J01d Drawings - PIMC CP and IR.pdf

PDF 13 MB Posted

Attached to
PIMC Mechanical Projects: HVAC and Central Plant & Isolation Rooms in Phoenix, AZ, Maricopa, County
Solicitation number
75H701-25-R-00001
Issued by

About this file

This is a 38-page construction drawing set detailing mechanical, electrical, and plumbing plans for renovations at the Phoenix Indian Medical Center (PIMC). The drawings cover two main project areas: (1) Central Plant Building 234 modifications including replacement of cooling tower valves, a heat exchanger, medical air system components, and installation of a new parking canopy, and (2) Main Hospital Building 233 third floor isolation rooms requiring above-ceiling ductwork replacement and associated ceiling/lighting adjustments.

The drawing set includes detailed floor plans, demolition plans, mechanical isometrics, electrical one-line diagrams, and equipment schedules. Key components shown include: new medical air compressor system with 7.5 HP triplex scroll configuration, duplex fuel oil pump system, dust collection system for the carpentry shop, and modifications to cooling tower piping and valves. The electrical scope includes relocating automatic transfer switches and providing power connections for new mechanical equipment. The drawings indicate phased construction requirements for maintaining operations, particularly for the isolation rooms which must maintain negative pressure relationships during renovations.

View the file

Other files

File Type Posted
B05 Amendment A00007 (75H70125R00001).pdf PDF
B05 Amendment A00006 (75H70125R00001).pdf PDF
B05 Amendment A00005 (75H70125R00001).pdf PDF
B05 Amendment A00004 (75H70125R00001).pdf PDF
Site Visit Sign-in (75H70125R00001).pdf PDF
J04 2025 Exemption Letter for a Qualifying Hospital.pdf PDF
B05 Amendment A00003 (75H70125R00001).pdf PDF
J02 WD AZ20250039 2025.01.03.pdf PDF
B05 Amendment A00002 (75H70125R00001).pdf PDF
B05 Amendment A00001 (75H70125R00001).pdf PDF
J01a Specifications - PIMC HVAC.pdf PDF
J01f PIMC Asbestos Survey - Bldg 233 Hospital (Feb 2003).pdf PDF
J01c Specifications - PIMC CP and IR.pdf PDF
B01 RFP 75H701-25-R-00001 PIMC HVAC CP and IR.pdf PDF
J01e Location Map.pdf PDF
J02 WD AZ20240039 Mod 6 2024.09.06.pdf PDF
J08 OF 306 Declaration for Federal Employment.pdf PDF
J04 2024 Exemption Letter for a Qualifying Hospital.pdf PDF
J09 Addendum to OF-306 (Childcare Form).pdf PDF
J05 Company Specialized Experience Form Construction.pdf PDF
J03 Self Performed Calculation Sheet.pdf PDF
J04a FORMS_TPT_5000HC_11228.pdf PDF
J01b Drawings - PIMC HVAC.pdf PDF
J06 PPQ.pdf PDF
J01h Above Ceiling Work Permit.pdf PDF
J07 IHS IEE Representation Form.pdf PDF
J01g Infection Control Risk Assessment Permit.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

R

VI

H

P

S

NI

D

C E

I

A

A N

HE TL H

SE

E

H

N M

E A R

P

T

OF

T

C D

SU

S

A

E

TAE L &H

N

VI

S E

R

UM

A

H U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

INDIAN HEALTH SERVICE

DIVISION OF FACILITIES ENGINEERING

PHOENIX AREA

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

4636 N. 32nd Street

Phoenix, Arizona 85018

480.980.9054 Fax 520.795.6171

www.bwsarchs.com

ARCHITECTS

CONSULTANTSOWNER

CONSTRUCTION DOCUMENTS

DRAWINGS

Indian Health Service

PIMC MECHANICAL PROJECT 2 -

ROOMS (BLDG234)

CENTRAL PLANT & ISOLATION

EEC, Inc

555 E. River Road, #301

Tucson, AZ 85704

Phone: 502.321.4625

Zona Technical Eng

6422 E. Speedway Blvd., Unit 130

Tucson, AZ 85710

Phone: 520.200.2612

Turner Structural

2806 N. Alvernon Way, Suite 400

Tucson, AZ 85712

Phone: 520.323.3422

CIVIL MEP STRUCTURAL

4212 N 16th Street

Phoenix, AZ 85016

1/15/2024

B W

S P ro je ct N o.

.0

IHS Project No.:PH22PH03H6

P

IM

C C

E N

T R

A L

P

LA

N T

I S O

LA

T

IO

N R

O O

M S

1/

/2

N

6t h S tr ee t

P ho en ix

, A Z

In d ia n H e a lt h S e rv ic e

MATCH LINE

IDENTIFYING REVISION

CODE DESIGNATION

CLOUD ENCLOSES

REVISION

ELEVATION INDICATOR

REVISION CLOUD

KEYNOTE TAG

WALL TYPE

MATCH LINE

SHEET WHERE DRAWN

DOOR NUMBER

DOOR MARK

ROOM NUMBER

ELEVATION REFERENCE NO.

SHEET WHERE DRAWN

DETAIL NUMBER

DRAWING NUMBER

SHEET WHERE DRAWN

SHEET WHERE DRAWN

SECTION NUMBER

ROOM NAME AND NUMBER

WINDOW MARK

DOOR MARK

EXTERIOR ELEVATION

INTERIOR ELEVATION

DETAIL MARK

ENLARGED AREA OR

WALL SECTION

SECTION LETTER

BUILDING SECTION

COLUMN GRID

16'- 0" A.F.F.

FF ELEV

A101

SIM

A101

SIM

View Name

SCALE: 1/8" = 1'-0"

/1 A101

/1 A101

1t

ROOM NAME

A6.1

A5.1

A1

1 1

A101

SIM

RIGHT OF WAYROW

EW EACH WAY

JT

JST

JOINT

JOIST

LLH LONG LEG HORIZONTAL

LIGHTWEIGHT

LOW POINT

LONG LEG VERTICAL

LT

LVR

LTWT

LP

LLV

LIGHT

LOUVER

LABORATORY

LINEAL FEET

KNOCK OUT

KICK PLATE

LENGTH, LONG

KNOCKED DOWN

LEFT HAND

LAB

LF

LAV

LAM

L

LH

LL

LAVATORY

LAMINATE

LIVE LOAD

KIT

KO

KD

KP

KITCHEN

GALV GALVANIZED

HP HIGH POINT

HEATING/VENTILATING/

INSULATED COMPOSITE

INSIDE DIAMETER

INCLUDING

INVERT ELEVATION

INSULATION

AIR CONDITIONING

HOT WATER

METAL WALL PANEL

JANITORS CLOSET

ID

IE

IN

INCL

INT

INSUL

JC

INCH(ES)

INTERIOR

HR

HVAC

HW

ICMWP

HOUR

HOSE BIBB

HOLLOW CORE

HARDBOARD

HARDWOOD

HARDWARE

HEAVY DUTY

GENERAL CONTRACT(OR)

GLASS, GLAZING

GYPSUM WALLBOARD

HORIZONTAL

HOLLOW METAL

HIGH IMPACT WOOD FIBER PANEL

H(T) HEIGHT

HDWD

HDWR

HB

HC

HDBD

HD

HORZ

HM

GC

GD

GL

GYP

GWB

HIW

GYPSUM

GRADE

FF FINISH FLOOR

FIBER REINFORCED PLASTIC

FIREPROOF

FOOT,FEET

FIRE RETARDANT

FURRED(ING)

FLUORESCENT

GAGE,(GUAGE)

FT

FTG

FUR

FUT

GA

FOOTING

FUTURE

FO

FP

FLUOR

FIN

FLA

FLEX

FRP

FR

FACE OF

FLASHING

FLEXIBLE

FINSH(ED)

EXTERIOR FINISH SYSTEM

FLOOR DRAIN

FOUNDATION

FIRE EXTINGUISHER

FABRICATE

EXPANSION

FAHRENHEIT

FIRE ALARM

ELECTRIC WATER COOLER

EXCAVAT(E)(ION)

FIRE EXTINGUISHER(CABINET)

EXT. INSULATION FINISH SYSTEM

FD

FE

FDN

F

FA

FAB

FEC

EXIST

EXH

EXP

EXT

EWC

EXC

EFS

EIFS

EXHAUST

EXISTING

EXTERIOR

VINYL WALL COVERINGVWC

WAINSCOTWSCT

WELDED WIRE FABRIC

YD

WT

WWF

YARD

WEIGHT

WIDTH, WIDE, WEST

WATERPROOFING

WATER REPELLENT

WALL HUNG, WATER HEATER

WOODWD

WH

WM

WP

WI

WDW

WR

WS

WIRE MESH

WINDOW

WROUGHT IRON

WEATHERSTRIP

W/

W/O

W

W/W

WC

WITHOUT

WITH

WALL TO WALL

WATER CLOSET

SYMMETRY(ICAL)SYM

TOP OF WALLTOW

TOILET PAPER DISPENSER

VINYL COMPOSITION TILE

UNLESS NOTED OTHERWISE

VENEER PLASTER

UNDERWRITERS LABORATORY

UNFINISHEDUNF

UNO

VB

VCT

VNR

VPL

VERT

VAPOR BARRIER

VENEER

VERTICAL

TPD

TV

TYP

U

UL

UG

TYPICAL

TELEVISION

URINAL

UNDERGROUND

THICKNESS, TEE

TONGUE AND GROOVE

TOP OF MASONRY

TOP OF CONCRETE

TOP OF PARAPET

TEMPERATURE, TEMPORARYTEMP

TERR

THK

TO

TOIL

TOM

TOC

TOS

TOP

TERRAZZO

THICK(NESS)

TOP OF

TOILET

TOP OF STEEL

T

T&G

TB

TD

TEL

TACKBOARD

TRENCH DRAIN

TELEPHONE

SHEET METALSM

SPECIFICATIONS

SEAMLESS VINYL

STAINLESS STEEL

SOUND TRANSMISSION COEFFICIENTSTC

STRUC

SV

SW

STD

STOR

SUSP

SWR

SWITCH

STANDARD

STORAGE

SUSPENDED

STRUCTURAL

SEWER

SQ

SS

SPECS

SP

SPKR

SPL

ST

SST

SQUARE

SPECIAL

SPEAKER

SERVICE SINK

SOUNDPROOF

STEEL, STREET

RAINWATER LEADER

SURFACE MOUNTED

SCHEDULESCHED

SF

SHWR

SHEET

SD

SDG

SECT

SIM

SHOWER

SHEET

SECTION

SIDING

SQUARE FEET

STORM DRAIN

SIMILAR

RWL

S

(S)

REQ'D

SC

REQUIRED

SEALED, SOUTH

SOLID CORE

BRG BEARING

CPT CARPET

DS DOWNSPOUT

ELEVATION, ELEVATOR

DRYWALL CHANNELS (HAT)

EPOXY PAINT

EMERGENCY

EQUIPMENT

EXPOSED STRUCTURE

EACH FACE

EXPANSION JOINT

ELECTRIC(AL)ELEC

EQUIP

EP

EQ

EMER

ES

ELEV

EST

EQUAL

ESTIMATE

DWG

DWC

DTL

EA

EF

E

EJ

DRAWING

DETAIL

EACH

EAST

DEMOLISH, DEMOLITION

DRINKING FOUNTAIN

DISPENSER

DIMENSION

DAMPPROOFING

COUNTERSINK

COLD WATER

CUBIC FOOT (FEET)

CERAMIC TILE

DIA

DF

DIAMETER

DN

DIAG

DIM

DISP

DO

DP

DR

DIAGONAL

DOWN

DITTO

DOOR

CT

CU FT

CW

CU

CSK

D

DEMO

CUBIC

DEPTH

CG CORNER GUARD

CORRIDOR,CORRUGATED

CONTINUOUS OR CONTINUE

CORRUGATED METAL PIPE

CONCRETE MASONRY UNIT

COMMENTS

CONSTRUCTION

CONNECTION

CONCRETE

CLEAN OUT

COMBINATION

CAST IRON

CONTROL JOINT

CLEAR(ANCE)

CAST IN PLACE

CO

CORR

CONST

CONT

CONN

COMB

CONC

COL COLUMN

CMTS

CMU

CI

CJ

CLG

CLR

CIP

CMP

CEILING

CONTRACTOR FURNISHED,

CONTRACTOR INSTALLED

CONTRACTOR FURNISHED,

CHALK BOARD,CATCH BASIN

OWNWER INSTALLED

COMPOSITE METAL

CENTER TO CENTER

WALL PANEL

BASEMENT

BUILT UP ROOFING

C/C

CFOI

CAB

CEM

CFCI

CB

CABINET

CEMENT

CMWP

C

BRK

BSMT

BUR

CHANNEL

BRICK

AC ACOUSTICAL CEILING

BLOCK(ING)

BENCH MARK

BOTTOM OF

ALUMINUM

AGGREGATE

ALTERNATE

BELOW FINISH FLOOR

ANCHOR, ANCHORAGE

ABOVE FINISH FLOOR

BLDG

BLK(G)

BM

BO

BOT

BFF

BD

BUILDING

BOTTOM

BOARD

AGG

ALT

ALUM

ANOD

ANCH

ADJ

AFF

ANODIZED

ADJACENT

AGGREGATE BASE COURSE

AIR CONDITIONING

ANCHOR BOLT

A/C

ABC

AB

AT

NOM NOMINAL

PO POWER OPERATED

RECESSED(R)

REFLECTED CEILING PLAN

RADIUS, RISER ROUND

REVISION(S), REVISED

RIGID FIBERGLASS

REINFORCED CONCRETE PIPE,

ROUGH OPENING

RELOCATIONRELO

RES

REV

RF

RH

RM

RFG

REPL

RO

RESILIENT

RIGHT HAND

ROOFING

ROOM

REPLACE

RA

RB

RCP

R

RD

RE(F)

RETURN AIR

ROOF DRAIN

REFERENCE

RESILIENT BASE

POUNDS PER SQUARE FOOT

POUNDS PER SQUARE INCH

PAPER TOWEL DISPENSER

PAPER TOWEL RECEPTOR

POLYVINYL CHLORIDE

PLYWOOD

PAVEMENT

PWD

PVMT

QT

QTR

QTY

QUARTER

QUANTITY

QUARRY TILE

PR

PSF

PSI

PT

PTD

PTR

PVC

PAIR

POINT

PAINT(ED)P

POUNDS PER CUBIC FOOT

PARTICLE BOARD

PRECAST CONCRETE

POUNDS PER LINEAL FOOT

PERPENDICULAR

PREFABRICATED

PLASTIC LAMINATE

PLASTER, PLATE, PROPERTY LINE

PERP

PNL

PJ

PL

PLBG

PF

PLF

PLAM

PANEL

PANEL JOINT

PLUMBING

PART BD

PREFAB

PERIM

PAR

PC

PCC

PART

PCF

PERIMETER

PARALLEL

PARTITION

PIECE

PERFORATE(D)

OUTSIDE DIAMETER

OVERFLOW ROOF DRAIN

NOISE REDUCTION COEFFICIENTS

OVERHEAD, OPPOSITE HAND

OWNER FURNISHED CONTRACTOR INSTALLED

OWNER FURNISHED OWNER INSTALLED

OFCI

ORD

OFF

OH

OPG

OPP

OFOI

OPENING

OPPOSITE

OFFICE

OA

OC

OD

NRC

NTS

NO

OVERALL

NUMBER

ON CENTER(S)

NOT TO SCALE

MECHANICALMECH

MANUFACTURER

MASONRY OPENING

NOT IN CONTRACT, (OFOI)

NOT APPLICABLE

METAL WALL PANEL (SYSTEM)

MODULARMOD

N

NA

NIC

MWP

MTD

MOV

NORTH

MOUNTED

MOVABLE

MFR

MH

MIN

MO

MISC

MET

MEZZ

MINIMUM

MANHOLE

MEZZANINE

METAL

MISCELLANOUS

MAS

MAX

MED

MATL

MASONRY

MAXIMUM

MATERIAL

MEDIUM

ARCHITECTURALLY EXPOSED STRUCTURAL STEELAESS

GENERAL NOTES:

A. TO THE BEST OF OUR KNOWLEDGE AND INFORMATION AND IN ACCORDANCE WITH

ACCEPTED PROFESSIONAL STANDARDS, WE HAVE COMPLIED WITH APPLICABLE

PORTIONS OF THE AMERICAN WITH DISABILITIES ACT PERTAINING TO BUILDING

ACCESSIBILITY FOR THE PHYSICALLY HANDICAPPED.

B. ALL DIMENSIONS GIVEN TO FACE OF MASONRY/CONCRETE, AND GYPSUM BOARD

AND METAL STUD CONSTRUCTION. EXCEPTIONS AS INDICATED ON DRAWINGS.

C. DRAWINGS SHALL NOT BE SCALED. ALL WORK SHALL BE LAID OUT BY DIMENSIONS

NOTED ON THE DRAWINGS.

D. CONTRACTOR IS RESPONSIBLE FOR CONSTRUCTION OF ALL EQUIPMENT PADS

REQUIRED BY EQUIPMENT MANUFACTURER. ACTUAL SIZE AND LOCATION TO BE

COORDINATED WHT APPROVED EQUIPMENT MANUFACTURER.

E. HVAC AND ELECTRICAL EQUIPMENT SHOWN ON ARCHITECTURAL DRAWINGS IS FOR

GENERAL REFERENCE ONLY. COORDINATE EQUIPMENT AND LOCATIONS WITH

MECHANICAL AND ELECTRICAL DRAWINGS.

F. FIRE RATINGS SHALL BE MAINTAINED AT FIRE RATED PARTITIONS BY PROVIDING FIRE

SAFING MATERIAL AT GAPS AND VOIDS CREATED BY PENETRATIONS, STRUCTURAL

MEMBERS, AND INTERSECTIONS WITH ADJACENT SURFACES AS REQUIRED. REFER TO

FIRE PROTECTION LISTINGS FOR SPECIFIC ASSEMBLIES.

G. ALL DETAILS APPLY WHETHER OR NOT SPECIFICALLY REFERENCED.

H. ITEM LOCATED IN CEILING TILES ARE TO BE CENTERED AT THE MIDPOINT OF EACH

TILE, TYPICAL. WHERE TWO ITEMS OCCUR, LOCATE AT THIRD POINTS, THREE ITEMS

TO BE LOCATED AT QUARTER POINTS.

APPLICABLE CODES:

APPLICABLE CODES & CODE INFORMATION CAN BE FOUND ON THE REMAINING "G" SHEETS

AS LISTED IN THE SHEET INDEX.

1. NONE

1. WELDING

2. EPOXY

ELEVATIONSECTION

METAL

[SMALL SCALE]

ROUGH WOOD

NON CONTINUOUS

WOOD

CONCRETE,

PLASTER

GWB

ACOUSTICAL

PANEL/TILE

PLYWOOD

GLASS

GYPSUM WALL BOARD

SHEET METAL

ROOFING / FLASHING

CONCRETE

METAL

[LARGE SCALE]

CONCRETE MASONRY

UNIT

POROUS FILL,

STONE,GRAVEL

EARTH

CERAMIC

TILE

ROUGH WOOD

CONTINUOUS

PLASTER, SAND

CEMENT & GROUT

INSULATION

BLANKET,BATTS

RIGID

INSULATION

BRICK MILLWORK

PROJECT

Blythe

Yuma

Tucson

Tempe

Sierra Vista

Sedona

Scottsdale

Prescott

Phoenix

Payson

Nogales

Lake Havasu City

Kingman

Green Valley

Florence

Flagstaff

Douglas

Casa Grande

Bullhead City

St. George

Show Low

Pinetop-Lakeside

Whiteriver

Globe

4212 N 16TH ST

PHOENIX, AZ

MATERIALS

INDEX TO DRAWINGSABBREVIATIONS SYMBOLS PROJECT DATA

GENERAL

CVR COVER

GENERAL

G1.10 INDEX, ABBREVIATIONS, SYMBOLS & PROJECT DATA

G1.20 CODE ANALYSIS, CODE REVIEW PLANS

G1.30 ARCHITECTURAL SITE PLAN

CIVIL

C1.0 CIVIL COVER SHEET

C2.0 SITE PLAN

ARCHITECTURAL

D2.30 DEMOLITION FLOOR PLAN - POWER PLANTS & ISOLATION ROOMS

D3.30 DEMOLITION CEILING PLAN - ISOLATION ROOMS

A1.20 ENLARGED SITE PLAN

A2.20 FLOOR PLAN - PARKING CANOPY & CARPENTRY BUILDING & ROOF PLAN - PARKING CANOPY

A2.30 FLOOR PLAN - LOWER LEVEL, LEVEL ONE, AND LEVEL THREE

A2.50 ROOM SCHEDULE, MATERIALS, FINISHES LEGEND & DETAILS

A3.30 REFLECTED CEILING PLAN - LEVEL THREE

A5.00 CANOPY ELEVATIONS & SECTION

STRUCTURAL

S1.1 FOUNDATION AND ROOF FRAMING PLANS - PARKING CANOPY

S1.2 STRUCTURAL DETAILS & STANDARD NOTES

MECHANICAL

M0.10 MECHANICAL GENERAL INFORMATION

MD2.30 MECHANICAL DEMO PLANS

M2.20 MECHANICAL PLAN - CARPENTRY BUILDING

M2.30 MECHANICAL PLANS

M4.30 MECHANICAL ROOF PLAN

M5.10 MECHANICAL ISOMETRICS

M5.20 MECHANICAL PIPING ISOMETRICS

M6.10 MECHANICAL EQUIPMENT SCHEDULES

M7.10 MECHANICAL DETAILS

M8.10 MECHANICAL CONTROLS

M8.20 MECHANICAL CONTROLS

M8.30 MECHANICAL CONTROLS

PLUMBING

PD2.30 PLUMBING DEMO PLANS

P2.30 PLUMBING PLANS

P5.10 PLUMBING ISOMETRICS

P6.10 PLUMBING SCHEDULES & DETAILS

ELECTRICAL

E0.10 ELECTRICAL GENERAL INFORMATION

ED2.30 ELECTRICAL DEMO PLAN - FIRST LEVEL POWER PLANT

E2.20 ELECTRICAL PLAN - LOWER LEVEL POWER PLANT

E2.30 ELECTRICAL PLAN - FIRST LEVEL POWER PLANT

E5.10 ELECTRICAL ONE-LINE

E6.10 ELECTRICAL SCHEDULES

Grand total: 38

LOCATION MAP

R

EG

IST

ERED ARCHITECT

A

R I Z O N A , U . S

A

D a te S ig n ed . .

CE

RT

IFICATE NO.30775

SUSAN M.

GRAY

EXPIRES 12/31/2026

R

VI

H

P

S

N I D

C E

I

A

A N

HE TL H

S

E

E

H

N M

E

A R

P

T O F

T

C

D

SU

S

A

E

TAE L

H

N V I

S E R

U M A

H U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

INDIAN HEALTH SERVICE

DIVISION OF FACILITIES ENGINEERING

PHOENIX AREA

ARCHITECTS

4636 N. 32nd Street

480.980.9054 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

DRAWN BY:

CONSULTANTS

Phoenix, Arizona 85018

CHECKED BY:

CAD DWG FILE:

PROJECT NO:

ISSUE:

SHEET OF

REVIEWED:

DFE ENGINEER/PROJECT MANAGER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

REV DATE DESCRIPTION

IHS PROJECT NO.

C

B

A

C

B

A

SHEET TITLE

Indian Health Service

CONSTRUCTION DOCUMENTS DRAWINGS

PIMC MECHANICAL PROJECT 2 -

CENTRAL PLANT &

ISOLATION ROOMS (BLDG 234)

1/

/2

G1.10

INDEX, ABBREVIATIONS,

SYMBOLS & PROJECT

DATA

1/15/2024 1818.015 bws

CIVIL

EEC, Inc

555 E. River Road, #301

Tucson, AZ 85704

Phone: 502.321.4625

MEP

Zona Technical Eng

6422 E. Speedway Blvd., Unit 130

Tucson, AZ 85710

Phone: 520.200.2612

STRUCTURAL

Turner Structural

2806 N. Alvernon Way, Suite

Tucson, AZ 85712

Phone: 520.323.3422

4212 N 16th Street

Phoenix, AZ 85016

PH22PH03H6

VICINITY MAP

APPLICABLE CODES

DEFERRED SUBMITTALS

SPECIAL INSPECTIONS

Applicable Codes:

2021 NFPA 101

2021 International Building Code (IBC)

2021 International Existing Building Code (IEBC)

2021 International Mechanical Code (IMC)

2021 International Plumbing Code (IPC)

2021 International Energy Conservation Code (IECC)

2021 International Fire Code (IFC)

2020 National Electric Code (NEC)

2022 Sprinkler Code NFPA 13R

2015 Architectural Barriers Act (ABA)

NFPA (In Total)

*And all other codes and ordinances as adopted by the governing agencies having jurisdiction (AHJ)

Project Title:

PIMC Mechanical Project 2 - Central Plant & Isolation Rooms (Bldg 234)

Project Description:

(Alteration Level 2) Replacement of 18 cooling tower valves and diesel autofill system at the Central Plant of Phoenix Indian

Medical Center as well as replacement and relocation of heat exchanger and compressor for medical air system at the

Central Plant Building. Work to also consist of new dust collection system for removal of wood dust and chips produced at the Carpentary Shop and replacement of ductwork at Third Floor Isolation Rooms at the Main Hospital Building of Phoenix

Indian Medical Center. In addition, install a new parking canopy for the Central Plant campus. Finally, above ceiling work in the Main Hospital Building Isolation Rooms on the third floor and replacement of existing ceilings.

No change in Area, Use or Occupancy is included in this renovation project.

2021 NFPA 101 - ANALYSIS PER CHAPTER 43

The cooling tower replacement valves scope of at the Central Plant shall be considered under 43.3 Repairs due to the replacement of of the 18 cooling tower valves.

The diesel autofill system scope at the Central Plant shall be considered under 43.5 Modifications due to the relocation and extension of the diesel autofill sytem.

The medical air system scope at the Central Plant shall be considered under 43.5 Modification due to the relocation of the medial air to the lower level of the Power Plant

The ductwork replacement shall be considered under 43.4 Renovations due to the replacement of ductwork at the Third

Floor Isolation Rooms (Building 234).

Occupancy Classification (Section 308, 311, 312):

Group I-2 Condition 2 Institution

Group S-2 Storage

Group U Miscellanous

Fire Protection: (Chapter 9)

Fire Alarm and Fire Sprinklers

Type of Construction (Tables 504.3, 504.4): Type IA (Hospital/Central Plant) Type IIB (Canopy/Carpentry)

Group I-2

Allowable Stories / Height UL / UL

Actual Height 5 stories / 72 feet

Group S-2

Allowable Stories / Height 3 stories / 55 feet

Actual Height 1 stories / 18 feet

Max Area 26,000 s.f.

Group U

Allowable Stories / Height 2 stories / 55 feet

Actual Height 1 stories / 18 feet

Max Area 8,550 s.f.

Area of work:

Carpentry Shop 1,326 s.f.

Parking Canopy 1,776 s.f.

TOTAL AREA 3,102 s.f.

*Considering the Carpentry Shop and Parking Canopy as a single building

Isolation Rooms - Level Three 639 s.f.

Fire Resistance Rating (Table 601 & 602): Type IA & IIB

See table to right

Fire and Smoke Protection Features Type IA & IIB

Section 705 Exterior Walls - 705.8 Openings

Smoke Barriers

Section 709

709.3 Fire-resistance rating

A 1-hour fire resistance rating is required for smoke barriers.

407.5.1 Smoke compartment size

Stories shall be divided into smoke compartments with an area of not more than 22,500 square feet in Group I-2 occupancies.

BUILDING CODE REVIEW - 2021 IBC

BUILDING ELEMENT

PRIMARY STRUCTURAL FRAME

BEARING WALLS - EXTERIOR

BEARING WALLS - INTERIOR

NONBEARING WALLS AND PARTITIONS:

EXTERIOR

NONBEARING WALLS AND PARTITIONS: INTERIOR

FLOOR CONSTRUCTION AND ASSOCIATED SECONDARY MEMBER

ROOF CONSTRUCTION AND ASSOCIATED SECONDARY MEMBER

0 HRS

0 HRS

0 HRS

X < 5= 1 HRS

5 ≤ X < 10= 1 HRS

10 ≤ X ≤ 30= 0 HRS

X ≥ 30= 0 HRS

0 HRS

0 HRS

0 HRS

TYPE ( IIB )

Exit and Occupant Loads (Table 1004.5): Refer to Code Plans

Accessory St./Mech./Eq. Rm. 300 SF / Occupant

Institutional

Inpatient Treatment Areas 240 SF / Occupant

Sleeping Areas 120 SF / Occupant

Exist Access Stairways (Table 1019.3):

Occupancies other than Groups I-2 and I-3. In other than Group I-2 and I-3 occupancies, floor openings containing exit access stairways or ramps that do not comply with one of the conditions listed in this section shall be enclosed with a shaft enclosure constructed in accordance with Section 713.

1. Exit access stairways and ramps that serve or atmospherically communicate between only two stories. Such interconnected stories shall not be open to other stories.

Width of Exits (Table 1005): Fully Sprinklered

Doors and Hallways Occupant Load x .15” / Occupant

Stairways Occupant Load x .20” / Occupant

Distance to Exits (Table 1017.2): with Fire Sprinklers

Group I-2 200 FT

Group S-2 300 FT

Group U 300 FT

Number of Exits (Table 1006.3.2):

All rooms and spaces within each story shall be provided with and have access to the minimum number of approved independent exits required by section

1006 based on the occupant load.

Minimum 2 Exits or Exit Access Doorways required > 49 occupants in any A & B space

Minimum 2 Exits or Exit Access Doorways required when Common Path of Egress >100 feet

3 Exits required when occupant load exceeds 500

4 Exits required when occupant load exceeds 1,000

TABLE 601 (FIRE RESISTANCE RATING REQUIREMENTS)

R

EG

IST

ERED ARCHITECT

A

R I Z O N A , U . S

A

D a te S ig n ed . .

CE

RT

IFICATE NO.30775

SUSAN M.

GRAY

EXPIRES 12/31/2026

R

VI

H

P

S

N I D

C E

I

A

A N

HE TL H

S

E

E

H

N M

E

A R

P

T O F

T

C

D

SU

S

A

E

TAE L

H

N V I

S E R

U M A

H U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

INDIAN HEALTH SERVICE

DIVISION OF FACILITIES ENGINEERING

PHOENIX AREA

ARCHITECTS

4636 N. 32nd Street

480.980.9054 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

DRAWN BY:

CONSULTANTS

Phoenix, Arizona 85018

CHECKED BY:

CAD DWG FILE:

PROJECT NO:

ISSUE:

SHEET OF

REVIEWED:

DFE ENGINEER/PROJECT MANAGER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

REV DATE DESCRIPTION

IHS PROJECT NO.

C

B

A

C

B

A

SHEET TITLE

Indian Health Service

CONSTRUCTION DOCUMENTS DRAWINGS

PIMC MECHANICAL PROJECT 2 -

CENTRAL PLANT &

ISOLATION ROOMS (BLDG 234)

1/

/2

G1.20

CODE ANALYSIS, CODE

REVIEW PLANS

1/15/2024 1818.015

BWS

CIVIL

EEC, Inc

555 E. River Road, #301

Tucson, AZ 85704

Phone: 502.321.4625

MEP

Zona Technical Eng

6422 E. Speedway Blvd., Unit 130

Tucson, AZ 85710

Phone: 520.200.2612

STRUCTURAL

Turner Structural

2806 N. Alvernon Way, Suite

Tucson, AZ 85712

Phone: 520.323.3422

4212 N 16th Street

Phoenix, AZ 85016

PH22PH03H6

LP

LP

LP LP

LP

LP

LP

LP

LP

LP

LP

LP LP

LP

LP

LP

LP

LP

LP

LP

LP LP

LP

LP

LP LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

FH

FH

FH

FH

FH

FH

FH

FH

T R A S H

C O M P A C T O R

Traffic Flow

LP

EXIST

SES

HVAC

E

E

E

E

E

E

E

E

E

E

HVAC

E

E

E

E

E

M

E

E

E

E

E

BM

#2

BM

#2

LIFTSTA.

LIFTSTA.

LIFT

STA.

LIFTSTA.

LIFTSTA.

GLENROSA AVENUE

CANAL

P

IN

E S

T R

E E T

PINE STREET

WEST LOT

NORTH LOT NORTH LOT

T H

S T R

E E T

A2.30

CANOPY

C A

R P

E N

T R

Y

B U

IL

D

IN

G

CLINIC

CLINIC

BUILDING

SPECIALTY

SERVICES

BUILDING 254

DENTAL

CLINIC

BUILDING 239

DENTAL

CLINIC

BUILDING 238

STORAGE

BUILDING 8

SOCIAL SERVICES

BUILDING 5/6

ADMIN

BUILDING 4

NIH

BUILDING 1

P A

T H

O

LO

G Y

B U

IL

D

IN

G

5WAREHOUSE

BUILDING 9

WIC

BLD'G 300

CT

BLD'G

MAIN HOSPITAL

BUILDING 233

POWER

PLANT

BUILDING

PCMC NORTH

BUILDING 010

PCMC

SOUTH

BUILDING

A1.20

A. CONTRACTOR IS RESPONSIBLE FOR ALL BARRICADES & SAFETY

CONCERNS WITHIN & ADJACENT TO CONSTRUCTION.

B. FIELD VERIFY ALL EXISTING CONDITIONS & DIMENSIONS PRIOR TO

CONSTRUCTION.

C. REFER TO CIVIL, STRUCTURAL, MECHANICAL & ELECTRICAL DRAWINGS

FOR MORE INFORMATION & UTILITY COORDINATION.

D. CONTRACTOR SHALL PATCH & REPAIR ALL EXISTING FINISHES ADJACENT

TO DEMOLITION, AS REQUIRED.

SCALE: 1" = 60'-0"1

CAMPUS SITE PLAN

SITE PLAN GENERAL NOTES

0' 8' 16' 32'

R

EG

IST

ERED ARCHITECT

A

R I Z O N A , U . S

A

D a te S ig n ed . .

CE

RT

IFICATE NO.30775

SUSAN M.

GRAY

EXPIRES 12/31/2026

R

VI

H

P

S

N I D

C E

I

A

A N

HE TL H

S

E

E

H

N M

E

A R

P

T O F

T

C

D

SU

S

A

E

TAE L

H

N V I

S E R

U M A

H U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

INDIAN HEALTH SERVICE

DIVISION OF FACILITIES ENGINEERING

PHOENIX AREA

ARCHITECTS

4636 N. 32nd Street

480.980.9054 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

DRAWN BY:

CONSULTANTS

Phoenix, Arizona 85018

CHECKED BY:

CAD DWG FILE:

PROJECT NO:

ISSUE:

SHEET OF

REVIEWED:

DFE ENGINEER/PROJECT MANAGER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

REV DATE DESCRIPTION

IHS PROJECT NO.

C

B

A

C

B

A

SHEET TITLE

Indian Health Service

CONSTRUCTION DOCUMENTS DRAWINGS

PIMC MECHANICAL PROJECT 2 -

CENTRAL PLANT &

ISOLATION ROOMS (BLDG 234)

1/

/2

G1.30

ARCHITECTURAL SITE

PLAN

1/15/2024 1818.015

Drawn By

CIVIL

EEC, Inc

555 E. River Road, #301

Tucson, AZ 85704

Phone: 502.321.4625

MEP

Zona Technical Eng

6422 E. Speedway Blvd., Unit 130

Tucson, AZ 85710

Phone: 520.200.2612

STRUCTURAL

Turner Structural

2806 N. Alvernon Way, Suite

Tucson, AZ 85712

Phone: 520.323.3422

4212 N 16th Street

Phoenix, AZ 85016

PH22PH03H6

PLAN

NORTH

4636 N. 32nd Street

480.980.9054 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

DRAWN BY:

CONSULTANTS

Phoenix, Arizona 85018

CHECKED BY:

CAD DWG FILE:

PROJECT NO:

ISSUE:

SHEET OF

REVIEWED:

DFE ENGINEER/PROJECT MANAGER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

REV DATE DESCRIPTION

IHS PROJECT NO.

C

B

A

C

B

A

SHEET TITLE

Indian Health Service

CONSTRUCTION DOCUMENTS

PIMC MECHANICAL PROJECT 2 -

CENTRAL PLANT &

ISOLATION ROOMS (BLDG 234)

U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

INDIAN HEALTH SERVICE

DIVISION OF FACILITIES ENGINEERING

PHOENIX AREA

ARCHITECTS

01/15/2024 1818.015

Author

CIVIL

EEC, Inc 555 E. River Road, #301 Tucson, AZ 85704 Phone: 502.321.4625

MEP

Zona Technical Eng 6422 E. Speedway Blvd., Unit 130 Tucson, AZ 85710 Phone: 520.200.2612

STRUCTURAL

Turner Structural 2806 N. Alvernon Way, Suite Tucson, AZ 85712 Phone: 520.323.3422

4212 N 16th Street Phoenix, AZ 85016

PH22PH03H6

C1.0

COVER SHEET

01/16/2024

EXPIRES 09/30/2024

rjohnson Rectangle rjohnson Text Box rjohnson Text Box

SD

VLV

GAS

4636 N. 32nd Street

480.980.9054 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

DRAWN BY:

CONSULTANTS

Phoenix, Arizona 85018

CHECKED BY:

CAD DWG FILE:

PROJECT NO:

ISSUE:

SHEET OF

REVIEWED:

DFE ENGINEER/PROJECT MANAGER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

REV DATE DESCRIPTION

IHS PROJECT NO.

C

B

A

C

B

A

SHEET TITLE

Indian Health Service

CONSTRUCTION DOCUMENTS

PIMC MECHANICAL PROJECT 2 -

CENTRAL PLANT &

ISOLATION ROOMS (BLDG 234)

U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

INDIAN HEALTH SERVICE

DIVISION OF FACILITIES ENGINEERING

PHOENIX AREA

ARCHITECTS

01/15/2024 1818.015

Author

CIVIL

EEC, Inc 555 E. River Road, #301 Tucson, AZ 85704 Phone: 502.321.4625

MEP

Zona Technical Eng 6422 E. Speedway Blvd., Unit 130 Tucson, AZ 85710 Phone: 520.200.2612

STRUCTURAL

Turner Structural 2806 N. Alvernon Way, Suite Tucson, AZ 85712 Phone: 520.323.3422

4212 N 16th Street Phoenix, AZ 85016

PH22PH03H6

C2.0

SITE PLAN

SITE KEYNOTES

01/16/2024

EXPIRES 09/30/2024

rjohnson Rectangle rjohnson Text Box rjohnson

309A308A305A

2331 29 19 15 11 9

U P

D N

# B

2-BED RM

STAIRS

CORRIDOR

CORRIDOR

SERVICE

ELEVATOR

SHAFT

MECH.

SHAFT

ELEVATOR

SERVICE

ELEVATOR

F.H.C.

E.W.C.

F.H.C.

PASSENGER

PASSENGER

ELEVATOR

Tunnel from Power Plant to Ground Level

LP

LP

LP LP

LP

LP

LP

LP

LP

LP

LP

LP LP

LP

LP

LP

LP

LP

LP

LP

LP LP

LP

LP

LP LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

FH

FH

FH

FH

FH

FH

FH

FH

FH

ROOF

ACCESS

HATCH ABOVE

10'-0"

T R

AS

H

C O M P A C

TO

R

Traffic Flow

LP

S ES

F U TU RELDPX F MR

EXIST

SES

H VAC

E

E

E

E

E

E

E

E

E

E

H VAC

E

E

E

E

E

M

E

E

E

E

E

GLENROSA LANE

th

S T

R E

E T

INDIAN SCHOOL RD.

C A N A L

MONTEROSA STREET

C A N A L

ST

R E E T

T

H P

L A

C E th

S T

R E

E T

DEVONSHIRE AVE

HEATHERBRAE DR

L O

A D

IN

G

D O

C K t h

S T

R E

E T t h

P L

A C

E

RAMADA

POWER

PLANT

BLDG 234

SPECIALTY SERVICES

BLDG 254

SHOP

BLDG

STORAGE

BLDG 8

BEHAVIORAL HEALTH &

SOCIAL SERVICES

BLDG 5/6

NIH

BLDG 1

PATHOLOGY

ADMINISTRATION

BLDG 4

WAREHOUSE

BLDG 9

PCMC NORTH

BLDG 010

DENTAL

CLINIC ANNEX

BLDG 238

PCMC SOUTH

BLDG 252

WOMENS

CLINIC

BLDG 253

MAIN

HOSPITAL

BLDG 233

WIC

BLDG 300

AZTEC

SQUARE

OEH

STORAGE

DENTAL CLINIC

BLDG 239

SWEATLODGE

SITE

CT

BLDG

PROPOSED

PEDS CLINIC

BM

#2

BM

#2

LIFTSTA.

LIFTSTA.

LIFT

STA.

LIFTSTA.

LIFTSTA.

A. THE CONTRACTOR IS RESPONSIBLE FOR DEMOLITION

AND REMOVAL WITHIN THE LIMITS OF DEMOLITION

U.N.O.

B. THE CONTRACTOR IS RESPONSIBLE FOR ALL

BARRICADES AND SAFETY CONCERNS WITHIN AND

ADJACENT TO CONSTRUCTION.

C. LIMITS OF DEMOLITION LINES ARE APPROXIMATE AND

ARE TO BE ESTABLISHED BY THE FLOOR PLANS. THE

ARCHITECT SHALL BE NOTIFIED IN WRITING OF ANY

DISCREPANCIES PRIOR TO DEMOLITION.

D. EXISTING FINISHES, MILLWORK, ETC. TO REMAIN SHALL

BE PROTECTED DURING DEMOLITION. CONTRACTOR

SHALL PATCH ALL EXISTING FINISHES TO REMAIN AS

REQUIRED BY NEW WORK.

ISOLATION

ROOM

ISOLATION

ROOM

ISOLATION

ROOM

ISOLATION

ROOM

PATIENT

ROOM

TOILET

309A

TOILET

308A

TOILET

305A

TOILET

302A

TOILET

301A

PLAN FOR REFERENCE -

REFER TO D3.30

PUMP PIT

PP-9

UP

015015

015015

AREA OF WORK

AREA OF WORK

DN UP

BOILER

ROOM

PP-1

PAINT SHOP

PP-2

LOCKER

PP-5

TOILET

PP-2

JANITOR

PP-6

SHOWER

PP-3

6' -9

/2

6'

-0

9'-9 1/4" 2 3/4"

R

EG

IST

ERED ARCHITECT

A

R I Z O N A , U . S

A

D a te S ig n ed . .

CE

RT

IFICATE NO.30775

SUSAN M.

GRAY

EXPIRES 12/31/2026

R

VI

H

P

S

N I D

C E

I

A

A N

HE TL H

S

E

E

H

N M

E

A R

P

T O F

T

C

D

SU

S

A

E

TAE L

H

N V I

S E R

U M A

H U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

INDIAN HEALTH SERVICE

DIVISION OF FACILITIES ENGINEERING

PHOENIX AREA

ARCHITECTS

4636 N. 32nd Street

480.980.9054 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

DRAWN BY:

CONSULTANTS

Phoenix, Arizona 85018

CHECKED BY:

CAD DWG FILE:

PROJECT NO:

ISSUE:

SHEET OF

REVIEWED:

DFE ENGINEER/PROJECT MANAGER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

REV DATE DESCRIPTION

IHS PROJECT NO.

C

B

A

C

B

A

SHEET TITLE

Indian Health Service

CONSTRUCTION DOCUMENTS DRAWINGS

PIMC MECHANICAL PROJECT 2 -

CENTRAL PLANT &

ISOLATION ROOMS (BLDG 234)

1/

/2

D2.30

DEMOLITION FLOOR PLAN

- POWER PLANTS &

ISOLATION ROOMS

1/15/2024 1818.015

Author

CIVIL

EEC, Inc

555 E. River Road, #301

Tucson, AZ 85704

Phone: 502.321.4625

MEP

Zona Technical Eng

6422 E. Speedway Blvd., Unit 130

Tucson, AZ 85710

Phone: 520.200.2612

STRUCTURAL

Turner Structural

2806 N. Alvernon Way, Suite

Tucson, AZ 85712

Phone: 520.323.3422

4212 N 16th Street

Phoenix, AZ 85016

PH22PH03H6

0' 4' 8' 16'

PLAN

NORTH

DEMOLITION KEYNOTE LEGEND

009 DEMOLISH MEDICAL AIR EQUIPMENT COMPLETELY -

REFER TO MECHANICAL

010 UNDERGROUND TUNNEL TO REMAIN

015 UNEXCAVATED AREA TO REMAIN

016 DEMOLISH CONCRETE SLAB COMPLETELY

017 DEMOLISH HEAT EXCHANGER - REFER TO

MECHANICAL

018 BOLLARD TO REMAIN

019 DEMOLISH PORTION OF PAVING - REFER TO SITE AND

CIVIL PLAN

DEMOLITION PLAN GENERAL NOTES

1/8" = 1'-0"1

DEMOLITION FLOOR PLAN - THIRD LEVEL ISOLATION ROOMS

1/8" = 1'-0"2

DEMOLITION FLOOR PLAN - LOWER LEVEL POWER PLANT

PLAN

NORTH

0' 4' 8' 16'

PLAN

NORTH

0' 4' 8' 16'

KEYPLAN - SITE PLAN

1/8" = 1'-0"3

DEMOLITION FLOOR PLAN - FIRST LEVEL POWER PLANT

U P

D N

# B

2-BED RM

STAIRS

CORRIDOR

CORRIDOR

SERVICE

ELEVATOR

SHAFT

MECH.

SHAFT ELEVATOR

SERVICE

ELEVATOR

F.H.C.

E.W.C.

F.H.C.

PASSENGER

PASSENGER

ELEVATOR

1-C1

1-C2

1-C3

1-C4

1-C5

1-C6

1-C7

1-C8

1-C9

1-C10

1-C11

1-C12

1-C13

1-C14

U P

D N

UP

DN

UPDN

308307306

# B

#A

321A

305304

349A350

353354

362360

303302301

318 316

314 313 312

341A

4-BED RM

4-BED RM

4-BED RM

LINEN

STORAGE

S T O R A G E

4-BED RM2-BED RM

TOIL.

TOIL.

2-BED RM

STAIRS

CORRIDOR

C O R R

ID

O R

CORRIDOR

SUPPLY

RM

UTILITY

UTILITY

CLOSET

2-BED RM

STAIRS

TOIL.

2-BED RM

MED.PREP.

STAT.

LOUNGE

TOIL.

NURSES OFFICE

TOIL.

SHSH

TOIL.

OFFICEDON

ADON

JAN.

SECRETARY

ROOMULTRASOUND

CORRIDOR

SERVICE

ELEVATOR

WHEEL CHAIRS

SHAFT TOIL.

ELECT.BOXES

NURSE LOUNGE

TOIL.

TOIL.

MONITORING

TOIL.

PROCEDURE ROOM

HOUSE/ FLOAT

WORK

RM.

ULTRASOUND

MED. PREP.

SH.C

O R R

ID

E R

STA.

DENTAL SURGERY

TREADMILL

ULTRASOUND

DARK RM

TOIL. TOIL.

STAIRS

# 2

TOIL.

TOIL.

1-BED RM 1-BED RM

ISOLATION

1-BED RM1-BED RM

ISOLATION

TOIL.

SH SH

TOIL.

ISOLATION

1-BED RM

SH

TOIL.

SERVICE

TOIL.

TOIL.

CONFERENCE

FILE

TOIL.

2-BED RM

TOIL.

TOIL.

2-BED RM

JAN.

TOIL.

2-BED RM 2-BED RM

TOIL.

TOIL.

2-BED RM

TOIL. TOIL.

CORRIDOR

NURSES.

P.T.

STA.

SH.

SUPPLY

TLT

MECH.

SHAFT

SH.

SOILED UTILITY

CLEAN UTILITY

CLOSET

ELECT.

ELEVATOR

SERVICE

ELEVATOR

STRETCHERS &

NURSES.

STA.

P.T.

STA.

NOURISH.

NURSES

UNIT

TREATMENT

SOILED

CLEAN

SH.

SH.

BATH

BATH

S H A F T

SH.

SH. MED. EQUIP

CLEAN

F.H.C.

F.H.C.

E.W.C.

E.W.C.

F.H.C. F.H.C.

F.H.C.

F.H.C.

E.W.C.PASSENGER

PASSENGER

ELEVATOR

TUB

E Q U

IP

EKG /

PHARMACY

WAITING RM

OFFICE

RM.

CLEANING

COMPRESSOR

ROOM

PATIENT

CLOTHES

SOCIAL

A. THE CONTRACTOR IS RESPONSIBLE FOR DEMOLITION

AND REMOVAL WITHIN THE LIMITS OF DEMOLITION

U.N.O.

B. THE CONTRACTOR IS RESPONSIBLE FOR ALL

BARRICADES AND SAFETY CONCERNS WITHIN AND

ADJACENT TO CONSTRUCTION.

C. LIMITS OF DEMOLITION LINES ARE APPROXIMATE AND

ARE TO BE ESTABLISHED BY THE FLOOR PLANS. THE

ARCHITECT SHALL BE NOTIFIED IN WRITING OF ANY

DISCREPANCIES PRIOR TO DEMOLITION.

D. EXISTING FINISHES, MILLWORK, ETC. TO REMAIN SHALL

BE PROTECTED DURING DEMOLITION. CONTRACTOR

SHALL PATCH ALL EXISTING FINISHES TO REMAIN AS

REQUIRED BY NEW WORK.

TYP

011 011 011012012 012012 012 012013 013

005 005 005

ISOLATION

ROOM

ISOLATION

ROOM

ISOLATION

ROOM

ISOLATION

ROOM

005005

TYP

DEMO

8' - 0 1/2" AFF

DEMO

8' - 0 1/2" AFF

DEMO

8' - 0 1/2" AFF

DEMO

8' - 0 1/2" AFF

TYP

DEMO

8' - 0 1/2" AFF

DEMO

8' - 0 1/2" AFF

DEMO

8' - 0 1/2" AFF

DEMO

8' - 0 1/2" AFF

PATIENT

ROOM

TOILET

309A

TOILET

308A

TOILET

305A

TOILET

302A

TOILET

301A

AREA OF WORK

R

EG

IST

ERED ARCHITECT

A

R I Z O N A , U . S

A

D a te S ig n ed . .

CE

RT

IFICATE NO.30775

SUSAN M.

GRAY

EXPIRES 12/31/2026

R

VI

H

P

S

N I D

C E

I

A

A N

HE TL H

S

E

E

H

N M

E

A R

P

T O F

T

C

D

SU

S

A

E

TAE L

H

N V I

S E R

U M A

H U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

INDIAN HEALTH SERVICE

DIVISION OF FACILITIES ENGINEERING

PHOENIX AREA

ARCHITECTS

4636 N. 32nd Street

480.980.9054 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

DRAWN BY:

CONSULTANTS

Phoenix, Arizona 85018

CHECKED BY:

CAD DWG FILE:

PROJECT NO:

ISSUE:

SHEET OF

REVIEWED:

DFE ENGINEER/PROJECT MANAGER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

REV DATE DESCRIPTION

IHS PROJECT NO.

C

B

A

C

B

A

SHEET TITLE

Indian Health Service

CONSTRUCTION DOCUMENTS DRAWINGS

PIMC MECHANICAL PROJECT 2 -

CENTRAL PLANT &

ISOLATION ROOMS (BLDG 234)

1/

/2

D3.30

DEMOLITION CEILING

PLAN - ISOLATION ROOMS

1/15/2024 1818.015

Author

CIVIL

EEC, Inc

555 E. River Road, #301

Tucson, AZ 85704

Phone: 502.321.4625

MEP

Zona Technical Eng

6422 E. Speedway Blvd., Unit 130

Tucson, AZ 85710

Phone: 520.200.2612

STRUCTURAL

Turner Structural

2806 N. Alvernon Way, Suite

Tucson, AZ 85712

Phone: 520.323.3422

4212 N 16th Street

Phoenix, AZ 85016

PH22PH03H6

DEMOLITION PLAN GENERAL NOTES

1/8" = 1'-0"1

DEMOLITION CEILING PLAN - THIRD LEVEL ISOLATION ROOMS 0' 4' 8' 16'

PLAN

NORTH

KEYPLAN - LEVEL THREE

KEYNOTES

005 DEMOLISH CEILING COMPLETELY

011 RELOCATE LIGHT FIXTURE - REFER TO ELECTRIC

012 DEMOLISH DIFFUSERS COMPLETELY

013 DEMOLISH ACCESS PANEL - REFER TO CEILING PLAN

014 REMOVE CEILING TILE AND SALVAGE FOR REUSE.

DEMO PORTION OF CEILING GRID TO REPLACE

TERMINAL UNITS ABOVE. REFER TO MECHANICAL

DN

A2.20

A2.20

A2.30

M2.20

NEW ASPHALT PAVING -

REFER TO CIVIL PLANS

S

LO

P E

D O

W N

TO

S

TR

EE

T

CARPENTRY

BUILDING

POWER

PLANT

BUILDING

COOLING

TOWER

PARKING

CANOPY

NEW ASPHALT PAVING -

REFER TO CIVIL PLANS

NEW CONCRETE

EQUIPMENT PAD -

REFER TO CIVIL &

STRUCTURAL PLANS

NEW CONCRETE EQUIPMENT

PAD - REFER TO CIVIL &

STRUCTURAL PLANS

NEW ASPHALT PAVING -

REFER TO CIVIL PLANS

EXISTING PAVED

AREA TO REMAIN

CATCH BASIN TO

REMAIN - PROTECT

IN PLACEEXISTING BUILDING TO

REMAIN - PROTECT IN PLACE

SITE WALL TO REMAIN -

PROTECT IN PLACE

SITE WALL TO REMAIN -

PROTECT IN PLACE

SITE WALL TO REMAIN -

PROTECT IN PLACE

SITE WALL AND METAL

RAILING TO REMAIN -

PROTECT IN PLACE

R

EG

IST

ERED ARCHITECT

A

R I Z O N A , U . S

A

D a te S ig n ed . .

CE

RT

IFICATE NO.30775

SUSAN M.

GRAY

EXPIRES 12/31/2026

R

VI

H

P

S

N I D

C E

I

A

A N

HE TL H

S

E

E

H

N M

E

A R

P

T O F

T

C

D

SU

S

A

E

TAE L

H

N V I

S E R

U M A

H U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

INDIAN HEALTH SERVICE

DIVISION OF FACILITIES ENGINEERING

PHOENIX AREA

ARCHITECTS

4636 N. 32nd Street

480.980.9054 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

DRAWN BY:

CONSULTANTS

Phoenix, Arizona 85018

CHECKED BY:

CAD DWG FILE:

PROJECT NO:

ISSUE:

SHEET OF

REVIEWED:

DFE ENGINEER/PROJECT MANAGER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

REV DATE DESCRIPTION

IHS PROJECT NO.

C

B

A

C

B

A

SHEET TITLE

Indian Health Service

CONSTRUCTION DOCUMENTS DRAWINGS

PIMC MECHANICAL PROJECT 2 -

CENTRAL PLANT &

ISOLATION ROOMS (BLDG 234)

1/

/2

A1.20

ENLARGED SITE PLAN

1/15/2024 1818.015

Author

CIVIL

EEC, Inc

555 E. River Road, #301

Tucson, AZ 85704

Phone: 502.321.4625

MEP

Zona Technical Eng

6422 E. Speedway Blvd., Unit 130

Tucson, AZ 85710

Phone: 520.200.2612

STRUCTURAL

Turner Structural

2806 N. Alvernon Way, Suite

Tucson, AZ 85712

Phone: 520.323.3422

4212 N 16th Street

Phoenix, AZ 85016

PH22PH03H6

1/8" = 1'-0"1

FLOOR PLAN - PARKING CANOPY 0' 4' 8' 16'

PLAN

NORTH

SHOP

BLDG

LP

LP

LP LP

LP

LP

LP

LP

LP

LP

LP

LP LP

LP

LP

LP

LP

LP

LP

LP

LP LP

LP

LP

LP LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

FH

FH

FH

FH

FH

FH

FH

FH

FH

ROOF

ACCESS

HATCH ABOVE

10'-0"

T R

AS

H

C O M P A C

TO

R

Traffic Flow

LP

S ES

F U TU RELDPX F MR

EXIST

SES

H VAC

E

E

E

E

E

E

E

E

E

E

H VAC

E

E

E

E

E

M

E

E

E

E

E

GLENROSA LANE

th

S T

R E

E T

INDIAN SCHOOL RD.

C A N A L

MONTEROSA STREET

C A N A L

ST

R E E T

T

H P

L A

C E th

S T

R E

E T

DEVONSHIRE AVE

HEATHERBRAE DR

L O

A D

IN

G

D O

C K t h

S T

R E

E T t h

P L

A C

E

RAMADA

POWER

PLANT

BLDG 234

SPECIALTY SERVICES

BLDG 254

SHOP

BLDG

STORAGE

BLDG 8

BEHAVIORAL HEALTH &

SOCIAL SERVICES

BLDG 5/6

NIH

BLDG 1

PATHOLOGY

ADMINISTRATION

BLDG 4

WAREHOUSE

BLDG 9

PCMC NORTH

BLDG 010

DENTAL

CLINIC ANNEX

BLDG 238

PCMC SOUTH

BLDG 252

WOMENS

CLINIC

BLDG 253

MAIN

HOSPITAL

BLDG 233

WIC

BLDG 300

AZTEC

SQUARE

OEH

STORAGE

DENTAL CLINIC

BLDG 239

SWEATLODGE

SITE

CT

BLDG

PROPOSED

PEDS CLINIC

BM

#2

BM

#2

LIFTSTA.

LIFTSTA.

LIFT

STA.

LIFTSTA.

LIFTSTA.

A5.00

18' - 0" 18' - 0" 18' - 0" 18' - 0"

A5.00

A5.00

A5.00

A5.00

TYP

TYP

217200

TYP

24'-9 1/2" 26'-5 1/8"

TYP

SHOP

AREA 1

STORAGE

SHOP

AREA 2

4'-0"

1' -8

/2

AREA OF WORK

AREA OF WORK

A5.00

72'-8"

401401

3/ 8"

2"

8"

A. DIMENSIONS ARE TO COLUMN CENTERLINE OR FACE OF WALL, U.N.O.

B. ALL WALLS ARE TO UNDERSIDE OF DECK, U.N.O.

C. REFER TO SHEET A2.50 FOR ROOM FINISHES.

R

EG

IST

ERED ARCHITECT

A

R I Z O N A , U . S

A

D a te S ig n ed . .

CE

RT

IFICATE NO.30775

SUSAN M.

GRAY

EXPIRES 12/31/2026

R

VI

H

P

S

N I D

C E

I

A

A N

HE TL H

S

E

E

H

N M

E

A R

P

T O F

T

C

D

SU

S

A

E

TAE L

H

N V I

S E R

U M A

H U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

INDIAN HEALTH SERVICE

DIVISION OF FACILITIES ENGINEERING

PHOENIX AREA

ARCHITECTS

4636 N. 32nd Street

480.980.9054 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

DRAWN BY:

CONSULTANTS

Phoenix, Arizona 85018

CHECKED BY:

CAD DWG FILE:

PROJECT NO:

ISSUE:

SHEET OF

REVIEWED:

DFE ENGINEER/PROJECT MANAGER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

REV DATE DESCRIPTION

IHS PROJECT NO.

C

B

A

C

B

A

SHEET TITLE

Indian Health Service

CONSTRUCTION DOCUMENTS DRAWINGS

PIMC MECHANICAL PROJECT 2 -

CENTRAL PLANT &

ISOLATION ROOMS (BLDG 234)

1/

/2

A2.20

FLOOR PLAN - PARKING

CANOPY & CARPENTRY

BUILDING & ROOF PLAN -

PARKING CANOPY

1/15/2024 1818.015

Author

CIVIL

EEC, Inc

555 E. River Road, #301

Tucson, AZ 85704

Phone: 502.321.4625

MEP

Zona Technical Eng

6422 E. Speedway Blvd., Unit 130

Tucson, AZ 85710

Phone: 520.200.2612

STRUCTURAL

Turner Structural

2806 N. Alvernon Way, Suite

Tucson, AZ 85712

Phone: 520.323.3422

4212 N 16th Street

Phoenix, AZ 85016

PH22PH03H6

1/8" = 1'-0"1

FLOOR PLAN - PARKING CANOPY 0' 4' 8' 16'

PLAN

NORTH

1/8" = 1'-0"3

FLOOR PLAN - CARPENTRY SHOP 0' 4' 8' 16'

PLAN

NORTH

KEYPLAN - SITE PLAN

1/8" = 1'-0"2

ROOF PLAN - PARKING CANOPY 0' 4' 8' 16'

PLAN

NORTH

FLOOR PLAN GENERAL NOTES

KEYNOTES

201 STEEL CANOPY COLUMN, PAINT (P-2) - REFER TO STRUCTURAL

202 PARKING STRIP - REFER TO CIVIL

216 PARKING CANOPY - REFER TO 1/A2.20

217 RE-PAVED AREA - REFER TO CIVIL

218 PROVIDE CONCRETE EQUIPMENT PAD LEVEL WITH EXISTING PAD.

PROVIDE #4 DOWELS @ 24"o.c. EPOXY GROUTED INTO EXISTING

SLAB WITH 8" MIN EMBED. PROVIDE 1/2" EXP. JOINT BETWEEN NEW

AND EXISTING PAD.

219 DUST COLLECTOR - REFER TO MECHANICAL

220 AT EXISTING OPENING, PROVIDE FLASHING ALL SIDES - REFER TO

6/A5.00

223 WHEEL STOP - REFER TO CIVIL

401 METAL DECKING, PAINT (P-2)

U P

D N

ATS

1-C1

1-C2

1-C3

1-C4

1-C5

1-C6

1-C7

1-C8

1-C9

1-C10

1-C11

1-C12

1-C13

1-C14

U P

D N

UP

DN

UPDN

308307306

# B

#A

321A

305304

349A350

353354

362360

303302301

318 316

314 313 312

341A

4-BED RM

4-BED RM

4-BED RM

LINEN

STORAGE

S T O R A G E

4-BED RM2-BED RM

TOIL.

TOIL.

2-BED RM

STAIRS

CORRIDOR

C O R R

ID

O R

CORRIDOR

SUPPLY

RM

UTILITY

UTILITY

CLOSET

2-BED RM

STAIRS

TOIL.

2-BED RM

MED.PREP.

STAT.

LOUNGE

TOIL.

NURSES OFFICE

TOIL.

SHSH

TOIL.

OFFICEDON

ADON

JAN.

SECRETARY

ROOMULTRASOUND

CORRIDOR

SERVICE

ELEVATOR

WHEEL CHAIRS

SHAFT TOIL.

ELECT.BOXES

NURSE LOUNGE

TOIL.

TOIL.

MONITORING

TOIL.

PROCEDURE ROOM

HOUSE/ FLOAT

WORK

RM.

ULTRASOUND

MED. PREP.

SH.C

O R R

ID

E R

STA.

DENTAL SURGERY

TREADMILL

ULTRASOUND

DARK RM

TOIL. TOIL.

STAIRS

# 2

TOIL.

TOIL.

1-BED RM 1-BED RM

ISOLATION

1-BED RM1-BED RM

ISOLATION

TOIL.

SH SH

TOIL.

ISOLATION

1-BED RM

SH

TOIL.

SERVICE

TOIL.

TOIL.

CONFERENCE

FILE

TOIL.

2-BED RM

TOIL.

TOIL.

2-BED RM

JAN.

TOIL.

2-BED RM 2-BED RM

TOIL.

TOIL.

2-BED RM

TOIL. TOIL.

CORRIDOR

NURSES.

P.T.

STA.

SH.

SUPPLY

TLT

MECH.

SHAFT

SH.

SOILED UTILITY

CLEAN UTILITY

CLOSET

ELECT.

ELEVATOR

SERVICE

ELEVATOR

STRETCHERS &

NURSES.

STA.

P.T.

STA.

NOURISH.

NURSES

UNIT

TREATMENT

SOILED

CLEAN

SH.

SH.

BATH

BATH

S H A F T

SH.

SH. MED. EQUIP

CLEAN

F.H.C.

F.H.C.

E.W.C.

E.W.C.

F.H.C. F.H.C.

F.H.C.

F.H.C.

E.W.C.PASSENGER

PASSENGER

ELEVATOR

TUB

E Q U

IP

EKG /

PHARMACY

WAITING RM

OFFICE

RM.

CLEANING

COMPRESSOR

ROOM

PATIENT

CLOTHES

SOCIAL

LP

LP

LP LP

LP

LP

LP

LP

LP

LP

LP

LP LP

LP

LP

LP

LP

LP

LP

LP

LP LP

LP

LP

LP LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

FH

FH

FH

FH

FH

FH

FH

FH

FH

ROOF

ACCESS

HATCH ABOVE

10'-0"

T R

AS

H

C O M P A C

TO

R

Traffic Flow

LP

S ES

F U TU RELDPX F MR

EXIST

SES

H VAC

E

E

E

E

E

E

E

E

E

E

H VAC

E

E

E

E

E

M

E

E

E

E

E

GLENROSA LANE

th

S T

R E

E T

INDIAN SCHOOL RD.

C A N A L

MONTEROSA STREET

C A N A L

ST

R E E T

T

H P

L A

C E th

S T

R E

E T

DEVONSHIRE AVE

HEATHERBRAE DR

L O

A D

IN

G

D O

C K t h

S T

R E

E T t h

P L

A C

E

RAMADA

POWER

PLANT

BLDG 234

SPECIALTY SERVICES

BLDG 254

SHOP

BLDG

STORAGE

BLDG 8

BEHAVIORAL HEALTH &

SOCIAL SERVICES

BLDG 5/6

NIH

BLDG 1

PATHOLOGY

ADMINISTRATION

BLDG 4

WAREHOUSE

BLDG 9

PCMC NORTH

BLDG 010

DENTAL

CLINIC ANNEX

BLDG 238

PCMC SOUTH

BLDG 252

WOMENS

CLINIC

BLDG 253

MAIN

HOSPITAL

BLDG 233

WIC

BLDG 300

AZTEC

SQUARE

OEH

STORAGE

DENTAL CLINIC

BLDG 239

SWEATLODGE

SITE

CT

BLDG

PROPOSED

PEDS CLINIC

BM

#2

BM

#2

LIFTSTA.

LIFTSTA.

LIFT

STA.

LIFTSTA.

LIFTSTA.

A. DIMENSIONS ARE TO COLUMN CENTERLINE OR FACE OF WALL, U.N.O.

B. ALL WALLS ARE TO UNDERSIDE OF DECK, U.N.O.

C. REFER TO SHEET A2.50 FOR ROOM FINISHES.

DOCTOR

OFFICE

NURSE

LOUNGE

ISOLATION

ROOM

ISOLATION

ROOM

ISOLATION

ROOM

ISOLATION

ROOM

TREATMENT

ROOM

336NURSE

OFFICE

MED PREP

321A

NURSES

STATION

NOURISH

NURSES

LOUNGE

UNIT

SUPPLY

SOILED

UTILITY

CLEAN

UTILITY

ELECT.

CLOSET

DOCTOR

TOILET

TOILET

305A

TOILET

308A

TOILET

309A

TOILET

301A

TOILET

302A

A3.30

PATIENT

ROOM

PLAN FOR REFERENCE -

REFER TO A3.30

BOILER

ROOM

PP-1

SHOWER

PP-3 JANITOR

PP-6

LOCKER

PP-5 TOILET

PP-2

PAINT SHOP

PP-2

DN

MIN.

10'-0"

M

IN

4' -0

9'

-1

1/ 4"

UP

2' -0

2'-0"

2' -0

212212 212212

PUMP PIT

PP-9

UP

+/-7'-11 5/8"

MIN.

3'-0"

M

IN

2' -6

6'

-2

/2

AREA OF WORK

AREA OF WORK

AREA OF WORK

R

EG

IST

ERED ARCHITECT

A

R I Z O N A , U . S

A

D a te S ig n ed . .

CE

RT

IFICATE NO.30775

SUSAN M.

GRAY

EXPIRES 12/31/2026

R

VI

H

P

S

N I D

C E

I

A

A N

HE TL H

S

E

E

H

N M

E

A R

P

T O F

T

C

D

SU

S

A

E

TAE L

H

N V I

S E R

U M A

H U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

INDIAN HEALTH SERVICE

DIVISION OF FACILITIES ENGINEERING

PHOENIX AREA

ARCHITECTS

4636 N. 32nd Street

480.980.9054 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

DRAWN BY:

CONSULTANTS

Phoenix, Arizona 85018

CHECKED BY:

CAD DWG FILE:

PROJECT NO:

ISSUE:

SHEET OF

REVIEWED:

DFE ENGINEER/PROJECT MANAGER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

REV DATE DESCRIPTION

IHS PROJECT NO.

C

B

A

C

B

A

SHEET TITLE

Indian Health Service

CONSTRUCTION DOCUMENTS DRAWINGS

PIMC MECHANICAL PROJECT 2 -

CENTRAL PLANT &

ISOLATION ROOMS (BLDG 234)

1/

/2

A2.30

FLOOR PLAN - LOWER

LEVEL, LEVEL ONE, AND

LEVEL THREE

1/15/2024 1818.015

Author

CIVIL

EEC, Inc

555 E. River Road, #301

Tucson, AZ 85704

Phone: 502.321.4625

MEP

Zona Technical Eng

6422 E. Speedway Blvd., Unit 130

Tucson, AZ 85710

Phone: 520.200.2612

STRUCTURAL

Turner Structural

2806 N. Alvernon Way, Suite

Tucson, AZ 85712

Phone: 520.323.3422

4212 N 16th Street

Phoenix, AZ 85016

PH22PH03H6

FLOOR PLAN GENERAL NOTES

KEYNOTES

207 MECHANICAL EQUIPMENT - REFER TO MECHANICAL FOR

ADDITIONAL INFORMATION

209 EXISTING BOLLARD TO REMAIN

211 UNDERGROUND TUNNEL TO REMAIN

212 UNEXCAVATED AREA TO REMAIN

213 NEW HOUSEKEEPING PAD - REFER TO CIVIL, STRUCTURAL, AND

MECHANICAL

214 NEW CONCRETE EQUIPMENT PAD, CONTRACTOR TO CONFIRM FINAL

SIZE WITH FINAL EQUIPMENT SELECTION - REFER TO STRUCTURAL

217 RE-PAVED AREA - REFER TO CIVIL

222 HEAT EXCHANGER - REFER TO MECHANICAL

1/8" = 1'-0"1

FLOOR PLAN - THIRD LEVEL ISOLATION ROOMS - FOR REFERENCE 0' 4' 8' 16'

PLAN

NORTH

1/8" = 1'-0"3

FLOOR PLAN - FIRST LEVEL POWER PLANT 0' 4' 8' 16'

PLAN

NORTH

1/8" = 1'-0"2

FLOOR PLAN - LOWER LEVEL POWER PLANT0' 4' 8' 16'

PLAN

NORTH

KEYPLAN - LEVEL THREE

KEYPLAN - SITE PLAN

MATERIAL MANUFACTURER SIZE / COLOR / NAME APPLICATION / LOCATION

PAINT

P-1 SHERWIN WILLIAMS SW7003 / TOQUE WHITE / EMERALD BRAND AS SCHEDULED

P-2 SHERWIN WILLIAMS SW7067 / CITYSCAPE / EXTERIOR CANOPY, COLUMNS, DECKING, BEAMS

P PAINT

A. SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR LOCATIONS

AND EXTENT OF SOFFITS.

B. ALL FINISHES TO BE SELECTED THROUGH PIMC STANDARD

COLORS, GC TO COORDINATE WITH PIMC.

C. COLOR SELECTIONS ARE SHOWN AS BASIS OF DESIGN, FINAL

COLOR SELECTIONS TBD DURING FINISH SUBMITTAL PROCESS

AND SHALL BE REVIEWED AND APPROVED BY PIMC AND

ARCHITECT.

1. PAINT TO MATCH EXISTING

R

EG

IST

ERED ARCHITECT

A

R I Z O N A , U . S

A

D a te S ig n ed . .

CE

RT

IFICATE NO.30775

SUSAN M.

GRAY

EXPIRES 12/31/2026

R

VI

H

P

S

N I D

C E

I

A

A N

HE TL H

S

E

E

H

N M

E

A R

P

T O F

T

C

D

SU

S

A

E

TAE L

H

N V I

S E R

U M A

H U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

INDIAN HEALTH SERVICE

DIVISION OF FACILITIES ENGINEERING

PHOENIX AREA

ARCHITECTS

4636 N. 32nd Street

480.980.9054 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

DRAWN BY:

CONSULTANTS

Phoenix, Arizona 85018

CHECKED BY:

CAD DWG FILE:

PROJECT NO:

ISSUE:

SHEET OF

REVIEWED:

DFE ENGINEER/PROJECT MANAGER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

REV DATE DESCRIPTION

IHS PROJECT NO.

C

B

A

C

B

A

SHEET TITLE

Indian Health Service

CONSTRUCTION DOCUMENTS DRAWINGS

PIMC MECHANICAL PROJECT 2 -

CENTRAL PLANT &

ISOLATION ROOMS (BLDG 234)

1/

/2

A2.50

ROOM SCHEDULE,

MATERIALS, FINISHES

LEGEND & DETAILS

1/15/2024 1818.015

Author

CIVIL

EEC, Inc

555 E. River Road, #301

Tucson, AZ 85704

Phone: 502.321.4625

MEP

Zona Technical Eng

6422 E. Speedway Blvd., Unit 130

Tucson, AZ 85710

Phone: 520.200.2612

STRUCTURAL

Turner Structural

2806 N. Alvernon Way, Suite

Tucson, AZ 85712

Phone: 520.323.3422

4212 N 16th Street

Phoenix, AZ 85016

PH22PH03H6

ROOM SCHEDULE

# ROOM NAME

FLOOR WALLS CEILING

COMMENTSFINISH BASE

NORTH EAST SOUTH WEST

SURFACE FINISHSURFACE FINISH SURFACE FINISH SURFACE FINISH SURFACE FINISH

301 ISOLATION ROOM EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST GWB P-1 1

302 ISOLATION ROOM EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST GWB P-1 1

303 ISOLATION ROOM EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST GWB P-1 1

304 ISOLATION ROOM EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST GWB P-1 1

MATERIALS & FINISHES LEGEND

ROOM FINISH ABBREVIATIONS

ROOM FINISH GENERAL NOTES

ROOM FINISH REMARKS

U P

D N

# B

2-BED RM

STAIRS

CORRIDOR

CORRIDOR

SERVICE

ELEVATOR

SHAFT

MECH.

SHAFT ELEVATOR

SERVICE

ELEVATOR

F.H.C.

E.W.C.

F.H.C.

PASSENGER

PASSENGER

ELEVATOR

1-C1

1-C2

1-C3

1-C4

1-C5

1-C6

1-C7

1-C8

1-C9

1-C10

1-C11

1-C12

1-C13

1-C14

U P

D N

UP

DN

UPDN

308307306

# B

#A

321A

305304

349A350

353354

362360

303302301

318 316

314 313 312

341A

4-BED RM

4-BED RM

4-BED RM

LINEN

STORAGE

S T O R A G E

4-BED RM2-BED RM

TOIL.

TOIL.

2-BED RM

STAIRS

CORRIDOR

C O R R

ID

O R

CORRIDOR

SUPPLY

RM

UTILITY

UTILITY

CLOSET

2-BED RM

STAIRS

TOIL.

2-BED RM

MED.PREP.

STAT.

LOUNGE

TOIL.

NURSES OFFICE

TOIL.

SHSH

TOIL.

OFFICEDON

ADON

JAN.

SECRETARY

ROOMULTRASOUND

CORRIDOR

SERVICE

ELEVATOR

WHEEL CHAIRS

SHAFT TOIL.

ELECT.BOXES

NURSE LOUNGE

TOIL.

TOIL.

MONITORING

TOIL.

PROCEDURE ROOM

HOUSE/ FLOAT

WORK

RM.

ULTRASOUND

MED. PREP.

SH.C

O R R

ID

E R

STA.

DENTAL SURGERY

TREADMILL

ULTRASOUND

DARK RM

TOIL. TOIL.

STAIRS

# 2

TOIL.

TOIL.

1-BED RM 1-BED RM

ISOLATION

1-BED RM1-BED RM

ISOLATION

TOIL.

SH SH

TOIL.

ISOLATION

1-BED RM

SH

TOIL.

SERVICE

TOIL.

TOIL.

CONFERENCE

FILE

TOIL.

2-BED RM

TOIL.

TOIL.

2-BED RM

JAN.

TOIL.

2-BED RM 2-BED RM

TOIL.

TOIL.

2-BED RM

TOIL. TOIL.

CORRIDOR

NURSES.

P.T.

STA.

SH.

SUPPLY

TLT

MECH.

SHAFT

SH.

SOILED UTILITY

CLEAN UTILITY

CLOSET

ELECT.

ELEVATOR

SERVICE

ELEVATOR

STRETCHERS &

NURSES.

STA.

P.T.

STA.

NOURISH.

NURSES

UNIT

TREATMENT

SOILED

CLEAN

SH.

SH.

BATH

BATH

S H A F T

SH.

SH. MED. EQUIP

CLEAN

F.H.C.

F.H.C.

E.W.C.

E.W.C.

F.H.C. F.H.C.

F.H.C.

F.H.C.

E.W.C.PASSENGER

PASSENGER

ELEVATOR

TUB

E Q U

IP

EKG /

PHARMACY

WAITING RM

OFFICE

RM.

CLEANING

COMPRESSOR

ROOM

PATIENT

CLOTHES

SOCIAL

MONITORING

DOCTOR

OFFICE

NURSE

LOUNGE

ISOLATION

ROOM

ISOLATION

ROOM

ISOLATION

ROOM

ISOLATION

ROOM

PATIENT

ROOM

TREATMENT

ROOM

336NURSE

OFFICE

MED PREP

321A

NURSES

STATION

NOURISH

NURSES

LOUNGE

UNIT

SUPPLY

SOILED

UTILITY

CLEAN

UTILITY

ELECT.

CLOSET

DOCTOR

TOILET

TOILET

305A

TOILET

308A

TOILET

309A

TOILET

301A

TOILET

302A

300302 300 300 300302 302 302

GWB

8' - 0 1/2" AFF

GWB

8' - 0 1/2" AFF

GWB

8' - 0 1/2" AFF

GWB

8' - 0 1/2" AFF

GWB

8' - 0 1/2" AFF

GWB

8' - 0 1/2" AFF

GWB

8' - 0 1/2" AFF

GWB

8' - 0 1/2" AFF303 303

A. SEE GENERAL NOTES ON SHEET G1.10 FOR SUSPENDED CEILING GRID

LAYOUT AND PLACEMENT OF CEILING MOUNTED DEVICES.

B. SEE FLOOR PLAN FOR PARTITION TYPES.

C. COORDINATE CEILING PLANS WITH MECHANICAL, FIRE PROTECTION AND

ELECTRICAL PLANS.

CEILING TYPES:

A

B

GWB / E.T.S.

CEILING EQUIPMENT:

LIGHT FIXTURE - RECESSED IN

CEILING.

GENERAL NOTES:

1. CEILING HEIGHTS SHOWN IN PLAN ARE NOMINAL AND SHOULD BE

COORDINATED WITH DETAILS AND SECTIONS.

2. COORDINATE EMERGENY LIGHTING, EXIT LIGHTING, AND NIGHT LIGHTING

WITH ELECTRICAL.

MECH - EXHAUST GRILL /

TRANSFER GRILL

MECH - SUPPLYGRILL

EXIT LIGHT

CEILING EQUIPMENT:

EB

EMERGENCY BATTERY PACK -

WALL MOUNT.

LED EXIT FIXTURE - CEILING MOUNT.

LED EXIT FIXTURE - WALL MOUNT.

2x4 SUSPENDED

ACOUSTICAL CEILING

SURFACE MOUNTED/CEILING

MOUNTED FIXTURE.

MECH - EXHAUST GRILL

AREA OF WORK

R

EG

IST

ERED ARCHITECT

A

R I Z O N A , U . S

A

D a te S ig n ed . .

CE

RT

IFICATE NO.30775

SUSAN M.

GRAY

EXPIRES 12/31/2026

R

VI

H

P

S

N I D

C E

I

A

A N

HE TL H

S

E

E

H

N M

E

A R

P

T O F

T

C

D

SU

S

A

E

TAE L

H

N V I

S E R

U M A

H U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

INDIAN HEALTH SERVICE

DIVISION OF FACILITIES ENGINEERING

PHOENIX AREA

ARCHITECTS

4636 N. 32nd Street

480.980.9054 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

DRAWN BY:

CONSULTANTS

Phoenix, Arizona 85018

CHECKED BY:

CAD DWG FILE:

PROJECT NO:

ISSUE:

SHEET OF

REVIEWED:

DFE ENGINEER/PROJECT MANAGER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

REV DATE DESCRIPTION

IHS PROJECT NO.

C

B

A

C

B

A

SHEET TITLE

Indian Health Service

CONSTRUCTION DOCUMENTS DRAWINGS

PIMC MECHANICAL PROJECT 2 -

CENTRAL PLANT &

ISOLATION ROOMS (BLDG 234)

1/

/2

A3.30

REFLECTED CEILING PLAN

- LEVEL THREE

1/15/2024 1818.015

Author

CIVIL

EEC, Inc

555 E. River Road, #301

Tucson, AZ 85704

Phone: 502.321.4625

MEP

Zona Technical Eng

6422 E. Speedway Blvd., Unit 130

Tucson, AZ 85710

Phone: 520.200.2612

STRUCTURAL

Turner Structural

2806 N. Alvernon Way, Suite

Tucson, AZ 85712

Phone: 520.323.3422

4212 N 16th Street

Phoenix, AZ 85016

PH22PH03H6

1/8" = 1'-0"1

CEILING PLAN - THIRD LEVEL ISOLATION ROOMS 0' 4' 8' 16'

PLAN

NORTH

REFLECTED CEILING PLAN GENERAL NOTES

REFLECTED CEILING PLAN LEGEND

KEYNOTES

300 RELOCATED LIGHT FIXTURE - REFER TO ELECTRIC

302 NEW ACCESS PANEL - REFER TO MECHANICAL

303 REPLACE PORTION OF CEILING GRID AND REPLACE CEILING TILES

WITH SALVAGED TILES

KEYPLAN - LEVEL THREE

A5.00

METAL DECKING

OVER STEEL BEAMS,

PAINT (P-2) - REF TO

STRUCTURAL

STEEL COLUMNS,

PAINT (P-2) - REF TO

STRUCTURAL

REPAVED DRIVE -

REF TO CIVIL

A5.00

METAL DECKING

OVER STEEL BEAMS,

PAINT (P-2) - REF TO

STRUCTURAL

STEEL COLUMNS,

PAINT (P-2) - REF TO

STRUCTURAL

REPAVED DRIVE -

REF TO CIVIL

METAL DECKING

OVER STEEL BEAMS,

PAINT (P-2) - REFER

TO STRUCTURAL

STEEL COLUMNS,

PAINT (P-2) - REFER

TO STRUCTURAL

REPAVED DRIVE -

REFER TO CIVIL

3/8" / 12"

METAL DECKING

OVER STEEL BEAMS,

PAINT (P-2) - REFER

TO STRUCTURAL

STEEL COLUMNS,

PAINT (P-2) - REFER

TO STRUCTURAL

REPAVED DRIVE -

REFER TO CIVIL

1/

4"

3/8" / 12"

/4

METAL DECKING OVER STEEL BEAMS,

PAINT (P-2) - REFER TO STRUCTURAL

STEEL COLUMNS,

PAINT (P-2) -

REFER TO

STRUCTURAL

REPAVED DRIVE -

REFER TO CIVIL

STEEL BEAM BEYOND,

PAINT (P-2) - REFER TO

STRUCTURAL

STEEL BEAM, PAINT

(P-2) - REFER TO

STRUCTURAL

STEEL BEAM, PAINT

(P-2) - REFER TO

STRUCTURAL

3/8" / 12"

1/

4"

/4

SITE WALL TO

REMAIN

SIDEWALK TO

REMAIN

CONCRETE

FOOTING BEYOND -

REFER TO

STRUCTURAL

SITE WALL

FENCING TO

REMAIN

A5.00

A5.00

A5.00

CONT. 1/2" EXP.

JOINT

ELECTRICAL

OUTLET - REFER TO

ELECTRICAL

4'-6" 2'-10" 7'-4" 7'-4"

WHEEL STOP -

REFER TO CIVIL

LIGHT FIXTURE - REFER

TO ELECTRICAL

HORIZONTAL METAL

PANEL TO REMAIN

OPENING FOR

DUCTWORK - REFER TO

MECHANICAL

STRUCTURAL BEAM

TO REMAIN

INSIDE CLOSURE BASE

TRIM AND FLASHING

INSIDE CLOSURE BASE

TRIM AND FLASHING

HORIZONTAL METAL

PANEL TO REMAIN

STRUCTURAL BEAM

TO REMAIN

4"

STEEL ANGLE, PAINT

(P-2) - REFER TO

STRUCTURAL

STEEL BEAM, PAINT

(P-2) - REFER TO

STRUCTURAL

CONT. MTL

FLASHING, TYP

MTL DECKING, PAINT

(P-2) - REFER TO

STRUCTURAL

STEEL BEAM

BEYOND, PAINT

(P-2) - REFER TO

STRUCTURAL

STEEL ANGLE, PAINT

(P-2) - REFER TO

STRUCTURAL

STEEL BEAM, PAINT

(P-2) - REFER TO

STRUCTURAL

CONT. MTL

FLASHING, TYP

MTL DECKING, PAINT

(P-2) - REFER TO

STRUCTURAL

STEEL BEAM

BEYOND, PAINT

(P-2) - REFER TO

STRUCTURAL

R

EG

IST

ERED ARCHITECT

A

R I Z O N A , U . S

A

D a te S ig n ed . .

CE

RT

IFICATE NO.30775

SUSAN M.

GRAY

EXPIRES 12/31/2026

R

VI

H

P

S

N I D

C E

I

A

A N

HE TL H

S

E

E

H

N M

E

A R

P

T O F

T

C

D

SU

S

A

E

TAE L

H

N V I

S E R

U M A

H U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

INDIAN HEALTH SERVICE

DIVISION OF FACILITIES ENGINEERING

PHOENIX AREA

ARCHITECTS

4636 N. 32nd Street

480.980.9054 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

DRAWN BY:

CONSULTANTS

Phoenix, Arizona 85018

CHECKED BY:

CAD DWG FILE:

PROJECT NO:

ISSUE:

SHEET OF

REVIEWED:

DFE ENGINEER/PROJECT MANAGER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

REV DATE DESCRIPTION

IHS PROJECT NO.

C

B

A

C

B

A

SHEET TITLE

Indian Health Service

CONSTRUCTION DOCUMENTS DRAWINGS

PIMC MECHANICAL PROJECT 2 -

CENTRAL PLANT &

ISOLATION ROOMS (BLDG 234)

1/

/2

A5.00

CANOPY ELEVATIONS &

SECTION

1/15/2024 1818.015

Author

CIVIL

EEC, Inc

555 E. River Road, #301

Tucson, AZ 85704

Phone: 502.321.4625

MEP

Zona Technical Eng

6422 E. Speedway Blvd., Unit 130

Tucson, AZ 85710

Phone: 520.200.2612

STRUCTURAL

Turner Structural

2806 N. Alvernon Way, Suite

Tucson, AZ 85712

Phone: 520.323.3422

4212 N 16th Street

Phoenix, AZ 85016

PH22PH03H6

1/8" = 1'-0"1

CANOPY NORTH ELEVATION

1/8" = 1'-0"2

CANOPY SOUTH ELEVATION

1/8" = 1'-0"4

CANOPY EAST ELEVATION

1/8" = 1'-0"3

CANOPY WEST ELEVATION

SCALE: 1/2" = 1'-0"5

CANOPY SECTION

SCALE: 1 1/2" = 1'-0"6

FLASHING DETAIL

SCALE: 1 1/2" = 1'-0"7

CANOPY EDGE DETAIL

SCALE: 1 1/2" = 1'-0"8

CANOPY EDGE DETAIL

W 12 x26

'-8

W 12 x26

W 12 x26

W 12 x26

72'-8"

4' -1

0"

18'-0" 18'-0" 18'-0" 4"4"

TYP.

TYP.

'-8

72'-8"

4"

18'-0" 18'-0" 18'-0" 4"4"

W

2x

W

2x

W

2x

W

2x

W 8x10 do do

W 8x10

W 8x10 do do

W 8x10

W 8x10 do do

W 8x10

TYP.

SL

OP

E

4' -6

2'

-1 0"

7' -4

7'

-4

4"

S1.2

TY

P.

S1.2

TY

P.

S1.2

TY

P.

W 12 x26

18'-0"

W

2x

W 8x10 do do

W 8x10

18'-0"

T.O .B. E

L.=

'-3

T.O .B. E

L.=

'-0

" 2

TYP.

DWGS., PROVIDE PAD 6" BEYOND

SEE ARCH., MECH., & ELEC.

EACH WAY

#4 AT 12" O.C.

EDGE OF ALL EQUIPMENT, TYP.

1 1/2" CLEAR

3/4" CHAMFER,

ALL AROUND

FIN. GRADE OR

CONC. SLAB

8" 6"

1/2" = 1'-0"

ROUGHEN SURFACE AND

CLEAN PRIOR TO PLACING

NEW CONCRETE

3/4" = 1'-0"

#4 AT 12" O.C.

EACH DIR.EXTG. CONC.

SLAB

2"

CLR.

4"

3/4" CHAMFER

3" EMBED

DWGS., PROVIDE PAD 6" BEYOND

SEE ARCH., MECH., & ELEC.

EDGE OF ALL EQUIPMENT, TYP.

EPOXY GROUT,

TYP.

1. ASPHALT DRIVE - REFER TO CIVIL DRAWINGS.

2. OUTLINE OF ROOF ABOVE. SEE B/S1.1.

1 2 3 4

A

B

C

B

C

1 2 3 4

REV

PROJECT NO: 1818.015

CAD DWG FILE:

DRAWN BY:

CHECKED BY:

DATE DESCRIPTION

SHEET ______ OF ______

SHEET TITLE

ARCHITECTS

CONSULTANTS

U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

ISSUE: 01/15/2024 100% CONSTRUCTION DOCUMENTS DRAWINGS

REVIEWED:

DFE ENGINEER/PROJECT MANAGER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

STRUCTURAL

Turner Structural Eng.

2806 N Alvernon Way, Suite Tucson, AZ 85712 Phone: (520) 323-3422

TURNER STRUCTURAL

ENGINEERING COMPANY

CIVIL

EEC, Inc 555 E. River Road, #301 Tucson, AZ 85704 Phone: 520.321.4625

MEP

Zona Technical Eng.

6422 E. Speedway Blvd., Unit 130 Tucson, AZ 85710 Phone: 520.200.2612

4636 N. 32nd Street

480.980.9054 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

Phoenix, Arizona 85018

IHS PROJECT NO.

Indian Health Service

PIMC MECHANICAL PROJECT 2 -

CENTRAL PLANT &

ISOLATION ROOMS (BLDG 234)

4212 N 16th Street Phoenix, AZ 85016

PH22PH03H6

A SCALE: 1/4" = 1'-0"

FOUNDATION PLAN - Parking Canopy 2' 4'0 8'

B SCALE: 1/4" = 1'-0"

ROOF FRAMING PLAN - Parking Canopy 2' 4'0 8'

1. 1 1/2" TYPE 'B' (WIDE RIB), 20 GAGE, PAINTED, STEEL ROOF DECK WITH THE

FOLLOWING MINIMUM SECTION PROPERTIES: S = 0.235 In I = 0.216 In

2. T.O.J. (TOP OF JOIST), T.O.B. (TOP OF BEAM), SET RELATIVE TO REFERENCE

FINISH FLOOR ELEVATION OF 0'-0".

FOUNDATION AND ROOF

FRAMING PLANS -

PARK…