City of Austin Network Protector Specification
This is a purchase specification document issued by the City of Austin Electric Utility Department for three-phase, 216Y/125 volt Network Protectors with submersible enclosures. The specification, designated E-1188 and effective November 6, 2019, establishes mandatory technical and functional requirements for network protectors to be procured on an annual basis through Invitation for Bid IFB 1100 CPG1005. The document specifies two amperage ratings: 1,875 amp units for 500 kVA transformers and 2,500 amp units for 750 kVA transformers. Network protectors must be motor-operated, trip-free, and automatic, manufactured in accordance with IEEE C57.12.44 and IEEE C57.12.40 standards. The specification mandates that protectors be Eaton CM52 network protectors or buyer-approved equivalents equipped with Cutler/Hammer MPVC plug-in communication relays compatible with AVO-Multiamp NPTS-1-X test sets. The specification was originally prepared on March 22, 1999, with subsequent revisions issued on April 28, 2009, May 30, 2014, and October 23, 2019, with the most recent revision removing sections 4.6 and 4.8 and adding sections 3.4 through 3.6 and 4.7.
The specification establishes comprehensive physical and production requirements, including submersible mild steel housings with 0.25-inch thickness and 0.2 percent copper bearing steel construction, viewing windows for relay and status indicators, and top-mounted NEMA spade-type terminations accommodating four 500 mcm cables for the 1,875 amp unit and six 500 mcm cables for the 2,500 amp unit. All protectors must be equipped with six Eaton 39C4004G23 locking quick latch handles or buyer-approved equivalents and require production testing encompassing operational, dielectric, insulation resistance, current path resistance, and mechanical categories, with test results provided with each delivered unit. Phase rotation is specified as CAB from left to right when facing the protector front, and all units must maintain a 10 kV BIL impulse withstand voltage rating with isolated phase bars and continuous barriers separating phases from each other and the case.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| IFB_1100_CPG1005_ATT_6_v1.docx | DOCX document | |
| IFB_1100_CPG1005_ATT_1_v1.docx | DOCX document | |
| RFQS_6100_CLMP390_SOS_v1.pdf | ||
| IFB_1100_CPG1005_ADD_2_v1.pdf | ||
| IFB_1100_CPG1005_ADD_1_v1.docx | DOCX document | |
| IFB_1100_CPG1005_ATT_5_v1.docx | DOCX document | |
| IFB_1100_CPG1005_ATT_2_v1.docx | DOCX document | |
| IFB_1100_CPG1005_ATT_8_v1.pdf | ||
| IFB_1100_CPG1005_PAC1_v5.docx | DOCX document | |
| IFB_1100_CPG1005_0600_v1.xlsx | XLSX spreadsheet | |
| IFB_1100_CPG1005_PAC1_v3.docx | DOCX document | |
| IFB_1100_CPG1005_ATT_3_v1.docx | DOCX document | |
| IFB_1100_CPG1005_ATT_4_v1.docx | DOCX document | |
| IFB_1100_CPG1005_0600_2_v2.xlsx | XLSX spreadsheet | |
| IFB_1100_CPG1005_ATT_9_v1.pdf | ||
| IFB_1100_CPG1005_ADD_3_v1.pdf |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Specification E-1188
November 6th, 2019
CITY OF AUSTIN ELECTRIC UTILITY DEPARTMENT
PURCHASE SPECIFICATION
FOR
PROTECTOR, NETWORK, 216Y-125V
DATE
PREPARED BY
ISSUANCE/REVISION
APPROVAL
PROCESS MANAGER/M&ESS MANAGER
03-22-99
04-28-09
05-30-14
Blankenship/
Boykin
Steven Booher
Daniel McReynolds
Revision
Revision
Update
10-23-19 Brantley Gosey Revision
REASON FOR REVISION AFFECTED PARAGRAPHS
03-22-99 Update
04-28-09 Update
05-30-14 Update
10-23-19 Update/Removal
Remove 1.1.3, added sections 3.2 and 5
Revision sections 1.1.2, 2.0, 3.2, 3.4, 4.3 and 5.0
Revision sections 1.2.2, 2.0, 4.1, 4.2, 5.1
Removal Section 4.6, 4.8 Add 3.4-3.6, 4.7
This specification, until rescinded, shall apply to each future purchase and contract for the commodity described herein.
Retain for future reference.
CITY OF AUSTIN ELECTRIC UTILITY
PURCHASE SPECIFICATION
FOR
PROTECTOR, NETWORK, 216Y-125V
1.0 Scope and Classification
1.1 Scope
1.1.1 This specification covers three-phase, 216Y/125 volt Network Protectors with submersible enclosures.
1.1.2 No deviation from this specification will be permitted.
1.2 Classification
1.2.1 Network Protector voltage shall be 216Y/125, three-phase, 60 cycle.
1.2.2 Network Protector ratings shall be as follows: (to be specified on the bid sheet)
1875 amp – 500 kVA transformer
2500 amp – 750 kVA transformer
2.0 Applicable Specifications
Unless otherwise stated in these specifications Network Protectors shall be manufactured, production tested and made ready for shipment in accordance with IEEE C57.12.44
Secondary Network Protectors and IEEE C57.12.40 Network Transformers.
3.0 Functional Requirements
3.1 Protector shall be motor operated, trip-free and automatic.
3.2 Each Network Protector shall be tested and supplied with Cutler/Hammer MPVC plug-in communication Network Protector relay. The Protector shall utilize the same relay for production acceptance testing as it is shipped with. This relay shall be made such that it can be tested on a AVO-Multiamp NPTS-1-X test set using the computer test sequence from the test set with no manual input.
3.3 Two (2) auxiliary switch contacts shall be furnished for operating indicating devices. These contacts shall be open when the breaker is closed.
3.4 Network protector shall be Eaton CM52 network protector or buyer approved equal.
3.5 Network protector shall have a fully interlocked, dead-front, four-position, draw out design.
3.6 Network Protector shall have a 10kV BIL impulse withstand voltage rating.
3.7 Phase rotation shall be CAB from left to right when facing the front of the
Protector.
4.0 Physical Requirements
4.1 Protector shall be furnished with submersible .25″ thick mild steel housing produced out of .2% copper bearing steel for added protection. The housing shall be designed for mounting on a Network transformer per IEEE C57.12.40.
4.2 A viewing window shall be provided for the Network relay and for the Protector open/close status indicator as well as a visible break window.
4.3 Network Protector enclosures shall be supplied with top-mounted NEMA spade type terminations for connection to the secondary spot or grid Network. Size of the terminations shall be as follows:
4-hole spade suitable for 4-500 mcm per phase cables for the 1875 amp
6-hole spade suitable for 6-500 mcm per phase cable for the 2500 amp
4.4 The phase bars of the Protector shall be isolated from each other and the case by continuous barriers.
4.5 Ammeter jacks shall be furnished on the Protector for load checking.
4.6 A nameplate shall be provided on the exterior of each Protector listing the manufacturer, date, and serial number.
4.7 The Protector shall be equipped with 6 Eaton 39C4004G23 locking quick latch handles or buyer approved equal.
5.0 Production Tests
5.1 Production tests shall be performed on every Network Protector. These tests shall be divided into the following categories and provided with each individual unit upon delivery:
Operational
Dielectric
Insulation resistance
Current path resistance
Mechanical