LVN B120 HVAC RTA Drawing Set.pdf

PDF 18 MB Posted

Attached to
Building 120 and 127 HVAC Repairs at Fort Leavenworth, KS
Solicitation number
W912DQ20R4019
Issued by

About this file

This document contains details of a federal solicitation for HVAC repairs at two buildings at Fort Leavenworth, Kansas. The U.S. Army Corps of Engineers, Kansas City District is seeking a single design-bid-build firm fixed price construction contract valued between $10-25 million to perform miscellaneous HVAC repairs and replacements at Building 120, including work on multistack units, space end units, and reducing humidity in the library, as well as replacing make-up air units, repairing lobby issues, and replacing heat pumps at Building 127. Interested vendors must be registered in the System for Award Management and submit responses in accordance with the solicitation, which will result in a single award for a 1,095 calendar day period of performance. Small business set-asides are encouraged to pursue teaming arrangements to meet bonding and financial requirements.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

US Army Corps of Engineers ®

KANSAS CITY DISTRICT

FORT LEAVENWORTH, KS

HVAC REPAIRS, BUILDING 120

READY TO ADVERTISE

SOLICITATION NO.: W912DQ-20-R-4019

CONTRACT NO.:

ISSUE DATE: 08-03-2020

G-001

C O

V E

R

S

H E

E T

B B

B L

D P

B L

BLDG 120,

FT LEAVENWORTH, KS 66027

NORTH

Envision. Enhance. Evolve.

715 KIRK DRIVE

KANSAS CITY, MO 64105

P:(816) 472-1201

WWW.HNTB.COM

9926 MANCHESTER ROAD, SUITE 202

ST. LOUIS, MO 63122

P:(314) 755-1920

WWW.ECSSTL.COM

1121 OLIVETTE EXECUTIVE PARKWAY, SUITE 100

OLIVETTE , MO 63132

P:(314) 533-2200

WWW.ETEGRA.COM

DONALD E HILL, PE

320 NW CAPITAL DR

LEE'S SUMMIT, MO 64086

P:(816) 215-3966

WWW.ATSIUSA.COM

239 HIGHLANDS AVENUE

EAST PITTSBURGH, PA 15112

P:(412) 823-0400

WWW.CRAWFORDCS.COM

US Army Corps of Engineers ®

SHEET ID

U S

A

R M

Y

C

O R

P

O

F

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

C T

N

S O

L I C

I T

A T

I O

N

N

O

I S

S U

E D

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

I T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

B

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

L

A V

E N

W O

R T

H

K

S

T A

K

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

W

D Q

R

G-002

H

E E

T

I N

D E

X

B B

X D P

B L

INDEX

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

W

D Q

R

G-003

O

F O

R M

A T

I O

N

B B

A K

G

D P

B L

CODE INFORMATION

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

W

D Q

R

LIST OF APPLICABLE CODES (WHERE MORE THAN ONE CODE IS LISTED, MOST STRINGENT REQUIREMENTS APPLY, EXCEPT

BY AGREEMENT OF THE CODE OFFICIAL. THESE CODES ARE BEING APPLIED TO APPLICABLE UPDATES. GENERAL BUILDING

CODE UPGRADE IS NOT INCLUDED IN THE SCOPE OF THIS PROJECT.):

BUILDING: UFC 1-200-01 DOD BUILDING CODE

INTERNATIONAL BUILDING CODE (2015 AS MODIFIED BY UFC 1-200-01 AND UFC 3-600-01)

INTERNATIONAL EXISTING BUILDING CODE (2015 AS MODIFIED BY UFC 1-200-01 AND UFC

3-600-01)

GENERAL BUILDING

DESCRIPTION: TYPE OF CONSTRUCTION:

TYPE I B, NONCOMBUSTIBLE IBC (602.2)

LIFE SAFETY: NFPA 101 LIFE SAFETY CODE (2018 AS MODIFIED BY UFC 1-200-01)

ACCESSIBILITY: ABA GENERAL BUILDING REQUIREMENTS (20 JUNE 2016)

MECHANICAL: INTERNATIONAL MECHANICAL CODE (2015 AS MODIFIED BY UFC 1-200-01)

NFPA 90A STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATION

SYSTEMS (2018)

PLUMBING: INTERNATIONAL PLUMBING CODE (2015 AS MODIFIED BY UFC 1-200-01)

ELECTRICAL: NFPA 70 NATIONAL ELECTRIC CODE (2017)

GAS : INTERNATIONAL FUEL GAS CODE

FIRE PROTECTION: NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS (2019)

NFPA 70 NATIONAL ELECTRIC CODE (2017)

NFPA 72 THE NATIONAL FIRE ALARM AND SIGNALING CODE (2019)

CONSTRUCTION TYPE: FIRE RESISTIVE RATING REQUIREMENTS FOR BUILDING ELEMENTS:

STRUCTURAL FRAME 2 HOURS IBC (TABLE 601)

EXTERIOR BEARING WALLS 2 HOURS IBC (TABLE 601)

>30FT FROM CENTERLINE OF RIGHT-OF-WAY

EXTERIOR NON BEARING WALLS 1 HOUR IBC (TABLE 601)

>30FT FROM CENTERLINE OF RIGHT-OF-WAY

INTERIOR BEARING WALLS 2 HOURS IBC (TABLE 601)

FLOOR CONSTRUCTION 2 HOURS IBC (TABLE 601)

ROOF CONSTRUCTION 1 HOUR IBC (TABLE 601)

EXTERIOR OPENINGS

UNPROTECTED NO LIMIT IBC (TABLE 705.8)

> 25 FT FIRE SEPARATION DISTANCE

SHAFT ENCLOSURES:

WHEN CONNECTING < 4 STORIES 1 HOUR IBC (713.8)

ENCLOSED ELEVATOR LOBBY NOT REQUIRED.

REQUIRED SEPARATION OF OCCUPANCIES IN MIXED OCCUPANCY BUILDINGS:

ASSEMBLY/BUSINESS 1 HOUR IBC (TABLE 508.4)

EXIT ENCLOSURE:

WHERE STRUCTURE < 4 STORIES 1 HOUR IBC (1023.2), NFPA 101 (7.1.3.2)

CORRIDORS:

GROUP A AND B OCCUPANCY

CORRIDOR CONSTRUCTION: NO RATING REQUIRED/NO SPECIAL REQUIREMENTS

IBC (TABLE 1020.1), NFPA (13.3.6, 39.3.6)

ELEVATORS:

HOISTWAY ENCLOSURE 2 HOUR SEPARATION IBC (TABLE 716.5)

HOISTWAY ENCLOSURE DOOR 1 1/2 HOUR IBC (TABLE 716.5)

MACHINE ROOM 2 HOUR SEPARATION IBC (TABLE 716.5)

OPENINGS 1 1/2 HOUR IBC (TABLE 716.5)

ALLOWABLE BUILDING

HEIGHT AND FLOOR AREA: SPRINKLER SYSTEM:

ENTIRE BUILDING IS PROVIDED WITH A SUPERVISED AUTOMATIC SPRINKLER.

ALLOWABLE HEIGHT: NO CHANGE

ALLOWABLE AREA: NO CHANGE

BUILDING AREA

(OR RENOVATION): NO CHANGE

USE GROUP CLASSIFICATION: NO CHANGE

MIXED USE OCCUPANCY

CLASSIFICATION: GROUP B OCCUPANCY - EDUCATIONAL OCCUPANCIES ABOVE

12TH GRADE IBC (304.1)

GROUP A OCCUPANCY - A-1 AUDITORIUM >1000

PEOPLE WITH STAGE IBC (303.2)

GROUP A OCCUPANCY - A-3 LIBRARY IBC (303.4)

OPEN STAIR IS A CONVENIENCE OPENING (NFPA 8.6.9)

OCCUPANCY LOAD: NO CHANGE

FIRE ALARM SYSTEM: NO CHANGE

FIRE EXTINGUISHER: NO CHANGE

EGRESS REQUIREMENTS: NO CHANGE

INTERIOR FINISHES: GROUP A OCCUPANCY:

INTERIOR WALL AND CEILING FINISH MATERIALS

CLASS A OR CLASS B IN CORRIDORS AND LOBBIES (NFPA 101: 12.3.3.2)

CLASS A IN ENCLOSED STAIRWAYS (NFPA 101: 12.3.3.2)

INTERIOR FLOOR MATERIALS

CLASS I OR CLASS II IN CORRIDORS AND EXITS (NFPA 101 TABLE 10.2.2)

GROUP B OCCUPANCY:

INTERIOR WALL AND CEILING FINISH MATERIALS

CLASS A OR CLASS B IN CORRIDORS AND LOBBIES (NFPA 101: 38.3.3.2)

CLASS A IN ENCLOSED STAIRWAYS (NFPA 101: 38.3.3.2)

INTERIOR FLOOR MATERIALS

CLASS I OR CLASS II IN CORRIDORS AND EXITS (NFPA 101 TABLE 10.2.2)

GENERAL NOTES: CODES REFERENCED ON THIS SHEET ARE ABBREVIATED AS FOLLOWS:

IBC REFERS TO INTERNATIONAL BUILDING CODE, 2015 EDITION

NFPA 10 REFERS TO NATIONAL FIRE PROTECTION ASSOCIATION 10, STANDARD FOR

PORTABLE FIRE EXTINGUISHERS, 2018 EDITION

NFPA 101 REFERS TO NATIONAL FIRE PROTECTION ASSOCIATION 101, LIFE SAFETY CODE,

2018 EDITION

GENERAL NOTES

1. THE RESPONSIBILITY OF REPAIRING THE MULTISTACK GROUND SOURCE HEAT PUMP HEATER CHILLER WILL BE

ASSIGNED BY THE CONTRACTOR TO MULTISTACK CORPORATION. MULTISTACK WILL FURNISH AND INSTALL FOR ALL

WORK ASSOCIATED WITH THE CHILLER/HEATER FROM WHERE THE BUILDING PIPING SYSTEMS (CHILLED, HOT, AND

CONDENSER WATER) CONNECT TO THE CHILLER/HEATER FLANGES AND ALL INTERNAL WORK TO THE CHILLER/HEATER.

THIS IS DEFINED AND REFERENCED AS THE "CHILLER FLANGE TO FLANGE" DEFINITION. THIS INCLUDES ALL "FLANGE TO

FLANGE" CONDENSER WATER, CHILLED WATER AND HOT WATER MODIFICATIONS AND CONNECTIONS, ELECTRICAL

CONNECTIONS AND CONTROLS; MANAGEMENT, OVERSIGHT, MATERIALS, EQUIPMENT, LABOR, AND CONTROLS

DIRECTLY ASSOCIATED WITH THE CHILLER/HEATER EQUIPMENT. MULTISTACK WILL ALSO FURNISH THE PRIMARY

CHILLED WATER AND HOT WATER PUMP, PRIMARY LOOP CONTROL VALVES AND BLENDED WATER TEMPERATURE

SENSORS TO THE CONTRACTOR FOR INSTALLATION. CONTROL WIRING FOR THE PRIMARY PUMPS, VALVES AND

BLENDED WATER TEMPERATURE SENSORS SHALL BE ROUTED BACK TO THE CHILLER CONTROL BOX (FOR

TERMINATION AND CONTROL BY MULTISTACK) SHALL BE INSTALLED BY THE GENERAL CONTRACTOR. ALL CONTROL

WIRING SHALL END IN A 10' COIL AT THE MULTISTACK CHILLER CONTROLLER, READY FOR TERMINATION AND CONTROL

BY MULTISTACK.

G-004

B

B R

E V

I A

T I O

Y M

B O

L S

B B

X D P

B L

GENERAL SYMBOLS LEGEND

SYMBOL DESCRIPTION

PLAN

NORTH

ROOM NAME

X#

X-###

X#

X-###

X#

X-###

X-###

X#

X#

X#X#

DRAWING TITLE

SCALE

PLAN NORTH ARROW

DASHED ARROW REPRESENTS TRUE

NORTH

SECTION MARK

DETAIL NUMBER

SHEET NUMBER

CALLOUT MARK

DETAIL NUMBER

SHEET NUMBER

EXTERIOR ELEVATION

DETAIL NUMBER

SHEET NUMBER

INTERIOR ELEVATION

DETAIL NUMBER

SHEET NUMBER

ROOM NAME

ROOM NUMBER

GRID BUBBLE

DOOR MARK

WINDOW TYPE MARK

WALL TYPE MARK

KEYED NOTE

REVISION MARK

DETAIL NUMBER

SCALE OF DRAWING

VIEW TITLE

A

AB ANCHOR BOLT

AC AIR CONDITIONING

ACC ACCESSIBLE

ACOUS ACOUSTICAL

AD AREA DRAIN

ADD ADDITIONAL

ADJ ADJUSTABLE

AFF ABOVE FINISH FLOOR

AGGR AGGREGATE

ALT ALTERNATE

ALUM ALUMINUM

ANCH ANCHOR

ANNO ANODIZED

APC ACOUSTICAL PANEL CEILING

APPD APPROVED

APPROX APPROXIMATE

ARCH ARCHITECTURAL

ATC ACOUSTICAL TILE CEILING

AUTO AUTOMATIC

AV AUDIO VISUAL

B

B BOILER

BEJ BRICK EXPANSION JOINT

BD BOARD

BLDG BUILDING

BLK BLOCK

BM BEAM

BOT BOTTOM

BRK BRICK

BSMT BASEMENT

BT BOLT

BUR BUILT-UP ROOFING

C

CAB CABINET

CAT CATEGORY

CB CATCH BASIN

CBD CHALK BOARD

CBU CEMENTITIOUS BACKER UNIT

CEM CEMENT

CER CERAMIC

CG CORNER GUARD

CH CHILLER

CHAN CHANNEL

CI CAST IRON

CIP CAST-IN-PLACE

CJ CONTROL JOINT /

CONSTRUCTION JOINT

CL CENTER LINE

CLG CEILING

CLR CLEAR

CMU CONCRETE MASONRY UNIT

CNTR COUNTER

CO CLEANOUT

COL COLUMN

COMPART COMPARTMENT

CONC CONCRETE

COND CONDITION

CONN CONNECTION

CONT CONTINUOUS

CONTR CONTRACTOR

COORD COORDINATE

CORR CORRIDOR

CT COOLING TOWER

CTR CENTER

CTSK COUNTER SUNK

CW COLD WATER (PIPING)

D

D DEEP, DEPTH

DA DISABLED

DBL DOUBLE

DEG DEGREE

DEMO DEMOLITION

DEPT DEPARTMENT

DET DETAIL

DF DRINKING FOUNTAIN

DIA DIAMETER

DIFF DIFFUSER

DIM DIMENSION

DIS DISABLED

DISP DISPENSER

DMPF DAMPPROOFING

DMT DEMOUNTABLE

DN DOWN

DO DOOR OPENING

DP DIMENSION POINT

DPTN DEMOUNTABLE PARTITION

DR DOOR

DRN DRAIN

DS DOWNSPOUT

DW DISHWASHER

DWG DRAWING

DWR DRAWER

E

(E) EXISTING

E EAST

EA EACH

EB EXPANSION BOLT

EIFS EXTERIOR INSULATION AND

FINISH SYSTEM

EFS EXTERIOR FINISH SYSTEM

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRICAL

ELEV ELEVATOR

EMERG EMERGENCY

ENCLO ENCLOSURE

EP ELECTRICAL PANELBOARD

EQ EQUAL

EQUIP EQUIPMENT

ESCAL ESCALATOR

EWC ELECTRICAL WATER COOLER

EXH EXHAUST

EXP EXPANSION

EXIST EXISTING

EXT EXTERIOR

F

FA FIRE ALARM

FB FACE BRICK

FC FACE

FD FLOOR DRAIN

FDC FIRE DEPARTMENT

CONNECTION

FND FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FF&E FURNITURE, FINISHES &

EQUIPMENT

FFEL FINISH FLOOR ELEVATION

FH FLAT HEAD

FHC FIRE HOSE CABINET

FIN FINISH

FIXT FIXTURE

FL FLOOR

FLASH FLASHING

FLUOR FLUORESCENT

FO FACE OF

FP FIRE PROTECTION

FPG FIREPROOFING

FR FRAME

FT FEET

FRTW FIRE RETARDANT

TREATED WOOD

FTG FOOTING

FURN FURNITURE

FURR FURRING

FWC FABRIC WALLCOVERING

FWP FABRIC WRAPPED PANEL

G

G GROUND

GA GAUGE / GAGE

GALV GALVANIZED

GB GRAB BAR

GC GENERAL CONTRACT(OR)

GRC GLASS FIBER REINFORCED

CONCRETE

GRG GLASS FIBER REINFORCED

GYPSUM

GL GLASS

GR GRADE

GRD GROUND

GYPBD GYPSUM WALLBOARD

H

H HIGH / HEIGHT

HB HOSE BIB

HC HOLLOW CORE

HCP HANDICAPPED

HDW HARDWARE

HDWD HARDWOOD

HP HORSEPOWER / HEAT PUMP

HS HEAT STRENGTHEND (GLASS)

HM HOLLOW METAL (STEEL

FRAME)

HNDRL HANDRAIL

HO HOLD-OPEN

HORIZ HORIZONTAL

HPT HIGH POINT

HRC HOSE REEL CABINET

HR HOUR

HT HEIGHT

HVAC HEATING, VENTILATION, AIR

CONDITIONING

HW HOT WATER

HYDR HYDRAULIC

I

ID INSIDE DIAMETER

IN INCH

INCAND INCANDESCENT

INCL INCLUDED / INCLUDING

INFO INFORMATION

INSUL INSULATION

INT INTERIOR

INTERM INTERMEDIATE

INV INVERT

IPS INTERNATIONAL PIPE

STANDARD

IRMA INVERTED ROOF MEMBRANE

ASSEMBLY

J

JAN JANITOR

JC JANITOR'S CLOSET

JST JOIST

JT JOINT

K

K KIP (1000 LBF)

KPL KICK PLATE

KG KILOGRAM

KIT KITCHEN

KO KNOCKOUT

L

L LONG OR LITER (METRIC

DOCS)

LAB LABORATORY

LDG LANDING

LAM LAMINATE / LAMINATION

LAV LAVATORY

LB POUND

LF LINEAR FOOT

LKR LOCKER

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LN LINE

LT LIGHT

LPT LOW POINT

M

M METER

MACH MACHINE

MAINT MAINTENANCE

MAS MASONRY

MATL MATERIAL

MAU MAKE UP AIR UNIT

MAX MAXIMUM

MB MACHINE BOLT

MBL MARBLE

MDF MEDIUM DENSITY

FIBERBOARD

MEP MECHANICAL, ELECTRICAL,

PLUMBING

MDO MEDIUM DENSITY OVERLAY

PLYWOOD

MECH MECHANICAL

MEMB MEMBRANE

MET METAL

MEZZ MEZZANINE

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MM MILLIMETER

MO MASONRY OPENING

MS MACHINE SCREW

MTD MOUNTED

MTG MOUNTING

MTL METAL

MULL MULLION

N

N NORTH

NA NOT APPLICABLE

NC NOISE CRITERIA

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NTS NOT TO SCALE

O

OA OUTSIDE AIR

OC ON CENTER

OCEW ON CENTER EACH WAY

OD OUTSIDE

DIAMETER / DIMENSION

OFCI OWNER FURNISHED, CONTR

INSTALLED

O (CONT.)

OFOI OWNER FURNISHED, OWNER

INSTALLED

OFF OFFICE

OH OVERHEAD

OPH OPPOSITE HAND

OPNG OPENING

OPP OPPOSITE

OPPHD OPPOSITE HAND

ORD OVERFLOW ROOF DRAIN

OUTS OUTSIDE

OVHD OVERHEAD

P

P PAINT / PUMP

PAV PAVING

PARTN PARTITION

PATD PAPER TOWEL DISPENSER

PBD PARTICLEBOARD

PC PRECAST CONCRETE

PDF POWER DRIVEN FASTENER

PERF PERFORATED

PERIM PERIMETER

PERP PERPENDICULAR

PF POINT OF INTERSECTION

PL PLATE

PLAM PLASTIC LAMINATE

PLAS PLASTER

PLBG PLUMBING

PLF POUNDS PER LINEAR FOOT

PLYWD PLYWOOD

PNL PANEL

POL POLISHED

PR PAIR

PREFAB PREFABRICATED

PROJ PROJECT

PSF POUNDS PER SQUARE FOOT

PT POINT

PTD PAINTED

PTN PARTITION

PTR PAPER TOWEL RECEPTACLE

Q

Q QUARRY TILE

QTY QUANTITY

R

(R) RELOCATED

R RADIUS OR RISER (PIPING)

RA RETURN AIR

RAD RADIUS

RB RESILIENT BASE

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

RECOM RECOMMENDED

RECPT RECEPTACLE

REC RECESSED

REF REFERENCE

REFL REFLECTED / REFLECTIVE /

REFLECT

REFR REFRIGERATOR

REG REGISTER

REINF REINFORCED / REINFORCING

REL RELOCATE

REM REMOVABLE

REQ REQUIRE / REQUIRED

RESIL RESILIENT

REV REVISION / REVISED

RM ROOM

RO ROUGH OPENING

RTD RATED

RTG RATING

RWL RAIN WATER LEADER

S

S SOUTH

SA SUPPLY AIR

SAN SANITARY

SC SOLID CORE

SCHED SCHEDULE

SD STORM DRAIN / SOAP

DISPENSER

SECT SECTION

STS SELF TAP METAL SCREW

SF SQUARE FEET / FOOT

SH SPRINKLER HEAD

SHT SHEET

SHR SHOWER

SIM SIMILAR

SM SHEET METAL OR SQUARE

METER (METRIC DOCS)

SND SANITARY NAPKIN DISPENSER

SP STANDPIPE

SPEC SPECIFICATION

SPR SPRINKLER

SPKR SPEAKER

S (CONT.)

SQ SQUARE

SSE STRUCTURE SLAB ELEVATION

SST STAINLESS STEEL

SSK SERVICE SINK

STA STATION

STD STANDARD

STL STEEL

STLJST STEEL JOIST

STOR STORAGE

STRG STRINGER

STRUC STRUCTURAL

SUBCAT SUBCATEGORY

SUSP SUSPENDED

SYMM SYMMETRICAL

SYS SYSTEM

T

T&G TONGUE AND GROOVE

T TREAD / THERMOSTAT

TB TOWEL BAR

TC TOP OF CURB

TCONC TOP OF CONCRETE

TEL TELEPHONE OR TELECOM

TEMP TEMPERATURE

TER TERRAZZO

TGB TOGGLE BOLT

THK THICKNESS

THRES THRESHOLD

THRU THROUGH

TKBD TACKBOARD

TMPD TEMPERED

TO TOP OF (SEE OTHER WORD)

TOS TOP OF SLAB, TOP OF

STRUCTURE

TOSTL TOP OF STEEL

TP TOP OF PAVEMENT

TPD TOILET PAPER DISPENSER

TRACT TRACTION

TV TELEVISION

TW TOP OF WALL

TYP TYPICAL

U

UNFIN UNFINISHED

UON UNLESS OTHERWISE NOTED

UR URINAL

V

VAV VARIABLE AIR VOLUME

W

W-A WATER TO AIR

W-W WATER TO WATER

ABBREVIATIONS

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

W

D Q

R

A1\A-104

A

F.E.C.

LIBRARY FIRST FLOOR

C100

MACHINE RM

C123

ELEV 2

E02

DIRECTOR

C109

CONFERENCE

C107

STAIR 3

C S03

STAIR 2

C S02

MEN

C101

WOMEN

C102

SYSTEMS LIBRARIAN

C112

ELEC

C106

STORAGE

C114A

REF. LIBRARIANS

C104

CHIEF PUBLIC SERVICE

C105

SYSTEMS

C114

JAN

C103

MICROFILM

C110

STACKING AREA

C124

ACQUISITIONS

C120

SEMINAR

C111

STAFF LOUNGE

C125

AV BOOTH

C129

AV BOOTH

C128

STUDY ROOM

C126

AV BOOTH

C127

COPYRIGHT TECH

C118

ACQ LIBRARIAN

C117

TECH SERVICES

C119

CORRIDOR

C115

ILL TECH

C116

CATALOGING

C121

SECRETARY

C108

STORAGE

C125A

TR

C113

HEAD CATALOGER

C122

CHILDRENS

C130

E01

ELEV 1

STAIR 1

C S01

VESTIBULE

C100A

STAIR 4

C S04

LEARNING CENTER

VESTIBULE

C131

C100B

ELEC

C133

MDF

C132

WORK ROOM

C134

ELEV 3

E03

MACHINE ROOM

G183

APFRI

G155

ELEC

G159

TR

G158

APFRI OFFICE SUITE

G161

APFRI

G164

APFRI

G162

APFRI

G163

AAFES

G173

AAFES

G171

COMPACTOR RM

G112

AAFES

G174

AAFES

G175

GIFT ARCHIVES

G182

ETV STUDIO

G180

CORRIDOR

G181

APFRI WAITING

G148

APFRI NUTRI.

G149

APFRI ASSESSMENT

G147

AAFES

G172

AAFES CAFETERIA

G169

CORRIDOR

G105

ENTRY / LOCKERS

G137

APFRI

G156

CORRIDOR

G160

APFRI

G157

APFRI RECEPTION

G140

VESTIBULE

G110A

LOADING DOCK

G111

APFRI RR

G144

APFRI RR

G145

APFRI BOD POD

G146

WATER HEATERS

G113

STAIR 6

G S06

ETV STUDIO

G179

ETV STUDIO ENTRY

G176

APFRI LOCKER

G150

OFFICE SUITE

G102

CONFERENCE

G103

ETV STUDIO

G178

WOMEN

G110

MEN

G108

LOBBY

G100

CONFERENCE

G101

STORAGE

G109

VESTIBULE

G108A

VESTIBULE

G100A

AAFES KITCHEN

G170

CLASSROOM XXI

G139

STORAGE

G136

AV

G136A

STAIR 9

G S09

APFRI

G168

APFRI

G167

MAINTENANCE WORKSHOP

G115A

MCN 120

G116

APFRI

G164

MECHANICAL

G120

STORAGE

G130C

DOCK OFFICE

G117

STORAGE

G115

STAIR 8

G S08

SOUND

G128

WOMEN

G124

ELEV. MACHINE RM

G118

ELEV 4

E04

STAIR 7

G S07

VESTIBULE

G119A

DePUY AUDITORIUM

G130

APFRI BREAK ROOM

G165

CONFERENCE

G103

BUSINESS CENTER

G133

JAN

G134

COATS

G127

STORAGE

G131

DISTRIBUTION RM

G135

PROJECTOR ROOM

G129

CORRIDOR

G122

VESTIBULE

G100A

APFRI

G166

MDF

G132

AV

G135A

A1\A-106

A

A

SECTOR

SECTOR

SECTOR

SECTOR

SECTOR

SECTOR

SECTOR

SECTOR

G-005

L E

V E

L

O V

E R

A L

L

K

E Y

P L

A N

B B

B L

D P

B L

SCALE:

A1

OVERALL KEYPLAN - LEVEL 1

1" = 20'-0"

NORTH

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

0 20 40

A

OFFICE

G230

AMSC OPS CENTER

G229

OFFICE

G231

OFFICE

G233

OFFICE

G235

OFFICE

G234

VESTIBULE

G217A

VESTIBULE

G216A

JAN

G218

OFFICE

G222

OFFICE

G221

OFFICE

G220

IDF

G227

OFFICE SUITE

G228

OFFICE SUITE

G232

ELEC

G237

OFFICE

G223

OFFICE

G226

OPEN OFFICE

G219

ELEC

G210

STAIR 7

G S07

VESTIBULE

G211A

VESTIBULE

G212A

ELEC

G255

SIPRNET DLDC CLASSROOM

G254

AV CLOSET

G238

SIPRNET CLASSROOM XXI

G239

SIPRNET CLASSROOM XXI

G247

SIPRNET CLASSROOM XXI

G240

SIPRNET CLASSROOM XXI

G243

SIPRNET CLASSROOM XXI

G250

LOBBY

G200

COPY / PRINT

G246

AV CLOSET

G245

AV CLOSET

G241

MEN

G217

WOMEN

G216

SIPR

G236

OFFICE

G224

OFFICE

G225

SIPRNET CLASSROOM XXI

G251

SIPRNET DLDC CLASSROOM

G244

AV CLOSET

G242

AV CLOSET

G253

AV CLOSET

G252

AV CLOSET

G249

AV CLOSET

G248

VENDING

G279

ELEV 3

E03

ELEC

G207

ELEC

G210

STAIR 6

G S06

BREAK AREA

G208

VESTIBULE

G204A

WOMEN

G206

ELEC

G205

CLASSROOM XXI

G260 CLASSROOM XXI

G261

SCP CLASSROOM XXI

G266

SCP CLASSROOM XXI

G267

SCP CLASSROOM XXI

G270

CLASSROOM XXI

G257

ELEC

G255

SCP CLASSROOM XXI

G276

SCP CLASSROOM XXI

G273

SCP CLASSROOM XXI

G275

AV CLOSET

G274

AV CLOSET

G265

AV CLOSET

G268

LOBBY

G200

AV CLOSET

G277

SCP CLASSROOM XXI

G278

AV CLOSET

G272

COPY / PRINT

G246

CORRIDOR

G209

CORRIDOR

G202

MEN

G204

VESTIBULE

G206A

SCP CLASSROOM

G271

AV CLOSET

G253

AV CLOSET

G252

AV CLOSET

G249

AV CLOSET

G248

AV CLOSET

G269

STORAGE

G281

SCP CLASSROOM

G264

STAIR 1

C S01

STAIR 4

C S04

CHARLES YOUNG ROOM

C212

STORAGE

C211

ELEC

C210

TR

C209

INDIVIDUAL STUDY AREA

C208

LIBRARY SECOND FLOOR

C200

ELEV 1

E01

VENDING

C206

STAIR 3

C S03

STAIR 2

C S02

STAIR 2

C S02

MEN

C201

JAN

C203

STORAGE

C207

ELEC

C204

TR

C205

A1\A-106

A

A

SECTOR

SECTOR

SECTOR

SECTOR

SECTOR

SECTOR

SECTOR

SECTOR

G-006

L E

V E

L

O V

E R

A L

L

K

E Y

P L

A N

B B

B L

D P

B L

SCALE:

A1

OVERALL KEYPLAN - LEVEL 2

1" = 20'-0"

NORTH

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

A

ELEV 1

E01

STAIR 1

C S01

ELEC

C327

TR

C326

BRANCH CHIEF

C328

BOOTH

C302

BOOTH

C303

BOOTH

C304

TS VAULT

C331

NATO VAULT

C334

CLASS. SERV.

C329

RARE BOOK

C335

TS READING

C330

NATO READING

C332

LOBBY

C301

STAIR 4

C S04

ARCHIVES COLLECTION

C325

ELEV 3

E03

CORRIDOR

G302

ELEC

G310

WOMEN

G306

STAIR 6

G S06

ELEC

G307

VESTIBULE

G304A

MEN

G304ELEC

G305

VESTIBULE

G306A

AV CLOSET

G372

COPY

G346

ELEC

G355

CLASSROOM XXI

G373

CLASSROOM XXI

G375

CLASSROOM XXI

G376

CLASSROOM XXI

G378

SIPRNET CLASSROOM XXI

G371

SIPRNET CLASSROOM XXI

G367

SIPRNET CLASSROOM XXI

G366

SIPRNET CLASSROOM XXI

G357

SIPRNET CLASSROOM XXI

G360

AV CLOSET

G377

AV CLOSET

G374

CORRIDOR

G302

SIPRNET CLASSROOM XXI

G370

COPY

G356

AV CLOSET

G358

AV CLOSET

G359

AV CLOSET

G362

AV CLOSET

G363

AV CLOSET

G353

AV CLOSET

G352

AV CLOSET

G349

AV CLOSET

G348

SIPRNET CLASSROOM XXI

G354

SIPRNET CLASSROOM XXI

G340

SIPRNET CLASSROOM XXI

G350

SIPRNET CLASSROOM XXI

G339

SIPRNET CLASSROOM XXI

G347

JAN

G318

OFFICE SUITE

G332

OFFICE

G335

ELEC

G337

OFFICE

G333

OFFICE

G334

VESTIBULE

G316A

OFFICE SUITE

G328

OFFICE

G329

OFFICE

G330

OFFICE

G331

VESTIBULE

G317A

WOMEN

G316

OPEN OFFICE

G319

WOMEN

G311

STAIR 7

G S07

VESTIBULE

G311A

VESTIBULE

G312A MEN

G312

CORRIDOR

G314

AV CLOSET

G345

STORAGE

G336

OFFICE

G320

OFFICE

G321

OFFICE

G322

OFFICE

G323

OFFICE

G324

OFFICE

G325

OFFICE

G326

SIPRNET CLASSROOM XXI

G344

AV CLOSET

G338

AV CLOSET

G341

AV CLOSET

G342

SIPRNET CLASSROOM XXI

G343

IDF

G327

A1\A-106

A

A

SECTOR

SECTOR

SECTOR

SECTOR

SECTOR

SECTOR

SECTOR

SECTOR

G-007

L E

V E

L

O V

E R

A L

L

K

E Y

P L

A N

B B

B L

D P

B L

SCALE:

A1

OVERALL KEYPLAN - LEVEL 3

1" = 20'-0"

NORTH

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

A

CARL ROOF (CR)

GIF ROOF (GR)

A1\A-106

A

A

SECTOR

SECTOR

SECTOR

SECTOR

SECTOR

SECTOR

SECTOR

SECTOR

G-008

R O

O F

O V

E R

A L

L

K

E Y

P L

A N

B B

B L

D P

B L

SCALE:

A1

OVERALL KEYPLAN - ROOF

1" = 20'-0"

NORTH

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

J

DEH-1

CU-1

1853 LBS

9,800 LBS

1 2 3 4 5

A

B

C

D

E

D.5

A

S

(S-132: NOT IN SCOPE)

W14X26

W14X26

W14X26

W14X26

N E

W

W

X

N E

W

W

X

N E

W

W

X

N E

W

W

X

N E

W

W

X

N E

W

W

X

W

X

W

X

W

X

W

X

NEW W8X10

(TYP.)

(TYP.)

NEW W8X10

S-131

S E

C T

O

O F

S T

R U

C T

U R

A

M I N

G

P

L A

N

B B

M B

A K

G

B L

SCALE:

A1

STRUCTURAL FRAMING PLAN - ROOF - SECTOR 1

1/8" = 1'-0"

NORTH

0 8' 16'4'

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

SHEET KEYED NOTES

GENERAL SHEET NOTES

XX

1. CONNECTION: 3/8" STIFFENER PLATE WELDED TO EXISTING W14 BOLTED

TO NEW W8 WITH 2 3/4" A325 BOLTS. REMOVE ANY DAMAGED

FIREPROOFING AT CONNECTIONS TO EXISTING BEAM AND PROVIDE NEW

1-HOUR FIREPROOFING AT EXISTING BEAM AS REQUIRED TO MAINTAIN

BEAM FIRE RATING.

2. CONNECTION: 3/8" STIFFENER PLATE WELDED TO NEW W8 BOLTED TO

NEW W8 WITH 2 3/4" A325 BOLTS. REMOVE ANY DAMAGED FIREPROOFING

AT CONNECTIONS TO EXISTING BEAM AND PROVIDE NEW 1-HOUR

FIREPROOFING AT EXISTING BEAM AS REQUIRED TO MAINTAIN BEAM

FIRE RATING.

1. ADD STRUCTURAL STEEL AS SHOWN, WELD TO EXISTING ROOFING

MEMBERS. COORDINATE EXACT LOCATIONS WITH MECHANICAL

CONTRACTOR.

2. SEE DETAIL SHEET S-501 FOR CONNECTIONS

3. PROVIDE NEW 1-HOUR SPRAY APPLIED FIREPROOFING TO MATCH

EXISTING FIREPROOFING. AT ALL NEW BEAMS AND PLATES TYP.

4. BEAMS ARE EXISTING UNLESS INDICATED AS NEW.

JJ

DEH-2

CU-2

307 LBS

8,000 LBS

6 7

8 9

A

B

C

D

E

AA

BB

CC

DD

D.5

FF

A

S

(S-133: NOT IN SCOPE)

(S-135: NOT IN SCOPE)

(S-136: NOT IN SCOPE)

W

X

W

X

W

X

W

X

W

X

W

X

W

X

W

X

W

X

W

X

W

X

W

X

N

W

X

N

X

N

X

N

X

N

X

N

X

N

X

N

X

W

X

W

X

W

X

W

X

(TYP.)

(TYP.)

C8

S-501

(TYP.)

W

X

S-134

S E

C T

O

O F

S T

R U

C T

U R

A

M I N

G

P

L A

N

B B

M B

A K

G

B L

SCALE:

A1

STRUCTURAL FRAMING PLAN - ROOF - SECTOR 4

1/8" = 1'-0"

NORTH

0 8' 16'4'

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

SHEET KEYED NOTES

GENERAL SHEET NOTES

XX

1. ADD STRUCTURAL STEEL AS SHOWN, WELD TO EXISTING ROOFING

MEMBERS. COORDINATE EXACT LOCATIONS WITH MECHANICAL

CONTRACTOR.

2. SEE DETAIL SHEET S-501 FOR CONNECTIONS

3. PROVIDE NEW 1-HOUR SPRAY APPLIED FIREPROOFING TO MATCH

EXISTING FIREPROOFING. AT ALL NEW BEAMS AND PLATES TYP.

4. BEAMS ARE EXISTING UNLESS INDICATED AS NEW.

1. CONNECTION: 3/8" STIFFENER PLATE WELDED TO EXISTING W16 BOLTED

TO NEW W10 WITH 2 3/4" A325 BOLTS. REMOVE ANY DAMAGED

FIREPROOFING AT CONNECTIONS TO EXISTING BEAM AND PROVIDE NEW

1-HOUR FIREPROOFING AT EXISTING BEAM AS REQUIRED TO MAINTAIN

BEAM FIRE RATING.

2. CONNECTION: 3/8" STIFFENER PLATE WELDED TO NEW W10 BOLTED TO

NEW W10 WITH 2 3/4" A325 BOLTS. REMOVE ANY DAMAGED FIREPROOFING

AT CONNECTIONS TO EXISTING BEAM AND PROVIDE NEW 1-HOUR

FIREPROOFING AT EXISTING BEAM AS REQUIRED TO MAINTAIN BEAM

FIRE RATING.

3. 4" O.D. SCHEDULE 40 PIPE COLUMN TYP.

BEAM - SEE PLAN

L4"x4"x5/16" N.S. & F.S.

NOTCHED IN ACCORDANCE

w/OSHA REGULATIONS

N O

O

F

Ø

A

N

B

O L o

C

S

E E

S C

H E

D U

L E

NOMINAL BEAM

DEPTH (INCHES)

NO. OF BOLTS

8" TO 10"

12" TO 14"

16"

18"

21"

24" AND 27"

ELASTOMERIC

RIB CAP

ANCHOR CLIP

SUB PURLIN

L5"X5"X3/8" TYP.

MTL FASCIA

L5"X3"X1/4"

3/16 3-12 WELD

FACE OF STRUCTURAL T

EMSEAL W/ COMP.

CLOSER

L5"X5"X3/8"

MTL FASCIA

SUB PURLIN

SEALANT

WT9X17.5 BENT

STL. ANGLE BRACE

RIB STEEL ROOF PANEL.

5'-9 1/2"

D-RING ANCHOR

MOUNTED TO BEAM

WT9X17.5 (TYPICAL)

L5x5x3/8 (TYPICAL)

EXISTING BEAM

4" OD SCHEDULE 40 PIPE

COL.

3/4 BASEPLATE W/ 4-5/8"

THROUGH BOLTS (TYP.)

9"X6"X3/4" PLATES W/

4-3/4" A325 BOLTS

C5

S-501

A5

S-501

C1

S-501

L5x3x1/4

1'-0 3/4"

S-501

S E

C T

T

R U

C T

U R

T

A I L

S

B B

M B

A K

G

B L

SCALE:

A1

TYPICAL SHEAR CONNECTION DETAIL

N.T.S.

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

W

D Q

R

SCALE:

C1

SECTION DETAIL

3" = 1'-0" SCALE:

C5

SECTION DETAIL

3" = 1'-0"

SCALE:

A5

SECTION DETAIL

3" = 1'-0"

SCALE:

C8

SECTION DETAIL

1/2" = 1'-0" 0 2' 4'1'

0 1/2' 3/4'1/4'

0 1/2' 3/4'1/4'0 1/2' 3/4'1/4'

A-001

R

C H

I T

E C

T U

R A

L

I N

F O

R M

A T

I O

Y M

B O

L S

B B

A K

G

D P

B L

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

W

D Q

R

MATERIALS LEGEND

SYMBOL DESCRIPTION

LEGEND

SYMBOL DESCRIPTION

NEW WALL

DEMO WALL

DEMO DOOR

EXISTING DOOR

NEW 6' DOOR

NEW DOOR WITH 180

DEGREE SWING AND

INACTIVE LEAF

GYPSUM BOARD

INSULATION - BATT

INSULATION - SPRAY FOAM

CHILDRENS

C130

STAIR 4

C S04

LEARNING CENTER

VESTIBULE

C131

C100B

ELEC

C133

MDF

C132

1 2 3 4 5

A

B

C

D

E

D.5

A

A

A1/A-102

AD101

S E

C T

E

V E

L

A R

C H

I T

E C

T U

R A

L

F

L O

A

N

D

E M

O

B B

A K

G

D P

B L

SCALE:

A1

ARCHITECTURAL FLOOR PLAN - LEVEL 1 - SECTOR 1

1/8" = 1'-0"

NORTH

SHEET KEYED NOTES

GENERAL SHEET NOTES

XX

1. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS TO INSTALL CONDUIT. SALVAGE AND PROTECT CEILING GRID

AND TILE FOR REINSTALLATION. - SEE SHEET E-101

2. CUT WALL FOR INSTALLATION OF CONDUIT.

0 8' 16'4'

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

1. SEE MECHANICAL DRAWINGS FOR VAV REMOVAL DETAILS.

2. REMOVE MEPF DEVICES AND CEILING MOUNTED SIGNAGE AS

NECESSARY TO PROVIDE ACCESS TO MECHANICAL EQUIPMENT.

SALVAGE AND PROTECT MEPF DEVICES AND SIGNAGE FOR

REINSTALLATION.

3. VAV BOX REPLACEMENT TO BE ACCOMPLISHED IN AN 8-HOUR PERIOD.

CEILING TILE TO BE REMOVED AND REPLACED AS REQUIRED TO CHANGE

OUT VAV BOX. LIGHTING FIXTURES, SPRINKLERS AND OTHER MEFP ITEMS

REQUIRED TO BE TEMPORARILY RELOCATED OR REMOVED FOR VAV BOX

REPLACEMENT, ARE REQUIRED TO BE REMOVED OR RELOCATED, AND

THEN REINSTALLED, WITHIN AN 8-HOUR PERIOD.

LIBRARY FIRST FLOOR

C100

MACHINE RM

C123

ELEV 2

E02

STAIR 3

C S03

STACKING AREA

C124

ACQUISITIONS

C120

STAFF LOUNGE

C125

AV BOOTH

C129

AV BOOTH

C128

STUDY ROOM

C126

AV BOOTH

C127

COPYRIGHT TECH

C118

ACQ LIBRARIAN

C117

TECH SERVICES

C119

CORRIDOR

C115

ILL TECH

C116

CATALOGING

C121

STORAGE

C125A

HEAD CATALOGER

C122

E

F

G

H

J

K

L

1 2 3 4 5

(AD101: NOT IN SCOPE)

A

A

D

AD102

S E

C T

E

V E

L

A R

C H

I T

E C

T U

R A

L

F

L O

A

N

D

E M

O

B B

A K

G

D P

B L

SCALE:

A1

ARCHITECTURAL FLOOR PLAN - DEMO - LEVEL 1 - SECTOR 2

1/8" = 1'-0"

NORTH

0 8' 16'4'

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

1. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS TO AFFECTED VAV FOR REPLACEMENT. SALVAGE AND PROTECT

CEILING GRID AND TILE FOR REINSTALLATION. - SEE SHEET MD102

1. SEE MECHANICAL DRAWINGS FOR VAV REMOVAL DETAILS.

2. REMOVE MEPF DEVICES AND CEILING MOUNTED SIGNAGE AS

NECESSARY TO PROVIDE ACCESS TO MECHANICAL EQUIPMENT.

SALVAGE AND PROTECT MEPF DEVICES AND SIGNAGE FOR

REINSTALLATION.

3. VAV BOX REPLACEMENT TO BE ACCOMPLISHED IN AN 8-HOUR PERIOD.

CEILING TILE TO BE REMOVED AND REPLACED AS REQUIRED TO CHANGE

OUT VAV BOX. LIGHTING FIXTURES, SPRINKLERS AND OTHER MEFP ITEMS

REQUIRED TO BE TEMPORARILY RELOCATED OR REMOVED FOR VAV BOX

REPLACEMENT, ARE REQUIRED TO BE REMOVED OR RELOCATED, AND

THEN REINSTALLED, WITHIN AN 8-HOUR PERIOD.

SHEET KEYED NOTES

GENERAL SHEET NOTES

XX

DIRECTOR

C109

CONFERENCE

C107

STAIR 2

C S02

MEN

C101

WOMEN

C102

SYSTEMS LIBRARIAN

C112

ELEC

C106

STORAGE

C114A

REF. LIBRARIANS

C104

CHIEF PUBLIC SERVICE

C105

SYSTEMS

C114

MICROFILM

C110

SEMINAR

C111

SECRETARY

C108

TR

C113

E

F

G

H

J

K

L

5 6 7 8 9

A1\AD104

A

A

D

3 3

AD103

S E

C T

E

V E

L

A R

C H

I T

E C

T U

R A

L

F

L O

A

N

D

E M

O

B B

A K

G

D P

B L

SCALE:

A1

ARCHITECTURAL FLOOR PLAN - DEMO - LEVEL 1 - SECTOR 3

1/8" = 1'-0"

NORTH

0 8' 16'4'

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

1. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS TO AFFECTED VAV FOR REPLACEMENT. SALVAGE AND PROTECT

CEILING GRID AND TILE FOR REINSTALLATION. - SEE SHEET MD103

2. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS TO INSTALL CONDUIT. SALVAGE AND PROTECT CEILING GRID

AND TILE FOR REINSTALLATION. - SEE SHEET E-103

3. CUT WALL FOR INSTALLATION OF CONDUIT.

1. SEE MECHANICAL DRAWINGS FOR VAV REMOVAL DETAILS.

2. REMOVE MEPF DEVICES AND CEILING MOUNTED SIGNAGE AS

NECESSARY TO PROVIDE ACCESS TO MECHANICAL EQUIPMENT.

SALVAGE AND PROTECT MEPF DEVICES AND SIGNAGE FOR

REINSTALLATION.

3. VAV BOX REPLACEMENT TO BE ACCOMPLISHED IN AN 8-HOUR PERIOD.

CEILING TILE TO BE REMOVED AND REPLACED AS REQUIRED TO CHANGE

OUT VAV BOX. LIGHTING FIXTURES, SPRINKLERS AND OTHER MEFP ITEMS

REQUIRED TO BE TEMPORARILY RELOCATED OR REMOVED FOR VAV BOX

REPLACEMENT, ARE REQUIRED TO BE REMOVED OR RELOCATED, AND

THEN REINSTALLED, WITHIN AN 8-HOUR PERIOD.

SHEET KEYED NOTES

JAN

C103

E01

ELEV 1

STAIR 1

C S01

VESTIBULE

C100A

WORK ROOM

C134

6 7

8 9

A

B

C

D

E

AA

BB

CC

DD

D.5

FF

A

D

N

O

P E

A1\AD103

A1\AD105

(AD106: NOT IN SCOPE)

AD104

S E

C T

E

V E

L

A R

C H

I T

E C

T U

R A

L

F

L O

A

N

D

E M

O

B B

A K

G

D P

B L

SCALE:

A1

ARCHITECTURAL FLOOR PLAN - DEMO - LEVEL 1 - SECTOR 4

1/8" = 1'-0"

NORTH

0 8' 16'4'

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

1. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS TO AFFECTED VAV FOR REPLACEMENT. SALVAGE AND PROTECT

CEILING GRID AND TILE FOR REINSTALLATION. - SEE SHEET MD104

2. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS TO INSTALL CONDUIT. SALVAGE AND PROTECT CEILING GRID

AND TILE FOR REINSTALLATION. - SEE SHEET E-103

1. SEE MECHANICAL DRAWINGS FOR VAV REMOVAL DETAILS.

2. REMOVE MEPF DEVICES AND CEILING MOUNTED SIGNAGE AS

NECESSARY TO PROVIDE ACCESS TO MECHANICAL EQUIPMENT.

SALVAGE AND PROTECT MEPF DEVICES AND SIGNAGE FOR

REINSTALLATION.

3. VAV BOX REPLACEMENT TO BE ACCOMPLISHED IN AN 8-HOUR PERIOD.

CEILING TILE TO BE REMOVED AND REPLACED AS REQUIRED TO CHANGE

OUT VAV BOX. LIGHTING FIXTURES, SPRINKLERS AND OTHER MEFP ITEMS

REQUIRED TO BE TEMPORARILY RELOCATED OR REMOVED FOR VAV BOX

REPLACEMENT, ARE REQUIRED TO BE REMOVED OR RELOCATED, AND

THEN REINSTALLED, WITHIN AN 8-HOUR PERIOD.

SHEET KEYED NOTES

F.E.C.

ELEV 3

E03

MACHINE ROOM

G183

APFRI OFFICE SUITE

G161

APFRI

G164

APFRI

G162

APFRI

G163

AAFES

G173

AAFES

G171

AAFES

G174

AAFES

G175

AAFES

G172

AAFES CAFETERIA

G169

CORRIDOR

G105

ENTRY /

G

OFFICE SUITE

G102

CONFERENCE

G103

LOBBY

G100

CONFERENCE

G101

VESTIBULE

G100A

AAFES KITCHEN

G170

CLASSROOM XXI

G139

STORAGE

G136

AV

G136A

APFRI

G168

APFRI

G167

APFRI

G164

APFRI BREAK ROOM

G165

CONFERENCE

G103

VESTIBULE

G100A

APFRI

G166

18 19 20 21 22

P

Q

R

S

T

U

V

(AD106: NOT IN SCOPE)

A

D

N

O

P E

AD105

S E

C T

E

V E

L

A R

C H

I T

E C

T U

R A

L

F

L O

A

N

D

E M

O

B B

A K

G

D P

B L

SCALE:

A1

ARCHITECTURAL FLOOR PLAN - DEMO - LEVEL 1 - SECTOR 5

1/8" = 1'-0"

NORTH

0 8' 16'4'

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

1. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS TO AFFECTED VAV FOR REPLACEMENT. SALVAGE AND PROTECT

CEILING GRID AND TILE FOR REINSTALLATION. - SEE SHEET MD105

1. SEE MECHANICAL DRAWINGS FOR VAV REMOVAL DETAILS.

2. REMOVE MEPF DEVICES AND CEILING MOUNTED SIGNAGE AS

NECESSARY TO PROVIDE ACCESS TO MECHANICAL EQUIPMENT.

SALVAGE AND PROTECT MEPF DEVICES AND SIGNAGE FOR

REINSTALLATION.

3. VAV BOX REPLACEMENT TO BE ACCOMPLISHED IN AN 8-HOUR PERIOD.

CEILING TILE TO BE REMOVED AND REPLACED AS REQUIRED TO CHANGE

OUT VAV BOX. LIGHTING FIXTURES, SPRINKLERS AND OTHER MEFP ITEMS

REQUIRED TO BE TEMPORARILY RELOCATED OR REMOVED FOR VAV BOX

REPLACEMENT, ARE REQUIRED TO BE REMOVED OR RELOCATED, AND

THEN REINSTALLED, WITHIN AN 8-HOUR PERIOD.

SHEET KEYED NOTES

STAIR 4

C S04

STORAGE

C211

ELEC

C210

TR

C209

LIBRARY SECOND FLOOR

C200

1 2 3 4 5

A

B

C

D

E

D.5

A

A

D

A1\AD112

AD111

S E

C T

E

V E

L

A R

C H

I T

E C

T U

R A

L

F

L O

A

N

D

E M

O

B B

A K

G

D P

B L

SCALE:

A1

ARCHITECTURAL FLOOR PLAN - DEMO - LEVEL 2 - SECTOR 1

1/8" = 1'-0"

NORTH

0 8' 16'4'

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

1. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS TO AFFECTED VAV FOR REPLACEMENT. SALVAGE AND PROTECT

CEILING GRID AND TILE FOR REINSTALLATION. - SEE SHEET MD111

2. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS FOR GAS PIPE INSTALLATION. SALVAGE AND PROTECT CEILING

GRID AND TILE FOR REINSTALLATION. - SEE SHEET M-111

3. CUT WALL FOR INSTALLATION OF GAS LINE

1. SEE MECHANICAL DRAWINGS FOR VAV REMOVAL DETAILS.

2. REMOVE MEPF DEVICES AND CEILING MOUNTED SIGNAGE AS

NECESSARY TO PROVIDE ACCESS TO MECHANICAL EQUIPMENT.

SALVAGE AND PROTECT MEPF DEVICES AND SIGNAGE FOR

REINSTALLATION.

3. VAV BOX REPLACEMENT TO BE ACCOMPLISHED IN AN 8-HOUR PERIOD.

CEILING TILE TO BE REMOVED AND REPLACED AS REQUIRED TO CHANGE

OUT VAV BOX. LIGHTING FIXTURES, SPRINKLERS AND OTHER MEFP ITEMS

REQUIRED TO BE TEMPORARILY RELOCATED OR REMOVED FOR VAV BOX

REPLACEMENT, ARE REQUIRED TO BE REMOVED OR RELOCATED, AND

THEN REINSTALLED, WITHIN AN 8-HOUR PERIOD.

SHEET KEYED NOTES

VENDING

C206

STAIR 3

C S03

STORAGE

C207

ELEC

C204

TR

C205

E

F

G

H

J

K

L

1 2 3 4 5

A1\AD111

A

A

D

AD112

S E

C T

E

V E

L

A R

C H

I T

E C

T U

R A

L

F

L O

A

N

D

E M

O

B B

A K

G

D P

B L

SCALE:

A1

ARCHITECTURAL FLOOR PLAN - DEMO - LEVEL 2 - SECTOR 2

1/8" = 1'-0"

NORTH

0 8' 16'4'

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

1. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS TO AFFECTED VAV FOR REPLACEMENT. SALVAGE AND PROTECT

CEILING GRID AND TILE FOR REINSTALLATION. - SEE SHEET MD112

1. SEE MECHANICAL DRAWINGS FOR VAV REMOVAL DETAILS.

2. REMOVE MEPF DEVICES AND CEILING MOUNTED SIGNAGE AS

NECESSARY TO PROVIDE ACCESS TO MECHANICAL EQUIPMENT.

SALVAGE AND PROTECT MEPF DEVICES AND SIGNAGE FOR

REINSTALLATION.

3. VAV BOX REPLACEMENT TO BE ACCOMPLISHED IN AN 8-HOUR PERIOD.

CEILING TILE TO BE REMOVED AND REPLACED AS REQUIRED TO CHANGE

OUT VAV BOX. LIGHTING FIXTURES, SPRINKLERS AND OTHER MEFP ITEMS

REQUIRED TO BE TEMPORARILY RELOCATED OR REMOVED FOR VAV BOX

REPLACEMENT, ARE REQUIRED TO BE REMOVED OR RELOCATED, AND

THEN REINSTALLED, WITHIN AN 8-HOUR PERIOD.

SHEET KEYED NOTES

STAIR 2

C S02

MEN

C201

E

F

G

H

J

K

L

5 6 7 8 9

A1/AD114

A

A

D

AD113

S E

C T

E

V E

L

A R

C H

I T

E C

T U

R A

L

F

L O

A

N

D

E M

O

B B

A K

G

D P

B L

SCALE:

A1

ARCHITECTURAL FLOOR PLAN - DEMO - LEVEL 2 - SECTOR 3

1/8" = 1'-0"

NORTH

0 8' 16'4'

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

1. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS TO AFFECTED VAV FOR REPLACEMENT. SALVAGE AND PROTECT

CEILING GRID AND TILE FOR REINSTALLATION. - SEE SHEET MD113

1. SEE MECHANICAL DRAWINGS FOR VAV REMOVAL DETAILS.

2. REMOVE MEPF DEVICES AND CEILING MOUNTED SIGNAGE AS

NECESSARY TO PROVIDE ACCESS TO MECHANICAL EQUIPMENT.

SALVAGE AND PROTECT MEPF DEVICES AND SIGNAGE FOR

REINSTALLATION.

3. VAV BOX REPLACEMENT TO BE ACCOMPLISHED IN AN 8-HOUR PERIOD.

CEILING TILE TO BE REMOVED AND REPLACED AS REQUIRED TO CHANGE

OUT VAV BOX. LIGHTING FIXTURES, SPRINKLERS AND OTHER MEFP ITEMS

REQUIRED TO BE TEMPORARILY RELOCATED OR REMOVED FOR VAV BOX

REPLACEMENT, ARE REQUIRED TO BE REMOVED OR RELOCATED, AND

THEN REINSTALLED, WITHIN AN 8-HOUR PERIOD.

SHEET KEYED NOTES

STAIR 1

C S01

CHARLES YOUNG ROOM

C212

INDIVIDUAL STUDY AREA

C208

ELEV 1

E01

STAIR 2

C S02

JAN

C203

6 7

8 9

A

B

C

D

E

AA

BB

CC

DD

D.5

FF

A A

D

A1/AD113

A1/AD115

A1/AD116

AD114

S E

C T

E

V E

L

A R

C H

I T

E C

T U

R A

L

F

L O

A

N

D

E M

O

B B

A K

G

D P

B L

SCALE:

A1

ARCHITECTURAL FLOOR PLAN - DEMO - LEVEL 2 - SECTOR 4

1/8" = 1'-0"

NORTH

0 8' 16'4'

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

1. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS FOR GAS PIPE INSTALLATION. SALVAGE AND PROTECT CEILING

GRID AND TILE FOR REINSTALLATION. - SEE SHEET M-114

2. CUT WALL FOR INSTALLATION OF GAS LINE

SHEET KEYED NOTES

GENERAL SHEET NOTES

XX

1. REMOVE MEPF DEVICES AND CEILING MOUNTED SIGNAGE AS

NECESSARY TO PROVIDE ACCESS TO MECHANICAL EQUIPMENT.

SALVAGE AND PROTECT MEPF DEVICES AND SIGNAGE FOR

REINSTALLATION.

2. VAV BOX REPLACEMENT TO BE ACCOMPLISHED IN AN 8-HOUR PERIOD.

CEILING TILE TO BE REMOVED AND REPLACED AS REQUIRED TO CHANGE

OUT VAV BOX. LIGHTING FIXTURES, SPRINKLERS AND OTHER MEFP ITEMS

REQUIRED TO BE TEMPORARILY RELOCATED OR REMOVED FOR VAV BOX

SIPRNET CLASSROOM XXI

G247

SIPRNET CLASSROOM XXI

G250

LOBBY

G200

COPY / PRINT

G246

AV CLOSET

G249

AV CLOSET

G248

ELEV 3

E03

CLASSROOM XXI

G260

SCP CLASSROOM XXI

G266

SCP CLASSROOM XXI

G267

CLASSROOM XXI

G257

SCP CLASSROOM XXI

G273

SCP CLASSROOM XXI

G275

AV CLOSET

G274

AV CLOSET

G265 AV CLOSET

G268

LOBBY

G200

COPY / PRINT

G246

CORRIDOR

G209

COR

G

AV CLOSET

G249

AV CLOSET

G248

18 19 20 21 22

P

Q

R

S

T

U

V

A1\AD116

A A

D

AD115

S E

C T

E

V E

L

A R

C H

I T

E C

T U

R A

L

F

L O

A

N

D

E M

O

B B

A K

G

D P

B L

SCALE:

A1

ARCHITECTURAL FLOOR PLAN - DEMO - LEVEL 2 - SECTOR 5

1/8" = 1'-0"

NORTH

0 8' 16'4'

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

1. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS TO AFFECTED VAV FOR REPLACEMENT. SALVAGE AND PROTECT

CEILING GRID AND TILE FOR REINSTALLATION. - SEE SHEET MD115

1. SEE MECHANICAL DRAWINGS FOR VAV REMOVAL DETAILS.

2. REMOVE MEPF DEVICES AND CEILING MOUNTED SIGNAGE AS

NECESSARY TO PROVIDE ACCESS TO MECHANICAL EQUIPMENT.

SALVAGE AND PROTECT MEPF DEVICES AND SIGNAGE FOR

REINSTALLATION.

3. VAV BOX REPLACEMENT TO BE ACCOMPLISHED IN AN 8-HOUR PERIOD.

CEILING TILE TO BE REMOVED AND REPLACED AS REQUIRED TO CHANGE

OUT VAV BOX. LIGHTING FIXTURES, SPRINKLERS AND OTHER MEFP ITEMS

REQUIRED TO BE TEMPORARILY RELOCATED OR REMOVED FOR VAV BOX

REPLACEMENT, ARE REQUIRED TO BE REMOVED OR RELOCATED, AND

THEN REINSTALLED, WITHIN AN 8-HOUR PERIOD.

SHEET KEYED NOTES

VESTIBULE

G217A

VESTIBULE

G216A

JAN

G218

OFFICE

G222

OFFICE

G221

OFFICE

G220

OFFICE

G223

OFFICE

G226

OPEN OFFICE

G219

AV CLOSET

G238

SIPRNET CLASSROOM XXI

G239

SIPRNET CLASSROOM XXI

G240

AV CLOSET

G241

MEN

G217

WOMEN

G216

OFFICE

G224

OFFICE

G225

VENDING

G279

JJ

KK

LL

MM

NN

HH

GG

18 19 20 21 22

V

W

Y

X

A A

D

A1\AD113

A1\AD115

A1\AD114

AD116

S E

C T

E

V E

L

A R

C H

I T

E C

T U

R A

L

F

L O

A

N

D

E M

O

B B

A K

G

D P

B L

SCALE:

A1

ARCHITECTURAL FLOOR PLAN - DEMO - LEVEL 2 - SECTOR 6

1/8" = 1'-0"

NORTH

0 8' 16'4'

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

1. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS TO AFFECTED VAV FOR REPLACEMENT. SALVAGE AND PROTECT

CEILING GRID AND TILE FOR REINSTALLATION. - SEE SHEET MD116

2. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS FOR GAS PIPE INSTALLATION. SALVAGE AND PROTECT CEILING

GRID AND TILE FOR REINSTALLATION. - SEE SHEET M-116

3. CUT WALL FOR INSTALLATION OF GAS LINE

1. SEE MECHANICAL DRAWINGS FOR VAV REMOVAL DETAILS.

2. REMOVE MEPF DEVICES AND CEILING MOUNTED SIGNAGE AS

NECESSARY TO PROVIDE ACCESS TO MECHANICAL EQUIPMENT.

SALVAGE AND PROTECT MEPF DEVICES AND SIGNAGE FOR

REINSTALLATION.

3. VAV BOX REPLACEMENT TO BE ACCOMPLISHED IN AN 8-HOUR PERIOD.

CEILING TILE TO BE REMOVED AND REPLACED AS REQUIRED TO CHANGE

OUT VAV BOX. LIGHTING FIXTURES, SPRINKLERS AND OTHER MEFP ITEMS

REQUIRED TO BE TEMPORARILY RELOCATED OR REMOVED FOR VAV BOX

REPLACEMENT, ARE REQUIRED TO BE REMOVED OR RELOCATED, AND

THEN REINSTALLED, WITHIN AN 8-HOUR PERIOD.

SHEET KEYED NOTES

OFFICE

G230

AMSC OPS CENTER

G229

OFFICE

G231

OFFICE

G233

OFFICE

G235

OFFICE

G234

IDF

G227

OFFICE SUITE

G228

OFFICE SUITE

G232

ELEC

G237

STAIR 7

G S07

VESTIBULE

G212A

SIPRNET CLASSROOM XXI

G243

AV CLOSET

G245

SIPR

G236

SIPRNET DLDC CLASSROOM

G244

AV CLOSET

G242

V

W

Z

Y

X

22 23 24 25 26 27

A1\AD118

A

A

D

AD117

S E

C T

E

V E

L

A R

C H

I T

E C

T U

R A

L

F

L O

A

N

D

E M

O

B B

A K

G

D P

B L

SCALE:

A1

ARCHITECTURAL FLOOR PLAN - DEMO - LEVEL 2 - SECTOR 7

1/8" = 1'-0"

NORTH

0 8' 16'4'

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

1. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS TO AFFECTED VAV FOR REPLACEMENT. SALVAGE AND PROTECT

CEILING GRID AND TILE FOR REINSTALLATION. - SEE SHEET MD117

2. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS FOR GAS PIPE INSTALLATION. SALVAGE AND PROTECT CEILING

GRID AND TILE FOR REINSTALLATION. - SEE SHEET M-117

3. CUT WALL FOR INSTALLATION OF GAS LINE

1. SEE MECHANICAL DRAWINGS FOR VAV REMOVAL DETAILS.

2. REMOVE MEPF DEVICES AND CEILING MOUNTED SIGNAGE AS

NECESSARY TO PROVIDE ACCESS TO MECHANICAL EQUIPMENT.

SALVAGE AND PROTECT MEPF DEVICES AND SIGNAGE FOR

REINSTALLATION.

3. VAV BOX REPLACEMENT TO BE ACCOMPLISHED IN AN 8-HOUR PERIOD.

CEILING TILE TO BE REMOVED AND REPLACED AS REQUIRED TO CHANGE

OUT VAV BOX. LIGHTING FIXTURES, SPRINKLERS AND OTHER MEFP ITEMS

REQUIRED TO BE TEMPORARILY RELOCATED OR REMOVED FOR VAV BOX

REPLACEMENT, ARE REQUIRED TO BE REMOVED OR RELOCATED, AND

THEN REINSTALLED, WITHIN AN 8-HOUR PERIOD.

SHEET KEYED NOTES

ELEC

G210

VESTIBULE

G211A

ELEC

G255

SIPRNET DLDC CLASSROOM

G254

SIPRNET CLASSROOM XXI

G251

AV CLOSET

G253

AV CLOSET

G252

ELEC

G207

ELEC

G210

STAIR 6

G S06

BREAK AREA

G208

VESTIBULE

G204A

WOMEN

G206

ELEC

G205

CLASSROOM XXI

G261

SCP CLASSROOM XXI

G270

ELEC

G255

SCP CLASSROOM XXI

G276

AV CLOSET

G277

SCP CLASSROOM XXI

G278

AV CLOSET

G272

IDOR

MEN

G204

VESTIBULE

G206A

SCP CLASSROOM

G271

AV CLOSET

G253

AV CLOSET

G252

AV CLOSET

G269

STORAGE

G281

SCP CLASSROOM

G264

P

Q

R

S

T

U

V

22 23 24 25 26 27

A1\AD117

A

A

D

AD118

S E

C T

E

V E

L

A R

C H

I T

E C

T U

R A

L

F

L O

A

N

D

E M

O

B B

A K

G

D P

B L

SCALE:

A1

ARCHITECTURAL FLOOR PLAN - DEMO - LEVEL 2 - SECTOR 8

1/8" = 1'-0"

NORTH

0 8' 16'4'

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

1. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS TO AFFECTED VAV FOR REPLACEMENT. SALVAGE AND PROTECT

CEILING GRID AND TILE FOR REINSTALLATION. - SEE SHEET MD118

1. SEE MECHANICAL DRAWINGS FOR VAV REMOVAL DETAILS.

2. REMOVE MEPF DEVICES AND CEILING MOUNTED SIGNAGE AS

NECESSARY TO PROVIDE ACCESS TO MECHANICAL EQUIPMENT.

SALVAGE AND PROTECT MEPF DEVICES AND SIGNAGE FOR

REINSTALLATION.

3. VAV BOX REPLACEMENT TO BE ACCOMPLISHED IN AN 8-HOUR PERIOD.

CEILING TILE TO BE REMOVED AND REPLACED AS REQUIRED TO CHANGE

OUT VAV BOX. LIGHTING FIXTURES, SPRINKLERS AND OTHER MEFP ITEMS

REQUIRED TO BE TEMPORARILY RELOCATED OR REMOVED FOR VAV BOX

REPLACEMENT, ARE REQUIRED TO BE REMOVED OR RELOCATED, AND

THEN REINSTALLED, WITHIN AN 8-HOUR PERIOD.

SHEET KEYED NOTES

ELEC

C327

TR

C326

STAIR 4

C S04

ARCHIVES COLLECTION

C325

1 2 3 4 5

A

B

C

D

E

D.5

A

A

D

A1\AD122

AD121

S E

C T

E

V E

L

A R

C H

I T

E C

T U

R A

L

F

L O

A

N

D

E M

O

B B

A K

G

D P

B L

SCALE:

A1

ARCHITECTURAL FLOOR PLAN - DEMO - LEVEL 3 - SECTOR 1

1/8" = 1'-0"

NORTH

0 8' 16'4'

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

1. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS TO AFFECTED VAV FOR REPLACEMENT. SALVAGE AND PROTECT

CEILING GRID AND TILE FOR REINSTALLATION. - SEE SHEET MD121

2. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS FOR DUCTWORK REPLACEMENT. SALVAGE AND PROTECT

CEILING GRID AND TILE FOR REINSTALLATION. - SEE SHEET M-121 AND

MD121

1. SEE MECHANICAL DRAWINGS FOR VAV REMOVAL DETAILS.

2. REMOVE MEPF DEVICES AND CEILING MOUNTED SIGNAGE AS

NECESSARY TO PROVIDE ACCESS TO MECHANICAL EQUIPMENT.

SALVAGE AND PROTECT MEPF DEVICES AND SIGNAGE FOR

REINSTALLATION.

3. VAV BOX REPLACEMENT TO BE ACCOMPLISHED IN AN 8-HOUR PERIOD.

CEILING TILE TO BE REMOVED AND REPLACED AS REQUIRED TO CHANGE

OUT VAV BOX. LIGHTING FIXTURES, SPRINKLERS AND OTHER MEFP ITEMS

REQUIRED TO BE TEMPORARILY RELOCATED OR REMOVED FOR VAV BOX

REPLACEMENT, ARE REQUIRED TO BE REMOVED OR RELOCATED, AND

THEN REINSTALLED, WITHIN AN 8-HOUR PERIOD.

SHEET KEYED NOTES

G

H

J

K

L

1 2 3 4 5

A1/AD121

A

A

D

AD122

S E

C T

E

V E

L

A R

C H

I T

E C

T U

R A

L

F

L O

A

N

D

E M

O

B B

A K

G

D P

B L

SCALE:

A1

ARCHITECTURAL FLOOR PLAN - DEMO - LEVEL 3 - SECTOR 2

1/8" = 1'-0"

NORTH

0 8' 16'4'

US Army Corps of Engineers ®

SHEET ID

M

Y

C

O R

E

N G

I N

E E

R S

D E

S I G

N E

D

B

Y

B

A

M A

R K

D E

S C

R I P

T I O

N D

A T

E

C

D

F

E

G

1 2 3 4 5 6 7 8 9 10

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

T

E

S I Z

E

A N

S I

D

F I L

E

N

U M

B E

R

K A

N S

T

Y

D

I S

T R

I C

T

E

T

H

S

T R

E E

T

K A

N S

T

Y

M

O

H N

R

P O

R A

T I O

N

K

I R

K

D

R I V

E

K

A N

S A

S

C

I T

Y

M

O

BLDG 120

H V

P

A I R

S

B

U I L D

I N

G

F O

A V

E N

W O

R T

H

K

S

T A

D

M

B E

R

U S

A C

E

K

A N

S A

S

C

I T

Y

D

I S

T R

I C

T

C

I V

I L

P

L A

N N

I N

G

RTA

KEYPLAN

TRUE

NORTH

2 3

W

D Q

R

1. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS TO AFFECTED VAV FOR REPLACEMENT. SALVAGE AND PROTECT

CEILING GRID AND TILE FOR REINSTALLATION. - SEE SHEET MD122

2. REMOVE CEILING TILE AND GRID AS NECESSARY TO PROVIDE COMPLETE

ACCESS FOR DUCTWORK REPLACEMENT. SALVAGE AND PROTECT

CEILING GRID AND TILE FOR REINSTALLATION. - SEE SHEETS M-122 AND

MD122

1. SEE MECHANICAL DRAWINGS FOR VAV REMOVAL DETAILS.

2. REMOVE MEPF DEVICES AND CEILING MOUNTED…

This is the start of the file's text. The full file is on GovTribe.