.7 ft H2O
Condenser flow: 647.9 gpm
Condenser Pressure drop: 21.7 ft H2O