This file contains interior inspection reports for two 2-million gallon above-ground concrete digesters owned by the Kenton County Airport Board at Cincinnati/Northern Kentucky International Airport (CVG) in Hebron, Kentucky. The reports document inspection and repair activities conducted between August 2023 and September 2025 by NACE Certified Coating Inspector Gregory Charles Hardig Sr. Digester #1 underwent initial interior inspection on August 4, 2023, involving grout application, sand broadcasting, and application of a 60-mil coating using a surface conditioner and ceramic-impregnated mortar (CIM). Subsequently, on September 8-10, 2025, Digester #1 required interior wall crack repair after CVG work crew identified an open and spalled vertical crack on the east-north-east side of the tank. The inspection revealed heavily corroded soft steel within a 10-12 inch wide by 10-foot tall crack located over a lap joint, along with deteriorated duct tape. Digester #2 required two separate repair efforts: a temporary wall cap crack repair on October 27, 2023, using polysulfide elastomeric sealant, and a more comprehensive wall and cap crack repair with waterproofing conducted June 18-20, 2024, involving abrasive blasting, diamond wheel grinding, primer application, and CIM 1000 pre-mix waterproofing application.
All repair work was performed to specification according to the inspecting engineer's recommendations, with materials including CIM trowel grade, EMT epoxy primer, crack filler, and waterproofing coatings. Batch numbers were recorded for quality control purposes, and work included scaffolding installation for safe interior access. The reports note attention to detail in sealed holes in the cap and crack areas near ladder access points. These inspection reports serve as supporting documentation for the Kenton County Airport Board's Tank Inspections & Repairs & On-Call Services contract opportunity, with bids due May 21, 2026, at 2:00 pm, and questions due by May 11, 2026, at 11:59 pm.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Inspection Report 8-4-2023
Cincinnati / Northern Kentucky International Airport
(CVG)
Kenton County Airport Board 2-Million gallon Above-ground Concrete
Digester # 1 Hebron KY 41048
Interior Inspection Report
August 4, 2023
Report commissioned by:
Scott Thacker, Sr. Manager Environmental Operations
Cincinnati / Northern Kentucky International Airport (CVG) Kenton County Airport Board
P.O. Box 752000 Cincinnati, OH 45275
Sthacker@cvgairport.com
Prepared by:
Gregory Charles Hardig Sr.
NACE CIP Level-3 Cert # 3494 mailto:Sthacker@cvgairport.com
General:
The plan for the day is to inspect the General condition of the #1 Digester 2-Mil Above-ground tank Interior.
With JSA and a meaningful discussion on safety complete, we are using a 5x gas air monitor to find the tank safe for entry.
The workers mixed the grout poured it out and then troweled it evenly onto the surface. They then broadcast sand into the top to aid in the adhesion of the CIM.
Workers mixed the CIM and first applied the surface conditioner, then poured out and using a notched squeegee applied the 60/mil coating.
It is noted that there was some slight outgassing, but it will not effect the abrasion resistance service.
Please feel free to reach out with any questions.
Respectfully submitted.
Gregory Charles Hardig Sr.
NACE Certified Coating Inspector Level-3 Cert #3494 My commission expires April 2025
Note: This report was assembled using the best means available in the current conditions. While we have applied our best experience and academic research to our conclusions, field conditions and recommendations are subject to change and the engineer/inspector assumes no liability for its use or outcome as contained in this report.
Corrosion Protection Resources LLC. All rights reserved www.cprcoatings.com http://www.cprcoatings.com/
Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025
Kenton County Airport Board 2-Million gallon Above-ground Concrete
Digester # 1
Interior Wall Crack Repair
Inspection Report
September 8 & 10, 2025
Cincinnati / Northern Kentucky International Airport (CVG) Kenton County Airport Board
P.O. Box 752000
Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025
9-8-2025
The plan for Digester #1 2-Mil Above-ground tank it to repair the open and spalled vertical wall crack noticed by CVG work crew.
With JSA and a meaningful discussion on safety complete, the crew began lowering scaffolding down into the tank. Two towers were setup.
Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025
We made safe entry and walked to parameter visually inspecting the walls for cracks.
The crack was swelling and raised from the rest of the surface of the interior wall on the east-north-east side of the tank
Scaffolding was built
Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025
We sounded it first with a hammer and then a chain. It appears to be about 10 to 12“ wide and about 10’ tall.
We put a pry bar in the center, and the surface concrete easily gave way. This the right side of the soft steel.
Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025
The steel was heavily corroded and not adhered to the exterior concrete.
The center of the crack is over a lap joint in the steel.
We pealed the loose lap steel and behind it was duct tape.
Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025
Overall look:
Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025
September 10-2025 We consulted the material supplier technical rep. He recommended that we cut out the loose corroded steel.
Abrasive blast the steel and surrounding, then contour and base fill the edges using 615CF crack filler.
Apply the EMT primer to the cement. Finish the repair with two lifts 70 to 80 mils each CIM Trowel grade.
Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025
After the crack repair filler was set, the high spots were grounded smooth. Then the first lift of CIM Trowel grade was applied. Batch numbers were recorded.
Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025
Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025
After the first lift was set up, the second lift was applied.
65-100/mils were applied in total.
Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025
Summary:
The crack was cleaned & blasted, primed and filler and waterproofing applied.
All work was completed in specification.
Please feel free to reach out with any questions.
Respectfully submitted.
Gregory Charles Hardig Sr.
NACE Certified Coating Inspector Level-3 Cert #3494 My commission expires April 2025
Note: This report was assembled using the best means available in the current conditions. While we have applied our best experience and academic research to our conclusions, field conditions and recommendations are subject to change and the engineer/inspector assumes no liability for its use or outcome as contained in this report.
Kenton County Airport Board 2-Mil Above-ground Digester # 2 Wall & cap crack Repair & Waterproofing Inspection Report 6-24-
Kenton County Airport Board 2-Million gallon Above-ground Concrete
Digester # 2 Hebron KY 41048
Wall Cap Crack Repair Waterproofing and coating
Inspection Report
June 25, 2024
Cincinnati / Northern Kentucky International Airport (CVG) Kenton County Airport Board
P.O. Box 752000
Kenton County Airport Board 2-Mil Above-ground Digester # 2 Wall & cap crack Repair & Waterproofing Inspection Report 6-24-
6-18-2024
The plan is to repair on the crack in the wall cap and down the inside of the wall, waterproof the cap and crack area, and to wash and waterproof the exterior surfaces on #2 Digester 2-Mil Above-ground tank.
With JSA and a meaningful discussion on safety complete, the crew began lowering scaffolding down into the tank. Two towers were setup.
Kenton County Airport Board 2-Mil Above-ground Digester # 2 Wall & cap crack Repair & Waterproofing Inspection Report 6-24-
The washing equipment was set up and washing began.
6-19-2024 The abrasive blast equipment was set up and blasting took place on the cap and inside of the walls where the cracks were noted.
Kenton County Airport Board 2-Mil Above-ground Digester # 2 Wall & cap crack Repair & Waterproofing Inspection Report 6-24-
The crack on the cap was also ground out with a diamond wheel.
Kenton County Airport Board 2-Mil Above-ground Digester # 2 Wall & cap crack Repair & Waterproofing Inspection Report 6-24-
Kenton County Airport Board 2-Mil Above-ground Digester # 2 Wall & cap crack Repair & Waterproofing Inspection Report 6-24-
6-20-2024 the crew moved to night shift to give the coatings better conditions for application and cure.
The crew masked off the exterior of the cap before coating application began.
A mix station was set up and batch numbers were recorded.
Kenton County Airport Board 2-Mil Above-ground Digester # 2 Wall & cap crack Repair & Waterproofing Inspection Report 6-24-
CIM EMT Epoxy primer was used on the cap before application of the CIM 1000 pre-mix Waterproofing
Kenton County Airport Board 2-Mil Above-ground Digester # 2 Wall & cap crack Repair & Waterproofing Inspection Report 6-24-
Material was mixed in small batches and applied using a brush. WFT was recorded at 15-20/mils/WFT were recorded.
Kenton County Airport Board 2-Mil Above-ground Digester # 2 Wall & cap crack Repair & Waterproofing Inspection Report 6-24-
It is noted that there were 3 holes about 3/8th” in dia. Located in the cap on the south side of the tank. The crew sealed them. After cure of the primer, the CIM 1000 was mixed and applied by brush.
Kenton County Airport Board 2-Mil Above-ground Digester # 2 Wall & cap crack Repair & Waterproofing Inspection Report 6-24-
Extra attention was given to the holes in the cap.
Kenton County Airport Board 2-Mil Above-ground Digester # 2 Wall & cap crack Repair & Waterproofing Inspection Report 6-24-
Also the crack near the ladder area.
The crack was cleaned & blasted, primed and filler and waterproofing applied.
The cap was blasted and waterproofed ready to receive top coating.
The exterior walls were washed and ready to receive waterproofing.
Please feel free to reach out with any questions.
Respectfully submitted.
Gregory Charles Hardig Sr.
NACE Certified Coating Inspector Level-3 Cert #3494 My commission expires April 2025
Note: This report was assembled using the best means available in the current conditions. While we have applied our best experience and academic research to our conclusions, field conditions and recommendations are subject to change and the engineer/inspector assumes no liability for its use or outcome as contained in this report.
Kenton County Airport Board 2-Mil Above-ground Digester # 2 Wall Cap Crack Repair Inspection Report 10-27-2023
Kenton County Airport Board 2-Million gallon Above-ground Concrete
Digester # 2
Wall Cap Crack Repair Inspection Report
October 27, 2023
Cincinnati / Northern Kentucky International Airport (CVG) Kenton County Airport Board
P.O. Box 752000
Kenton County Airport Board 2-Mil Above-ground Digester # 2 Wall Cap Crack Repair Inspection Report 10-27-2023
The plan for the day is to Complete a temporary repair on the crack in the wall cap on #2 Digester 2-Mil Above-ground tank.
With JSA and a meaningful discussion on safety complete, we began scraping the crack area. All work will be done off the stairs mounted to the outside of the wall around the crack.
Kenton County Airport Board 2-Mil Above-ground Digester # 2 Wall Cap Crack Repair Inspection Report 10-27-2023
A Polysulfide elastomeric sealant will be used to make the seal.
Kenton County Airport Board 2-Mil Above-ground Digester # 2 Wall Cap Crack Repair Inspection Report 10-27-2023
The crack was cleaned, solvent wiped, and sealant applied. This will stabilize the area till more long term repairs can be completed in the spring.
Please feel free to reach out with any questions.
Respectfully submitted.
Gregory Charles Hardig Sr.
NACE Certified Coating Inspector Level-3 Cert #3494 My commission expires April 2025
Note: This report was assembled using the best means available in the current conditions. While we have applied our best experience and academic research to our conclusions, field conditions and recommendations are subject to change and the engineer/inspector assumes no liability for its use or outcome as contained in this report.
http://www.cprcoatings.com/
| Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Inspection Report 8-4-2023 |
| Kenton County Airport Board 2-Mil Above-ground Digester # 1 Interior Wall crack Repair Inspection Report 9-8-2025 |
| 6b. 2 Mil Digester 2 - B2.pdf |
| Kenton County Airport Board 2-Mil Above-ground Digester # 2 Wall & cap crack Repair & Waterproofing Inspection Report 6-24-2024 |
| Kenton County Airport Board 2-Mil Above-ground Digester # 2 Wall cap crack Repair Inspection Report 10-27-2023 |
File details come from the government source that posted it. Updated .