IFB_1100_CPG1005_ATT_8_v1.pdf

PDF 257 KB Posted

Attached to
Electric protective device
Solicitation number
IFB 1100 CPG1005
Issued by
Texas

About this file

This is a Purchase Specification document issued by the City of Austin Electric Utility Department for Network Protectors rated at 480Y-277 volts, effective October 23, 2019. The specification establishes technical and manufacturing requirements for three-phase network protectors with submersible enclosures to be procured on an annual basis. The protectors are available in three amperage ratings: 1,875 amps for 500 and 1,000 kVA transformers, 2,500 amps for 1,500 kVA transformers, and 3,000 amps for 2,000 kVA transformers. All protectors must be manufactured in accordance with IEEE C57.12.44 and IEEE C57.12.40 standards and must be motor-operated, trip-free, and automatic. The specification mandates that each unit be supplied with a Cutler/Hammer MPVC plug-in communication Network Protector relay compatible with AVO-Multiamp NPTS-1-X test sets and specifies that the protector shall be an Eaton CM52 model or buyer-approved equivalent with a fully interlocked, dead-front, four-position draw-out design featuring a 10 kV BIL impulse withstand voltage rating.

The specification requires protectors to be housed in submersible, .25-inch thick mild steel construction produced from .2% copper-bearing steel and equipped with top-mounted NEMA spade-type terminations sized according to amperage rating. Additional functional requirements include an arc reduction system capable of lowering fault current levels to 100 kA with a trip initiation time of 4 milliseconds or less, visual status identification, and switchable on/off controls from a distance not exceeding 100 feet. Each unit must include two auxiliary switch contacts, ammeter jacks for load checking, viewing windows for the relay and status indicators, six Eaton 39C4004G23 locking quick latch handles, and a nameplate displaying manufacturer, date, and serial number. Production testing is mandatory for all units and must encompass operational, dielectric, insulation resistance, current path resistance, and mechanical tests, with results provided upon delivery. The specification has been subject to multiple revisions since its initial preparation in 1999, with the most recent revision in October 2019 addressing sections 3.4, 4.7, and removal of former sections 4.6 and 4.8.

View the file

Other files

File Type Posted
IFB_1100_CPG1005_ATT_5_v1.docx DOCX document
IFB_1100_CPG1005_ATT_2_v1.docx DOCX document
IFB_1100_CPG1005_ATT_7_v1.pdf PDF
IFB_1100_CPG1005_PAC1_v5.docx DOCX document
IFB_1100_CPG1005_ATT_6_v1.docx DOCX document
IFB_1100_CPG1005_ATT_1_v1.docx DOCX document
RFQS_6100_CLMP390_SOS_v1.pdf PDF
IFB_1100_CPG1005_ADD_2_v1.pdf PDF
IFB_1100_CPG1005_ADD_1_v1.docx DOCX document
IFB_1100_CPG1005_0600_v1.xlsx XLSX spreadsheet
IFB_1100_CPG1005_PAC1_v3.docx DOCX document
IFB_1100_CPG1005_ATT_3_v1.docx DOCX document
IFB_1100_CPG1005_ATT_4_v1.docx DOCX document
IFB_1100_CPG1005_0600_2_v2.xlsx XLSX spreadsheet
IFB_1100_CPG1005_ATT_9_v1.pdf PDF
IFB_1100_CPG1005_ADD_3_v1.pdf PDF
Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Specification E-1189 October 23, 2019

CITY OF AUSTIN ELECTRIC UTILITY DEPARTMENT

PURCHASE SPECIFICATION

FOR

PROTECTOR, NETWORK, 480Y-277V

DATE

PREPARED BY

ISSUANCE/REVISION

APPROVAL

PROCESS MANAGER/M&ESS MANAGER

03-22-99

04-28-09

05-30-14

10-23-19

Blankenship/

Boykin

Steven Booher

Daniel McReynolds

Brantley Gosey

Revision

Update

REASON FOR REVISION AFFECTED PARAGRAPHS

03-22-99 Update

04-28-09 Revision

05-30-14 Update

10-23-19 Revision

Remove 1.1.3, added sections 3.2 and 5

Revision sections 1.2, 2.0, 3.0, 4.0 and 5.0

Added section 3.6, Revision sections 1.2.2, 2.0, 3.6, 4.1, 4.2, 4.3, 5.1

Revision Section 3.4 and 4.7 Removal 4.6 and 4.8

This specification, until rescinded, shall apply to each future purchase and contract for the commodity described herein.

Retain for future reference.

CITY OF AUSTIN ELECTRIC UTILITY

PURCHASE SPECIFICATION

FOR

PROTECTOR, NETWORK, 480Y-277V

1.0 Scope and Classification

1.1 Scope

1.1.1 This specification covers three-phase, 480Y/277 volt network Protectors with submersible enclosures.

1.1.2 No deviation from this specification will be permitted.

1.2 Classification

1.2.1 Network Protector voltage shall be 480Y/277, three-phase, 60 cycle.

1.2.2 Network Protector ratings shall be as follows: (to be specified on the bid sheet)

• 1875 amp - 500 and 1000 kVA transformer

• 2500 amp - 1500 kVA transformer

• 3000 amp - 2000 kVA transformer

2.0 Applicable Specifications

Unless otherwise stated in these specifications Network Protectors shall be manufactured, production tested and made ready for shipment in accordance with IEEE C57.12.44 Secondary Network Protectors and IEEE C57.12.40 Network Transformers.

3.0 Functional Requirements

3.1 Protector shall be motor operated, trip-free and automatic.

3.2 Each Network Protector shall be tested and supplied with Cutler/Hammer MPVC plug-in communication Network Protector relay. The protector shall utilize the same relay for production acceptance testing as it is shipped with. This relay shall be made such that it can be tested on a AVO-Multiamp NPTS-1-X test set using the computer test sequence from the test set with no manual input.

3.3 Two (2) auxiliary switch contacts shall be furnished for operating indicating devices. These contacts shall be open when the breaker is closed.

3.4 Network protector shall be Eaton CM52 network protector or buyer approved equal.

3.5 Network protector shall have a fully interlocked, dead-front, four-position, draw out design.

3.6 Network Protector shall have a 10kV BIL impulse withstand voltage rating.

3.7 Phase rotation shall be CAB from left to right when facing the front of the protector.

3.8 Arc reduction system shall lower fault current levels (100 kA) to a level where

PPE of 8 cal/cm2 are appropriate. The system shall have a trip initiation time of 4 ms or less under either forward or reverse current, shall include visual status identification of protector, shall be switched in the on/off position by a switch located a distance not to exceed 100 ft. from protector, and this switch shall activate all protectors grouped together. The system shall be able to be switched on/off with protector door closed.

4.0 Physical Requirements

4.1 Protector shall be furnished with submersible .25″ thick mild steel housing produced out of .2% copper bearing steel for added protection. The housing shall be designed for mounting on a network transformer per IEEE C57.12.40.

4.2 A viewing window shall be provided for the network relay and for the protector open/close status indicator, as well as a visible break window.

4.3 Network Protector enclosures shall be supplied with top-mounted NEMA spade type terminations for connection to the secondary spot or grid network. Size of the terminations shall be as follows:

• 4-hole spade suitable for 4-500 mcm per phase cables for the 1875.

• 6-hole spade suitable for 6-per 500 mcm per phase cables for the 2500 and

3000 amp protectors.

4.4 The phase bars of the protector shall be isolated from each other and the case by continuous barriers.

4.5 Ammeter jacks shall be furnished on the protector for load checking.

4.6 A nameplate shall be provided on the exterior of each protector listing the manufacturer, date, and serial number.

4.7 The Protector shall be equipped with 6 Eaton 39C4004G23 locking quick latch handles or buyer approved equal.

5.0 Production Tests

5.1 Production tests shall be performed on every Network Protector. These tests shall be divided into the following categories and provided with each individual unit upon delivery:

• Operational

• Dielectric

• Insulation resistance

• Current path resistance

• Mechanical

ATTACHMENT 1

CITY OF austin ELECTRIC UTILITY DEPARTMENT
CITY OF austin ELECTRIC UTILITY DEPARTMENT
PURCHASE SPECIFICATION
PURCHASE SPECIFICATION
FOR
FOR
PROTECTOR, NETWORK, 480Y-277V
PROTECTOR, NETWORK, 480Y-277V
APPROVALPROCESS MANAGER/M&ESS MANAGER
ISSUANCE/REVISION
PREPARED BY
DATE
Revision
Blankenship/
03-22-99
Boykin
Revision
Steven Booher
04-28-09
Update
Daniel McReynolds
05-30-14
Revision
Brantley Gosey
10-23-19
AFFECTED PARAGRAPHS
REASON FOR REVISION
Remove 1.1.3, added sections 3.2 and 5
03-22-99 Update
Revision sections 1.2, 2.0, 3.0, 4.0 and 5.0
04-28-09 Revision
Added section 3.6, Revision sections 1.2.2, 2.0, 3.6, 4.1, 4.2, 4.3, 5.1
05-30-14 Update
Revision Section 3.4 and 4.7 Removal 4.6 and 4.8
10-23-19 Revision
This specification, until rescinded, shall apply to each future purchase and contract for the commodity described herein. Retain for future reference.
This specification, until rescinded, shall apply to each future purchase and contract for the commodity described herein. Retain for future reference.
CITY OF AUSTIN ELECTRIC UTILITY
CITY OF AUSTIN ELECTRIC UTILITY
PROTECTOR, NETWORK, 480Y-277V
PROTECTOR, NETWORK, 480Y-277V