Kenton_County_Airport_Board_South_Glycol_Pump_Station_II_East_-125_&_West-125_Interior_Inspection_Report_8-2-2023_(1).docx

DOCX document 32 MB Posted

Attached to
Tank Inspections & Repairs & On-Call Services
Solicitation number
26-031-ITB
Issued by
Bell County, Kentucky

About this file

This is an interior inspection report prepared for the Kenton County Airport Board at Cincinnati/Northern Kentucky International Airport (CVG) documenting the condition of the South Glycol Pump Station II tanks located in Hebron, Kentucky. The inspection, conducted on August 2, 2023, by NACE Certified Coating Inspector Gregory Charles Hardig Sr., evaluated the interior conditions of both the East 125 and West 125 tanks. The East 125 tank was found to be in good condition requiring no repairs. The West 125 tank was identified as requiring repairs at two locations: a 2-inch repair at the boot bridging two precast joints on the east end south side, and a 12-inch repair at the third seam from the east end. The recommended repair methodology involves cleaning the affected locations, abrading mating surfaces, applying CIM surface conditioner, patching with CIM trowel grade material, and resealing the joint.

The inspection report was commissioned by Scott Thacker, Sr. Manager of Environmental Operations at CVG, and serves as a foundation document for the related Kenton County Airport Board solicitation for Tank Inspections & Repairs & On-Call Services. Questions regarding this procurement are due by May 11, 2026, with answers posted by May 14, 2026, and bids must be received by May 21, 2026 at 2:00 pm. The inspection findings directly inform the scope of work and repair requirements that potential bidders must address in their proposals for the tank maintenance and repair contract.

View the file

Other files

File Type Posted
Tank_Inspections_&_Repairs_&_On-Call_Services_(Addendum_#2_Revision).pdf PDF
KCAB_Policy_#5102_Confined_Space_Entry_Plan.pdf PDF
Tank_Inspections_&_Repairs_&_On-Call_Services.pdf PDF
26-031-ITB_Tank_Inspection_&_Repair_Svcs_-_Ad.pdf PDF
26-031-ITB_Tank_Inspection_&_Repair_Services_-_Sample_Agreement_-_Attachment_C.pdf PDF
2_Mil_Sludge_Holding_Tank_-_B3.pdf PDF
2_Mil_Digester_#1_&_#2_-_Attachment_B2.pdf PDF
S_Glycol_Pump_Station_II_East_&_West_Inspection_Reports_-_Attachment_B1.pdf PDF
Petrograpic_Exam_CRT_Report_P-2020_Rev_w_Chem_Analysis_-_Attachment_A4.pdf PDF
3_Mil_Gallon_Tank_Inspection_Reports_-_South_Tank_2_-_Attachment_A3.pdf PDF
3_Mil_Gallon_Tank_Inspection_Reports_-_North_Tank_1_-_Attachment_A2.pdf PDF
2_Mil_Gallon_Tank_Inspections_Reports_-_Attachment_A1.pdf PDF
3_MIl.pdf PDF
2_Mil.pdf PDF
REV_Inspection_Report_Erlanger,_KY_2024R032_Tank_3_-_MLMDSS.pdf PDF
SludgeHT.pdf PDF
Dig_2.pdf PDF
REV_Inspection_Report_Erlanger,_KY_2024R032_Tank_2_-_MLMDSS.pdf PDF
DIG1.pdf PDF
REV_Inspection_Report_Erlanger,_KY_2024R032_Tank_1_-_MLMDDSS.pdf PDF
Petrograpic_Exam_CRT_Report_P-2020_Revision_with_Chem_Analysis.pdf PDF
Kenton_County_Airport_Board_South_Glycol_Pump_Station_II_West-125_Interior_Inspection_Report_8-7-2023.docx DOCX document
2018_Structural_Integrity_150k_Glycol_Holding_Tanks.pdf PDF
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Cincinnati / Northern Kentucky International Airport (CVG) Kenton County Airport Board South Glycol pump Station 2 East 125 Tank & West 125 tank Hebron KY 41048 Interior Inspection Report

August 2, 2023

Report commissioned by:

Scott Thacker, Sr. Manager Environmental Operations Cincinnati / Northern Kentucky International Airport (CVG) Kenton County Airport Board P.O. Box 752000 Cincinnati, OH 45275 Sthacker@cvgairport.com

Prepared by:

Gregory Charles Hardig Sr.

NACE CIP Level-3 Cert # 3494

General:

The plan for the day is to inspect the General condition of the South Glycol Pump Station II East & West 125 tank Interiors.

With JSA and a meaningful discussion on safety complete, we are using a 5x gas air monitor to find the tank safe for entry.

In the WEST tank there were two repairs identified. The First was about 2” long where the boot bridges the two precast joints. (East end, South side last joint.)

The second spot is located at the third seam from the east end and is about 12” long.

Summary:

The EAST 125 tank is in good shape and no repairs are needed.

The WEST 125 tank has two spots that need repairs. The method would be to clean the location and abrade the mating surfaces. Then apply CIM surface conditioner and patch with CIM Trowel grade the re-seal the joint.

Please feel free to reach out with any questions.

Respectfully submitted.

Gregory Charles Hardig Sr.

NACE Certified Coating Inspector Level-3 Cert #3494 My commission expires April 2025

Note: This report was assembled using the best means available in the current conditions. While we have applied our best experience and academic research to our conclusions, field conditions and recommendations are subject to change and the engineer/inspector assumes no liability for its use or outcome as contained in this report.

Corrosion Protection Resources LLC. All rights reserved www.cprcoatings.com