This solicitation is for a battery-based electrical energy storage system to provide primary power for Providencia Island, Colombia. The system will include cells, modules, battery racks, inverters, a battery management system, control and monitoring systems, auxiliary services, and a SCADA system to integrate the battery energy storage system into the island's hybrid power grid. The contractor will participate in developing a 1.8 megawatt-peak solar power plant project on Providencia Island, which has an existing electrical system of three diesel generators totaling 3,150 kilowatts. The battery storage system must have a delivery capacity of 2.5 megawatt-hours and sustain delivery for a minimum of one hour. It will supply the island's peak demand of up to 1.8 megawatts for one hour and provide black start capability and continuous voltage regulation. The US Agency for International Development in Colombia issued the solicitation.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Página 1 de 1 Archivo: ECP-MCE-ECC21007-ID-01-ELE-ET-101-0
INGENIERÍA DE DETALLE DEL PROYECTO PLANTA SOLAR
FOTOVOLTAICA DE PROVIDENCIA
FICHA TÉCNICA INVERSORES
ECP-MCE-ECC21007-ID-01-ELE-ET-101
REVISIÓN No. 0
Revisión Modificaciones Fecha
A Revisión Interna 07/07/2022
0 Aprobado para construcción 12/09/2022
SUN2000-215KTL-H0
Smart String Inverter
Circuit Diagram
DC
Switch 1
DC
Switch 2
DC
Switch 3
SPD
EMI
Filter
Current Sensor
DC/AC
Inverter
Output Filter
L1 L2 L3
PE
Output Relay
SPD
SPD
SPD
EMI
Filter
MPPT1
MPPT2
MPPT3
MPPT4
MPPT5
MPPT6
MPPT7
MPPT8
MPPT9
MPP Trackers
99.0% Max. Efficiency
String-level Management
Smart I-V Curve Diagnosis Supported
MBUS
Supported
Fuse Free Design
Surge Arresters for
DC & AC
IP66
Protection
Efficiency Curve
90%
91%
92%
93%
94%
95%
96%
97%
98%
99%
100%
0% 20% 40% 60% 80% 100%
880 V
1080 V
1174 V
1200 V
Efficiency
Load
SUN2000-215KTL-H0
Technical Specifications
Efficiency Max. Efficiency ≥99.00%
European Efficiency ≥98.60%
Input Max. Input Voltage 1,500 V
Max. Current per MPPT 30 A
Max. Short Circuit Current per MPPT 50 A
Start Voltage 550 V
MPPT Operating Voltage Range 500 V ~ 1,500 V
Nominal Input Voltage 1,080 V
Number of Inputs 18
Number of MPP Trackers 9
Output Nominal AC Active Power 200,000 W
Max. AC Apparent Power 215,000 VA
Max. AC Active Power (cosφ=1) 215,000 W
Nominal Output Voltage 800 V, 3W + PE
Rated AC Grid Frequency 50 Hz / 60 Hz
Nominal Output Current 144.4 A
Max. Output Current 155.2 A
Adjustable Power Factor Range 0.8 LG ... 0.8 LD
Max. Total Harmonic Distortion <1%
Protection Input-side Disconnection Device Yes
Anti-islanding Protection Yes
AC Overcurrent Protection Yes
DC Reverse-polarity Protection Yes
PV-array String Fault Monitoring Yes
DC Surge Arrester Type II
AC Surge Arrester Type II
DC Insulation Resistance Detection Yes
Residual Current Monitoring Unit Yes
Communication Display LED Indicators, WLAN + APP
USB Yes
MBUS Yes
RS485 Yes
General Dimensions (W x H x D) 1,035 x 700 x 365 mm (40.7 x 27.6 x 14.4 inch)
Weight (with mounting plate) ≤86 kg (189.6 lb.)
Operating Temperature Range -25°C ~ 60°C (-13°F ~ 140°F)
Cooling Method Smart Air Cooling
Max. Operating Altitude without Derating 4,000 m (13,123 ft.)
Relative Humidity 0 ~ 100%
DC Connector Staubli MC4 EVO2
AC Connector Waterproof Connector + OT/DT Terminal
Protection Degree IP66
Topology Transformerless