20200803 LBNL SSM-THUP B 50pPD Mech Calcs.pdf
PDF 5 MB Posted
- Solicitation number
- GK021120
- Issued by
-
Department of Energy
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SSM
Mechanical Calculations 100% 3A / 50% 3B Submittal
August 3, 2020
SSM
Mechanical Calculations
100% 3A / 50% 3B Submittal
Appendix A. Mechanical Space and Ventilation Calculations
Project and Climate LBNL-Welcome Center IES VIRTUAL ENVIRONMENT
VE 2019
Model Data
Project file LBNL-Welcome Center.mit
Source HVAC file Proposed.asp
HVAC file snapshot Vista\Baseline-07212020-1.asp
Model floor area 46,054.6 ft²
Building conditioned floor area 46,054.5 ft²
Building conditioned volume 889,379.7 ft³
Number of conditioned rooms 147
Model Orientation 55.0°
Load analysis methodology ASHRAE Heat Balance Method
Calculated 2020/07/21 13:07
Version No. 2019.2.0.0
Location Data
Location Oakland Intl Airport , California
Latitude 37.72 N
Longitude 122.22 W
Altitude 6.6 ft
Time Zone 8.0 hours behind GMT
Design Weather Data
Source ASHRAE design weather database
Monthly percentile:
For heating loads design weather 99.60 %
For cooling loads design weather 0.40 %
Barometric pressure 29.9143 inHg
Air density 0.0749 lb/ft³
Air specific heat 0.7886 Btu/lb·°F
Density-specific heat product 0.0591 Btu/ft³·°F
Summer ground reflectance 0.2
Winter ground reflectance 0.2
Carbon dioxide (ambient) 400.00 ppm
Cooling Calculation Data
Results file Baseline-07212020-1.cln
Calculated 2020/07/21 13:07
Profile Month May - Sep
Max outdoor temp. dry bulb 83.0 °F
Max outdoor temp. wet bulb 63.0 °F
Heating Calculation Data
Results file Baseline-07212020-1.htn
Calculated 2020/07/21 13:06
Profile Month Jan
Outdoor winter design temp 33.0 °F
Project Loads Summary
Cooling loads: kBtu/h Btu/h·ft²
Coincident peak space load 998.69 21.68
Coincident peak plant & equipment load 1,557.10 33.81
Heating loads:
Coincident peak space load 264.43 5.74
Coincident peak plant & equipment load 1,133.84 24.62
Baseline-07212020-1 | 2020/07/21 13:07 | Project and climate - Page 1 of 1Project Cooling and Heating loads are coincident peak value for all conditioned spaces without oversizing.
Paragraph 1 of 1
Space Loads and Ventilation
LBNL-Welcome Center 03 a FAN COIL UNITS - Layer 1
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
System - 0.000 - - - - - - - - 0 0.000 0 -
01-IT/BDF-102 7.459 0.000 7.459 30.50 0 0.000 2.297 9.39 0 0.000 0 0.000 0 -
01-IT/BDF-102 7.459 0.000 7.459 30.50 341 1.394 2.297 9.39 341 1.394 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 1 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 2 of 1
0.000
LBNL-Welcome Center 03 a FAN COIL UNITS - Layer 2
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
System - 0.000 - - - - - - - - 0 0.000 0 -
01-ELECTRICAL-106 25.304 0.000 25.304 129.42 578 2.958 5.348 27.35 578 2.958 0 0.000 0 -
01-ELECTRICAL-106 25.304 0.000 25.304 129.42 578 2.958 5.348 27.35 578 2.958 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 2 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 3 of 1
LBNL-Welcome Center 03 a FAN COIL UNITS - Layer 3
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
System - 0.000 - - - - - - - - 0 0.000 0 0.000
01-ELECTRICAL ROOM-146 17.474 0.000 17.474 121.96 399 2.787 5.045 35.21 399 2.787 0 0.000 0 0.000
01-ELECTRICAL ROOM-146 17.474 0.000 17.474 121.96 399 2.787 5.045 35.21 399 2.787 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 3 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 4 of 1
LBNL-Welcome Center 03 a FAN COIL UNITS - Layer 4
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
System - 0.000 - - - - - - - - 0 0.000 0 0.000
02-ELEC-224 18.036 0.000 18.036 127.92 412 2.923 4.740 33.62 412 2.923 0 0.000 0 0.000
02-ELEC-224 18.036 0.000 18.036 127.92 412 2.923 4.740 33.62 412 2.923 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 4 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 5 of 1
LBNL-Welcome Center 03 a FAN COIL UNITS - Layer 5
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
System - 0.000 - - - - - - - - 0 0.000 0 0.000
02-ELEVATOR SHAFT-225 0.000 0.000 0.000 0.00 478 3.707 0.000 0.00 239 1.854 131 1.013 0 0.000
02-ELEVATOR SHAFT-225 0.000 0.000 0.000 0.00 0 0.000 0.000 0.00 0 0.000 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 5 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 6 of 1
LBNL-Welcome Center 03 a FAN COIL UNITS - Layer 6
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
System - 0.000 - - - - - - - - 0 0.000 0 0.000
02-COLD STORAGE-227 1.544 0.000 1.544 17.27 78 0.877 0.000 0.00 78 0.877 0 0.000 0 0.000
02-COLD STORAGE-227 1.544 0.000 1.544 17.27 78 0.877 0.000 0.00 78 0.877 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 6 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 7 of 1
LBNL-Welcome Center 03 a FAN COIL UNITS - Layer 7
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
System - 0.000 - - - - - - - - 0 0.000 0 0.000
02-COLD STORAGE-228 2.023 0.000 2.023 20.88 103 1.060 -0.021 -0.22 103 1.060 0 0.000 0 0.000
02-COLD STORAGE-228 2.023 0.000 2.023 20.88 103 1.060 0.021 0.22 103 1.060 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 7 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 8 of 1
LBNL-Welcome Center 03 a FAN COIL UNITS - Layer 8
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
System - 0.000 - - - - - - - - 0 0.000 0 0.000
02-ELEC-206 27.438 0.000 27.438 137.97 627 3.153 4.983 25.06 627 3.153 0 0.000 0 0.000
02-ELEC-206 27.438 0.000 27.438 137.97 627 3.153 4.983 25.06 627 3.153 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 8 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 9 of 1
LBNL-Welcome Center 03 a FAN COIL UNITS - Layer 9
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
System - 0.000 - - - - - - - - 0 0.000 0 -
LL-MAIN ELECTRICAL ROOM-L… 38.400 0.000 38.400 148.91 1,950 7.562 0.564 2.19 1,950 7.562 0 0.000 0 -
LL-MAIN ELECTRICAL ROOM-L…38.400 0.000 38.400 148.91 1,950 7.562 0.564 2.19 1,950 7.562 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 9 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 10 of 1
LBNL-Welcome Center 03 a FAN COIL UNITS - Layer 10
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
System - 0.000 - - - - - - - - 0 0.000 0 -
LL-ELEVATOR MAHCHINE ROOM… 0.773 0.000 0.773 6.96 39 0.353 0.545 4.91 39 0.353 0 0.000 0 -
LL-ELEVATOR MAHCHINE ROOM…0.773 0.000 0.773 6.96 39 0.353 0.545 4.91 39 0.353 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 10 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 11 of 1
LBNL-Welcome Center 03 a FAN COIL UNITS - Layer 11
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
System - 0.000 - - - - - - - - 0 0.000 0 -
LL-FOOD SERVICE STORAGE-L… 2.707 0.000 2.707 7.44 137 0.378 1.729 4.75 137 0.378 0 0.000 0 -
LL-FOOD SERVICE STORAGE-L…2.707 0.000 2.707 7.44 137 0.378 1.729 4.75 137 0.378 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 11 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 12 of 1
LBNL-Welcome Center 03 a FAN COIL UNITS - Layer 12
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
System - 0.000 - - - - - - - - 0 0.000 0 -
LL-STAIRS-L01 0.824 0.000 0.824 3.22 47 0.182 1.273 4.98 47 0.182 0 0.000 0 -
LL-STAIRS-L01 0.824 0.000 0.824 3.22 47 0.182 1.273 4.98 47 0.182 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 12 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 13 of 1
LBNL-Welcome Center 03 a FAN COIL UNITS - Layer 13
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
System - 0.000 - - - - - - - - 0 0.000 0 -
LL-BUILDING STORAGE-L04 1.644 0.000 1.644 7.56 84 0.384 1.063 4.89 84 0.384 0 0.000 0 -
LL-BUILDING STORAGE-L04 1.644 0.000 1.644 7.56 84 0.384 1.063 4.89 84 0.384 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 13 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 14 of 1
LBNL-Welcome Center 03 a FAN COIL UNITS - Layer 14
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
System - 0.000 - - - - - - - - 0 0.000 0 -
LL-ELEVATOR-L05 0.000 0.000 0.000 0.00 1,392 10.509 0.000 0.00 696 5.254 324 2.448 0 -
LL-ELEVATOR-L05 0.000 0.000 0.000 0.00 0 0.000 0.000 0.00 0 0.000 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 14 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 15 of 1
LBNL-Welcome Center 03 a FAN COIL UNITS - Layer 15
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
System - 0.000 - - - - - - - - 0 0.000 0 -
LL-CORRIDOR-L03 0.705 0.000 0.705 3.28 36 0.167 0.896 4.18 36 0.167 0 0.000 0 -
LL-CORRIDOR-L03 0.705 0.000 0.705 3.28 36 0.167 0.896 4.18 36 0.167 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 15 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 16 of 1
LBNL-Welcome Center 03 a FAN COIL UNITS - Layer 16
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
System - 0.000 - - - - - - - - 0 0.000 0 -
LL-JANITOR-L02 0.083 0.000 0.083 1.54 16 0.301 0.445 8.23 16 0.301 0 0.000 0 -
LL-JANITOR-L02 0.083 0.000 0.083 1.54 16 0.301 0.445 8.23 16 0.301 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 16 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 17 of 1
LBNL-Welcome Center 03 a FAN COIL UNITS - Layer 17
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
System - 0.000 - - - - - - - - 0 0.000 0 0.000
02-STAIRS-201 39.872 0.000 39.872 34.07 2,025 1.730 12.398 10.59 2,025 1.730 0 0.000 0 0.000
02-STAIRS-201 34.938 0.000 34.938 48.97 1,729 2.423 9.689 13.58 1,729 2.423 - - - -
01-STAIRS-101 4.934 0.000 4.934 10.80 296 0.648 2.708 5.93 296 0.648 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 17 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 18 of 1
LBNL-Welcome Center 03 a FAN COIL UNITS - Layer 18
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
System - 0.000 - - - - - - - - 0 0.000 0 0.000
02-STAIRS-231 25.138 0.000 25.138 48.61 1,277 2.468 9.459 18.29 1,277 2.468 0 0.000 0 0.000
01-CORRIDOR-149 13.319 0.000 13.319 50.97 646 2.472 4.185 16.01 646 2.472 - - - -
02-STAIRS-231 11.818 0.000 11.818 46.19 631 2.465 5.274 20.61 631 2.465 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 18 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 19 of 1
LBNL-Welcome Center 07 a AHU-1
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
System 807.072 205.233 1,012.304 24.38 43,875 1.057 214.570 5.17 26,436 0.637 0 0.000 22,271 0.693
01-MENS RESTROOM-110 0.218 0.000 0.218 0.33 0 0.000 2.030 3.12 0 0.000 0 0.000 385 -
01-MENS RESTROOM-110 0.068 0.000 0.068 0.20 0 0.000 1.223 3.62 0 0.000 - - - -
01-WOMEN RESTROOM-111 0.156 0.000 0.156 0.50 0 0.000 0.808 2.57 0 0.000 - - - -
01-JC-108 1.871 0.000 1.871 27.02 578 8.351 -0.264 -3.81 578 8.351 0 0.000 84 -
01-JC-108 1.871 0.000 1.871 27.02 95 1.372 0.264 3.81 29 0.412 - - - -
01-SHOWER-109 0.674 0.000 0.674 7.16 399 4.244 0.215 2.29 399 4.244 0 0.000 59 -
01-SHOWER-109 0.674 0.000 0.674 7.16 34 0.364 0.215 2.29 13 0.139 - - - -
01-OFFICE-116B 1.365 0.138 1.503 11.86 412 3.253 0.507 4.00 412 3.253 0 0.000 29 -
01-OFFICE-116B 1.365 0.138 1.503 11.86 69 0.547 0.507 4.00 35 0.274 - - - -
01-BADGES OFFICE-116A 9.417 1.075 10.492 9.75 478 0.444 3.117 2.90 239 0.222 131 0.121 201 5.781
01-BADGES OFFICE-116A 9.417 1.075 10.492 9.75 478 0.444 3.117 2.90 239 0.222 - - - -
01-KITCHEN-120 3.527 0.901 4.429 10.28 78 0.182 1.619 3.76 78 0.182 0 0.000 103 4.939
01-KITCHEN-120 2.603 0.901 3.505 17.30 129 0.639 0.727 3.59 129 0.639 - - - -
01-STORAGE-121 0.924 0.000 0.924 4.05 71 0.309 0.892 3.91 71 0.309 - - - -
01-PRIVATE ROOM-118 7.685 1.386 9.071 19.43 103 0.220 1.423 3.05 103 0.220 0 0.000 99 3.659
01-HUDDLE ROOM-117 2.169 0.729 2.898 19.90 112 0.771 0.452 3.11 34 0.231 - - - -
01-COPY PRINT-119 4.112 0.524 4.636 25.15 201 1.088 0.570 3.09 60 0.326 - - - -
01-PRIVATE ROOM-118 1.403 0.133 1.537 11.22 77 0.565 0.401 2.93 23 0.169 - - - -
01-SMALL CONFERENCE ROOM-… 5.493 1.491 6.984 31.37 627 2.816 2.911 13.08 627 2.816 0 0.000 139 -
01-SMALL CONFERENCE ROOM-…5.493 1.491 6.984 31.37 279 1.253 2.911 13.08 177 0.797 - - - -
01-AV CLOSET-114 1.185 0.000 1.185 7.01 1,950 11.533 1.349 7.98 1,950 11.533 0 0.000 42 -
01-AV CLOSET-114 1.185 0.000 1.185 7.01 82 0.486 1.349 7.98 82 0.486 - - - -
01-PERSONEL FILE-113 2.332 0.000 2.332 7.06 39 0.119 2.637 7.98 39 0.119 0 0.000 83 -
01-PERSONEL FILE-113 2.332 0.000 2.332 7.06 161 0.486 2.637 7.98 161 0.486 - - - -
01-BREAKOUT-123 5.733 0.000 5.733 8.44 137 0.202 6.058 8.92 137 0.202 0 0.000 141 0.317
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 19 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 20 of 1
LBNL-Welcome Center 07 a AHU-1
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
01-BREAKOUT-123 5.733 0.000 5.733 8.44 291 0.429 6.058 8.92 369 0.543 - - - -
01-OPERATIONS OFFICE-112 15.305 1.268 16.573 11.05 47 0.031 7.845 5.23 47 0.031 0 0.000 346 52.928
01-OPERATIONS OFFICE-112 15.305 1.268 16.573 11.05 777 0.518 7.845 5.23 478 0.319 - - - -
01-CORRIDOR-131 23.097 0.000 23.097 15.42 84 0.056 15.227 10.16 84 0.056 0 0.000 406 2.288
01-CORRIDOR-131 23.097 0.000 23.097 15.42 1,173 0.783 15.227 10.16 928 0.619 - - - -
01-LOBBY RECEPTION-133 27.418 5.344 32.763 17.95 1,392 0.763 4.036 2.21 696 0.381 324 0.178 587 2.323
01-LOBBY RECEPTION-133 27.418 5.344 32.763 17.95 1,392 0.763 4.036 2.21 696 0.381 - - - -
01-PREFUNCTION-133 29.725 5.543 35.268 37.66 36 0.038 3.113 3.32 36 0.038 0 0.000 382 0.411
01-PREFUNCTION-133 29.725 5.543 35.268 37.66 1,510 1.612 3.113 3.32 453 0.484 - - - -
01-EXCE CONF ROOM-125 12.099 5.740 17.838 33.44 16 0.031 1.814 3.40 16 0.031 0 0.000 308 0.578
01-EXCE CONF ROOM-125 12.099 5.740 17.838 33.44 614 1.152 1.814 3.40 369 0.691 - - - -
01-EXCE CONF ROOM-125 12.060 5.748 17.808 34.49 2,025 3.921 1.956 3.79 2,025 3.921 0 0.000 308 0.596
01-EXCE CONF ROOM-125 12.060 5.748 17.808 34.49 612 1.186 1.956 3.79 367 0.712 - - - -
01-MEDIUM TRAINING-126 12.586 3.265 15.851 23.06 1,277 1.857 1.765 2.57 1,277 1.857 0 0.000 318 0.463
01-MEDIUM TRAINING-126 12.586 3.265 15.851 23.06 639 0.930 1.765 2.57 384 0.558 - - - -
01-LARGE CONF ROOM-129 17.559 6.727 24.285 23.69 892 0.870 2.672 2.61 535 0.522 302 0.294 442 0.431
01-LARGE CONF ROOM-129 17.559 6.727 24.285 23.69 892 0.870 2.672 2.61 535 0.522 - - - -
01-LARGE CONF ROOM-130 18.210 6.702 24.912 24.41 925 0.906 2.784 2.73 555 0.544 302 0.295 456 0.447
01-LARGE CONF ROOM-130 18.210 6.702 24.912 24.41 925 0.906 2.784 2.73 555 0.544 - - - -
01-WORK PREP-122 1.557 0.530 2.086 12.04 79 0.456 0.780 4.50 48 0.274 25 0.147 38 0.477
01-WORK PREP-122 1.557 0.530 2.086 12.04 79 0.456 0.780 4.50 48 0.274 - - - -
01-LOBBY-133-EX 12.242 2.680 14.922 22.72 622 0.947 3.614 5.50 311 0.473 143 0.218 262 0.636
01-LOBBY-133-EX 12.242 2.680 14.922 22.72 622 0.947 3.614 5.50 311 0.473 - - - -
01-HEALTH SERVICES CORRID… 17.834 0.000 17.834 17.36 906 0.882 10.569 10.29 644 0.627 0 0.000 437 1.408
01-HEALTH SERVICES CORRID…17.834 0.000 17.834 17.36 906 0.882 10.569 10.29 644 0.627 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 20 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 21 of 1
LBNL-Welcome Center 07 a AHU-1
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
01-WAITING ROOM-137 6.105 1.388 7.494 20.95 780 2.181 0.988 2.76 780 2.181 179 0.500 401 3.296
01-WAITING ROOM-137 6.105 1.388 7.494 20.95 780 2.181 0.988 2.76 780 2.181 - - - -
01-MULTIPURPOSE ROOM-139 17.131 8.551 25.682 38.58 870 1.307 3.231 4.85 522 0.784 327 0.492 428 0.921
01-MULTIPURPOSE ROOM-139 17.131 8.551 25.682 38.58 870 1.307 3.231 4.85 522 0.784 - - - -
01-BUILDING STORAGE-103 7.036 0.000 7.036 16.59 357 0.843 0.188 0.44 107 0.253 64 0.150 90 -
01-CONTROLS-104 3.777 0.000 3.777 42.96 183 2.082 0.000 0.00 55 0.625 - - - -
01-BUILDING STORAGE-103 3.407 0.000 3.407 10.13 174 0.518 0.188 0.56 52 0.156 - - - -
01-PRIVATE CONF ROOM-127 3.600 1.523 5.123 30.91 183 1.103 0.532 3.21 110 0.662 62 0.377 89 0.537
01-PRIVATE CONF ROOM-127 3.600 1.523 5.123 30.91 183 1.103 0.532 3.21 110 0.662 - - - -
01-PRIVATE CONF ROOM-128 3.499 1.526 5.025 31.16 178 1.102 0.518 3.21 107 0.661 62 0.385 87 0.539
01-PRIVATE CONF ROOM-128 3.499 1.526 5.025 31.16 178 1.102 0.518 3.21 107 0.661 - - - -
01-DISSABILITY MANAGEMENT… 4.878 0.596 5.474 16.05 248 0.726 0.774 2.27 74 0.218 44 0.130 63 -
01-PRINT/COPY-140 2.256 0.275 2.531 25.49 109 1.098 0.231 2.32 33 0.329 - - - -
01-DISSABILITY MANAGEMENT…1.308 0.161 1.469 12.26 69 0.577 0.269 2.25 21 0.173 - - - -
01-DISSABILITY MANAGEMENT…1.314 0.160 1.475 12.10 70 0.571 0.274 2.25 21 0.171 - - - -
01-MEDICAL DIRECTOR-167 6.009 0.417 6.426 13.50 275 0.577 3.333 7.00 203 0.427 54 0.114 126 0.264
01-MEDICAL DIRECTOR-167 2.006 0.140 2.145 13.70 92 0.584 1.107 7.07 68 0.432 - - - -
01-PHYSICIAN ROTATIONAL-1… 2.078 0.137 2.215 13.49 95 0.577 1.141 6.95 70 0.426 - - - -
01-CLINIC MANAGERL-169 1.925 0.140 2.065 13.30 88 0.570 1.085 6.98 65 0.421 - - - -
01-NURSE OFFICE-171 5.079 0.693 5.772 17.55 258 0.784 2.273 6.91 139 0.421 50 0.151 98 0.480
01-NURSE OFFICE-171 2.481 0.346 2.827 17.08 127 0.768 1.144 6.91 68 0.412 - - - -
01-NURSE OFFICE-170 2.598 0.347 2.945 18.02 131 0.800 1.129 6.91 70 0.430 - - - -
01-WELLNESS SPECIALIST-16… 3.352 0.499 3.851 12.39 170 0.548 0.551 1.77 85 0.274 42 0.135 72 0.231
01-WELLNESS SPECIALIST-16… 1.887 0.345 2.233 13.34 95 0.569 0.296 1.77 48 0.284 - - - -
01-SHARED OFFICE-160 1.465 0.153 1.618 11.28 75 0.523 0.255 1.78 37 0.261 - - - -
01-CLINIC STORAGE-157 2.141 0.000 2.141 8.10 264 1.000 0.451 1.71 264 1.000 88 0.333 136 0.514
01-CLINIC STORAGE-157 2.141 0.000 2.141 8.10 264 1.000 0.451 1.71 264 1.000 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 21 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 22 of 1
LBNL-Welcome Center 07 a AHU-1
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
01-AUDIOMETRY EXAM-158 2.982 0.487 3.468 16.49 210 1.000 0.255 1.21 210 1.000 70 0.333 108 0.514
01-AUDIOMETRY EXAM-158 1.574 0.233 1.807 16.14 112 1.000 0.149 1.33 112 1.000 - - - -
01-SPIROMETRY EXAM-155 1.408 0.254 1.662 16.88 98 1.000 0.107 1.08 98 1.000 - - - -
01-PATIENT TOILET-164 0.857 0.000 0.857 4.70 130 0.713 0.339 1.86 130 0.713 0 0.000 67 0.366
01-PATIENT TOILET-164 0.448 0.000 0.448 4.78 67 0.720 0.173 1.85 67 0.720 - - - -
01-PATIENT TOILET-165 0.409 0.000 0.409 4.61 63 0.704 0.166 1.87 63 0.704 - - - -
01-PROCEDURE ROOM-159 2.070 0.071 2.141 12.14 176 1.000 0.253 1.43 176 1.000 59 0.333 91 0.514
01-PROCEDURE ROOM-159 2.070 0.071 2.141 12.14 176 1.000 0.253 1.43 176 1.000 - - - -
01-EXAM-144 4.087 0.239 4.326 13.75 315 1.000 0.510 1.62 315 1.000 105 0.333 162 8.497
01-URGENT EXAM-143 2.059 0.069 2.128 12.00 167 0.942 0.381 2.15 167 0.942 - - - -
01-EXAM-144 2.028 0.355 2.383 17.37 148 1.075 0.129 0.94 148 1.075 - - - -
01-EMPLOYEE ASSISTANCE-13… 3.973 0.686 4.658 13.28 202 0.575 0.665 1.90 101 0.288 51 0.146 85 0.396
01-PR DISABILITY MANAGEME…1.016 0.043 1.059 11.76 51 0.568 0.166 1.84 26 0.284 - - - -
01-EMPLOYEE ASSISTANCE-13…2.016 0.342 2.358 13.30 102 0.576 0.342 1.93 51 0.288 - - - -
01-DISABILITY BENEFITS-17… 0.961 0.061 1.021 12.25 48 0.581 0.158 1.89 24 0.291 - - - -
01-OPTOMETRIST-175 4.344 0.674 5.018 12.94 388 1.000 0.779 2.01 388 1.000 129 0.333 199 0.514
01-OPTOMETRIST-175 1.927 0.345 2.272 13.53 170 1.011 0.315 1.87 170 1.011 - - - -
01-PHYSICAL THERAPY-176 2.417 0.328 2.746 12.48 218 0.992 0.465 2.11 218 0.992 - - - -
01-SOILED HOLDING-150 0.995 0.000 0.995 11.84 84 1.000 0.229 2.73 84 1.000 28 0.333 44 0.520
01-SOILED HOLDING-150 0.995 0.000 0.995 11.84 84 1.000 0.229 2.73 84 1.000 - - - -
01-PA SHARED OFFICE-152 3.650 0.359 4.009 18.09 185 0.837 1.120 5.06 68 0.308 22 0.101 50 0.224
01-STAFF TOILET-151 0.545 0.000 0.545 6.13 30 0.343 0.262 2.95 11 0.126 - - - -
01-PA SHARED OFFICE-152 3.245 0.359 3.604 27.17 155 1.168 0.858 6.47 57 0.430 - - - -
01-CORRIDOR-148 11.651 0.000 11.651 8.38 624 0.449 2.092 1.50 624 0.449 0 0.000 321 0.307
01-CORRIDOR-166 1.602 0.000 1.602 4.72 105 0.308 0.753 2.22 105 0.308 - - - -
01-CORRIDOR-172 1.823 0.000 1.823 7.08 127 0.492 1.028 3.99 127 0.492 - - - -
01-CORRIDOR-148 0.913 0.000 0.913 10.51 43 0.490 0.046 0.53 43 0.490 - - - -
01-CORRIDOR-154 7.625 0.000 7.625 10.78 351 0.496 0.265 0.37 351 0.496 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 22 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 23 of 1
LBNL-Welcome Center 07 a AHU-1
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
02-JANITOR-208 2.093 0.000 2.093 30.97 106 1.573 -0.308 -4.56 100 1.480 0 0.000 54 0.804
02-JANITOR-208 2.093 0.000 2.093 30.97 106 1.573 0.308 4.56 100 1.480 - - - -
02-LACTATION-209 1.342 0.354 1.696 17.88 68 0.719 0.228 2.41 47 0.500 0 0.000 30 0.316
02-LACTATION-209 1.342 0.354 1.696 17.88 68 0.719 0.228 2.41 47 0.500 - - - -
02-MEN RESTROOM-210 3.853 0.000 3.853 5.83 750 1.135 2.257 3.42 750 1.135 0 0.000 385 0.583
02-MEN RESTROOM-210 1.858 0.000 1.858 5.56 366 1.096 1.277 3.82 366 1.096 - - - -
02-WOMEN RESTROOM-211 2.308 0.000 2.308 7.06 384 1.174 0.981 3.00 384 1.174 - - - -
02-DISH RETURN-212 13.433 0.209 13.642 33.37 682 1.669 3.310 8.10 205 0.501 139 0.340 172 0.422
02-DISH RETURN-212 13.433 0.209 13.642 33.37 682 1.669 3.310 8.10 205 0.501 - - - -
02-DINING-EAST-E-214 32.385 9.706 42.091 51.37 1,645 2.007 10.897 13.30 987 1.204 653 0.797 701 0.856
02-DINING-EAST-E-214 32.385 9.706 42.091 51.37 1,645 2.007 10.897 13.30 987 1.204 - - - -
02-DINING-SOUTH E-215A 43.676 12.353 56.029 57.83 2,218 2.289 11.508 11.88 1,331 1.374 818 0.844 961 0.992
02-DINING-SOUTH E-215A 43.676 12.353 56.029 57.83 2,218 2.289 11.508 11.88 1,331 1.374 - - - -
02-DINING-BILLING-215B 4.566 1.105 5.671 29.12 232 1.191 0.966 4.96 162 0.833 100 0.514 115 0.590
02-DINING-BILLING-215B 4.566 1.105 5.671 29.12 232 1.191 0.966 4.96 162 0.833 - - - -
213-DINING-SOUTH WEST E-2… 19.576 2.781 22.358 47.24 994 2.100 7.579 16.01 596 1.260 247 0.522 468 0.995
213-DINING-SOUTH WEST E-2…19.576 2.781 22.358 47.24 994 2.100 7.579 16.01 596 1.260 - - - -
02-LOBBY-220 39.013 4.523 43.536 32.78 1,981 1.492 4.856 3.66 594 0.448 256 0.193 501 0.163
02-LOBBY-220 39.013 4.523 43.536 32.78 1,981 1.492 4.856 3.66 594 0.448 - - - -
03-CENTER LOBBY LOFT 0.000 0.000 0.000 0.00 0 0.000 0.000 0.00 0 0.000 - - - -
02-DINING CENTER CORE-219 62.200 4.145 66.345 57.15 3,159 2.721 10.129 8.72 948 0.816 496 0.427 798 0.456
02-DINING CENTER CORE-219 62.200 4.145 66.345 57.15 3,159 2.721 10.129 8.72 948 0.816 - - - -
02-CAFETERIA-221 59.802 4.898 64.700 15.97 3,037 0.750 17.821 4.40 1,822 0.450 1,146 0.283 1,499 0.370
02-CAFETERIA-221 59.802 4.898 64.700 15.97 3,037 0.750 17.821 4.40 1,822 0.450 - - - -
02-DINING-WEST CORE-217 32.101 14.328 46.430 33.73 1,630 1.184 4.778 3.47 1,630 1.184 1,013 0.736 838 0.609
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 23 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 24 of 1
LBNL-Welcome Center 07 a AHU-1
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
02-DINING-WEST CORE-217 32.101 14.328 46.430 33.73 1,630 1.184 4.778 3.47 1,630 1.184 - - - -
02-DINING-EAST CORE-216 27.885 14.321 42.206 30.34 1,700 1.222 5.005 3.60 1,700 1.222 1,016 0.730 874 0.628
02-DINING-EAST CORE-216 27.885 14.321 42.206 30.34 1,700 1.222 5.005 3.60 1,700 1.222 - - - -
02-DINING-NORTH-E-213 26.299 6.100 32.399 43.10 1,336 1.777 10.193 13.56 801 1.066 497 0.662 565 0.752
02-DINING-NORTH-E-213 26.299 6.100 32.399 43.10 1,336 1.777 10.193 13.56 801 1.066 - - - -
02-DINING-CONFERENCE-1 2.307 1.152 3.459 34.84 117 1.180 0.517 5.21 117 1.180 79 0.792 60 0.607
02-DINING-CONFERENCE-1 2.307 1.152 3.459 34.84 117 1.180 0.517 5.21 117 1.180 - - - -
02-DINING-CONFERENCE-B 2.278 1.152 3.429 34.54 116 1.165 0.375 3.78 116 1.165 79 0.792 59 0.599
02-DINING-CONFERENCE-B 2.278 1.152 3.429 34.54 116 1.165 0.375 3.78 116 1.165 - - - -
02-RISER-203 1.997 0.000 1.997 23.59 101 1.198 0.000 0.00 30 0.359 0 0.000 26 0.303
02-RISER-203 1.997 0.000 1.997 23.59 101 1.198 0.000 0.00 30 0.359 - - - -
02-FIRE CONTROL-204 3.122 0.000 3.122 19.42 159 0.986 0.000 0.00 48 0.296 0 0.000 40 0.249
02-FIRE CONTROL-204 3.122 0.000 3.122 19.42 159 0.986 0.000 0.00 48 0.296 - - - -
02-VEST-202 5.236 0.000 5.236 19.61 266 0.996 4.120 15.42 251 0.940 20 0.075 135 0.507
02-VEST-202 5.236 0.000 5.236 19.61 266 0.996 4.120 15.42 251 0.940 - - - -
02-STORAGE-235 3.842 0.000 3.842 10.05 195 0.510 2.564 6.71 156 0.409 57 0.150 95 0.249
02-STORAGE-235 3.842 0.000 3.842 10.05 195 0.510 2.564 6.71 156 0.409 - - - -
02-LOCKERS-233 0.979 0.000 0.979 10.22 0 0.000 0.209 2.19 0 0.000 0 0.000 64 0.671
02-LOCKERS-233 0.979 0.000 0.979 10.22 0 0.000 0.209 2.19 0 0.000 - - - -
02-STAFF TOILET-232 1.690 0.000 1.690 10.15 0 0.000 0.457 2.75 0 0.000 0 0.000 64 0.386
02-STAFF TOILET-234 0.880 0.000 0.880 10.35 0 0.000 0.205 2.41 0 0.000 - - - -
02-STAFF TOILET-232 0.810 0.000 0.810 9.93 0 0.000 0.252 3.09 0 0.000 - - - -
02-KITCHEN-222 136.710 5.671 142.381 57.70 6,943 2.814 8.717 3.53 2,083 0.844 790 0.320 13,195 5.348
02-KITCHEN-222 136.710 5.671 142.381 57.70 6,943 2.814 8.717 3.53 2,083 0.844 - - - -
02-CORRIDOR-226 6.788 0.000 6.788 30.12 345 1.529 3.504 15.55 214 0.947 17 0.075 156 0.692
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 24 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 25 of 1
LBNL-Welcome Center 07 a AHU-1
IES VIRTUAL ENVIRONMENT
VE 2019
Zone Rooms Sensible Cooling
Load (kBtu/h)
Latent Cooling
Load (kBtu/h)
Total Cooling
Load (kBtu/h)
Total Cooling
Load (Btu/h·ft²)
Cooling Airflow (cfm)
Cooling Airflow (cfm/ft²)
Heating Load
(kBtu/h)
Heating Load
(Btu/h·ft²)
Heating Airflow (cfm)
Heating Airflow (cfm/ft²)
Outdoor Airflow
Req.
(cfm)
Outdoor Airflow
Req.
(cfm/ft²)
Min OA Airflow (cfm)
Min OA Airflow (cfm/ft²)
02-CORRIDOR-226 6.788 0.000 6.788 30.12 345 1.529 3.504 15.55 214 0.947 - - - -
02-WASTE STORAGE-230 1.637 0.000 1.637 13.34 0 0.000 0.314 2.56 0 0.000 0 0.000 64 0.524
02-WASTE STORAGE-230 1.637 0.000 1.637 13.34 0 0.000 0.314 2.56 0 0.000 - - - -
02-OFFICE-229 2.366 0.141 2.507 20.82 120 0.998 0.000 0.00 36 0.299 15 0.127 30 0.252
02-OFFICE-229 2.366 0.141 2.507 20.82 120 0.998 0.000 0.00 36 0.299 - - - -
01-JC-156 0.600 0.000 0.600 5.60 0 0.000 0.179 1.68 0 0.000 0 0.000 51 0.480
01-JC-156 0.600 0.000 0.600 5.60 0 0.000 0.179 1.68 0 0.000 - - - -
01-EXAM-161 3.703 0.226 3.928 12.28 320 1.000 0.554 1.73 320 1.000 107 0.333 164 0.787
01-EXAM-161 1.597 0.195 1.792 14.08 136 1.067 0.211 1.65 136 1.067 - - - -
01-BLOOD DRAW-163 2.106 0.030 2.136 11.09 184 0.956 0.344 1.78 184 0.956 - - - -
01-PT OT OFFICE-177 2.732 0.343 3.075 17.53 139 0.791 1.331 7.59 117 0.667 58 0.333 67 2.212
01-PT OT OFFICE-177 2.732 0.343 3.075 17.53 139 0.791 1.331 7.59 117 0.667 - - - -
01-MA-136 1.521 0.355 1.876 16.44 77 0.677 0.269 2.36 76 0.667 38 0.333 39 -
01-MA-136 1.521 0.355 1.876 16.44 77 0.677 0.269 2.36 76 0.667 - - - -
01-CONFERENCE-153 6.537 1.128 7.665 32.89 332 1.424 2.185 9.37 133 0.571 55 0.236 99 0.424
01-CONFERENCE-153 6.537 1.128 7.665 32.89 332 1.424 2.185 9.37 133 0.571 - - - -
Baseline-07212020-1 | 2020/07/21 13:07 | System Summary - Page 25 of 25System load and airflow are the coincident peak for constituent zones, as simulated.
Zone loads for cooling and heating are each coincident peak values with respect to constituent rooms without oversizing factors applied.
Zone airflows are design values that include oversizing and other influences as set for individual zones in System Parameters.
Paragraph 26 of 1
System Loads Report LBNL-Welcome Center 03 a FAN COIL UNITS - Layer 1
IES VIRTUAL ENVIRONMENT
VE 2019
ZONE COOLING COIL PEAK
Time of Peak (Mo/Hr:Mn) 6 / 17:30
Outside Air (DB/WB/RH) 81.0 / 60.5 / 28.5
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls -67 - -67 -0.9 Roofs 14 - 14 0.2 Ground/Exposed Floors -536 - -536 -7.4 External Doors 0 - 0 0.0 Windows Conduction 0 - 0 0.0 Skylights Conduction 0 - 0 0.0 Solar 0 - 0 0.0 Infiltration 38 - 38 0.5 Nat/Aux Vent 0 - 0 0.0
Internal Building Gains/Losses Internal Walls/Openings -1,115 - -1,115 -15.4 Internal Floors/Air/Furn. 0 - 0 0.0 Ceilings -178 - -178 -2.5 Duct Conduction 0 - 0 0.0 Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total -1,844 0 -1,844
Internal Gains Lights 501 - 501 6.9 People 0 - 0 0.0 Misc, Computers, Equip 8,346 - 8,346 115.2
Sub Total 8,847 0 8,847
Mechanical Gains/Losses Ventilation (sensible) 0 - 0 0.0 Transfer Air † - - - - SA Duct Leakage † - - - - Fans 244 - 244 3.4 SA Duct (conduction) 0 - 0 0.0 Supply Air Plenum - - - - Room Units, Coils, etc. 0 - 0 0.0 Latent Cooling 0 - 0 0.0 Dehumid Oversizing † - - - -
Sub Total 244 0 244
TOTAL 7,247 0 7,247 100
SYSTEM PEAK
6 / 17:30
81.0 / 60.5 / 28.5
Zones Percent (Sensible) of Total
Btu/h % -67 -1.0 14 0.2
-536 -7.6 0 0.0 0 0.0 0 0.0 0 0.0
38 0.5 0 0.0
-1,115 -15.9
-178 -2.5
0 0.0 0 0.0
-1,844
501 7.2
8,346 119.2
8,847
7,003 100
COOLING COILS
Total Capacity Sensible Cap Airflow Enter DB / WB / RH Leave DB / WB / RH ton MBh MBh cfm °F °F % °F °F % System Cooling ‡ - - - - - - - - - - Ventilation - - - - - - - - - - Indirect Evap - - - - - - - - - - Direct Evap - - - - - - - - - -
TOTAL 0.0 0.0 0.0
ZONE HEATING OR REHEAT COIL PEAK
Time of Peak (Mo/Hr:Mn) Heating Design
Outside Air (DB/WB/RH) 33.0 / 27.6 / 50.0
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls -375 - -375 - Roofs -101 - -101 - Ground/Exposed Floors -467 - -467 - External Doors 0 - 0 - Windows Conduction 0 - 0 - Skylights Conduction 0 - 0 - Solar 0 - 0 - Infiltration -283 - -283 - Nat/Aux Vent 0 - 0 -
Internal Building Gains/Losses Internal Walls/Openings -992 - -992 - Internal Floors/Air/Furn. 0 - 0 - Ceilings -234 - -234 - Duct Conduction 0 - 0 - Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total -2,452 0 -2,452
Internal Gains Lights 0 - 0 - People 0 - 0 - Misc, Computers, Equip 0 - 0 -
Sub Total 0 0 0
Mechanical Gains/Losses Ventilation (sensible) 0 - 0 - Transfer Air † - - - - SA Duct Leakage † - - - - Fans 244 - 244 - SA Duct (conduction) 0 - 0 - Supply Air Plenum - - - - Room Units, Coils, etc. -5,251 - -5,251 -
Sub Total -5,007 0 -5,007
TOTAL -7,459 0 -7,459 0
HEATING COILS
Total Capacity Airflow Enter Leave
MBh cfm °F °F System Heating - - - - Ventilation - - - - Pre-Heat - - - -
TOTAL 0.0
AREAS
Gross Glass Glass ft² ft² % Wall 265.1 0.0 0.0 Roof 70.3 0.0 0.0 External Floor 244.6 - - Door 0.0 - - Partition/Door 677.8 - - Internal Ceiling 174.3 - - Internal Floor 0.0 - -
TEMPERATURES
Cooling Heating
°F °F Supply Air (design) 55.0 95.0 Supply Air (actual) 57.0 81.9 Return Air (actual) 75.8 75.3 Plenum (actual) - - Mixed Air (actual) 75.8 75.3 Fan Blade Temperature Rise (dT) 0.5 0.5 Fan Motor Temperature Rise (dT) 0.2 0.2 Fan Configuration Blow-through Blow-through
AIRFLOW
Cooling Heating cfm cfm Supply (design) 341 341 Supply (actual) 341 341 Reheat Minimum (design) 341 341 Leakage at Design Flow 0 0 Return (actual) 341 341 Exhaust and Relief (actual) 0 0 Ventilation (requirement) 0 0 Ventilation (actual) 0 0 Infiltration 6 6
CHECKS
Number of People 0.00 ft²/Person 0.00 Btu/h/ft² - Cooling 29.63 Btu/h/ft² - Heating 30.50 ft²/ton - Cooling 405.01 ft²/ton - Heating 393.50 cfm/ft² - Cooling 1.39 cfm/ft² - Heating 1.39 % Outside Air - Cooling 0.00 % Outside Air - Heating 0.00 Outdoor Air cfm/ft² 0.00 Outdoor Air cfm/person - Peak Latent Load (Btu/h) 0.00 Sensible Heat Ratio 1.00
Baseline-07212020-1 | 2020/07/21 13:07 | System loads - Page 1 of 19Coil and room unit capacities do not include oversizing † Not carried across to the Net Value column ‡ Blow-through fan configuration
Paragraph 27 of 1
03 a FAN COIL UNITS - Layer 2
IES VIRTUAL ENVIRONMENT
VE 2019
ZONE COOLING COIL PEAK
Time of Peak (Mo/Hr:Mn) 8 / 17:30
Outside Air (DB/WB/RH) 79.5 / 61.6 / 35.0
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls -385 - -385 -1.5 Roofs 0 - 0 0.0 Ground/Exposed Floors -1,489 - -1,489 -5.8 External Doors 0 - 0 0.0 Windows Conduction 0 - 0 0.0 Skylights Conduction 0 - 0 0.0 Solar 0 - 0 0.0 Infiltration -87 - -87 -0.3 Nat/Aux Vent 0 - 0 0.0
Internal Building Gains/Losses Internal Walls/Openings -6,413 - -6,413 -25.1 Internal Floors/Air/Furn. 136 - 136 0.5 Ceilings -483 - -483 -1.9 Duct Conduction 0 - 0 0.0 Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total -8,721 0 -8,721
Internal Gains Lights 400 - 400 1.6 People 0 - 0 0.0 Misc, Computers, Equip 33,356 - 33,356 130.6
Sub Total 33,756 0 33,756
Mechanical Gains/Losses Ventilation (sensible) 86 - 86 0.3 Transfer Air † - - - - SA Duct Leakage † - - - - Fans 414 - 414 1.6 SA Duct (conduction) 0 - 0 0.0 Supply Air Plenum - - - - Room Units, Coils, etc. 0 - 0 0.0 Latent Cooling 0 - 0 0.0 Dehumid Oversizing † - - - -
Sub Total 500 0 500
TOTAL 25,536 0 25,536 100
SYSTEM PEAK
8 / 17:30
79.5 / 61.6 / 35.0
Zones Percent (Sensible) of Total
Btu/h % -385 -1.5
0 0.0 -1,489 -5.9
0 0.0 0 0.0 0 0.0 0 0.0
-87 -0.3
-6,413 -25.6
136 0.5 -483 -1.9
0 0.0 0 0.0
-8,721
400 1.6
33,356 133.2
33,756
25,036 100
COOLING COILS
Total Capacity Sensible Cap Airflow Enter DB / WB / RH Leave DB / WB / RH ton MBh MBh cfm °F °F % °F °F % System Cooling ‡ - - - - - - - - - - Ventilation - - - - - - - - - - Indirect Evap - - - - - - - - - - Direct Evap - - - - - - - - - -
TOTAL 0.0 0.0 0.0
ZONE HEATING OR REHEAT COIL PEAK
Time of Peak (Mo/Hr:Mn) Heating Design
Outside Air (DB/WB/RH) 33.0 / 27.6 / 50.0
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls -384 - -384 - Roofs 0 - 0 - Ground/Exposed Floors -682 - -682 - External Doors 0 - 0 - Windows Conduction 0 - 0 - Skylights Conduction 0 - 0 - Solar 0 - 0 - Infiltration -296 - -296 - Nat/Aux Vent 0 - 0 -
Internal Building Gains/Losses Internal Walls/Openings -2,840 - -2,840 - Internal Floors/Air/Furn. 0 - 0 - Ceilings 10 - 10 - Duct Conduction 0 - 0 - Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total -4,192 0 -4,192
Internal Gains Lights 0 - 0 - People 0 - 0 - Misc, Computers, Equip 0 - 0 -
Sub Total 0 0 0
Mechanical Gains/Losses Ventilation (sensible) 0 - 0 - Transfer Air † - - - - SA Duct Leakage † - - - - Fans 414 - 414 - SA Duct (conduction) 0 - 0 - Supply Air Plenum - - - - Room Units, Coils, etc. 0 - 0 -
Sub Total 414 0 414
TOTAL -3,778 0 -3,778 0
HEATING COILS
Total Capacity Airflow Enter Leave
MBh cfm °F °F System Heating - - - - Ventilation - - - - Pre-Heat - - - -
TOTAL 0.0
AREAS
Gross Glass Glass ft² ft² % Wall 214.1 0.0 0.0 Roof 0.0 0.0 - External Floor 195.5 - - Door 0.0 - - Partition/Door 622.5 - - Internal Ceiling 195.5 - - Internal Floor 0.0 - -
TEMPERATURES
Cooling Heating
°F °F Supply Air (design) 55.0 95.0 Supply Air (actual) 56.6 95.0 Return Air (actual) 96.2 88.4 Plenum (actual) - - Mixed Air (actual) 96.4 88.4 Fan Blade Temperature Rise (dT) 0.5 0.5 Fan Motor Temperature Rise (dT) 0.2 0.2 Fan Configuration Blow-through Blow-through
AIRFLOW
Cooling Heating cfm cfm Supply (design) 578 578 Supply (actual) 578 578 Reheat Minimum (design) 578 578 Leakage at Design Flow 0 0 Return (actual) 578 578 Exhaust and Relief (actual) 0 0 Ventilation (requirement) 0 0 Ventilation (actual) 0 0 Infiltration 5 5
CHECKS
Number of People 0.00 ft²/Person 0.00 Btu/h/ft² - Cooling…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .