Hospital Water Filter Performance Specification VHA Directive 1061.rev3_2024.docx
VHA Directive Rev. 3, 2024 DOCX document 15 KB Posted
- Attached to
- J045--Legionella Filters Installation
- Solicitation number
- 36C26225Q0071
About this file
This is a technical performance specification document for hospital water filters combined with a solicitation for installation services at VA Greater Los Angeles Healthcare System. The specification requires FDA 510k Class II cleared filters with specific capabilities including 5nm porosity for ice machine/drinking/sink filters and 100nm porosity for terminal point-of-use filters, with strict bacteria, virus, and endotoxin reduction requirements and 180-day FDA clearance periods.
The associated solicitation (36C26225Q0071) is an SDVOSB set-aside seeking a contractor to install Nephros or equivalent Legionella filters in buildings 99, 213, 215, 257, and 525 across the West Los Angeles and Sepulveda campuses. The scope includes installing 904 total filters with specific installation schedules throughout the year, requiring both thermal and chemical disinfection processes. The period of performance is 02/01/2025-01/31/2025, with a firm-fixed-price contract under NAICS 238220. Quotes are due by 10am PST on January 3rd, 2025, and will be evaluated based on price, capabilities, and past performance in Legionella filter installation. RFIs are due by December 16th, 2024.
View the file
Other versions and copies of VHA Directive 1061
Show all 20
Who attaches VHA Directive 1061
Other files
| File | Type | Posted |
|---|---|---|
| Legionella Filters Install Enclosure 1 updated.docx | DOCX document | |
| 36C26225Q0071 0001_1.docx | DOCX document | |
| RFQ 36C26225Q0071 updated.docx | DOCX document | |
| Vendor Questions.docx | DOCX document | |
| 36C26225Q0071.docx | DOCX document | |
| Legionella Filters Install Enclosure 1.docx | DOCX document | |
| Legionella Filters Install Enclosure 2.docx | DOCX document |
On GovTribe
Work with this file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Hospital Water Filter Performance Specification VHA Directive 1061 / ASHRAE 188-2017 & ASHRAE 514-2023 Ultra-filters and Sub-Micron Filtration to filter Environmental Protection Agency (EPA) quality drinking water to remove microbiological contaminants. Filters retain bacteria, viruses and endotoxin. By providing ultrapure water for patient washing and drinking, the filters aid in infection control.
Must produce water that is suitable for wound cleansing Must produce water for cleaning of equipment used in medical procedures Must produce water suitable for washing of surgeon's hands.
Filters are not intended to provide water that can be used as a substitute for USP sterile water.
Minimum requirements:
• FDA 510k Class II Clearance (mandatory) *Published ASHRAE 514, 2023
• Ice machine / Drinking & Bottle Filling (in-line), Sink (in-line) / Shower (in-line) filter must have 5nm (.005) micron porosity or smaller
◦ 15kDa particulate retention
◦ 11-log reduction of Bacteria
◦ 8-log reduction of Viruses
◦ 5-log reduction of Endotoxins
◦ FDA Clearance for up to 180-days – (no exceptions) ◦ No known equivalent Terminal “POU” Point of Use, Sub-Micro Filtration Sink and Shower Filter must have a 100nm (.1) micron porosity or smaller
· 9-log reduction of Bacteria
· FDA Clearance for up to 90-days – (no exceptions)
· No known equivalent Minimum Operating conditions and Performance:
· Must be capable of supporting an opening pressure of between 75 - 100psi
· Must have the ability to perform from 3 to 6 months without replacement.
· Installations MUST meet Uniform and State plumbing codes related to healthcare hand washing sinks and accessibility “ADA”. (no exceptions)