IFB_1100_CPG1005_ATT_9_v1.pdf

PDF 109 KB Posted

Attached to
Electric protective device
Solicitation number
IFB 1100 CPG1005
Issued by
Texas

About this file

This specification document, issued by the City of Austin through Austin Energy on April 9, 2018, establishes the technical and physical requirements for a Thermal Event System for Network Protection (Specification E-1807). The system comprises three primary components: a Remote Terminal Unit (RTU) module, a Human Machine Interface (HMI), and an enclosure. The RTU utilizes a passive backplane connection board that connects a main processor module to various input/output modules via a high-speed bus, with the entire assembly enclosed in a heavy-duty aluminum chassis. The HMI features a 12.1-inch (307 mm) 800 x 600 TFT-LCD resistive touch screen display, universal connectivity including Ethernet 10/100Base-T with two USB 2.0 ports, two serial ports, and an optional 2-port CAN module. The enclosure is constructed of high-impact, UV-resistant polycarbonate with bases and covers available in hinged or non-hinged configurations with 2-screw, 4-screw, or stainless steel metal latched lid options in standard light gray with gloss finish. The specification details specific module configurations including processor modules, status input modules, relay output modules, analog input modules, and DC analog input modules with corresponding power requirements.

The specification requires compliance with UL-50 (Enclosures for Electrical Equipment), UL-508 (Industrial Control Panels), ANSI/ISA 12.12.01 (Class I, Division 2 Hazardous Locations), and UL-50 Type 4X standards. The HMI meets NEMA-4X and IP66 specifications, is UL 50 Type 4X and Class 1 Division 2 certified, and holds marine ABS certification, with operating temperature capabilities ranging from -30 to 70 degrees Celsius. The optional Vault Gard component allows connection of up to 32 MPCV relays and features DNP 3.0 protocol compatibility for both Ethernet and RS-485 connections, enabling communication with third-party devices and integration with Power Xpert software networking capabilities.

View the file

Other files

File Type Posted
IFB_1100_CPG1005_ATT_6_v1.docx DOCX document
IFB_1100_CPG1005_ATT_1_v1.docx DOCX document
RFQS_6100_CLMP390_SOS_v1.pdf PDF
IFB_1100_CPG1005_ADD_2_v1.pdf PDF
IFB_1100_CPG1005_ADD_1_v1.docx DOCX document
IFB_1100_CPG1005_ATT_5_v1.docx DOCX document
IFB_1100_CPG1005_ATT_2_v1.docx DOCX document
IFB_1100_CPG1005_ATT_7_v1.pdf PDF
IFB_1100_CPG1005_ATT_8_v1.pdf PDF
IFB_1100_CPG1005_PAC1_v5.docx DOCX document
IFB_1100_CPG1005_0600_v1.xlsx XLSX spreadsheet
IFB_1100_CPG1005_PAC1_v3.docx DOCX document
IFB_1100_CPG1005_ATT_3_v1.docx DOCX document
IFB_1100_CPG1005_ATT_4_v1.docx DOCX document
IFB_1100_CPG1005_0600_2_v2.xlsx XLSX spreadsheet
IFB_1100_CPG1005_ADD_3_v1.pdf PDF
Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Specification E-1807 Created 04/09/18

Cover Page

AUSTIN ENERGY

PURCHASE SPECIFICATION

FOR

THERMAL EVENT SYSTEM FOR NETWORK PROTECTION

DATE

PREPARED BY

ISSUANCE/REVISION

APPROVAL

DIVISION MANAGER/STANDARDS MANAGER

04/9/18 Obaid Rehman Issuance

REASON FOR REVISION AFFECTED PARAGRAPHS

This specification, until rescinded, shall apply to each future purchase and contract for the commodity described herein.

Retain for future reference.

AUSTIN ENERGY

PURCHASE SPECIFICATION

FOR

THERMAL EVENT SYSTEM FOR NETWORK PROTECTION

1.0 SCOPE

This specification shall define the minimum physical and electrical characteristics required by Austin Energy

(AE) for thermal event system for network protection .This specification applies to the High Thermal Event

System which includes the high speed RTU module and the Human Machine Interface .This specification shall cover the enclosure of the High Thermal Event System.

2.0 APPLICABLE STANDARDS

All characteristics, definitions, and terminology, except as specifically covered in this specification shall be in accordance with the latest revision of the following ANSI/UL standards: .

UL-50- Enclosures for Electrical Equipment.

UL-508-Industrial Control panels

ANSI/ISA 12.12.01 (formerly UL 1604) Class I, Div. 2-Hazardous Locations

2.4 UL-50 Type 4X- Industrial Control panels

3.0 GENERAL

3.1. RTU 3.1.1. Live data gathered or generated by the RTU is stored in a database. This database is stored in the random access memory (RAM) of the processor module, and the RTU allocates this database at startup. The various IO modules connected to the processor continuously update this database, and data may originate from an external source, such as a DNP slave device connected to a communications port that is programmed as the DNP master.

Data is organized into five types.

1. Binary Input data

2. Binary Output data

3. Counter data

4. Analog Input data

5. Analog Output data

3.2. HMI 3.2.1 The High Thermal Event System’s HMI is designed and built for your most rugged applications. Industrially hardened to perform in extreme environments, the HMI meets NEMA-4x and IP66 specifications and is UL 50 Type 4X, Class 1 Div 2 and marine ABS certified. This rugged HMI features universal connectivity, a bright 12.1" (307 mm), 800 x 600 TFT-LCD display, resistive touch screen, Ethernet 10/100Base-T with two USB 2.0 full-speed host ports, two serial ports to connect to nearly any device, and an optional 2-port CAN module.

3.3 Enclosure 3.3.1. Standard configurations including hinged or non-hinged lids in 2-screw, 4-screw, or stainless steel metal latched lids. The Standard color is light gray with a gloss finish

4. Physical Requirements

4.1 RTU Construction

4.1.1 A passive backplane connection board connects a main processor module to various input/output (IO) modules via a high-speed bus. All boards plug into this backplane. The entire assembly is enclosed in a heavy-duty aluminum chassis. Two screws hold each board securely to the chassis, and provide an electrical path for the surge protection grounds

4.2 HMI Construction

4.2.1 The rugged human machine interface will connect to your RTU Module. The HMI includes a large touch screen display, optional CANbus, is UL listed Class I Div 2 and marine ABS certified and can operate in -30 to 70 °C.

4.3 Enclosure Construction

4.3.1 Best material – bases, opaque covers and clear covers are all made of high-impact, UV resistant polycarbonate. Flexible interior mounting – features the unique and adjustable depth “T-Rail” back panel mounting system.

5. Configuration Requirements.

5.1 RTU Configuration 5.1.1 The current required to power the RTU is mainly dependent on the power supply voltage and IO module configuration

Module Type Description Current as 12 V (mA) Current at 24 V (mA)

PDC Processor 38 22

16s 16 status inputs 5 2

8R 8 relay outputs (all relays off)

ACVI 12 AC analog inputs w/low impedance current inputs

20 10

ACVV 12 AC analog inputs w/low impedance current inputs

22 110

16 DC 16 DC analog inputs 15 10

6. [Optional Vault Gard]

6.1 Connect up to 32 MPCV relays on one Vault Gard for application flexibility.

6.2 Easy to navigate on-board web pages so there is no software needed.

6.4 Compatible with Power Xpert software if you want to link all Gateway units in a network.

6.4 Vault Gard can easily communicate with third-party devices: DNP 3.0 up and downlink, over Ethernet;

and DNP 3.0 via RS-485 connection.

File details come from the government source that posted it. Updated .