HollinsHSLiftStationReplacementElecSS.pdf
PDF 3 MB Posted
- Attached to
- Lift Station Replacement
- Solicitation number
- 26-CD-033
- Issued by
- Pinellas County, Florida
About this file
Summary
This is an electrical engineering design document prepared by BCER Engineering for the Pinellas County School Board in Florida, detailing the one-for-one replacement of a lift station at Dixie Hollins High School located at 4940 62nd Street North in St. Petersburg, Florida. The project involves replacing existing lift station power infrastructure while reusing existing conduit to the extent possible. The electrical work includes disconnecting the existing lift station power feeder, removing feeder back to the lift station disconnect switch in the electrical room, and providing a new feeder with three #6 AWG conductors plus one #10 ground conductor from the disconnect in the electrical room to the new lift station location. The new lift station is rated at 208 volts, three-phase, 10 horsepower with a full load amperage of 30.8 amps and a minimum circuit ampacity of 38.5 amps. The project requires replacing existing fuses with 50-amp fuses in the existing fused disconnect and providing fuse reducers to accommodate the 50-amp fuse in the 200-amp disconnect. The bid deadline is 4:00 pm on Monday, August 31, 2026, with bids submitted electronically through the Pinellas County School District e-Procurement Portal at https://procurement.opengov.com/portal/PCSB. The design is dated July 10, 2026, and prepared in compliance with the 2023 Florida Building Code, 2023 Florida Existing Building Code, and NFPA 70-2020 National Electrical Code.
The project specifies that all electrical equipment and materials must be listed or labeled by UL or other recognized testing facilities and installed in accordance with applicable codes. The contractor is responsible for providing permits, inspections, submittals for review, and complete as-built documents within 90 days of certificate of occupancy receipt. The electrical contractor must coordinate with other trades, provide complete and functional systems, and bear responsibility for any costs associated with approved equipment substitutes or field modifications required for coordination. Since this is a one-for-one replacement with no added load, existing electrical infrastructure will be leveraged where possible, with surge protective devices to be added to the existing circuit if not already installed. The contractor must also perform short circuit current calculations and an arc-flash study for the electrical distribution system based on actual installation conditions and utility company parameters.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Issue Record:
Sheet Title:
Sheet no:
Drawn by:
Checked by:
Scale:
Date:
No: Date:Description:
7/10/2026
AS NOTED
BCER PROJECT
6555 N. WICKHAM ROAD, SUITE 104
MELBOURNE, FL 32940 | 321.241.4124
CA# 9303
132325003
© Copyright BCER Engineering
ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER
ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE
PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW,
STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.
D
IX
IE
H
O
LL
IN
S
H S
LI
FT
ST
AT
IO
N
R
EP
LA
C
EM
EN
T
2n d
St N
St . P et er sb ur g, F
L
JRB
MC
COVER SHEET
CS
LIFT STATION REPLACEMENT
DIXIE HOLLINS HIGH SCHOOL
at
PROJECT NO: 245719
BID AND PERMIT SET July 10, 2026
PREPARED FOR
SCHOOL BOARD OF PINELLAS COUNTY
LAURA HINE - CHAIRPERSON
CAPRICE EDMOND - VICE CHAIRPERSON
KATIE BLAXBERG
LISA N. CANE
STEPHANIE MEYER
DAWN M. PETERS
EILEEN M. LONG
SUPERINTENDENT OF SCHOOLS
KEVEN K. HENDRICK
Sheet List Table Sheet Number Sheet Title
CS COVER SHEET
C1.0 GENERAL NOTES
C2.0 DEMOLITION, UTILITY AND SITE, AND GRADING PLAN
C3.0 SITE DETAILS
C4.0 LIFT STATION DETAILS
E0.01 ELECTRICAL GENERAL INFORMATION
E0.02 ELECTRICAL PROJECT NOTES
ED1.01 ELECTRICAL SITE DEMOLITION PLAN
E1.01 ELECTRICAL SITE PLAN
AutoCAD SHX Text DIMSCALE=1 \\bcercloud\10-projects\132325003\20-production\20-hollinshsliftstationreplacement\hollinshsliftstationreplacement\Sheets\CS COVER SHEET.dwg JUL 8, 2026 6:51AM JBERKEBILE
AutoCAD SHX Text XREFS=(xx-tb-24x36) Layouts=(CS COVER SHEET)
Sheet no:
Drawn by:
Checked by:
Scale:
Date:
No: Date:Description:
7/10/2026
AS NOTED
BCER PROJECT
6555 N. WICKHAM ROAD, SUITE 104
MELBOURNE, FL 32940 | 321.241.4124
CA# 9303
XXXXXXXX
© Copyright BCER Engineering
ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER
ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE
PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW,
STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.
D
IX
IE
H
O
LL
IN
S
H S
LI
FT
ST
AT
IO
N
R
EP
LA
C
EM
EN
T
2n d
St N
St . P et er sb ur g, F
L
JRB
MC
ELECTRICAL
GENERAL
INFORMATION
E0.01
PROJECT NARRATIVE
PROVIDE POWER FOR ONE-FOR-ONE REPLACEMENT OF LIFT STATION. CONDUIT AND
FEEDERS WILL BE REUSED.
DENVER AND COLORADO SPRINGS OFFICES
14143 DENVER WEST PKWY, SUITE 550
GOLDEN, CO 80401
303.422.7400
TAMPA BAY AND MELBOURNE OFFICES
6555 N. WICKHAM ROAD, SUITE 104
MELBOURNE, FL 32940
321.241.4142
CONTACT LIST
PROJECT ENGINEER / DESIGNER
JOE BERKEBILE
321.355.0297
JBERKEBILE@BCER.COM
PROJECT MANAGER
DAVID WALLACE
727.800.7314
DWALLACE@BCER.COM
ADOPTED/ENFORCED CODES REQUIRED
2023 FLORIDA BUILDING CODE
2023 FLORIDA EXISTING BUILDING CODE
2023 FLORIDA PLUMBING CODE
2023 FLORIDA MECHANICAL CODE
NFPA 70-2020, NATIONAL ELECTRICAL CODE
NFPA 72-2019, NATIONAL FIRE ALARM CODE
TYPICAL DEVICE MOUNTING HEIGHTS
NOTES:
1. DEVICES ABOVE DOORS SHALL BE CENTERED BETWEEN TOP OF DOOR TRIM AND
CEILING LINE.
2. MOUNTING HEIGHTS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL GOVERN
OVER THOSE SHOWN ABOVE.
3. MOUNTING HEIGHTS SHALL BE COORDINATED WITH OTHER DEVICES, ARCHITECT,
AND BE COMPLIANT WITH ADA AND CODE REQUIREMENTS.
T
J
3' -6
4' -0
M
AX
9"
(6 '7
M
AX
9"
(6 '7
P
ER
N
EC
.8
(A
TOP OF OPERABLE DEVICE/HANDLE
FINISHED FLOOR
CENTER OF DEVICE
1' -6
TOP OF OPERABLE DEVICE/HANDLE
CENTER OF DEVICE
VFD
LC
KEYLESS FIXTURE
POLE FIXTURE - BOXROUND DOWNLIGHT
(RECESSED)
SCONCE - CIRCLE/OVAL
EXIT SIGN W/ARROW
BATTERY PACK
BOLLARD FIXTURE
SINGLE-POLE SWITCH
b
C
L
WALL WASH
b
LIGHTING CONTACTOR
W/ NUMBER OF POLES
KEY ON LUMINAIRE
SCHEDULE
SWITCHING
#= DEVICE TYPE
2 = DOUBLE-POLE SWITCH
3 = THREE-WAY SWITCH
4 = FOUR-WAY SWITCH
P = SWITCH AND PILOT LIGHT
K = KEY OPERATED SWITCH
D = DIMMER SWITCH
POLE FIXTURE - PUCK
POLE FIXTURE - COBRA
SQUARE DOWNLIGHT
(SURFACE)
FROGEYE
K
DRUM (PENDANT)
LINEAR FIXTURE
(RECESSED) FLOOD LIGHT
WALL PACK
STRIP FLEXIBLE
CEILING FAN
DUPLEX RECEPTACLE
(CEILING)
SINGLE RECEPTACLE
RACEWAY TURNED UP
LP
EXOTHERMIC CONNECTION
VS
AS AMMETER SELECTOR
SWITCH
AMMETER
VOLTMETER
FUSE AND SWITCH < 600V
FUSE < 600V
CIRCUIT BREAKER < 600V
CAPACITOR
SWITCH AIR BREAK
FUSE > 600V
CABLE TERMINATION
ST
G ENGINE-GENERATOR UNIT
G DIFFERENTIAL RELAY
LOCKOUT RELAY
PRESSURE SWITCH
OVER VOLTAGE RELAY
AC CIRCUIT BREAKER
TIME OVER
CURRENT RELAY
MANUAL SELECTOR
SWITCH
UNDER VOLTAGE RELAY27
OVERHEAD GUY
OVERHEAD LINE
DOWN GUY AND ANCHOR
A
WORK NOTE SYMBOL
ROOM NUMBER220
BATTERY
PAD MOUNTED
TRANSFORMER
GFP
AHU-1
GROUNDING CONDUCTORG
EXTERNAL GROUNDING
BUS BARGROUND ROD
GROUNDING ELECTRODE
PATIENT
GROUNDING POINT
G
QUADPLEX RECEPTACLE
(CEILING)
DUPLEX RECEPTACLE
SPLIT WIRED
PRIMARY FUSE CUTOUT
OIL TYPE
CURRENT TRANSFORMER
W/RATIO
POTENTIAL
TRANSFORMER W/RATIO
VOLTMETER SELECTOR
SWITCH
AUTOMATIC TRANSFER
SWITCH
MANUAL TRANSFER SWITCH
END OF LINE RESISTOR
(EOL)
RED AND GREEN PILOT
LIGHTS
PUSH-BUTTON-NORMALLY
OPEN
CONTACT NORMALLY
OPEN (N.O.)
CONTACT NORMALLY
CLOSED (N.C.)
AMP TRIPAT
MANUAL TRANSFER SWITCHMTS
RELOCATED(R)
CKT
C
CIRCUIT
CONDUIT
ATS
AIC
AF
AFG
AFF
+4'-6"
A/AMP
AMPERE INTERRUPTING
CAPACITY
AMP FRAME
AUTOMATIC TRANSFER SWITCH
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
MOUNTING HEIGHT AFF
AMPERE
G GROUND
ENCL
EWC
EPO
EMT
(E)
ELECTRIC METALLIC TUBING
ELECTRIC WATER COOLER
EXISTING
MDS
MH
MDP
MCC
MAIN DISTRIBUTION
SWITCHBOARD
MANHOLE
MAIN DISTRIBUTION PANEL
MOTOR CONTROL CENTER
KW
KVAR
KV
KVA
GRC
HG
KILOWATT
KILOVAR
KILO VOLT-AMPERE
KILOVOLT
GALVANIZED RIGID CONDUIT
PT POTENTIAL TRANSFORMER
RM ROOM
PF
PH
PDU
NO
NC
NIC
N
POWER FACTOR
POWER DISTRIBUTION UNIT
PHASE
NORMALLY CLOSED
NORMALLY OPEN
NOT IN CONTRACT
NEUTRAL
UPS
UG UNDERGROUND
TTB
SW
SCA
TELEPHONE TERMINAL BOARD
SWITCH
WP
WHM
VFD
VDC
VAC
WEATHERPROOF
WATTHOUR METER
VARIABLE FREQUENCY DRIVE
VOLTS DIRECT CURRENT
AC ALTERNATING CURRENT
CP CONTROL PANEL
EC ELECTRICAL CONTRACTOR
FLA FULL LOAD AMPS
LOW VOLTAGELV
MECHANICAL CONTRACTORMC
ac ABOVE COUNTER
REMOVE & RELOCATE(RR)
CURRENT TRANSFORMERCT
UC UNDERCABINET
UF UNDERFLOOR
UNO UNLESS NOTED OTHERWISE
OH
OHG
GROUND FAULT CIRCUIT
INTERRUPTER
HOSPITAL GRADE
VOLTS ALTERNATING CURRENT
UNINTERRUPTIBLE POWER
SUPPLY
EQUIPMENT SCHEDULE
WEATHER HEAD
SERVICE ENTRANCE
SINGLE PHASE
TRANSFORMER: NUMERAL
INDICATES RATING IN KVA
PRIMARY FUSE
CUTOUT AIR TYPE
SWITCH AIR BREAK,
GANG OPERATED
MANHOLE: NUMERAL
INDICATES THE
ASSIGNED NUMBER
AND THE LETTER
INDICATES THE TYPE
PUSH-BUTTON-
NORMALLY CLOSED
OPERATING COIL
(LADDER DIAGRAM)
OPERATING COIL
(SCHEMATIC DIAGRAM)
INSTANTANEOUS OVER
CURRENT RELAY
PANELBOARD
V = VOLTAGE:
L = 208 OR 240
H = 480
S = SPECIAL LOAD:
C = COMPUTER OR
CRITICAL (HC)
E = EMERGENCY OR
EQUIP BRANCH
(HC)
K = KITCHEN
L = LABORATORY OR
LIFESAFETY (HC)
M = MECHANICAL
S = STANDBY
U = UPS
# = FLOOR NUMBER
A = AREA/ZONE
TRANSFORMER (SEE
TRANFORMER SCHEDULE)
CIRCUIT BREAKER WITH
GROUND FAULT
PROTECTIONBREAKER WITH DRAWOUT
FEATURE < 600V
BREAKER WITH DRAWOUT
FEATURE > 600V
FUSED DISCONNECT
SWITCH > 600V
CIRCUIT BREAKER WITH:
ST = SHUNT TRIP
K = KEY INTERLOCKED
E = ELECTRIC OPERATED
LIGHTNING
PROTECTION BARE
CONDUCTOR
SURGE ARRESTER
PLUS GROUND
LIGHTNING PROTECTION
AIR TERMINAL
GROUND ROD WITH
INSPECTION WELL
WR WEATHER RESISTANT
SPD
NL NIGHT LIGHT
TR TAMPER RESISTANT
ALL SYMBOLS IN LEGEND MAY NOT NECESSARILY BE USED ON THIS PROJECT
ABBREVIATIONS AND DESCRIPTIONS
ONE-LINE DIAGRAMS
GROUNDING/LIGHTNING
ELECTRICAL LEGEND
POWER
LIGHTING AND LIGHTING CONTROLS
(D) DEDICATED
ARC FAULT CIRCUIT
INTERRUPTER
AFCI
AHJ AUTHORITY HAVING
JURISDICTION
AUTO AUTOMATIC
CL CENTER LINE
COMM COMMUNICATION
DAS DISTRIBUTED
ANTENNA SYSTEM
DB DECIBAL
DISC DISCONNECT
EOR ENGINEER OF RECORD
EMERGENCY NPOWER OFF
ENCLOSURE
FC FOOTCANDLE
F FUSE
FF FURNITURE FEED
FS FIRE SUPPRESION
HORSEPOWERHP
HIGH PRESSURE SODIUMHPS
HOURHR
HIGH VOLTAGEHV
HERTZHZ SHORT CIRCUIT CURRENT
AVAILABLE
GF GAS FIREPLACE
IMC INTERMEDIATE METAL CONDUIT
SURGE PROTECTIVE DEVICE
TO BE DEMOLISHED WORK IS
SHOWN AS BOLD DASHED LINES
FEEDER SCHEDULE
REVISION NUMBER
MOTOR STARTER OF
CONTACTOR
ENCLOSED FUSED
DISCONNECT SWITCH
ENCLOSED DISCONNECT
SWITCH
ENCLOSED CIRCUIT
BREAKER
VFD
MOTOR
MANUAL PUSHBUTTON
PHOTOCELL
TIME CLOCK
METER
COMBINATION MOTOR
STARTER
SURGE PROTECTOR DEVICE
TAP, SPLICE, LUG OR
CONNECTION
M
VFD
CB
M
TC
ELEC ELECTRICAL
AL ALUMINUM
ARCH
APPROX APPROXIMATE
ARCHITECT
CB CIRCUIT BREAKER
CLG CEILING
COPPERCU
(F) FUTURE
GFP GROUND FAULT PROTECTION
GND GROUND
GD GARBAGE DISPOSAL
GC GENERAL CONTRACTOR
GEN GENERATOR
GEC
AWG AMERICAN WIRE GAUGE
DPDT DOUBLE POLE DOUBLE THROW
DPST DOUBLE POLE SINGLE THROW
DWG DRAWING
DW DISHWASHER
P POLE
PLC PROGRAMMABLE LOGIC
CONTROLLER
PNL PANEL
HH HAND HOLE
HC HEALTH CARE
HOA HAND-OFF-AUTOMATIC
HID HIGH INTENSITY DISCHARGE
NEW WORK IS SHOWN AS BOLD
SOLID LINES
(N) NEWø PHASE
N
E-5
NTS NOT TO SCALE
CONTINUATION
CAP
RACEWAY TURNED DOWN
DUPLEX RECEPTACLE
(FLOOR)
DUPLEX RECEPTACLE
(WALL)
QUADPLEX RECEPTACLE
(FLOOR)
QUADPLEX RECEPTACLE
(WALL)
DUPLEX RECEPTACLE/
SWITCH COMBINATION
TO
30/3 30A
BUZZER (CEILING)
HORN (CEILING)
BELL (CEILING)
SOLENOID (LOW VOLTAGE)
RELAY (LOW VOLTAGE)
TIME CLOCK
THERMOSTAT (LINE VOLTAGE)
MOTOR
PULL BOX
ELECTRIC DAMPER
THERMAL OVERLOAD
SWITCH
M S
SEAL OFF
FEEDER BUS DUCT
6(C)18
UG
W
EXTENSION WHIP
MDS, MCC, CP OR OTHER
EQUIPMENT ENCLOSURE
MULTI-OUTLET ASSEMBLY
OR SURFACE RACEWAY
# = QUANTITY OF REC
*=SPACING IN INCHES OC
MANUAL MOTOR STARTER
DISCONNECT W/SIZE -
CIRCUIT BREAKER
DISCONNECT SWITCH
W/SIZE - FUSED
MOTOR STARTER
OR CONTACTOR
MOTOR STARTER /
DISCONNECT SWITCH
COMBINATION
CABLE TRAY WITH
DEPTH/LOAD/WIDTH
CONCEALED RACEWAY
S = SURFACE
UF = UNDERFLOOR
UG = UNDERGROUND
W = WIREWAY
UF
SPECIAL PURPOSE
RECEPTACLE (CEILING)
SPECIAL PURPOSE
RECEPTACLE (FLOOR)
SPECIAL PURPOSE
RECEPTACLE (WALL)
GROUND FAULT CIRCUIT
INTERRUPTER RECEPTACLE J #M*
OC ON-CENTER
JUNCTION BOX (CEILING)
JUNCTION BOX (FLOOR)
JUNCTION BOX (WALL)
BLANKED FACE DEVICE
(GFCI, AFCI, ETC.)
BRANCH CIRCUIT
PANELBOARD
MAIN DISTRIBUTION
PANEL OR SWITCHBOARD
MECHANICAL EQUIPMENT
J-BOX WITH MANUAL
MOTOR STARTERJ
M
BUZZER (WALL)
HORN (WALL)
BELL (WALL)
VFD VARIABLE-FREQUENCY
DRIVE
DISCONNECT SWITCH
W/SIZE - NON-FUSED30/3
PB
CB
M
M
B
J
J
J
R
S
T
TC
GENERATOR
T
METER
TRANSFORMER
G
M
PUSH BUTTON
OCPD OVERCURRENT PROTECTIVE
DEVICE
OFCI OWNER FURNISHED,
CONTRACTOR INSTALLED
JB JUNCTION BOX
GFCI
EXISTING WORK IS SHOWN AS
LIGHT LINES
GROUNDING ELECTRODE
CONDUCTOR
ILLUMINATING ENGINEERING
SOCIETY
IES
KCMIL KILO CIRCULAR MILS
K KILO (ONE-THOUSAND)
KWH KILOWATT-HOURS
LCD LIGHTING CONTROL DEVICE
LCP LIGHTING CONTROL PANEL
LED LIGHT EMITTING DIODE
LF LLINEAR FOOT
LOH LOCK-ON HANDLE
LRA LOCEKD ROTOR AMPS
LTG LIGHTING
MAXIMUMMAX
MCB MAIN CIRCUIT BREAKER
MCA MINIMUM CIRCUIT AMPACITY
MCM THOUSANDS OF
CIRCULAR MILLS
MFS MAXIMUM FUSE SIZE
MECH MECHANICAL
MIN MINIMUM
MLO MAIN LUG ONLY
MOCP MAXIMUM OVERCURRENT
PROTECTION
MTD MOUNTED
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SYM SYMMETRICAL
TBD TO BE DETERMINED
TECH TECHNOLOGY
TELE TELEPHONE
TEMP TEMPERATURE OR
TEMPORARY
MW MICROWAVE OVEN
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NM NON-METALLIC
PVC POLYVINYL CHLORIDE
REC RECEPTACLE
REF REFERENCE OR REFRIGERATOR
RGS RIGID GALVANIZED STEEL
RLA RATED LOAD AMPS
REQ REQUIRED
RIGID NON-METALLIC CONDUITRNC
RIGID METAL CONDUITRMC
SEC SECONDARY
SF SQUARE FOOT
SPEC SPECIFICATION
STD STANDARD
ST SHUNT TRIP
TV TELEVISION
TYP TYPICAL
W WATT, WIRE OR WASHER
W/ WITH
W/D WASHER/DRYER
W/O WITHOUT
XFMR TRANSFORMER
UNIVERSAL SERIAL BUSUSB
VOLT AMPEREVA
BREAK LINE
4WG100
NUMBER DESIGNATES DETAIL
SHEET DETAIL IS LOCATED
POINT OF CONNECTION
NEW TO EXISTING
NORTH ARROW
RECTANGLE FIXTURE
(SURFACE)
ROUND DOWNLIGHT
(EMERGENCY)
LINEAR FIXTURE (WALL)
LINEAR FIXTURE
(SURFACE/PENDANT)
SQUARE FIXTURE
(SURFACE)
SQUARE FIXTURE
(RECESSED)
LINEAR FIXTURE
(EMERGENCY)
SQUARE FIXTURE
(EMERGENCY)
A
RECTANGLE FIXTURE
(RECESSED)
RECTANGLE FIXTURE (WALL)
RECTANGLE FIXTURE
(EMERGENCY)
SQUARE FIXTURE (WALL)
B
TRACK LIGHTING
SCONCE -
SQUARE/RECTANGLE
SQUARE DOWNLIGHT
(RECESSED)
UNDER CABINET
STRIP FIXTURE
ROUND DOWNLIGHT
(RECESSED)
SQUARE DOWNLIGHT
(EMERGENCY)DRUM (EMERGENCY)
P
SPD
P TRANSFORMER FEEDER
(PRIMARY)
S TRANSFORMER FEEDER
(SECONDARY)
G TRANSFORMER FEEDER
(GROUND)
T
PNL
LOAD BREAK ELBOW
SEPARABLE CONNECTION
R
C
T
A
V
EXTERNAL GROUNDING BUS
BAR
ELECTRICAL EQUIPMENT
ENCLOSURE
OS OS = OCCUPANCY SENSOR
MD = MOTION DETECTOR
TC = TIME CLOCK
Sheet List Table
Sheet Number Sheet Title
E0.01 ELECTRICAL GENERAL INFORMATION
E0.02 ELECTRICAL PROJECT NOTES
ED1.01 ELECTRICAL SITE DEMOLITION PLAN
E1.01 ELECTRICAL SITE PLAN
This item has been electronically signed and sealed by Robert M. Cordero on the date adjacent to the seal using a SHA authentication code.
Printed copies of this document are not considered signed and the SHA authentication code must be verified on any electronic copies.
Sheet no:
Drawn by:
Checked by:
Scale:
Date:
No: Date:Description:
7/10/2026
AS NOTED
BCER PROJECT
6555 N. WICKHAM ROAD, SUITE 104
MELBOURNE, FL 32940 | 321.241.4124
CA# 9303
XXXXXXXX
© Copyright BCER Engineering
ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER
ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE
PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW,
STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.
D
IX
IE
H
O
LL
IN
S
H S
LI
FT
ST
AT
IO
N
R
EP
LA
C
EM
EN
T
2n d
St N
St . P et er sb ur g, F
L
JRB
MC
ELECTRICAL
PROJECT NOTES
E0.02
1. REFER TO ELECTRICAL GENERAL INFORMATION SHEET FOR LEGEND AND
ADDITIONAL INFORMATION APPLICABLE TO THE PROJECT.
2. REFER TO THE ELECTRICAL SPECIFICATIONS AND DETAILS FOR ADDITIONAL
INSTALLATION REQUIREMENTS. DRAWINGS AND SPECIFICATIONS ARE
COMPLIMENTARY. WHATEVER IS CALLED FOR IN EITHER IS BINDING AS THOUGH
CALLED FOR IN BOTH. SHOULD DRAWINGS AND SPECIFICATIONS DIFFER IN WHAT IS
REQUIRED, THE STRICTER REQUIREMENT SHALL APPLY UNLESS WRITTEN
CLARIFICATION IS OBTAINED FROM THE ENGINEER TO GO WITH THE LESSOR
REQUIREMENT.
3. THE EQUIPMENT SPECIFIED ON THE DRAWINGS HAS BEEN SELECTED AS THE BASIS
OF DESIGN. THE USE OF REVIEWED OR SPECIFIED EQUALS SHALL BE
COORDINATED BY THE CONTRACTOR AS TO SPACE REQUIREMENTS, EQUIPMENT
DIMENSIONS, AND PERFORMANCE. ANY ADDITIONAL COSTS EITHER DIRECTLY OR
INDIRECTLY CAUSED BY EQUALS SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR.
4. DRAWINGS ARE DIAGRAMMATIC AND SHOW THE GENERAL DESIGN INTENT,
ARRANGEMENT AND EXTENT OF SYSTEMS. DO NOT SCALE DRAWINGS NOR USE AS
SHOP DRAWINGS. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF EXACT
ROUTING OF ALL SERVICES WITH ALL OTHER TRADES. WHERE ALTERNATE
ROUTING, OFFSETS, AND TRANSITIONS ARE REQUIRED FOR FIELD COORDINATION
OF ALL TRADES, THIS CONTRACTOR SHALL MAKE CHANGES WITHOUT ADDITIONAL
COSTS.
5. PROVIDE ELECTRICAL EQUIPMENT, INSTALL, AND SUPPORT IN COMPLIANCE WITH
SEISMIC, WIND LOAD, SNOW LOAD, SOIL CONDITIONS AND OTHER CRITERIA FOR
PROJECT SITE. REFER TO CIVIL, STRUCTURAL OR OTHER PROJECT DOCUMENTS
FOR DEFINITION OF SUCH CRITERIA FOR PROJECT SITE.
6. CONTRACTOR'S FAILURE TO ORDER OR RELEASE ORDER FOR MATERIALS AND/OR
EQUIPMENT IN A TIMELY MANNER WILL NOT BE ACCEPTED AS A REASON TO
SUBSTITUTE ALTERNATE MATERIALS, EQUIPMENT, OR INSTALLATION METHODS.
7. ALL ELECTRICAL SYSTEM COMPONENTS SHALL BE LISTED OR LABELED BY UL OR
OTHER RECOGNIZED TESTING FACILITY.
8. ALL ELECTRICAL SYSTEMS INCLUDING WORK, MATERIALS, AND EQUIPMENT SHALL
BE INSTALLED IN ACCORDANCE WITH THE CODES LISTED ON THE GENERAL
INFORMATION SHEET, THE ARCHITECTURAL CODE PLAN, AND THOSE ADOPTED BY
THE AUTHORITY HAVING JURISDICTION.
9. PROVIDE PERMITS AND INSPECTIONS REQUIRED.
10. PROTECT ELECTRICAL EQUIPMENT THROUGHOUT CONSTRUCTION.
11. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S
APPROVED WIRING DIAGRAMS, DETAILS, AND INSTRUCTIONS UNLESS SPECIFICALLY
DIRECTED OTHERWISE. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
PROVIDE MATERIALS AND EQUIPMENT COMPATIBLE WITH EQUIPMENT ACTUALLY
SUPPLIED. CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING EQUIPMENT
WHICH IS DAMAGED DUE TO INCORRECT FIELD WIRING PROVIDED UNDER THIS
SECTION, OR FACTORY WIRING IN EQUIPMENT PROVIDED UNDER THIS SECTION.
12. SYSTEMS SHALL BE COMPLETE, OPERABLE, AND READY FOR CONTINUOUS
OPERATION PRIOR TO FINAL PUNCH. LIGHTS, SWITCHES, RECEPTACLES, MOTORS,
ETC. SHALL BE CONNECTED, PROGRAMMED, AND OPERABLE. SYSTEMS SHALL BE
TESTED FOR PROPER OPERATION. IF CONTRACTOR'S TESTS SHOW THAT WORK IS
DEFECTIVE, CONTRACTOR SHALL MAKE CORRECTIONS NECESSARY AT NO COST TO
OWNER PRIOR TO FINAL PUNCH.
13. CONTRACTOR SHALL PROVIDE SUBMITTALS ON ITEMS LISTED IN THE ELECTRICAL
SCHEDULES AND AS REQUIRED IN SPECIFICATIONS TO THE ENGINEER FOR REVIEW
PRIOR TO THE ORDER, PURCHASE, OR INSTALLATION OF THESE SAME ITEMS.
SUBMITTALS SHALL INCLUDE, BUT NOT BE LIMITED TO LIGHTING FIXTURES, LIGHTING
CONTROLS, SWITCHGEAR, SWITCHBOARDS, PANELBOARDS, WIRING DEVICES,
SAFETY SWITCHES, FUSES, MOTOR STARTERS, CONDUIT, CONDUIT FITTINGS,
BUILDING WIRE AND CABLE, AND TRANSFORMERS.
14. CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATION AND INSTALLATION OF
SLEEVES, INSERTS AND SUPPORTS AS REQUIRED FOR THIS SCOPE OF WORK
AND/OR ANY CORE DRILLING. X-RAY THE FLOOR PRIOR TO CORE DRILL UNLESS
NOTED OTHERWISE. COORDINATE WITH G.C. AND STRUCTURAL ENGINEER AS
REQUIRED.
15. DO NOT ROUTE CONDUIT WITHIN STRUCTURAL FLOORS, TOPPING SLABS,
CONCRETE SHEAR WALLS, OR CONCRETE FLOOR BEAMS OR JOISTS UNLESS
SPECIFICALLY NOTED OTHERWISE AND WRITTEN APPROVAL IS OBTAINED FROM THE
STRUCTURAL ENGINEER. TOP OF CONDUIT TO BE 12" MINIMUM CLEAR FROM
BOTTOM OF JOISTS. DO NOT DAMAGE REINFORCING BARS.
16. PROTECT STRUCTURE AND OWNER EQUIPMENT FROM DAMAGE. IMMEDIATELY
REPLACE OR REPAIR, TO ORIGINAL CONDITION, DAMAGE CAUSED BY THE
CONTRACTOR WHETHER EQUIPMENT APPEARS TO BE CURRENTLY IN USE OR NOT,
UNLESS WRITTEN AUTHORIZATION IS OBTAINED FROM THE OWNER INDICATED
OTHERWISE. PREPARE LISTING OF ALL EXISTING DAMAGED ITEMS AND SUBMIT TO
OWNER PRIOR TO BEGINNING WORK.
17. ALL PENETRATIONS OF FIRE RATED PARTITIONS DUE TO THE INSTALLATION OR
REMOVAL OF ELECTRICAL SYSTEMS SHALL BE SEALED TO MAINTAIN THE FIRE
RATING OF THE WALL. REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS
FOR REQUIREMENTS, MATERIALS, AND METHODS OF SEALING PENETRATIONS
THROUGH WALLS. THROUGH-PENETRATION FIRESTOP SHALL COMPLY WITH IBC.
18. PROVIDE TYPED, AND DATED DIRECTORY CARDS UNDER PLASTIC COVER FOR
BRANCH CIRCUIT PANELBOARDS. DIRECTORIES SHALL DESCRIBE CIRCUIT BEING
SERVED, ROOM NAMES, AND ROOM NUMBERS WHERE DEVICES OR FIXTURES ARE
LOCATED. ROOM NAMES AND NUMBERS SHALL MATCH THE GRAPHICS INSTALLED IN
THE FIELD IF DIFFERENT FROM THE ROOM NAMES AND NUMBERS ON THE
DRAWINGS.
19. PROVIDE EXPANSION COUPLINGS, UNIONS, AND FITTINGS AS NECESSARY ON EACH
CONDUIT; AT MINIMUM, PROVIDE EXPANSION COUPLINGS AT EACH ENTRY/EXIT OF
ENCASED CONDUIT AND AT EACH CONCRETE EXPANSION JOINT. COORDINATE WITH
STRUCTURAL DRAWINGS AND GENERAL CONTRACTOR FOR SUCH LOCATIONS.
20. CONDUITS PENETRATING THROUGH ROOF SHALL HAVE ROOF FLASHING WITH
CAULK TYPE COUNTER FLASHING SLEEVE. INSTALLATION SHALL BE WATERTIGHT.
21. IF IT IS NECESSARY TO INSTALL EXPOSED CONDUIT, PAINT EXPOSED CONDUIT TO
MATCH EXISTING FINISHES WITHIN THE SURROUNDING AREA.
22. BACK-TO-BACK MOUNTING OF DEVICES WITHIN A COMMON WALL STRUCTURE IS
NOT PERMITTED. THE MINIMUM SEPARATION IS 6-INCHES IN COMMON WALLS AND
24-INCHES IN SOUND RATED WALLS.
23. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING COMPLETE AND FUNCTIONAL
SYSTEMS BY COORDINATING WORK BETWEEN TRADES. COORDINATE WITH OTHER
TRADES FOR PROVISION OF STARTERS, DISCONNECTS, 120V CONTROL WIRING,
BOXES AND ANY REQUIRED RACEWAYS. FACTOR STARTERS, VFDS, DISCONNECTS,
AND COMBINATION STARTERS SHALL BE UTILIZED ON MECHANICAL EQUIPMENT
WHEN POSSIBLE. TECHNOLOGY CONTRACTOR MAY UTILIZE EQUIPMENT PROVIDED
BY ELECTRICAL CONTRACTOR AND VICE VERSA TO DELIVER A FULLY OPERATIONAL
SYSTEM. REFER TO THE MECHANICAL, PLUMBING, FIRE ALARM, AND TECHNOLOGY
DRAWINGS, DETAILS AND DIVISION 22, 23, 27 AND 28 SPECIFICATIONS FOR
LOCATIONS, SIZES, AND ANY ADDITIONAL INFRASTRUCTURE REQUIREMENTS.
24. MAKE ALL FINAL ELECTRICAL CONNECTIONS TO EQUIPMENT REQUIRING
ELECTRICAL CONNECTION. THIS SHALL INCLUDE BUT NOT BE LIMITED TO ALL
MECHANICAL AND OTHER EQUIPMENT INCLUDED IN THIS PROJECT BY OTHER
TRADES AND THE OWNER. FOR EQUIPMENT SUPPLIED BY OTHERS (INCLUDING
OFOI, OFCI, AND CFCI EQUIPMENT), COORDINATE CONNECTION, CONTROLS,
ROUGH-IN REQUIREMENTS, AND LOCATIONS WITH EQUIPMENT SUPPLIER, OWNER,
AND ARCHITECT PRIOR TO ROUGH-IN.
25. WIRE SHALL BE COPPER, 60 DEGREES C RATED FOR ALL CIRCUITS/FEEDERS 100
AMPS OR LESS, 75 DEGREES C RATED FOR ALL CIRCUITS/FEEDERS OVER 100 AMPS.
WIRING WITHIN 3 INCHES OF FLUORESCENT BALLASTS WIRE SHALL BE COPPER,
MINIMUM 90 DEGREES C RATED. SIZES INDICATED ARE FOR INSTALLATION IN A
MAXIMUM 30 DEGREES C AMBIENT. CONDUCTOR AMPACITY SHALL BE DE-RATED
FOR HIGHER AMBIENT INSTALLATIONS.
26. ALL CIRCUITS SHALL INCLUDE A SEPARATE GREEN INSULATED GROUNDING
CONDUCTOR SIZED IN ACCORDANCE WITH NEC ARTICLE 250, OR LARGER IF NOTED
(#12 AWG MINIMUM SIZE).
27. PROVIDE INDIVIDUAL NEUTRALS ON ALL NEW CIRCUITS.
28. SUPPORT ALL CONDUITS, CABLES, AND BOXES FROM STRUCTURE.
29. IDENTIFY JUNCTION BOXES WITH PANEL AND CIRCUIT NUMBER.
30. CONTRACTOR SHALL PROVIDE WORKING CLEARANCES ABOUT ELECTRICAL
EQUIPMENT PER NEC ARTICLE 110.
31. DEVICES AT MASONRY AND EXPOSED CONCRETE WALLS IN FINISHED AREAS NOT
SCHEDULED TO HAVE GYP FURRING ARE TO BE FLUSH MOUNTED. AT CONCRETE
WALLS AND CEILINGS, EMBED CONDUIT IN CONCRETE.
32. A HOUSEKEEPING PAD SHALL BE PROVIDED FOR GRADE OR FLOOR MOUNTED
EQUIPMENT UNLESS NOTED OTHERWISE. REFER TO SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS.
33. ALL EMPTY CONDUIT SHALL BE DEBURRED, CLEANED, CAPPED, TAGGED, AND
FURNISHED WITH PULL-WIRES AND INSULATION BUSHINGS ON CONDUIT ENDS.
34. PER THE REQUIREMENTS OF THE IECC, THE CONTRACTOR SHALL TURN OVER
AS-BUILT DOCUMENTS TO THE BUILDING OWNER OR OWNER'S AUTHORIZED AGENT
WITHIN 90 DAYS OF THE DATE OF RECEIPT OF THE CERTIFICATE OF OCCUPANCY.
ELECTRICAL GENERAL NOTES
1. REFER TO THE MECHANICAL EQUIPMENT CONNECTION SCHEDULE ON THE
ELECTRICAL SCHEDULES SHEET FOR MECHANICAL EQUIPMENT FEEDER
INFORMATION AND BREAKER SIZES.
2. PROVIDE FUSES SIZED FOR EQUIPMENT INDICATED TO HAVE A FUSED DISCONNECT
PER EQUIPMENT MANUFACTURER REQUIREMENTS.
3. DISCONNECT SWITCH LOCATIONS ARE SHOWN DIAGRAMMATICALLY AND SHALL BE
INSTALLED IN AN ACCESSIBLE LOCATION TO SUIT EQUIPMENT AND SPACE.
DISCONNECT SWITCHES SHALL BE WITHIN SIGHT OF THE EQUIPMENT THEY SERVE
AND MOUNTED AT A MAXIMUM 6'-3" TO THE TOP OF THE OPERATING HANDLE.
MAINTAIN NEC WORKSPACE CLEARANCES AND REQUIREMENTS.
4. RECEPTACLES INDICATED TO BE MOUNTED ABOVE COUNTER ARE TO BE MOUNTED
HORIZONTALLY 6" ABOVE COUNTER.
5. COORDINATE AND VERIFY EXACT MOUNTING LOCATIONS AND HEIGHTS OF WALL
AND FLOOR DEVICES WITH ARCHITECTURAL PLANS, ELEVATIONS, AND MILLWORK
SHOP DRAWINGS OR ANY FURNITURE OR SPECIALTY EQUIPMENT SUPPLIER
DRAWINGS PRIOR TO ROUGH-IN. HEIGHTS INDICATED ARE TO THE CENTERLINE OF
THE DEVICE UNLESS OTHERWISE INDICATED.
6. COORDINATE EXACT REQUIREMENTS AND LOCATIONS OF MECHANICAL, PLUMBING,
FIRE/LIFE SAFETY, AND TECHNOLOGY EQUIPMENT WITH MECHANICAL, PLUMBING,
FIRE/LIFE SAFETY, AND TECHNOLOGY DRAWINGS, SPECIFICATIONS, DETAILS AND
CONTRACTORS PRIOR TO ROUGH-IN.
7. ALL GENERAL-PURPOSE RECEPTACLES IN SHOP AND/OR UTILITY AREAS SHALL BE
GFCI RATED AND MOUNTED AT +42" AFF.
8. NO RECEPTACLES SHALL BE MOUNTED BELOW +18" AFF UNLESS NOTED
OTHERWISE.
9. FOR RECEPTACLES DENOTED "TV", COORDINATE RECEPTACLE LOCATION AND
MOUNTING HEIGHT WITH TV BRACKET AND CATV OUTLET PRIOR TO ROUGH-IN.
10. THE CONTRACTOR SHALL TAKE DIMENSIONS FOR FLOOR MOUNTED DEVICES FROM
ARCHITECTURAL AND VENDOR DRAWINGS.
11. ALL 125V THROUGH 250V RECEPTACLES INSTALLED FOR VENDING MACHINES OR IN
LOCKER ROOMS, BATHROOMS, KITCHENS, ROOFTOPS, SHOPS, AND OUTDOORS,
AND WITHIN 6' OF THE OUTSIDE EDGE OF SINKS OR A WATER SOURCE SHALL BE
GFCI TYPE IN AN ACCESSIBLE LOCATION PER NEC OR PROTECTED BY A GFCI
BREAKER. WHERE RECEPTACLE IS NOT READILY ACCESSIBLE, PROVIDE A REMOTE
GFCI RESET BUTTON IN AN ACCESSIBLE LOCATION AND A NON-GFCI RECEPTACLE
IN THE INACCESSIBLE LOCATION. DO NOT DAISY CHAIN OR FEED-THROUGH GFCI
DEVICES.
12. RECEPTACLES FOR ELECTRIC WATER COOLERS TO BE CONCEALED BEHIND
SHROUD. REMOTE GFCI RESET BUTTON SHALL BE INSTALLED CENTERED 6" BELOW
THE BOTTOM OF THE ELECTRIC WATER COOLER. PROVIDE A SEPARATE
RECEPTACLE FOR EACH DRINKING FOUNTAIN COMPARTMENT. SEPARATE
RECEPTACLES CAN SHARE CIRCUIT INDICATED.
13. [DELETE MOTORS AND TRANSFORMERS IF YOU DON'T HAVE ANY] FINAL
CONNECTIONS TO MOTORS, TRANSFORMERS, AND OTHER VIBRATING EQUIPMENT
SHALL BE WITH SEAL TIGHT FLEX AND APPROVED FITTINGS. DO NOT SECURE
CONDUITS, DISCONNECTS, OR DEVICES TO DUCTWORK OR MECHANICAL
EQUIPMENT.
14. RECEPTACLES MOUNTED BACK-TO-BACK IN FIRE RATED WALLS SHALL BE
PROVIDED WITH A THROUGH-PENETRATION FIRESTOP SYSTEM.
15. ALL EXTERIOR RECEPTACLES TO HAVE METALLIC WEATHERPROOF WHILE IN-USE
COVERS.
16. PROVIDE AND INSTALL A RECEPTACLE WITHIN 25' OF HVAC EQUIPMENT.
17. MOUNT ROOF-MOUNTED RECEPTACLE ENCLOSURE ON STAINLESS STEEL
UNISTRUT CHANNEL SUPPORT/STAND 18-INCHES ABOVE FINISHED ROOF TO
BOTTOM OF RECEPTACLE. PROVIDE FLASHING AT CONDUIT ROOF PENETRATION.
CONDUIT SHALL BE GALVANIZED RIGID STEEL AT PENETRATION EXTENDING TO
RECEPTACLE BOX CONNECTION. RECEPTACLE MAY BE MOUNTED TO ROOFTOP
EQUIPMENT OR ROOFTOP EQUIPMENT SUPPORTS IN LIEU OF SUPPORT/STAND IF
NEC AND IMC REQUIREMENTS ARE MAINTAINED AND SUCH MOUNTING IS
ACCEPTABLE TO ROOFTOP EQUIPMENT MANUFACTURER/SUPPLIER.
18. CONNECTIONS TO ITEMS INDICATED BY WORK NOTES OR OTHER NOTATION SHALL
BE 20A, 120V, 1[(2#12 + 1#12G) 3/4"C] UNLESS NOTED OTHERWISE.
19. FEEDS TO FURNITURE SYSTEM PANELS SHALL BE CONFIGURED TO MATCH
FURNITURE SYSTEM CIRCUITRY REQUIREMENTS, WITH THE SAME NUMBER OF
PHASE, NEUTRAL, AND GROUND CONDUCTORS. MULTIPLE CIRCUITS SHARING A
COMMON NEUTRAL CONDUCTOR IN THE SAME BRANCH CIRCUIT FEED SHALL HAVE
COMMON HANDLE TIE ON BREAKERS.
20. PROVIDE TAMPER RESISTENT RECEPTACLES IN ALL SPACES REQUIRED BY THE
NEC.
21. PROVIDE WALL AND FLOOR MOUNTED DEVICES IN MEETING ROOMS AS REQUIRED
IN NEC 210.65. PROVIDE UNIT PRICE FOR ADDITIONAL FLOOR BOXES AND
WALL-MOUNTED RECEPTACLES INCLUDING INSTALLATION AS REQUIRED BY
INSPECTOR (AHJ).
POWER PLAN GENERAL NOTES
1. DEMOLITION DRAWINGS MAY NOT SHOW EVERY ITEM TO BE DEMOLISHED. DURING
PRE-BID SITE VISIT, CONTRACTOR SHALL DETERMINE THE EXACT EXTENT OF
DEMOLITION TO FACILITATE ALL WORK INDICATED BY THE CONTRACT DOCUMENTS
PRIOR TO QUOTATION. NO EXTRAS WILL BE ALLOWED FOR WORK REQUIRED TO
ACHIEVE THE END RESULT AS INDICATED BY THE CONTRACT DOCUMENTS.
REMOVE OR REWORK EXISTING ELECTRICAL SYSTEMS AS REQUIRED WHEN IN
CONFLICT WITH NEW CONSTRUCTION. REWORK EXISTING TERMINATIONS,
CONNECTIONS, CONDUIT, WIRING, ETC. TO ACCEPT NEW WORK. MAINTAIN CIRCUIT
CONTINUITY TO EXISTING CIRCUITS AND DEVICES TO REMAIN OR BE RELOCATED.
WIRING AND RACEWAY SHALL BE PROVIDED AS NECESSARY TO REENERGIZE
EXISTING DEVICES TO REMAIN WHEN POWER TO SUCH DEVICES IS INTERRUPTED
DUE TO DEMOLITION OF OTHER DEVICES ON THE SAME CIRCUIT. PRIOR TO
COMMENCEMENT OF ANY DEMO WORK, CONFIRM EXISTING CONDITIONS AND
NOTIFY ENGINEER OF ANY DISCREPANCIES REQUIRING RESOLUTION.
2. COORDINATE WITH ARCHITECTURAL DRAWINGS FOR WALL, FLOOR, AND CEILING
DEMOLITION REQUIREMENTS.
3. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SCHEDULE ALL DEMOLITION
WORK WITH THE OWNER WELL IN ADVANCE. WORK SHALL BE PERFORMED AT
SUCH TIMES AND UNDER SUCH CONDITIONS AS SUITS THE OWNER. DEMOLITION
SHALL BE STAGED TO MINIMIZE THE AMOUNT OF DOWNTIME.
4. PRIOR TO DEMOLITION WORK, THE CONTRACTOR SHALL CIRCUIT TRACE ALL
DEVICES AND BRANCH CIRCUITS WITHIN THE AREA OF RENOVATION. ALL EXISTING
PANELBOARD DIRECTORY CARDS SHALL BE UPDATED TO REFLECT FINDINGS.
5. WHERE COMPLETE CIRCUITS ARE DEMOLISHED, THE WIRING SHALL BE
DEMOLISHED BACK TO THE BRANCH CIRCUIT PANELBOARD. UNDER NO
CIRCUMSTANCES ARE ABANDONED DEVICES OR BRANCH CIRCUITS ALLOWED. DO
NOT LEAVE WIRES CONNECTED TO SPARE CIRCUIT BREAKERS. RACEWAYS MAY
REMAIN, AND BE REUSED WHERE APPLICABLE. RACEWAYS AND BRANCH CIRCUITS
NOT REUSED FOR NEW CONSTRUCTION SHALL BE COMPLETELY DEMOLISHED,
INCLUDING PIPE HANGERS, STRAPS, OR TIE WIRES ANCHORED IN CONCRETE SLAB
ABOVE CEILING THAT ARE NO LONGER IN USE. PATCH HOLES LEFT IN WALLS AND
FLOORS AFTER REMOVAL OF EXISTING PIPING, CONDUIT, ETC. TO MATCH NEW OR
EXISTING CONSTRUCTION AND FIRE RATING.
6. ALL ITEMS IDENTIFIED TO BE REMOVED SHALL BE REMOVED IN THEIR ENTIRETY
INCLUDING ALL WIRING AND EXPOSED CONDUIT AND CONDUIT SUPPORTS BACK TO
POINT OF ORIGIN OR NEXT DEVICE TO REMAIN. CONTRACTOR SHALL USE CARE IN
REMOVING DEVICES AND FIXTURES AND THEN SHALL MAKE THEM AVAILABLE TO
THE OWNER FOR FUTURE USE. OWNER ACCEPTED ITEMS, UNLESS OTHERWISE
NOTED, SHALL BE STORED IN AN AREA DESIGNATED BY THE OWNER. ALL DEVICES
AND FIXTURES NOT RETAINED BY THE OWNER SHALL BE DISPOSED OF LEGALLY BY
THE CONTRACTOR. IF ANY HAZARDOUS MATERIALS ARE DISCOVERED DURING
DEMOLITION, NOTIFY OWNER AND ARCHITECT FOR FURTHER DIRECTION.
7. WALL BOXES IN EXISTING WALLS TO REMAIN SHALL BE LEFT IN PLACE. REUSE
THESE BOXES FOR NEW WIRING DEVICES IF THE EXISTING BOX IS WITHIN
12-INCHES LATERALLY OF NEW DEVICE LOCATION AND AT THE SAME MOUNTING
HEIGHT AND WHERE CURRENT NEC AND LOCAL CODE REQUIREMENTS ARE
MAINTAINED. EXISTING BOXES CAN ONLY BE RE-UTILIZED IN PLACE AND CANNOT
BE RELOCATED. PROVIDE BLANK COVERPLATES FOR EXISTING BOXES NOT
REUSED FOR NEW DEVICES.
8. WHERE EXISTING CONDUITS ARE BEING REMOVED AND HAVE BEEN ROUTED IN
CONCRETE FLOOR SLABS, CONCRETE WALLS, OR CONCRETE CEILINGS, THEY
SHALL BE CUT BACK FLUSH WITH CONCRETE. FILL WITH GROUT TO ACHIEVE A
SMOOTH AND EVEN FINISH FLUSH WITH CONCRETE SURFACE AFTER CONDUCTORS
HAVE BEEN REMOVED.
9. REFER TO OTHER TRADES' DRAWINGS FOR ITEMS DEMOLISHED BY OTHERS.
ELECTRICAL CONTRACTOR SHALL DEMOLISH ALL RELATED ELECTRICAL WIRING,
CONDUIT AND ASSOCIATED ELECTRICAL EQUIPMENT, ETC. AS REQUIRED AS PART
OF THIS PROJECT.
ELECTRICAL DEMOLITION GENERAL NOTES
1. REFER TO ELECTRICAL SCHEDULES SHEET FOR LIGHTING CONTROL SCHEDULE
AND LIGHTING CONTROL SCHEDULE AND NOTES.
2. COORDINATE AND VERIFY EXACT MOUNTING LOCATIONS AND HEIGHTS OF WALL
DEVICES WITH ARCHITECTURAL PLANS, ELEVATIONS, AND MILLWORK SHOP
DRAWINGS PRIOR TO ROUGH-IN. HEIGHTS INDICATED ARE TO THE CENTERLINE OF
THE DEVICE UNLESS OTHERWISE INDICATED.
3. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR CEILING TYPES AND
EXACT LOCATION OF ALL FIXTURES. COORDINATE AND VERIFY ALL LUMINAIRE
REQUIREMENTS WITH ARCHITECT PRIOR TO PREPARING SUBMITTALS INCLUDING,
BUT NOT LIMITED TO, MOUNTING METHOD, MOUNTING HEIGHT(S), CEILING TYPES,
AND FINISHES AND/OR COLORS. COORDINATE LUMINAIRE LOCATIONS WITH
MECHANICAL PIPING, DUCTWORK, FIRE PROTECTION, CABLE TRAY, CONDUIT, ETC.
TO AVOID CONFLICTS.
4. RECESSED FIXTURES INSTALLED INDOORS SHALL BE THERMALLY PROTECTED.
5. SUPPORT ALL LUMINAIRES FROM STRUCTURE. LAY-IN FIXTURES SHALL BE
SUPPORTED WITH TWO #12AWG WIRES FROM OPPOSITE ENDS UNLESS OTHERWISE
NOTED.
6. PROVIDE NEUTRAL AND GROUND CONDUCTORS THROUGHOUT ALL LIGHTING
BRANCH CIRCUITS INCLUDING ALL SWITCH OR LIGHTING CONTROL DEVICE
LOCATIONS.
7. ALL LIGHTING CONTROLS SHALL COMPLY WITH IECC. REFER TO APPLICABLE
CODES LISTED ON ARCHITECTURAL CODE PLAN AND ELECTRICAL GENERAL
INFORMATION SHEET FOR SPECIFIC VERSION OF IECC APPLICABLE TO PROJECT.
8. LOCATIONS OF OCCUPANCY SENSORS ARE DIAGRAMMATIC. FIELD COORDINATE
EXACT LOCATIONS OF CEILING MOUNTED OCCUPANCY SENSORS PER
MANUFACTURER'S INSTRUCTIONS. MANUFACTURER DRAWINGS SHALL BE
PROVIDED INDICATING COVERAGE AREAS. IF ADDITIONAL SENSORS ARE NEEDED
FOR COMPLETE COVERAGE OF SPACE, THEY SHALL BE PROVIDED AND INSTALLED
BY THE CONTRACTOR AS REQUIRED TO PROVIDE COMPLETE SPACE COVERAGE.
DO NOT LOCATE OCCUPANCY SENSORS WITHIN SIX FEET OF AN HVAC SUPPLY
DEVICE. CARE SHALL BE TAKEN TO LOCATE SENSORS AWAY FROM WINDOWS TO
MINIMIZE NUISANCE TRIPPING.
9. CONTRACTOR SHALL PROVIDE ALL NECESSARY SWITCH PACKS FOR OCCUPANCY
SENSORS TO PROVIDE FUNCTION INDICATED.
10. ALL OCCUPANCY SENSORS SHALL HAVE AN AUXILIARY CONTACT THAT WILL ALLOW
THEM TO INTERFACE WITH THE HVAC SYSTEM.
11. ALL EMERGENCY LIGHTING SHALL BE NORMALLY CONTROLLED. LOSS OF UTILITY
POWER SHALL ENERGIZE ALL EGRESS LIGHTING TO FULL BRIGHT. THE DESIGN
SHALL MEET ALL UL STANDARDS FOR EMERGENCY REQUIREMENTS.
12. LOW VOLTAGE LIGHTING CONTROL WIRING IN EXPOSED SPACES SHALL BE RUN
CONCEALED IN WALLS WHERE POSSIBLE. EXPOSED RUNS ACROSS CEILING SHALL
BE RUN IN CONDUIT, PAINTED TO MATCH ADJACENT FINISH.
LIGHTING GENERAL NOTES
1. DISTRIBUTION EQUIPMENT SHALL BE FULLY RATED (NOT SERIES RATED).
2. PROVIDE A FRAMED RECORD DRAWING OF ONE-LINE MOUNTED ON MAIN
ELECTRICAL ROOM WALL FOR REFERENCE.
3. SOME PANELBOARDS HAVE MULTIPLE SECTIONS. REFER TO FLOOR PLANS AND
PANEL SCHEDULES FOR NUMBER OF SECTIONS PER PANELBOARD AND
ADDITIONAL INFORMATION ON BRANCH CIRCUITING. IF USING AN 84-POLE SINGLE
SECTION PANEL, WIREWAY SHALL NOT BE LOCATED MORE THAN 2' ABOVE PANEL
UNLESS WIRING IS DERATED.
4. REFER TO THE MECHANICAL EQUIPMENT CONNECTION SCHEDULE ON ELECTRICAL
SCHEDULES SHEET FOR MECHANICAL EQUIPMENT FEEDER INFORMATION AND
BREAKER SIZES.
5. REFER TO THE DRY TYPE TRANSFORMER SCHEDULE ON THE ELECTRICAL ONE-LINE
DIAGRAM SHEET FOR TRANSFORMER FEEDERS AND GROUNDING REQUIREMENTS.
NOT ALL TRANSFORMER SIZES INDICATED ARE UTILIZED AS PART OF THIS
PROJECT.
6. REFER TO THE FEEDER TABLE ON THE ELECTRICAL ONE-LINE DIAGRAM SHEET FOR
FEEDER SIZING REQUIRMENTS. NOT ALL FEEDERS INDICATED ARE UTILIZED AS
PART OF THIS PROJECT.
7. CONNECTION OF CONDUCTORS TO EQUIPMENT TERMINALS SHALL BE IN
ACCORDANCE WITH NEC SECTION 110.14.
8. SHORT CIRCUIT CURRENT CALCULATIONS AND AIC RATINGS ON DRAWINGS SHALL
BE CONSIDERED PRELIMINARY (BASED ON ENGINEER ASSUMPTION OF UTILITY
TRANSFORMER SIZE AND FEEDER LENGTHS) FOR CONTRACTOR PRICING
PURPOSES. CONTRACTOR SHALL PERFORM SHORT CIRCUIT CURRENT
CALCULATIONS AND ARC-FLASH STUDY FOR BUILDING ELECTRICAL DISTRIBUTION
BASED ON INTENDED INSTALLATIONS AND ISSUE SUCH STUDY WITH DISTRIBUTION
EQUIPMENT SUBMITTALS. UTILIZE TRANSFORMER SIZE AND AVAILABLE FAULT
LEVEL AS DICTATED BY UTILITY COMPANY FOR SUCH CALCULATIONS. BASED ON
STUDY, CONTRACTOR SHALL:
A. ADJUST AIC RATINGS OF EQUIPMENT IN SUBMITTALS BASED ON SHORT CIRCUIT
CURRENT STUDY.
B. PROVIDE ARC-FLASH HAZARD WARNING LABELING ON EQUIPMENT PER NEC
REQUIREMENTS BASED ON SUCH STUDY RESULTS.
C. COORDINATE WITH MECHANICAL CONTRACTOR TO ENSURE THAT MECHANICAL
EQUIPMENT AIC RATINGS ARE ABOVE SUCH CALCULATED SHORT CIRCUIT CURRENT
LEVELS. ELECTRICAL CONTRACTOR SHALL PROVIDE LOCAL FUSED DISCONNECT
SWITCHES TO ASSIST MECHANICAL CONTRACTOR WITH RESOLUTION OF CONDITIONS
WHERE LARGER AIC RATINGS OF MECHANICAL EQUIPMENT IS NOT AVAILABLE BUT LET
THROUGH OF FUSES AND AIC RATING OF FUSED DISCONNECT CAN ADDRESS THE ISSUE.
ELECTRICAL ONE-LINE GENERAL NOTES
M 1
Sheet Title:
Sheet no:
Drawn by:
Checked by:
Scale:
Date:
No: Date:Description:
7/10/2026
AS NOTED
BCER PROJECT
6555 N. WICKHAM ROAD, SUITE 104
MELBOURNE, FL 32940 | 321.241.4124
CA# 9303
XXXXXXXX
© Copyright BCER Engineering
ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER
ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE
PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW,
STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.
D
IX
IE
H
O
LL
IN
S
H S
LI
FT
ST
AT
IO
N
R
EP
LA
C
EM
EN
T
2n d
St N
St . P et er sb ur g, F
L
JRB
MC
ELECTRICAL SITE
DEMOLITION PLAN
ED1.01
GENERAL NOTES
**REFER TO ELECTRICAL PROJECT NOTES SHEET FOR ADDITIONAL REQUIREMENTS**
DISCONNECT EXISTING LIFT STATION POWER FEEDER. REMOVE FEEDER BACK TO
LIFT STATION DISCONNECT SWITCH IN ELECTRICAL ROOM. MAINTAIN CONDUIT TO
BE REUSED.
WORK NOTES
N
ELECTRICAL SITE DEMOLITION PLAN
1" = 10'-0"
05' 5' 10' 20'
M 1
Issue Record:
Sheet Title:
Sheet no:
Drawn by:
Checked by:
Scale:
Date:
No: Date:Description:
7/10/2026
AS NOTED
BCER PROJECT
6555 N. WICKHAM ROAD, SUITE 104
MELBOURNE, FL 32940 | 321.241.4124
CA# 9303
XXXXXXXX
© Copyright BCER Engineering
ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER
ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE
PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW,
STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.
D
IX
IE
H
O
LL
IN
S
H S
LI
FT
ST
AT
IO
N
R
EP
LA
C
EM
EN
T
2n d
St N
St . P et er sb ur g, F
L
JRB
MC
ELECTRICAL SITE
PLAN
E1.01
NEW LOCATION OF LIFTSTATION PUMP AND CONTROLLER. PROVIDE NEW FEEDER
WITH (3) #6AWG + (1) #10G FROM DISCONNECT IN ELECTRICAL ROOM TO NEW
LOCATION OF LIFT STATION AND CONNECT TO NEW CONTROLLER. REUSE
EXISTING CONDUIT AND EXTEND TO NEW LOCATION AS REQUIRED. PROVIDE
CONDUIT AND WIRING BETWEEN CONTROLLER, PUMPS, AND SENSORS PER
MANUFACTURER INSTALLATION INSTRUCTION. THE LIFT STATION IS A
ONE-FOR-ONE REPLACEMENT. NO ADDED LOAD.
REPLACE EXISTING FUSES WITH 50A FUSES IN EXISTING FUSED DISCONNECT.
PROVIDE FUSE REDUCERS SUCH THAT 50A FUSE WILL FIT IN 200A DISCONNECT.
CONTRACTOR SHALL CONFIRM TYPE OF FUSES BEFORE PROCURING.
WORK NOTES
N
ELECTRICAL SITE PLAN
1" = 10'-0"
05' 5' 10' 20'
EQUIPMENT SCHEDULE
PLAN CODE
LS-1
GENERAL NOTES
A.
NOTES
1.
2.
3.
DESCRIPTION
LIFT STATION
COORDINATE AND VERIFY ALL EQUIPMENT REQUIREMENTS WITH SUPPLIER AND MECHANICAL DRAWINGS PRIOR TO SUBMITTALS INCLUDING, BUT NOT LIMITED TO, VOLTAGE, OVERCURRENT PROTECTION, CONTROL, DICONNECTING MEANS, ETC.
SINGLE POINT ELECTRICAL CONNECTION. DISCONNECT INTERGRAL TO CONTROLLER.
MANUFACTURER PROVIDED FUSED DISCONNECT SWITCH SHALL BE INTEGRAL TO CONTROLLER AND CONNNECTED BY DIVISION 26.
PROVIDE SPD ON EXISTING CIRCUIT IF ONE IS NOT INSTALLED. (PQ PROTECTION PQM200)
VOLTAGE
PH
HP
FLA
30.8
MCA
38.5
MOCP
EX
KVA
11.1
SIZE
FUSE SIZE
NEMA RATING
4X
PANEL
EX
CIRCUIT
EX
CB SIZE
EX
FEEDER SIZE
(3) #6AWG + (1) #10G IN EX C
NOTES
1, 2, 3
GENERAL NOTES
**REFER TO ELECTRICAL PROJECT NOTES SHEET FOR ADDITIONAL REQUIREMENTS**
HollinsHSLiftStationReplacement-Elec 1
File details come from the government source that posted it. Updated .