J.7.14 - ECP-MCE-ECC21007-ID-01-ELE-ET-101.pdf

PDF 540 KB Posted

Attached to
Providencia Island Solar Power Plant Project
Solicitation number
72051423R00004
Issued by

About this file

This solicitation is for a battery-based electrical energy storage system to provide primary power for Providencia Island, Colombia. The system will include cells, modules, battery racks, inverters, a battery management system, control and monitoring systems, auxiliary services, and a SCADA system to integrate the battery energy storage system into the island's hybrid power grid. The contractor will participate in developing a 1.8 megawatt-peak solar power plant project on Providencia Island, which has an existing electrical system of three diesel generators totaling 3,150 kilowatts. The battery storage system must have a delivery capacity of 2.5 megawatt-hours and sustain delivery for a minimum of one hour. It will supply the island's peak demand of up to 1.8 megawatts for one hour and provide black start capability and continuous voltage regulation. The US Agency for International Development in Colombia issued the solicitation.

View the file

Other files

File Type Posted
72051423R00004 conformed to mod 04.pdf PDF
72051423R00004 (04).pdf PDF
72051423R00004 (03) List of Changes.pdf PDF
J.7.16 - Ubicacion_Shelter_PMS.pdf PDF
72051423R00004 (03) - Conformed Solicitation (informational).pdf PDF
72051423R00004 (03) Attachments.pdf PDF
J.7.13 - EPC-MCE-ECC21007-ID-01-INS-PL-112.pdf PDF
J.7.15 - Arquitectura_Control_SOPESA.pdf PDF
Providencia QandA.pdf PDF
J.7.1 - HiRes ECP-MCE-ECC21007-ID-01-ELE-PL-48-0-01.pdf PDF
72051423R00004 (02).pdf PDF
72051423R00004 Providencia Solar RFP Attachments.pdf PDF
J.7.5 - ECP-MCE-ECC21007-ID-01-INS-ET-117-B.pdf PDF
72051423R00004 Providencia Solar RFP.pdf PDF
J.7.10 - ECP-MCE-ECC21007-ID-01-INS-ET-155-C.pdf PDF
J.6 Budget Template.xlsx XLSX spreadsheet
J.7.2 - ECP-MCE-ECC21007-ID-01-CIV-PL-027-E-01.pdf PDF
J.7.12 - ECP-21007-IB01-0-INS-ET-003.pdf PDF
J.7.11 - ECP-21007-IB01-0-INS-ET-002.pdf PDF
J.7.3 - ECP-MCE-ECC21007-ID-01-CIV-PL-027-E-02.pdf PDF
J.7.1 - ECP-MCE-ECC21007-ID-01-ELE-PL-48-0-01.pdf PDF
J.7.9 - ECP-MCE-ECC21007-ID-01-INS-ET-157-0.pdf PDF
J.7.6 - EPC-MCE-ECC21007-ID-01-INS-PL-112-4.pdf PDF
J.7.4 - ECP-MCE-ECC21007-ID-01-CIV-PL-027-E-03.pdf PDF
J.7.7 - EPC-MCE-ECC21007-ID-01-INS-PL-112-6.pdf PDF
J.2. MME MOU.pdf PDF
J.7.8 - EPC-MCE-ECC21007-ID-01-INS-PL-112-8.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Página 1 de 1 Archivo: ECP-MCE-ECC21007-ID-01-ELE-ET-101-0

INGENIERÍA DE DETALLE DEL PROYECTO PLANTA SOLAR

FOTOVOLTAICA DE PROVIDENCIA

FICHA TÉCNICA INVERSORES

ECP-MCE-ECC21007-ID-01-ELE-ET-101

REVISIÓN No. 0

Revisión Modificaciones Fecha

A Revisión Interna 07/07/2022

0 Aprobado para construcción 12/09/2022

SUN2000-215KTL-H0

Smart String Inverter

Circuit Diagram

DC

Switch 1

DC

Switch 2

DC

Switch 3

SPD

EMI

Filter

Current Sensor

DC/AC

Inverter

Output Filter

L1 L2 L3

PE

Output Relay

SPD

SPD

SPD

EMI

Filter

MPPT1

MPPT2

MPPT3

MPPT4

MPPT5

MPPT6

MPPT7

MPPT8

MPPT9

MPP Trackers

99.0% Max. Efficiency

String-level Management

Smart I-V Curve Diagnosis Supported

MBUS

Supported

Fuse Free Design

Surge Arresters for

DC & AC

IP66

Protection

Efficiency Curve

90%

91%

92%

93%

94%

95%

96%

97%

98%

99%

100%

0% 20% 40% 60% 80% 100%

880 V

1080 V

1174 V

1200 V

Efficiency

Load

SUN2000-215KTL-H0

Technical Specifications

Efficiency Max. Efficiency ≥99.00%

European Efficiency ≥98.60%

Input Max. Input Voltage 1,500 V

Max. Current per MPPT 30 A

Max. Short Circuit Current per MPPT 50 A

Start Voltage 550 V

MPPT Operating Voltage Range 500 V ~ 1,500 V

Nominal Input Voltage 1,080 V

Number of Inputs 18

Number of MPP Trackers 9

Output Nominal AC Active Power 200,000 W

Max. AC Apparent Power 215,000 VA

Max. AC Active Power (cosφ=1) 215,000 W

Nominal Output Voltage 800 V, 3W + PE

Rated AC Grid Frequency 50 Hz / 60 Hz

Nominal Output Current 144.4 A

Max. Output Current 155.2 A

Adjustable Power Factor Range 0.8 LG ... 0.8 LD

Max. Total Harmonic Distortion <1%

Protection Input-side Disconnection Device Yes

Anti-islanding Protection Yes

AC Overcurrent Protection Yes

DC Reverse-polarity Protection Yes

PV-array String Fault Monitoring Yes

DC Surge Arrester Type II

AC Surge Arrester Type II

DC Insulation Resistance Detection Yes

Residual Current Monitoring Unit Yes

Communication Display LED Indicators, WLAN + APP

USB Yes

MBUS Yes

RS485 Yes

General Dimensions (W x H x D) 1,035 x 700 x 365 mm (40.7 x 27.6 x 14.4 inch)

Weight (with mounting plate) ≤86 kg (189.6 lb.)

Operating Temperature Range -25°C ~ 60°C (-13°F ~ 140°F)

Cooling Method Smart Air Cooling

Max. Operating Altitude without Derating 4,000 m (13,123 ft.)

Relative Humidity 0 ~ 100%

DC Connector Staubli MC4 EVO2

AC Connector Waterproof Connector + OT/DT Terminal

Protection Degree IP66

Topology Transformerless