This document outlines requirements for the Providencia Island Solar Power Plant Project solicitation. The solicitation seeks a contractor to manufacture or procure a battery-based electrical energy storage system to serve as the primary energy source for Providencia Island, Colombia. Key requirements include cells, modules, battery racks, inverters, a battery management system, control and monitoring systems, auxiliary services, and a SCADA system to integrate the battery energy storage system into the island's hybrid system. The system must deliver 2.5 megawatt hours to the electric grid for a minimum of one hour and support peak demand up to 1.8 megawatts. The selected contractor will participate in developing the project, which consists of a 1.8 megawatt photovoltaic solar power plant, battery energy storage system, and power management system to incorporate the island's existing diesel generators. The Agency for this opportunity is the US Agency for International Development Colombia.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INGENIERÍA DEL POWER MANAGEMENT SYSTEM
(PMS) PARA EL PROYECTO FOTOVOLTAICO EPC
EN LA ISLA PROVIDENCIA
DIMENSIONAMIENTO DEL HARDWARE PMS
DOCUMENTO: ECP-MCE-ECC21007-ID-01-INS-ET-155-C
REVISION C
Elaboración – Revisión – Aprobación
Revisión Modificaciones Elaboración Revisión Aprobación Fecha
A Emisión original JT JN MU 16/09/2022
B Actualización Comentarios 1 JT JN MU 19/09/2022
C Actualización Comentarios 2 JT JN MU 07/10/2022
INGENIERÍA DEL POWER MANAGEMENT
SYSTEM (PMS) PARA EL PROYECTO
FOTOVOLTAICO EPC EN LA ISLA
PROVIDENCIA
Doc. No.
ECP-MCE-
ECC21007-ID-01-
INS-ET-155-C
DIMENSIONAMIENTO DEL HARDWARE
PMS
REVISIÓN: B
FECHA: 07/10/2022
Archivo: ECP-MCE-ECC21007-ID-01-INS-ET-155-B 2 de 19
CONTENIDO
1. OBJETO
2. JUSTIFICACIÓN
3. GLOSARIO
4. DOCUMENTOS DE REFERENCIA
5. CRITERIOS DE DISEÑO
6. DISTRIBUCIÓN FÍSICA DE EQUIPOS EN GABINETES
6.1 GABINETE DE LLEGADA
6.2 GABINETE DE COMUNICACIONES Y SERVIDORES
7. VIRTUALIZACIÓN SERVIDORES
7.1 SERVIDOR BASE 1: Sistema base para Virtualización Servidor 1
7.2 SERVIDOR BASE 2: Sistema base para Virtualización Servidor 2
7.3 SERVIDOR AD1V: Servidores ADMS 1
7.4 SERVIDOR AD2V: Servidores ADMS 2
7.5 PR1V: Servidores de Procesamiento Dedicado 1
7.6 PR2V: Servidores de Procesamiento Dedicado 2
7.7 QA1V: Servidor QAS
7.8 OT1V: Servidor OTS
8. HARDWARE SERVIDORES
8.1 DIMENSIONAMIENTO
8.2 CARACTERÍSTICAS TÉCNICAS SERVIDORES
9. MONITOR DE TV
10. ESTACIONES DE TRABAJO
10.1 MONITOR
10.2 UNIDAD CENTRAL DE PROCESAMIENTO (CPU)
10.3 IMPRESORA
11. RELOJ DE SINCRONIZACIÓN DE TIEMPO (GPS)
12. SWITCH CAPA 2
13. SWITCH CAPA 3
14. DISTRIBUIDOR DE FIBRA ÓPTICA (ODF)
15. PARTCHCORD
ECC21007-ID-01-
INS-ET-155-C
DIMENSIONAMIENTO DEL HARDWARE
PMS
3 de 19
16. SFPs / Transductores ópticos para uso con Fibra óptica
ECC21007-ID-01-
INS-ET-155-C
DIMENSIONAMIENTO DEL HARDWARE
PMS
4 de 19
1. OBJETO
El presente documento consta de la descripción correspondiente al hardware relacionado con servidores, workstations y equipos periféricos del sistema PMS perteneciente al proyecto INGENIERIA SISTEMA PMS PROVIDENCIA, con el fin de indicar las principales características.
2. JUSTIFICACIÓN
Tomando como referencia los análisis previos para el sistema PMS en la isla de providencia, se planteará a lo largo de este documento las características y funcionalidades que harán parte del sistema a nivel de Hardware.
3. GLOSARIO
SCADA: Control de supervisión y la adquisición de datos (SCADA) es una arquitectura de sistema de control que comprende computadoras, comunicaciones de datos en red e interfaces gráficas de usuario para la supervisión de alto nivel de máquinas y procesos.
GPS: Global Positioning System (Sistema de posicionamiento local – Sincronización de tiempo).
PMS: Power Management System (Sistema de Administración de Potencia).
HMI: Human-Machine Interface (Interfaz Hombre-Máquina).
LAN: Local Área Network (Red de Área Local).
NIVEL 2: Sistema de control y automatización referente a interfaz con locaciones externas con las cuales existe interacción de datos para monitoreo y control. Es el nivel de Subestación, en el cual desde un sistema SCADA HMI, se realizan las funciones de control, supervisión y adquisición de datos de toda la Subestación.
NIVEL 3: Sistema de control y automatización referente al sistema que controlará interfaz con locaciones externas con las cuales existe interacción de datos para monitoreo y control.
Es el nivel de Centro de Control – SCADA, en este nivel se concentra la información de los sistemas SCADA HMI monitoreados de nivel 2.
4. DOCUMENTOS DE REFERENCIA
ESPECIFICACIONES TÉCNICAS DE SISTEMAS DE INSTRUMENTACIÓN-NIVEL 2 Y
COMUNICACIONESECP-21007-IB01-0-INS-ET-003. (Se presentan actualizaciones y ajustes de acuerdo a los criterios de diseño del presente documento)
DESCRIPCION DE SERVIDORES Y SOFTWARE PMS ECP-MCE-ECC21007-ID-01-INS-PL-156-A
ECC21007-ID-01-
INS-ET-155-C
DIMENSIONAMIENTO DEL HARDWARE
PMS
5 de 19
5. CRITERIOS DE DISEÑO
Premisas para dimensionamiento de los equipos y sistemas:
1. El presente diseño tiene en cuenta las restricciones de espacio que pueden existir en el Shelter para hacer viable las actividades de Instalación y logística en
Providencia.
2. Las aplicaciones que deriven la utilización de varios servidores serán virtualizadas, buscando minimizar la cantidad de equipos a instalar, lo anterior según lo sugerido en el documento de especificaciones técnicas ECP-21007-IB01-0-INS-ET-003.
3. Se buscará optimizar y minimizar el consumo de energía del sistema PMS.
4. Se seguirán las recomendaciones del fabricante Survalent para implementación del sistema en su versión más reciente, la arquitectura de diseño del Software de
SURVALENT permite manejar de forma centralizada y con estructura 100%
REDUNDANTE las aplicaciones Avanzadas, Front End e Histórcos en un mismo entorno agregando rapidez y respuesta en tiempos de procesamiento.
6. DISTRIBUCIÓN FÍSICA DE EQUIPOS EN GABINETES
Teniendo en cuenta los criterios de diseños mencionados, los gabinetes de comunicaciones y de servidores se organizan en los siguientes Gabinetes:
6.1 GABINETE DE LLEGADA
El gabinete de llegada de comunicaciones consiste en equipos Pasivos asociados a conexiones de comunicaciones provenientes de sistemas los siguientes sistemas:
Nivel 2 Parque Solar Fotovoltaico
Nivel 2 Central de generación
Previsión de conexión Futura de Centro de control SOPESA.
Monitoreo y control de sistemas complementarios del Shelter.
ECC21007-ID-01-
INS-ET-155-C
DIMENSIONAMIENTO DEL HARDWARE
PMS
6 de 19
La vista de la distribución de los equipos se muestra en la siguiente imagen. (Las vistas de detalle se encuentran en el documento ECP-MCE-ECC21007-ID-01-INS-PL-156-A):
ECC21007-ID-01-
INS-ET-155-C
DIMENSIONAMIENTO DEL HARDWARE
PMS
7 de 19
6.2 GABINETE DE COMUNICACIONES Y SERVIDORES
El Gabinete de Comunicaciones y Servidores consta de los siguientes equipos:
La vista de la distribución de los equipos se muestra en la siguiente imagen. (Las vistas de detalle se encuentran en el documento ECP-MCE-ECC21007-ID-01-INS-PL-156-A):
ECC21007-ID-01-
INS-ET-155-C
DIMENSIONAMIENTO DEL HARDWARE
PMS
8 de 19
7. VIRTUALIZACIÓN SERVIDORES
Teniendo en cuenta los criterios de diseños mencionados, para el diseño actual se establece un sistema REDUNDANTE virtualizado organizado en dos servidores físicos independientes. Los servidores que ejecutarán los servicios necesarios para el sistema PMS serán virtualizados en dos servidores físicos de acuerdo con la siguiente ilustración:
Figura 1. Servidores virtualizados.
AD1V y AD2V: Servidores ADMS
PR1V y PR2V: Servidores de Procesamiento Dedicado
QA1V: Servidor QAS
OT1V: Servidor OTS
En esta solución que el sistema será redundante con dos servidores físicos en donde se implementarán las aplicaciones descritas anteriormente, lo anterior para brindar una mayor seguridad y confiabilidad para la operación y facilitando labores de mantenimiento debido al posible cambio o modificación de la arquitectura. Adicionalmente, se considera bajo una estructura Cliente/Servidor, para así garantizar la flexibilidad del sistema al aumentar la cantidad de usuarios sin verse afectado el funcionamiento de la red y que la información se encuentre centralizada.
FOTOVOLTAICO EPC EN LA ISLA
PROVIDENCIA
Doc. No.
ECP-MCE-
ECC21007-ID-01-
INS-ET-155-C
DIMENSIONAMIENTO DEL HARDWARE
PMS
REVISIÓN: B
FECHA: 07/10/2022
Archivo: ECP-MCE-ECC21007-ID-01-INS-ET-155-B 9 de 19
7.1 SERVIDOR BASE 1: Sistema base para Virtualización Servidor 1
SERVIDOR
FÍSICO
NOMBRE TIPO CARACTERÍSTICAS
SERVIDOR 1 SISTEMA
BASE SERVIDOR
VIRTUALIZADO
OS: Windows Server 2019 Standard Edition (16 Cores) or superior.
7.2 SERVIDOR BASE 2: Sistema base para Virtualización Servidor 2
SERVIDOR
FÍSICO
NOMBRE TIPO CARACTERÍSTICAS
SERVIDOR 2 SISTEMA BASE
SERVIDOR 1
VIRTUALIZADO
OS: Windows Server 2019 Standard Edition (16 Cores) or superior.
7.3 SERVIDOR AD1V: Servidores ADMS 1
SERVIDOR
FÍSICO
NOMBRE TIPO CARACTERÍSTICAS
SERVIDOR 1 SERVIDOR
AD1V
VIRTUALIZADO
OS: Windows Server 2019 Standard Edition (16 Cores) or superior.
CARACTERÍSTICA UNIDAD SISTEMA BASE 1
NÚCLEOS DE PROCESAMIENTO UND 4
HILOS DEL PROCESADOR UND 8
MEMORIA RAM GB 12
DISCO DURO GB 128
CARACTERÍSTICA UNIDAD SISTEMA BASE 2
NÚCLEOS DE PROCESAMIENTO UND 4
HILOS DEL PROCESADOR UND 8
MEMORIA RAM GB 12
DISCO DURO GB 128
CARACTERÍSTICA UNIDAD AD1V
NÚCLEOS DE PROCESAMIENTO UND 8
HILOS DEL PROCESADOR UND 16
MEMORIA RAM GB 16
DISCO DURO GB 960
FOTOVOLTAICO EPC EN LA ISLA
PROVIDENCIA
Doc. No.
ECP-MCE-
ECC21007-ID-01-
INS-ET-155-C
DIMENSIONAMIENTO DEL HARDWARE
PMS
REVISIÓN: B
FECHA: 07/10/2022
Archivo: ECP-MCE-ECC21007-ID-01-INS-ET-155-B 10 de 19
7.4 SERVIDOR AD2V: Servidores ADMS 2
SERVIDOR
FÍSICO
NOMBRE TIPO CARACTERÍSTICAS
SERVIDOR 2 SERVIDOR
AD2V
VIRTUALIZADO
OS: Windows Server 2019 Standard Edition (16 Cores) or superior.
7.5 PR1V: Servidores de Procesamiento Dedicado 1
SERVIDOR
FÍSICO
NOMBRE TIPO CARACTERÍSTICAS
SERVIDOR 1 SERVIDOR
PR1V
VIRTUALIZADO
OS: Windows Server 2019 Standard Edition (16 Cores) or superior.
7.6 PR2V: Servidores de Procesamiento Dedicado 2
SERVIDOR
FÍSICO
NOMBRE TIPO CARACTERÍSTICAS
SERVIDOR 2 SERVIDOR
PR2V
VIRTUALIZADO
OS: Windows Server 2019 Standard Edition (16 Cores) or superior.
CARACTERÍSTICA UNIDAD AD2V
NÚCLEOS DE PROCESAMIENTO UND 8
HILOS DEL PROCESADOR UND 16
MEMORIA RAM GB 16
DISCO DURO GB 960
CARACTERÍSTICA UNIDAD PR1V
NÚCLEOS DE PROCESAMIENTO UND 4
HILOS DEL PROCESADOR UND 8
MEMORIA RAM GB 12
DISCO DURO GB 256
CARACTERÍSTICA UNIDAD PR2V
NÚCLEOS DE PROCESAMIENTO UND 4
HILOS DEL PROCESADOR UND 8
MEMORIA RAM GB 12
DISCO DURO GB 256
ECC21007-ID-01-
INS-ET-155-C
DIMENSIONAMIENTO DEL HARDWARE
PMS
11 de 19
7.7 QA1V: Servidor QAS
SERVIDOR
FÍSICO
NOMBRE TIPO CARACTERÍSTICAS
SERVIDOR 1 SERVIDOR
QA1V
VIRTUALIZADO
OS: Windows Server 2019 Standard Edition (16 Cores) or superior.
7.8 OT1V: Servidor OTS
SERVIDOR
FÍSICO
NOMBRE TIPO CARACTERÍSTICAS
SERVIDOR 2 SERVIDOR
OT1V
VIRTUALIZADO
8. HARDWARE SERVIDORES
8.1 DIMENSIONAMIENTO
A continuación se presenta el dimensionamiento de cada uno de los servidores físicos de acuerdo a la información de cada uno de los servidores virtualizados:
Con relación a la RAM, El equipo seleccionado cuenta con 16 ranuras para ampliación de la Memoria RAM hasta un máximo de 1TB.
CARACTERÍSTICA UNIDAD QA1V
NÚCLEOS DE PROCESAMIENTO UND 4
HILOS DEL PROCESADOR UND 8
MEMORIA RAM GB 12
DISCO DURO GB 480
CARACTERÍSTICA UNIDAD OT1V
NÚCLEOS DE PROCESAMIENTO UND 4
HILOS DEL PROCESADOR UND 8
MEMORIA RAM GB 12
DISCO DURO GB 480
CARACTERÍSTICA UNIDAD SISTEMA BASE 1 AD1V PR1V QA1V TOTAL
NÚCLEOS DE PROCESAMIENTO UND 4 8 4 4 20
HILOS DEL PROCESADOR UND 8 16 8 8 40
MEMORIA RAM GB 12 16 12 12 52
DISCO DURO GB 128 960 256 480 1.824
SERVIDOR 1
ECC21007-ID-01-
INS-ET-155-C
DIMENSIONAMIENTO DEL HARDWARE
PMS
12 de 19
Con relación al Disco Duro, el equipo seleccionado cuenta con la siguiente configuración en sus bahías frontales:
Hasta 4 SAS / SATA (HDD / SSD) de 3,5 pulgadas máximo 64 TB .
SAS/SATA (HDD/SSD) de hasta 8 x 2,5 pulgadas y 61,4 TB
8.2 CARACTERÍSTICAS TÉCNICAS SERVIDORES
De acuerdo al dimensionamiento presentado anteriormente, se consideran dos servidores físicos Cauno de los servidores contará con las siguientes características:
Características técnicas:
NOMBRE CARACTERÍSTICAS TÉCNICAS
SERVIDOR 1
SERVIDOR 2
Processor: Intel® Xeon® Silver 4316 2.3G, 20C/40T, 10.4GT/s, 30M Cache, Turbo, HT (150W) DDR4-
Memory Capacity: 64GB RDIMM, 3200MT/s, Dual Rank, 16Gb
Hard Drives: 1.92TB SSD SATA Read Intensive 6Gbps 512 2.5in Hot-plug AG Drive,3.5in HYB CARR, 1
DWPD
Installation Type: Rack Mounted 19”.
Preliminarmente se consideran Servidores marca DELL Referencia: PowerEdge R450
CARACTERÍSTICA UNIDAD SISTEMA BASE 2 AD2V PR2V OT1V TOTAL
NÚCLEOS DE PROCESAMIENTO UND 4 8 4 4 20
HILOS DEL PROCESADOR UND 8 16 8 8 40
MEMORIA RAM GB 12 16 12 12 52
DISCO DURO GB 128 960 256 480 1.824
SERVIDOR 2
ECC21007-ID-01-
INS-ET-155-C
DIMENSIONAMIENTO DEL HARDWARE
PMS
13 de 19
9. MONITOR DE TV
A continuación se presentan las características técnicas para el MONITOR TV:
ECC21007-ID-01-
INS-ET-155-C
DIMENSIONAMIENTO DEL HARDWARE
PMS
14 de 19
Referencia Preliminar: Dell 55 4K Conference Room Monitor – C5519Q
10. ESTACIONES DE TRABAJO
10.1 MONITOR
A continuación se presentan las características técnicas para los Monitores de las Estaciones de trabajo:
Referencia Preliminar: Dell 22 Monitor - P2222H MMCLA
ECC21007-ID-01-
INS-ET-155-C
DIMENSIONAMIENTO DEL HARDWARE
PMS
15 de 19
10.2 UNIDAD CENTRAL DE PROCESAMIENTO (CPU)
A continuación se presenta el dimensionamiento para cada CPU de las estaciones de trabajo:
ESTACIONES DE TRABAJO 1, 2 y 3
CARACTERÍSTICA UNIDAD SISTEMA BASE
NÚCLEOS DE PROCESAMIENTO UND 6
HILOS DEL PROCESADOR UND 12
MEMORIA RAM GB 16
DISCO DURO GB 512
TARJETA DE VIDEO UN 1
Se consideran tres (3) estaciones de trabajo, de acuerdo al dimensionamiento anterior, con las siguientes características:
NOMBRE CARACTERÍSTICAS TÉCNICAS
ESTACIÓN DE TRABAJO 1
ESTACIÓN DE TRABAJO 2
ESTACIÓN DE TRABAJO 3
Procesador: Intel® Xeon® W-2235 (8.25 MB cache, 6 cores, 12 threads, 3.80 GHz to 4.60 GHz Turbo, 130 W) Memoria: 16 GB, 2 x 8 GB, DDR4, 2933 MHz, ECC Disco Duro: Unidad de estado sólido PCIe NVMe, M.2, clase 40 de 512GB Tarjeta de Video: NVIDIA® T1000, 4 GB GDDR6 Sistema Operativo: Windows 10 Pro.
Tipo de Instalación: Torre.
Referencia Preliminar: DELL Precision 5820
ECC21007-ID-01-
INS-ET-155-C
DIMENSIONAMIENTO DEL HARDWARE
PMS
16 de 19
10.3 IMPRESORA
A continuación se presentan las características técnicas para las impresoras de las Estaciones de trabajo:
Velocidad De Impresión, Negro: 21 - 30
Color O Negro: Blanco y Negro
Tipo De Producto: Laser printers
Puertos: 1 Hi-Speed USB 2.0; 1 para red Ethernet 10/100
Capacidades De Red: Ethernet 10/100
Referencia Preliminar: HP LaserJet Pro de la serie M203
11. RELOJ DE SINCRONIZACIÓN DE TIEMPO (GPS)
A continuación se presentan las características técnicas para el reloj de Sincronización de tiempo (GPS):
Servidor de tiempo de montaje en rack de 1U de 19 pulgadas
Admite hasta 2 puertos combinados de 100/1000 M
100-360 V CC/85-264 V CA, entradas de alimentación redundantes
Canales satelitales duales (GPS, BDS, GLONASS Opcional)
Admite TCXO u OCXO integrado para la retención de tiempo
Admite un algoritmo de selección de múltiples fuentes seguro y confiable para garantizar la precisión de la salida de tiempo
Admite visualización de pantalla LCD y operación mediante teclas en el panel frontal
Admite hasta 10 puertos BNC para TTL PPS/IRIG-B (DC) o 4 puertos BNC para
IRIG-B (AC)+6 puertos BNC para TTL PPS/IRIG-B (DC)
Admite 2 puertos DB9 para RS232 TOD
Admite la función de gestión del estado del tiempo
Soporte Web, gestión SNMP
Admite PTP (protocolo de sincronización de precisión), NTP (protocolo de tiempo de red), IRIG-B, 1PPS, 1PPM, 1PPH y TOD, etc. salida de señal de sincronización de tiempo como propósito de sincronización de tiempo. Es compatible con TMS
(Sistema de gestión del tiempo).
Referencia: Kyland PTS-10A Time Server
ECC21007-ID-01-
INS-ET-155-C
DIMENSIONAMIENTO DEL HARDWARE
PMS
17 de 19
12. SWITCH CAPA 2
A continuación se presentan las características técnicas para los switches capa 2:
Switch Ethernet industrial administrado de capa 2.
Operación de manera confiable en entornos industriales y subestaciones de servicios eléctricamente exigentes y climáticamente exigentes.
Hasta 4 puertos Gigabit de fibra/cobre y 24 puertos Fast Ethernet de fibra/cobre
Estándares IEC61850 e IEEE1613
Instalación montable en rack 1U de 19 pulgadas
VLAN, multidifusión, QoS, anillo redundante rápido.
Gestión por consola, Telnet, administración web y software de administración de red basado en SNMP.
Referencia preliminares: Kyland SICOM3024P Switch Capa 2, Kyland SICOM3000A Switch Capa 2
13. SWITCH CAPA 3
A continuación se presentan las características técnicas para los switches capa 2:
Diseño modular flexible para una fácil expansión, admite puertos de fibra/cobre de
28 gigabits como máximo.
Admite DT-Ring, DRP, MSTP y VRRP para redundancia de red.
Admite protocolos de enrutamiento de capa 3 como RIP y OSPF.
Admite IEEE1588v2 y la precisión de sincronización alcanza ±100 ns, con PTP
1588 basado en SW y PTP 1588 basado en HW opcional
Admite Ethernet síncrona ITU-TG8261/G.8262 y la precisión de sincronización alcanza ±50 ns.
Admite módulo HSR/PRP, módulo TimeServer, módulo GPS, módulo IRIG-B, módulo TMS-trigger, módulo de servidor serie, módulo LED.
Admite fuentes de alimentación intercambiables en caliente.
Admite la gestión de MMS IEC61850.
Soporta prueba de cable.
Cumple con IEC61850-3 e IEEE1613.
KEMA, CE, FCC, EN50155/EN50121, UL61010 , NEMA-TS2.
Referencias preliminares: Kyland SICOM3028GPT Switch Capa 3, Kyland SICOM 6416G Switch Capa 3.
ECC21007-ID-01-
INS-ET-155-C
DIMENSIONAMIENTO DEL HARDWARE
PMS
18 de 19
14. DISTRIBUIDOR DE FIBRA ÓPTICA (ODF)
Se suministrará ODF para instalación en Rack de 19”.
Capacidad para conexión de cables de por lo menos 24 fibras ópticas multimodo o monomodo según aplique, las cuales serán realizadas por el método de fusión a los “pig-tails” del distribuidor, los cuales deben estar incluidos. Los latiguillos de fibra serán del mismo tipo de fibra del cable suministrado, con conector terminal tipo LC y un espesor mínimo de 2,0 mm, aptos para resistir manipulaciones durante labores de fusión o re-fusión y con la longitud suficiente para estas labores y para reserva de fibra en el ODF.
15. PARTCHCORD
Patch-cord de Cobre: Se suministrará “patch-cord” de cobre en cable en cobre ftp o sftp categoría 6A. Se incluirá la prueba de cada tramo. Las longitudes serán de acuerdo a la conexión entre los equipos activos.
Patch-cord de Fibra óptica:
Se suministrará “patch-cord” tipo dúplex certificado de fábrica. Dicha certificación incluirá los valores probados de atenuación o pérdidas de inserción y reflectancia. Será del mismo tipo de fibra del cable dieléctrico terminal o de los “pig–tails” del ODF y terminales conectores LC. Recubrimiento que lo proteja de manipulaciones indebidas durante las conexiones, con un espesor mínimo de 2,5 mm, flexible para facilitar la conexión a los equipos y la organización en los bastidores. La longitud deberá ser apropiada para conectar al equipo activo correspondiente. de modo que esta conexión no sea forzada en ningún extremo, quede reserva de longitud y ésta pueda organizarse a la salida de cada extremo.
16. SFPs / Transductores ópticos para uso con Fibra óptica
Los SFPs utilizados en las instalaciones del PMS, serán apropiados para el tipo de Fibra óptica según corresponda:
SFPs de para conexión con Fibra proveniente del Parque Solar:
o Standard: SFF-8472 , IEEE 802.3 o Interface: LC Connector o Velocidad: 10/100Mbps o Tipo de Fibra: Monomodo.
o Características físicas Dimensiones 13,7 mm × 12,7 mm × 56,6 mm (ancho
× alto × profundidad) o Peso 40g
ECC21007-ID-01-
INS-ET-155-C
DIMENSIONAMIENTO DEL HARDWARE
PMS
19 de 19 o Límites ambientales Temperatura de funcionamiento -40 ℃~+85 ℃ o Temperatura de almacenamiento -40 ℃ ~ + 85 ℃ o Humedad relativa ambiental 5~95% (sin condensación)
SFPs de para conexión con Fibra proveniente de la central de Generación Bahía
Garret:
o Standard: SFF-8472 , IEEE 802.3 o Interface: LC Connector o Velocidad: 10/100Mbps o Tipo de Fibra: Multimodo.
o Características físicas Dimensiones 13,7 mm × 12,7 mm × 56,6 mm (ancho
× alto × profundidad) o Peso 40g o Límites ambientales Temperatura de funcionamiento -40 ℃~+85 ℃
SFPs de para conexión con Fibra proveniente de equipos al interior del Shelter
(Para los casos que aplique):
o Standard: SFF-8472 , IEEE 802.3 o Interface: LC Connector o Velocidad: 10/100Mbps o Tipo de Fibra: Multimodo.
o Características físicas Dimensiones 13,7 mm × 12,7 mm × 56,6 mm (ancho
× alto × profundidad) o Peso 40g o Límites ambientales Temperatura de funcionamiento -40 ℃~+85 ℃
File details come from the government source that posted it. Updated .