PANEL_SCHEDULE_CHART_Q A.xlsx
XLSX spreadsheet 17 KB Posted
- Attached to
- Richland Federal Building Electrical Upgrade Federal contract opportunity
- Solicitation number
- GS-10P-14-LT-R-0047
About this file
Panel Schedule Chart
View the file
Other files for this federal contract opportunity
Show all 38
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| NAME | BUILDING | FLOOR | ROOM | PRINT GRID LINES | VOLTAGE | SIZE | MIN# OF POLES | MAIN CB | FEED FROM | FEEDS SUB-PANEL | NOTES / COMMENTS | INSITE GROUP INC. RESPONSE 7/22/2015 |
| K-5 | FED | G | 120/208 | 225 | 42 | 225 | NOT ON DETAIL OR 1-LINE | Panel to be replaced per General Note # 2 on sheet E-500. | ||||
| DP | FED | G | KITCHENETTE G2C | 277/480 | 400 | 42 | 400 | NOT ON DETAIL OR 1-LINE | Panel to be replaced per General Note # 2 on sheet E-500. | |||
| IG-3 | COURT | E-177 | K-24 | NOT ON DETAIL OR 1-LINE | Panel to be replaced per General Note # 8 on sheet E-500. | |||||||
| 8A | PENT | ELEV | 120/208 | 225 | 37 | MLO | NOT ON DETIAL | Panel to be replaced per General Note # 8 on sheet E-500. | ||||
| C-3 | FED | G | E-G112 | H-17 | 277/480 | C-2 | NONE | NOT ON GSA PNL SCHEDULE | Panel to be replaced per electrical plan note #1 on sheet E-412. | |||
| 1A-5 | FED | 1 | E-150 | S-15 | 120/208 | 1A-2 | NONE | NOT ON GSA PNL SCHEDULE | Panel to be replaced. | |||
| 1D-4 | FED | 1 | E-165 | H-17 | 120/208 | 100 | 47 | 100 | NOT ON 1-LINE | Panel to be replaced per General Note # 8 on sheet E-500. | ||
| 1D-5 | FED | 1 | E-165 | H-17 | 120/208 | 1D-2 | NONE | NOT ON GSA PNL SCHEDULE | Existing panel is a newer panel and does not need to be replaced. Panel to remain and be re-fed. | |||
| 1D-6 | FED | 1 | E-165 | H-17 | 277/480 | 125 | NOT ON GSA PNL SCHED OR 1-LINE | Existing panel is a newer panel and does not need to be replaced. Panel to remain and be re-fed. Panel to be relocated per electrical plan note #7 on sheet E-413. | ||||
| 2C | FED | 2 | E-214 | H-17 | 150 | NOT ON GSA PNL SCHED OR 1-LINE | "150A PANEL 2C" shown on sheet E-414 is a disconnect serving panels "2C-1" and "2C-2". Disconnect 2C does not need to be replaced. | |||||
| 2D | FED | 2 | E-214 | H-17 | NOT ON GSA PNL SCHED OR 1-LINE | "PANEL 2D" shown on sheet E-414 is a disconnect serving panels "2D-1" and "2D-2". Disconnect 2D does not need to be replaced. | ||||||
| 3D | FED | 3 | E-304 | H-17 | 225 | NOT ON GSA PNL SCHED OR 1-LINE | "PANEL 3D" shown on sheet E-415 is a disconnect serving panels "3D-1" and "3D-2". Disconnect 3D does not need to be replaced. | |||||
| SUB-PNL A | 120/208 | 8 | A | NONE | NOT ON GSA PNL SCHED OR DETAIL | Panel to be replaced. | ||||||
| CTV-H&V | 277/480 | 4C | NONE | NOT ON GSA PNL SCHED OR DETAIL | Existing panel is a newer panel and does not need to be replaced. Panel to remain and be re-fed. | |||||||
| 1H | 277/480 | DIST PNL #2 | NONE | NOT ON GSA PNL SCHED OR DETAIL | Panel to be replaced. There is a 200 A breaker in Distribution Panel #2 serving the panel. Location of panel 1H to be determined. | |||||||
| SM | 277/480 | 100 | MAIN DIST #2 EAST | NONE | NOT ON GSA PNL SCHED OR DETAIL | Panel has already been removed. Remove panel "SM" and 100 A breaker serving it from one-line diagram shown on sheet E-500. | ||||||
| DP-1 | COURT | 1 | E-177 | K-24 | 120/208 | 100 | 37 | MLO | NOT ON 1-LINE | Panel to be replaced per electrical plan note #1 on sheet E-402. | ||
| DP-2 | COURT | 1 | E-177 | K-24 | 120/208 | 100 | 30 | MLO | NOT ON 1-LINE | Panel to be replaced per electrical plan note #1 on sheet E-402. | ||
| DP-3 | COURT | 1 | E-177 | K-24 | 120/208 | 100 | 30 | MLO | NOT ON 1-LINE | Panel to be replaced per electrical plan note #1 on sheet E-402. | ||
| K1 | FED | G | CORRIDOR G-5 | K-11 | 120/208 | 400 | 42 | MLO | NOT ON 1-LINE | Panel to be replaced per General Note # 2 on sheet E-500. | ||
| K2 | FED | G | CORRIDOR G-5 | K-11 | 120/208 | 400 | 42 | MLO | NOT ON 1-LINE | Panel to be replaced per General Note # 2 on sheet E-500. | ||
| K3 | FED | G | CORRIDOR G-5 | K-11 | 120/208 | 400 | 42 | MLO | NOT ON 1-LINE | Panel to be replaced per General Note # 2 on sheet E-500. | ||
| FC | FED | G | W. TRANS VAULT | D-17 | 277/480 | 600 | 42 | MLO | NOT ON 1-LINE | Panel to be replaced per General Note # 8 on sheet E-500. | ||
| 4E | FED | G | E. TRANS VAULT | D-16 | NOT ON GSA PNL SCHED OR 1-LINE | Panel to remain and be re-fed. | ||||||
| 45 KVA TXF | FED | 1 | E-165 | H-17 | NOT ON 1-LINE | Existing transformer is a newer transformer and does not need to be replaced. Transformer to remain and be re-fed. | ||||||
| TENANT PNL | FED | 3 | E-304 | H-17 | NOT ON GSA PNL SCHED OR 1-LINE | Panel to remain and be re-fed. | ||||||
| CAR HEAT OUTLET | PO | 1 | J-4 | NOT ON GSA PNL SCHED OR 1-LINE | Panel to be replaced per electrical plan note #1 on sheet E-422. | |||||||
| 150KVA TXF | PO | PENT | MECH ROOM PENT | G-9 | NOT ON 1-LINE | Transformer to be replaced per electrical plan note #1 on sheet E-423. | ||||||
| 9C | PENT | ELEV | 120/208 | 225 | 37 | MLO | 7C | NONE | NOT ON DETAIL | Panel to be replaced per General Note # 8 on sheet E-500. | ||
| 3H | 120/208 | 100 | 42 | MLO | 3G-1 | NONE | NOT ON DETAIL | Panel to be replaced per General Note # 8 on sheet E-500. | ||||
| TXF-7 | MCC #10 | 1-P | NOT ON DETAIL | Transformer to be replaced per Sheet Note # 7 on sheet E-500. | ||||||||
| E-1 | FED | G | E-G112 | 277/480 | 225 | 65 | MLO | ATS | E-2 | NOT ON DETAIL | Panel to be replaced per General Note # 8 on sheet E-500. | |
| 9D | PENT | ELEV | 120/208 | 400 | 24 | MLO | 7D-1 | NONE | NOT ON DETAIL - 1-LINE SHOWS AS 208v & GSA SCHEDULE SHOWS 480V | Panel to be replaced per General Note # 8 on sheet E-500. Panel should be 120/208V per one-line diagram. | ||
| 1I | COURT | G | G42 | 277/480 | 225 | 42 | MLO | DIST PNL #1 | NONE | NOT ON DETAIL | Panel to be replaced. | |
| 400A ELEV PNL | PENT | ELEV | 277/480 | 400 | 24 | MLO | NOT ON DETAIL | This a new panel. Final location to be determined. | ||||
| TF-H8V | FED | 4 | E-404 | H-17 | NOT ON 1-LINE - TENANT PNL , RECONNECT ONLY | Tenant panel. Reconnect only. |