DIG1.pdf

PDF 6 MB Posted

Attached to
Tank Inspections & Repairs & On-Call Services
Solicitation number
26-031-ITB
Issued by
Bell County, Kentucky

About this file

This file contains two interior inspection reports prepared by NACE Certified Coating Inspector Gregory Charles Hardig Sr. for the Kenton County Airport Board's 2-million gallon above-ground concrete digester located in Hebron, Kentucky, at Cincinnati/Northern Kentucky International Airport (CVG). The first inspection, dated August 4, 2023, documented the general condition of Digester #1's interior, including surface preparation with grout and sand broadcasting, application of a surface conditioner, and installation of a 60-mil coating using a cement-based material (CIM). The second inspection report, dated September 8-10, 2025, detailed the discovery and repair of a vertical wall crack on the east-north-east side of the tank that was approximately 10-12 inches wide and 10 feet tall. The crack repair process involved removal of corroded steel reinforcement, abrasive blasting, application of crack filler, primer, and two lifts of CIM trowel-grade coating totaling 65-100 mils. Both inspections were commissioned by Scott Thacker, Sr. Manager Environmental Operations at CVG.

The inspection reports serve as supporting documentation for the related Kenton County Airport Board contract opportunity for Tank Inspections & Repairs & On-Call Services, with questions due by May 11, 2026, and bids due by May 21, 2026 at 2:00 pm. The reports demonstrate the scope and complexity of work required for the tank's ongoing maintenance and restoration, including interior access procedures, safety protocols (JSA and gas monitoring), detailed photographic documentation of work progress, material specifications, and batch number recording. The inspector's qualifications included NACE Level-3 certification (expiring April 2025) and affiliation with Corrosion Protection Resources LLC, indicating the specialized expertise required for this infrastructure project.

View the file

Other files

File Type Posted
Tank_Inspections_&_Repairs_&_On-Call_Services_(Addendum_#2_Revision).pdf PDF
KCAB_Policy_#5102_Confined_Space_Entry_Plan.pdf PDF
Tank_Inspections_&_Repairs_&_On-Call_Services.pdf PDF
26-031-ITB_Tank_Inspection_&_Repair_Svcs_-_Ad.pdf PDF
26-031-ITB_Tank_Inspection_&_Repair_Services_-_Sample_Agreement_-_Attachment_C.pdf PDF
2_Mil_Sludge_Holding_Tank_-_B3.pdf PDF
2_Mil_Digester_#1_&_#2_-_Attachment_B2.pdf PDF
S_Glycol_Pump_Station_II_East_&_West_Inspection_Reports_-_Attachment_B1.pdf PDF
Petrograpic_Exam_CRT_Report_P-2020_Rev_w_Chem_Analysis_-_Attachment_A4.pdf PDF
3_Mil_Gallon_Tank_Inspection_Reports_-_South_Tank_2_-_Attachment_A3.pdf PDF
3_Mil_Gallon_Tank_Inspection_Reports_-_North_Tank_1_-_Attachment_A2.pdf PDF
2_Mil_Gallon_Tank_Inspections_Reports_-_Attachment_A1.pdf PDF
3_MIl.pdf PDF
2_Mil.pdf PDF
Kenton_County_Airport_Board_South_Glycol_Pump_Station_II_East_-125_&_West-125_Interior_Inspection_Report_8-2-2023_(1).docx DOCX document
REV_Inspection_Report_Erlanger,_KY_2024R032_Tank_3_-_MLMDSS.pdf PDF
SludgeHT.pdf PDF
Dig_2.pdf PDF
REV_Inspection_Report_Erlanger,_KY_2024R032_Tank_2_-_MLMDSS.pdf PDF
REV_Inspection_Report_Erlanger,_KY_2024R032_Tank_1_-_MLMDDSS.pdf PDF
Petrograpic_Exam_CRT_Report_P-2020_Revision_with_Chem_Analysis.pdf PDF
Kenton_County_Airport_Board_South_Glycol_Pump_Station_II_West-125_Interior_Inspection_Report_8-7-2023.docx DOCX document
2018_Structural_Integrity_150k_Glycol_Holding_Tanks.pdf PDF
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Inspection Report 8-4-2023

Cincinnati / Northern Kentucky International Airport

(CVG)

Kenton County Airport Board 2-Million gallon Above-ground Concrete

Digester # 1 Hebron KY 41048

Interior Inspection Report

August 4, 2023

Report commissioned by:

Scott Thacker, Sr. Manager Environmental Operations

Cincinnati / Northern Kentucky International Airport (CVG) Kenton County Airport Board

P.O. Box 752000 Cincinnati, OH 45275

Sthacker@cvgairport.com

Prepared by:

Gregory Charles Hardig Sr.

NACE CIP Level-3 Cert # 3494 mailto:Sthacker@cvgairport.com

General:

The plan for the day is to inspect the General condition of the #1 Digester 2-Mil Above-ground tank Interior.

With JSA and a meaningful discussion on safety complete, we are using a 5x gas air monitor to find the tank safe for entry.

The workers mixed the grout poured it out and then troweled it evenly onto the surface. They then broadcast sand into the top to aid in the adhesion of the CIM.

Workers mixed the CIM and first applied the surface conditioner, then poured out and using a notched squeegee applied the 60/mil coating.

It is noted that there was some slight outgassing, but it will not effect the abrasion resistance service.

Please feel free to reach out with any questions.

Respectfully submitted.

Gregory Charles Hardig Sr.

NACE Certified Coating Inspector Level-3 Cert #3494 My commission expires April 2025

Note: This report was assembled using the best means available in the current conditions. While we have applied our best experience and academic research to our conclusions, field conditions and recommendations are subject to change and the engineer/inspector assumes no liability for its use or outcome as contained in this report.

Corrosion Protection Resources LLC. All rights reserved www.cprcoatings.com http://www.cprcoatings.com/

Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025

Cincinnati / Northern Kentucky International Airport

(CVG)

Kenton County Airport Board 2-Million gallon Above-ground Concrete

Digester # 1 Hebron KY 41048

Interior Wall Crack Repair

Inspection Report

September 8 & 10, 2025

Report commissioned by:

Scott Thacker, Sr. Manager Environmental Operations

Cincinnati / Northern Kentucky International Airport (CVG) Kenton County Airport Board

P.O. Box 752000 Cincinnati, OH 45275

Sthacker@cvgairport.com

Prepared by:

Gregory Charles Hardig Sr.

NACE CIP Level-3 Cert # 3494 mailto:Sthacker@cvgairport.com

Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025

9-8-2025 General:

The plan for Digester #1 2-Mil Above-ground tank it to repair the open and spalled vertical wall crack noticed by CVG work crew.

With JSA and a meaningful discussion on safety complete, the crew began lowering scaffolding down into the tank. Two towers were setup.

Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025

We made safe entry and walked to parameter visually inspecting the walls for cracks.

The crack was swelling and raised from the rest of the surface of the interior wall on the east-north-east side of the tank

Scaffolding was built

Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025

We sounded it first with a hammer and then a chain. It appears to be about 10 to 12“ wide and about 10’ tall.

We put a pry bar in the center, and the surface concrete easily gave way. This the right side of the soft steel.

Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025

The steel was heavily corroded and not adhered to the exterior concrete.

The center of the crack is over a lap joint in the steel.

We pealed the loose lap steel and behind it was duct tape.

Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025

Overall look:

Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025

September 10-2025 We consulted the material supplier technical rep. He recommended that we cut out the loose corroded steel.

Abrasive blast the steel and surrounding, then contour and base fill the edges using 615CF crack filler.

Apply the EMT primer to the cement. Finish the repair with two lifts 70 to 80 mils each CIM Trowel grade.

Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025

After the crack repair filler was set, the high spots were grounded smooth. Then the first lift of CIM Trowel grade was applied. Batch numbers were recorded.

Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025

Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025

After the first lift was set up, the second lift was applied.

65-100/mils were applied in total.

Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025

Summary:

The crack was cleaned & blasted, primed and filler and waterproofing applied.

All work was completed in specification.

Please feel free to reach out with any questions.

Respectfully submitted.

Gregory Charles Hardig Sr.

NACE Certified Coating Inspector Level-3 Cert #3494 My commission expires April 2025

Note: This report was assembled using the best means available in the current conditions. While we have applied our best experience and academic research to our conclusions, field conditions and recommendations are subject to change and the engineer/inspector assumes no liability for its use or outcome as contained in this report.

Corrosion Protection Resources LLC. All rights reserved www.cprcoatings.com http://www.cprcoatings.com/

Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Inspection Report 8-4-2023
Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025

File details come from the government source that posted it. Updated .