The provided file is a set of supporting photos and technical drawings for a federal contract opportunity (Solicitation Number FTQW-17-1015-2) for renovations at Building 1300, Eielson Air Force Base in Alaska. The technical drawings and photos detail extensive repair and replacement work, including:

Fire Pump Room Repairs: Replacing seven 300 PSI pressure gauges, converting pre-action risers to a dry valve system, removing and capping OS&Y valves from foam generators, and converting the system to a one-pump configuration. Roof-related work includes replacing all four roof drains, interior rain leaders, and associated horizontal and vertical piping. The project involves comprehensive system modifications, such as reconnecting and insulating piping, installing ball valves, and ensuring compliance with safety standards. The solicitation is set aside for small businesses with a NAICS code of 236210 and a size standard of $45M, with the project magnitude estimated between $1-5 million.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

KNOWN REPAIR AREAS IN CAC, B1300

Repairs In Fire Pump Room (Domestic Water System)

Reconnect and Insulate 2-1/2” Line, And Install a 2-1/2” Ball Valve

Demo

1521310908A Typewritten Text Photo 01

Repairs In Fire Pump Room (Pressure Gauges)

Replace Seven (7) Broken/Damaged Fire Suppression System Liquid Filled (Oil Filled), 300 PSI Pressure Gauges

1521310908A

Photo 02

(Remove OS&Y Valves)

Remove All Three (3) 6” OS&Y System Isolation Valves From the Foam Generators, and Replace Them With Blind Flanged Spools (Blind Flange on Both Ends of Each Spool)

The Abandoned Foam Risers Are Supported by the Pipe Header, So This Work Will Require Temporary Support of the Risers

1521310908A

Photo 03

Convert pre action riser to a dry valve system and tie into the current nitrogen system to serve bays 1 & 2

1521310908A

Photo 04

Inspect, repair if needed, and certify. Convert the system into a one-pump configuration. Isolate and cap the secondary pump ensuring compliance with safety standards.

1521310908A

Photo 05

Replace All Roof Drains and Interior Rain Leaders

Replace All Four (4) Roof Drains And All of the Interior Rain Leaders (all above ground, horizontal and vertical piping, fittings, etc.)

1521310908A

Photo 06

SS-304

STAINLESS STEEL

1 6-GAUGE\

'--!----..-----+-____, ....l >----- 2'-5 r ----<

>-------.i.·-, i" ___ __, FlELC\.'ffllf'I'

CHIMNEY EXTENDER

X-SEC'flO.'.J NTS

I

'ix)

Q

I I I I I I fl_rLJL.JL

/1\

\SJ

U-Lrlf=l'

(2\

\SJ

NEW

SCUPPER

TYP. (E)

68'-0"

I I I I I

'I I

I

I

\___ EXISTING

PAVERS

u..1,: IOo 0...J'a:: (/)

EXISTING

ROOF DRAIN

� ®SIMILAR

L.. w 1 /1\ 0 0..

og �v a::(/)

Q 68'-0" 30'-0"

I I

I I

EXISTING I

LADDER

�I

I I

EXISTING --

VENT '4 \

EXISTING - ,. J

;-�TYP.

• 4'-2"SQ. '

CHIMNEY (C)

EXISTING

(4\ 'n

• 2'-0"SQ.

EXHAUST (A) \8) _

TYP/ 3 \):;¼

(7\ \A2 /

NEW/ '-& I OOF DRAIN�

I I,' NEW NEW OVERFLOW PAVERS - DRAIN

302'-0"

68'-o"

I I

I

I I I /1\ I �v

I ----t;7 NEW

\___ EXISTING

1, PAVERS

I

(7\

PAVERS

\SJ

EXISTING

3" VENT TYP. (O)

EXISTING

2 1/2" VENT

EXISTING EXISTING

5 1 /4" VENT ROOF DRAIN

EXISTING

2 1/2" VENT

6P cp 68'-0"

I I I I I I I

I

I u..1,: j Oo

O...J a::(/)

�SIMILAR

(2'\

NEW \SJ

L..

1,'. t

SCUPPER

Oo O...J a::(/) cp

I I I I I I lJLJl Jl-

/1\

::iJ717cu

I/

------0

------0 'ix)

I """'

------0

---'---0 f-@--';-, --�-?-

LE

'.-, -�-�-._N_o_----------------------------------------------------------------------------(S)

0 0 0 0

I 0 0 f

..--- 2•-5 r --�,TYPICAL AU. 4 SIDES

CHIMNEY EXTENQER

PLAN 'Y\EW NTS

al

,_z ·� 0 �� ,_ -� �, i � ..

� i:i!;

�z w

5t

X-SECTION !>.TS

L,-,r-J f------- -6'-1" -------, CURB Cl� T 2" FlEL!l � NOTE: SIOES NOT EQUAL

CHIMNEY EXTENDER

PL.AN 'v\EW SECTION NTS

OF PAAM'ET INTERSECTIO,.,

SS-304

STAINLESS STEEL

16-GAUGE

ADDED 2 LAYERS

5/8 GWB

T.

0 ' •

TYPICAL 2-HR RATED

PARAPET WALL:

2x6 FRAMING @ 2•-0•

W/ DBL LAYER 5/8 GWB

AND 1 LAYER 1/2 COX

EACH SIDE

r r il r: 4. ., C> ., ., ., . ·C> q t>., q C> C> ., C> "

'c, · q q I C>

C>

J q t> C>

., q q t> C>

4 1/4" FACE OF CONCRETE

TO FACE OF FRAMING

RAIN COLL.AR

PLAN 'v1£W NTS

LINE OF CUTOUT IN

NEW' DECKING

FLUE CONCRffi

FLUE LINER

NOTES

1. A- REMOVE EXISTING GOOSE NECK, SAVE AND REINSTALL.

2.

PROVIDE NEW FLASHING AND COUNTER FLASHING AS REQUIRED.

8- PROVIDE NEW CURB TO MATCH EXISTING DUCT AND GOOSE NECK TO AVOID

THE NEW PARAPET WALL. REMOVE EXISTING GOOSE NECK, SAVE AND REINSTALL.

PROVIDE NEW FLASHING AND COUNTER FLASHING AS REQUIRED.

C- EXTEND EXISTING CHIMNEY HEIGHT TO 3'-0" ABOVE THE TOP OF THE ADJACENT

PARAPET WALL PER USC AND UMC.

D- REMOVE EXISTING VTR'S (5 TOTAL), SAVE AND REINSTALL. FLASH AND COUNTERFLASH

PER ROOF MEMBRANE MANUFACTURER'S RECOMMENDATIONS.

E- LOCATE SCUPPERS 36 INCHES WEST OF GRID LINE "C". BOTTOM OF SCUPPER SHALL BE

NO MORE THAN 2 INCHES ABOVE PAVERS AT LOW POINT OF ROOF .

SEE ELECTRICAL FOR EXISTING ELECTRICAL DEVICES.

u :::v

"""'I

0...

U)

:::v u s:;:

z:

0)

U7

DJ'<

0::::,-"' - ["Tl::::, <.O

U) --I ::::0 C --I C ::::0 ::::0 ---0

::::0 U)

OJ

C

CJ

z:

C) v-J

N <..D

0 � -

<..D 0-, ml z a z ml ml ffl ti z

0 "' (/) -o· u c......u o_

DJ'<

--c) �-:::v "' 0 ,...,.

l'l (D

0:::)

OJ

T"

CJ0 ,...,."'

["Tl::::, <.O

(.,.J U7

..p,..,-,..

n

[77 ::::l

<.D ::::l (1) (1) """'I

U) ...0 C """'I ::::l

--c)..., 0 0 z

(D 0 U7

I � U7 r\i Q c· ,," e,, Q � Q ' c, gi � a C C .,., Cl

$ z a ,:

z C

� :5'.

c::

C: --c'7 � C C -,., � z z C

� :5'. 7 '" � " m,. .,., C: -- G q)

T T -t- T

,I - t T

I+ + t T l .,.- + +

1 -r T + .,. I --,- ""T"

I+ + .., T l ---:- --j-

0 0 68'-0" 68'-0"

BAY 4 BAY 3

REMOVE ROOFING

REMOVE 1x6 FLAT T&G

REMOVE 2x14 @ 24" O.C. @ ALL BAYS & CORE AREA

302'-0"

30'-0"

CORE AREA

68'-0"

BAY 2

ELEC ROOM ROOF

BELOW TO REMAIN

® 0

68' -0"

BAY 1

SPRAYED ON FIREPROOFING TO BE REMOVED & REPLACED

FOR DIAGONAL MEMBER FlX ON TYPE 'B'

TRUSSES.

TRUSS 'B'

·bI �1 I :

Ni N

I

N N

W16x36 TRUSS 'A' TO REMAIN, TYP /TRUSS 'A '

·zs /� ZS w�\

_L__

_______'c, _I c... �

"----- IIL-�

I

__::,,_I "

��- �-j--�-:,-' c,--- ----ji' : 1 �" �-�I � 1 / � I -----OJ:©- ,_i���/�����/=�1-�/��i�=�/==�==�l������1�w�16�x36���=�/=/=T���ss�·B�·/���=�/=��=� .1

R u s s s

RUSS ,- ' RUSS 'B'

PERIMETER SHEATHING �� 1

Tee Ma\ 2S !6: OS. 12 1996

& SIDING TO REMAIN. TRIM AS REQD :':l' �v @ ROOF TO BRING FLUSH W/ NEW ROOF ELEVATION ROOF ALL BEAMS IN CORE �Tu�¢- ' I AREA TO REMAIN "'-' 0

EXISTING CROSS BRACE TO REMAIN -� SUSPENDED CEILING, LIGHTS, MECH ���1� TO

SEE S4 FOR STRENGTHENING %

TYP (6) LOCATIONS & ELEC TO BE REMOVED & REPAIRS

REINSTALLED, OR TEMPORARILY

HUNG DURING ROOF RECONSTRUCTION,

@ CONTRACTOR'S OPTION.

DEMOLITION PLAN

EXISTING ROOF FRAMING PLAN

TRUSS ROD X-BRACING TO _J

REMAIN UNTIL ROOF DECK

IS SECURELY FASTENED. RODS

MAY BE USED FOR TEMPORARY

SUPPORT OF MECH & ELEC EQUIPMENT

AS REQD, TYP.

O.H. DOOR SUPPORT TRUSSES

& BRACING TO REMAIN, TYP.

- S 2 1/16"=1·-o· 112RFPN1 r REMOVE WOOD DECKING & ROOF.

W6x15, TYP

�1---------------=66_'-=-2· _________ �� 10'-9" 10'-3" 11'-1' 11 '-4" 1 O' -8'' 10'-3" i ,1•-3''

COL

I .11 7

'NICO

1� <O ::;uLJJLr'..U _t__ 1--,!;J.._.....,=B=C'i----1;;;.,.._,1=='1----";.:i...---i==�-�L...---i�-...J:..:�--i""BCiai,-_J,:J.:,i_....;=iai,-----1=-!--,-l J2

I . Jl 9

TYP

TYPICAL EXISTING 112TRSB2

3 EXISTING TRUSS TYPE A -�--------------

2 BRACE FRAME ELEVATION

S 2 S2 ½"=1 ·-o"

TYPE B DIMS VARY

S2 S2 1 /8" = 1 ·-0· 112DETOB

EXIST W6 BM

EXIST W8 COL

I I • Ii

• I i" GYP BOARD -�

IN CORE AREA

TO BE DEMOLISHED

SUSPENDED CEILING -

IN CORE AREA - REMOVE

& REPLACE

CORE AREA

\ j

; I

4 SECTION

S2 S2 1 1/2"=1 '-o"

I ' I

_J I, REMOVE 2x14's '\

-....__ EXIST

W6

,,,-- - EXIST

W8 COL

BEYOND

TYP BAY

112CET15

JOINT

J1/2

J3

J4

J5

J6

J7

JS

J9

J 10

JOINT

J1/J2

J3

J4

J5

J6

J7

JS

J9

J10

TRUSS A

MEMBER #

# RIVETS

M1A •

TC •

M18 9 M2 6

BC 7

M2 6

TC 8

M5 5

TC 4

M6 2 M5 5 M6 2 M7 4

BC 6

M7 4

TC 8

MlO 3

TC 4

Ml 1 2 Ml 0 3 Ml 1 2 Ml 2 3 BC lg) ;'f.lV!:)3_ M12 3

TC 7

M15 2

TC 4

M16 2

MEMBER

SIZE

T4x3x,;

T6x3.!.x"'-2 16 T 4x3x 1� 7r3¼x3xfs 1r 4x4x±

1 5 7r3,x3x,.:

7r6x3.lx2.

2 16 7r3x2x,,i

T6x3½xfi 7r21x2x.,i_

2 16 7r3x2x 1� 1r2½x2x 1�

1 1 27r3-x2-x-2 2 16 1r 4x4x¼ T3½x2½x,56

7r6x3½xfi 7r3x2x¼ T6x31x2

2 16 T2.!.x2x""

2 16 7r3x2x¼ T2½x2x 1� 7r3x2x± T4x4x¼ 7r3x2x1

T6x3.lx2 2 16

7r21x2x.,i_ 2 16 7r6x3.!.x2

2 16 7rz1.x2x2.

2 16

TRUSS B

MEMBER # OF

# RIVETS

MlA 10

TC 6

M1B 10 M2 3

BC 6

M2 3

TC 7

M5 3

TC 4

M6 2 M5 3 M6 2 M7 3

BC 4

M7 3

TC 6

M10 2

TC 6

M11 4 M10 2 M11 2 M12 2

BC 4

M12 2

TC 6

M15 2

TC 4

M16 2

TRUSS NOTES:

MEMBER

SIZE

lr4x3x± 7r5x31x2

2 16 1 1 7r3X22X4

7r3x2½xt 1 1 7r4x3,x,:

7r3x2.lxl 2 4

7r5x3½x 1� 1 3 'f2,x2x,., 1 5 7r5x32X 15 7r2½x2x 1� 1r21.x2x2.

2 16 'f21x2x2.

2 16 1 1 7r3x2-x- 2 4

1r 4x3.!.x.!.

2 4

7r3x2½x¼ 7r5x3.!.x2.

2 16 7r3x2½xt

1 5 7r5X32Xf6 7r3½x3xi 7r3x21x12 4

7r31x3x1 2 4

7r2½x2xfs 1r 4x3.!.x.!.

2 4

7r21x2x'1 2 16

7r5x31x2 2 16

7r2½x2xfs 7r5x3½x� 7r2x2x2.16

1) ALL DIAGS., TC & BC HAVE

LONG LEGS VERTICAL

2l RIVETS ARE ¾o

3 ALL CONNECTION its ARE ¾°

JOINT MEMBER

M15

J 11 M16 M17

BC

M17

J12 TC

M20

TC

J13 M21 M20

J14 M21 M22

BC

M22

J15 TC

M25 M25

Jl 6 M26 M27

BC

J17 M26

TC

M27

J18 TC

M30 M51A

TC

J19/20 M30 M31B

BC

JOINT MEMBER

M15

J 11 M16 M17

BC

M17

J12 TC

M20

TC

J13 M21 M20

J14 M21 M22

BC

M22

J15 TC

M25 M25

J16 M26 M27

BC

J17 M26

TC

M27

Jl 8 TC M30 M30

TC

J19/20 M31A

BC

M31B

TRUSS A

Rl,ETS

(?\iRIVETS * A325

MEMBER

SIZE

7r2.lx2x.,i_ 2 16 7r2½x2xfs

1 3 7r2,x2x,., 1r 4x4x.!.4 1r2½x2xfs 7r6x3.!.x2. 2 16 1r21.x2x""

2 16 7r6x3½xfs 7r31x21x12 2 4 1r2½x2xfs T31x21x1

2 2 4 1 3 7r2,x2x,., 7r4x4x¼ 7r21x2x..J. 2 16 7r6x31x22 16 7rz.!.x2x_,)_

2 16 7r2½x2xfs 7r21xzx'1 2 16 1r2½x2xfs 'f4x4x¼ T2½x2x,i 'f6x3¼xfi 'f21x2x,,i 2 16 'f6x31x 0

2 16 'f3x21x1

2 4

'f21x3x12 4 T6x31.x2. 2 16 T3x21x12 4 T3½x3xi T4x4x14

TRUSS 8

# OF

RIVETS

MEMBER

SIZE

7r21x2x" 2 16 1r2x2x;i 1r2.1x2x_.,_

2 16 1r 4x3¼xt 1r21.x2x2.2 16 7r5x3.lx22 16 1r2.1x2x.1

2 4

7r5x3�xt 7r31x3x12 4 1r2.1x2x_,)_2 16 7r3.lx3x.l

2 4

1 31r22x2xi6 1 1 1r 4x3,x,;

1r2½x2xfs 7r5x31x o 2 16 1r2.1x2x.,i_ 2 16 1r2½x2xtl;

31r2x2x 16 1 3 1r22x2x 16 31 1 7r4x -x-

2 4

1r2x2x,i 31 5 1rsx ,,x1s1 37r22x2x 16

7r5x3�x� 7r3x2½x¼ 7r3x21x1

2 4 1 5 7r5x32X 16 1 1 1 1r2-x2-x-

2 2 4 .

7r4x3¼x¼ 7r3½x3xf m ,, a:

, i � -ffl

C:

l!

i ,.., :'i ::, = C C ,-

I . 0

8 s:

0 , . z < z 0 8 m C z

0 m rn � > :,.

i.

() > 7 -·

,; ;",1 al'" � > .,., ,c a - :i

(1)

(1)

©12) c::, c::, (1)

0 CJ) � ..o·::, ::, (1) c.... r � C) 0

OJ N 7J UJO

-:::r (0 .............. I (I) ;::S. 2 � C iI e.►�5l.o -- (0� ..... � 6 - !,_

' 0 <O Z

>l/. N "" (") 7J . ' ::m. ;::o9 ::r a

" 0, <O (0 0

7.. "''O -' " "'

(1) �- ., --·

0 I u - ;o (1) . Qcil o, CD 2 l rr, ,+

;o ::, 0 ' <Q

<9. rr, ,. I

(') 0 ::, - :,. ::, '° 0 •• '

(1) v 0

(1": (1) C

::, -·"" -, (1) ""

0 r7 s:::

en r

0 Cz: n u --1

C ()l

::::0 rrl _,,,. z:

J>

,....,. - (D � ;o

U) 0

C ::::0 0 <

U) rrl

U) u J> r7 R" J> => cO ::::0 rn => en (1)

C C ;o ,- 0 --

0 "" C >-r7 CD J> � 0 C 0 (.I) � z ...0 � ,-- U) C

0 a 77 z CJ -:;,;::- 0 z ;o 0...

)> 0 C "" s::: 0 ., ,. � :,. Ir7 C) => f.i ,; l"'\i r7 > .,., ' ,-r ___,, ,, I r7 GJ � 3;; 0 z:

(./) c::, 7J ::r 0 77 a ,+

(1) --, �-

(1) N 0 n

(D (D � s::: 0

0 � (.)7

- I

(D

� CJ) �

()l (.)7

Slide 1: REPAIR FREEZE DAMAGE IN CAC, B1300
Slide 2: Replace Complete Water Softner System
Slide 3: Replace Water Filters
Slide 4: Replace Boiler Feed Unit Makeup Water (Complete System)
Slide 5: Replace Entire Makeup Water to Boiler Feed Unit
Slide 6: Replace Complete Boiler Feed Chemical Injection System
Slide 7: Replace Complete Boiler Feed Water System
Slide 8: Replace HX-1’s Entire Condensate System
Slide 9: Replace Condensate Lines Between Boiler and Condensate Receiver
Slide 10: Replace Entire Temperature Control Station Drip Leg
Slide 11: Replace Strainer in 2/3 Stage Location of HX-1 Temperature Control Station
Slide 12: Replace Boiler Feed Water Tank Heat & Condensate Tank Motive Steam Supply
Slide 13: Replace Boiler Feed Tank Vent Line
Slide 14: Replace Boiler Feed Water Pipe and Fittings As Necessary
Slide 15: Lower View of Boiler Feed Unit
Slide 16: 6 Inch Steam Blow-Off Valve
Slide 17: Repairs In Fire Pump Room (Domestic Water System)
Slide 18: Repairs In Fire Pump Room (Pressure Gauges)
Slide 19: Repairs In Fire Pump Room (Remove OS&Y Valves)
Slide 20: Repairs In Fire Pump Room (Rebuild 6” Pre-Action Fire Alarm Valves)
Slide 21: Repairs In Fire Pump Room (Inspect & Maintain Fire Pumps)
Slide 22: Replace All Roof Drains and Interior Rain Leaders

File details come from the government source that posted it. Updated .