Fire Dampers Report - 2014.pdf
PDF 307 KB Posted
- Attached to
- Z1DA--FIRE DAMPERS -Repair, Install, Inspect and Testing Federal contract opportunity
- Solicitation number
- 36C24221B0065
About this file
This document contains a fire damper inspection report and notice of a forthcoming solicitation for repair, installation, inspection, testing and decommissioning of fire dampers. The inspection report details seventy-six fire dampers at two buildings of a Veterans Affairs medical center that require repair or replacement. The forthcoming solicitation will be set aside for Veteran-owned small businesses and cover approximately three hundred and fifty fire dampers across the two buildings. Work will include preparing as-built drawings, inspecting and testing dampers, providing access to inaccessible dampers, and submitting a final report with drawings and photos. The estimated cost range is two hundred thousand to five hundred thousand dollars. Prospective contractors must be verified Veteran-owned small businesses and registered in SAM.gov. The performance period is three hundred and sixty days from notice to proceed. The solicitation is expected to be issued on or about August 27, 2021.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Bid Sheet -36C24221B0065 Rev.pdf | ||
| 36C24221B0065 0004.docx | DOCX document | |
| 36C24221B0065 0003.docx | DOCX document | |
| Site Visit - Sign In 36C24221B0065 Fire Damper.pdf | ||
| Bid Sheet -36C24221B0065.pdf | ||
| RFIs -36C24221B0065 Answers.pdf | ||
| VA NOTICE OF LIMITATIONS ON SUBCONTRACTING CERTIFICATION.pdf | ||
| 36C24221B0065 0002.docx | DOCX document | |
| 36C24221B0065 0001.docx | DOCX document | |
| Building 1.pdf | ||
| 015816 Temp Int Signage 08-11 Edited 121511.pdf | ||
| 017419 Const Waste management 09-10 edited 121511.pdf | ||
| 014529 Testing Lab Srvcs 05-09 - Edited - 121511.pdf | ||
| Building 6.pdf | ||
| 015719Temp Env Cntrls 01-11 - Edited 121511.pdf | ||
| 013323 Shop Dwgs Product Data and Samples - Edited - 121511.pdf | ||
| 010000 Gen Req 6-11- Edited -121311.pdf | ||
| DB Wage Determination dtd 10-22-2021.pdf | ||
| 014219 Ref Standards 09-11 - Edited - 121511.pdf | ||
| 36C24221B0065.docx | DOCX document |
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DATE OF REPORT: 07/01/14
C O
U N
T
B u il d in g
Damper
Number DAMPER TYPE Location Pass/ Fail
REVISED**
PASS/FAIL
REVISED** COMMENTS
Bldg-1
Main
FD-G-336 FIRE INSIDE MECHANICAL ROOM INACCESSIBLE PASS
YELLOW EXTENSION CORD NEEDS TO BE
REMOVED FROM DAMPER OPENING
Bldg-1
Main
FD-G-337 FIRE INSIDE MECHANICAL ROOM INACCESSIBLE PASS
Bldg-1
Main
FD-3-328 FIRE INSIDE SOUTH MECHANICAL ROOM #3052-S INACCESSIBLE PASS
Bldg-1
Main
FD-5-313 FIRE INSIDE WEST MECHANICAL ROOM INACCESSIBLE PASS
Bldg-1
Main
FD-5-314 FIRE INSIDE WEST MECHANICAL ROOM INACCESSIBLE PASS
Bldg-1
Main
FD-6-301 FIRE INSIDE CORE LAB ROOM #6074-S INACCESSIBLE PASS
Bldg-1
Main
FD-7-297 FIRE ABOVE FIRE EQUIPMENT CLOSET #7023-W INACCESSIBLE HIGH VELOCITY
AIR HANDLER NEEDS TO BE SLOWED DOWN TO
BE TESTED
Bldg-1
Main FD-8-062A FIRE NEAR FIRE EQUIPMENT CLOSET #8073-S INACCESSIBLE CONST. AREA IN CONSTRUCTION AREA
Bldg-1
Main
FD-8-295 FIRE INSIDE ROOM #8022-W INACCESSIBLE PASS HIGH VELOCITY DUCT
Bldg-1
Main
FD-10-078 FIRE
INSIDE NORTH STAIRWAY NEXT TO FIRE
EQUIPMENT CLOSET #10134-N
INACCESSIBLE P.I.R.
PATIENT IN ROOM (P.I.R)- 10134N - NEED TO
SCHEDULE
Bldg-1
Main
FD-12-072 FIRE ABOVE FIRE EQUIPMENT CLOSET #12128-N INACCESSIBLE HIGH VELOCITY
AIR HANDLER NEEDS TO BE SLOWED DOWN TO
BE TESTED
Bldg-1
Main
FD-12-288 FIRE ABOVE DOOR TO ROOM #12020-B INACCESSIBLE HIGH VELOCITY
AIR HANDLER NEEDS TO BE SLOWED DOWN TO
BE TESTED
Bldg-1
Main
FD-13-070 FIRE
ABOVE DOOR TO FIRE CLOSET ROOM #13139-
N
INACCESSIBLE P.I.R.
PATIENT IN ROOM (P.I.R)- 13139N - NEED TO
SCHEDULE
Bldg-1
Main
FD-13-071 FIRE
IN HALLWAY FIRE EQUIPMENT CLOSET #13138-
N
INACCESSIBLE HIGH VELOCITY
AIR HANDLER NEEDS TO BE SLOWED
DOWN TO BE TESTED
Bldg-1
Main
FD-13-286 FIRE ABOVE FIREHOSE DOOR #13015-W INACCESSIBLE HIGH VELOCITY
AIR HANDLER NEEDS TO BE SLOWED
DOWN TO BE TESTED
Bldg-1
Main
FD-14-284 FIRE ABOVE FIRE EQUIPMENT CLOSET #14021-W INACCESSIBLE HIGH VELOCITY
AIR HANDLER NEEDS TO BE SLOWED
DOWN TO BE TESTED
Bldg-1
Main
FD-17-046 FIRE BY STAIRWELL #17010-W INACCESSIBLE HIGH VELOCITY
NEED TO INSTALL HATCH DOOR TO ACCESS
DAMPER (17011W) and AIR HANDLER NEEDS TO
BE SLOWED DOWN
Bldg-1
Main
FD-17-047 FIRE BY STAIRWELL #17133-S INACCESSIBLE HIGH VELOCITY
AIR HANDLER NEEDS TO BE SLOWED
DOWN TO BE TESTED
Bldg-1
Main
FD-19-026 FIRE PENTHOUSE WEST SIDE INACCESSIBLE RECHECK NEED TO RECHECK
Bldg-1
Main
FD-19-027 FIRE PENTHOUSE WEST SIDE INACCESSIBLE RECHECK NEED TO RECHECK
Bldg-6
OPC
FD-1-268 FIRE IN HALLWAY NEAR ROOM #1632B INACCESSIBLE PASS
Bldg-6
OPC
FD-1-269 FIRE IN HALLWAY NEAR ROOM #1632B INACCESSIBLE PASS
Bldg-6
OPC
FD-1-270 FIRE INSIDE ROOM #1609 INACCESSIBLE PASS
DIFFICULT TO ACCESS - NEEDS LARGER
HATCH DOOR
Bldg-6
OPC
FD-1-271 FIRE
INSIDE OXYGEN TANK STORAGE ROOM
#1542
INACCESSIBLE PASS
DIFFICULT TO ACCESS - NEEDS LARGER
ACCESS DOOR
Bldg-6
OPC
FD-2-257 FIRE ACROSS FROM CAFÉ INACCESSIBLE PASS
Bldg-6
OPC
FD-2-258 FIRE ACROSS FROM CAFÉ INACCESSIBLE PASS
Bldg-6
OPC
FD-2-259 FIRE ACROSS FROM CAFÉ INACCESSIBLE PASS
Bldg-6
OPC
FD-2-260 FIRE ACROSS FROM CAFÉ INACCESSIBLE PASS
Bldg-6
OPC
FD-2-261 FIRE IN HALLWAY OUTSIDE ROOM #2677 INACCESSIBLE PASS NEED 12' LADDER
Bldg-6
OPC
FD-5-101 FIRE 5th FLOOR I.B.S. INACCESSIBLE PASS
Bldg-6
OPC
FD-5-130 FIRE 5th FLOOR I.B.S. INACCESSIBLE PASS
Bldg-6
OPC
FD-5-163 FIRE 5th FLOOR I.B.S. INACCESSIBLE HIGH VELOCITY
AIR HANDLER NEEDS TO BE SLOWED
DOWN TO BE TESTED
Bldg-6
OPC
FD-5-164 FIRE 5th FLOOR I.B.S. INACCESSIBLE HIGH VELOCITY
AIR HANDLER NEEDS TO BE SLOWED
DOWN TO BE TESTED
INACCESSIBLE
VERY DIFFICULT TO ACCESS. SCAFFOLD
REQUIRED TO ACCESS DAMPERS.
Project Title: Repair/Test Fire Dampers Project Number: 630-11-106
REVISED** ALL DAMPERS NOT PASSED
INCLUDES DAMPERS OF ALL TYPES IN WHICH DID NOT PASS INSPECTION
Bldg-6
OPC
FD-5-165 FIRE 5th FLOOR I.B.S. INACCESSIBLE INACCESSIBLE
NEEDS LARGER ACCESS DOOR AND TWO
PEOPLE TO TEST
Bldg-6
OPC
FD-5-182 FIRE 5th FLOOR I.B.S. INACCESSIBLE HIGH VELOCITY
AIR HANDLER NEEDS TO BE SLOWED
DOWN TO BE TESTED
Bldg-6
OPC
FD-5-184 FIRE 5th FLOOR I.B.S. INACCESSIBLE PASS
Bldg-6
OPC
FD-5-228 FIRE 5th FLOOR I.B.S. INACCESSIBLE PASS
Bldg-6
OPC
FD-5-230 FIRE 5th FLOOR I.B.S. INACCESSIBLE HIGH VELOCITY
AIR HANDLER NEEDS TO BE SLOWED
DOWN TO BE TESTED
Bldg-6
OPC
FD-5-232 FIRE 5th FLOOR I.B.S. INACCESSIBLE PASS
Bldg-1
Main FD-18-028 FIRE ABOVE DOUBLE DOOR NEAR ROOM #18093-S DISABLED DISABLED SCREW IN TRACK. DISABLED.
Bldg-1
Main FD-18-029 FIRE ABOVE DOUBLE DOOR NEAR ROOM #18093-S DISABLED DISABLED SCREW IN TRACK. DISABLED.
Bldg-1
Main FD-18-030 FIRE ABOVE DOUBLE DOOR NEAR ROOM #18093-S DISABLED DISABLED SCREW IN TRACK. DISABLED.
Bldg-1
Main FD-18-031 FIRE ABOVE DOUBLE DOOR NEAR ROOM #18093-S DISABLED DISABLED SCREW IN TRACK. DISABLED.
Bldg-1
Main
FD-18-040 FIRE
ABOVE DOUBLE DOOR NORTH WING AIDS
RESEARCH
DISABLED DISABLED SCREW IN TRACK. DISABLED.
Bldg-1
Main
FD-18-041 FIRE
ABOVE DOUBLE DOOR NORTH WING AIDS
RESEARCH
DISABLED DISABLED SCREW IN TRACK. DISABLED.
Bldg-6
OPC
FD-5-221 FIRE
INSIDE MECHANICAL ROOM NEAR EXIT
DOOR
DISABLED DISABLED SCREW IN TRACK. DISABLED.
Bldg-6
OPC
FD-5-236 FIRE 5th FLOOR I.B.S. DISABLED DISABLED SCREW IN TRACK. DISABLED.
Bldg-1
Main FSD-5-312 COMBINATION INSIDE WEST MECHANICAL ROOM FAIL FAIL BROKEN ACTUATOR NEEDS TOBE REPLACED
Bldg-1
Main FD-10-076A FIRE ABOVE FIRE EQUIPMENT CLOSET 10134-N FAIL P.I.R. PATIENT IN ROOM 10134N NEED TO SCHEDULE
Bldg-1
Main
FD-12-073 FIRE INSIDE ROOM #12130-N FAIL PASS DAMPER FIXED
Bldg-1
Main
SD-18-032 SMOKE
INSIDE NORTH 18th FLOOR MECHANICAL
ROOM
FAIL NO AIR TO ACTUATOR, AIR LINE BROKEN
Bldg-1
Main
SD-18-033 SMOKE
INSIDE NORTH 18th FLOOR MECHANICAL
ROOM
FAIL INOPERABLE ACTUATOR, ARM BROKEN
Bldg-1
Main
SD-18-035 SMOKE
INSIDE NORTH 18th FLOOR MECHANICAL
ROOM
FAIL INOPERABLE ACTUATOR, ARM BROKEN
Bldg-1
Main
FSD-18-044 COMBINATION INSIDE ROOM #18063-S FAIL NO POWER TO ACTUATOR
Bldg-1
Main
FSD-18-045 COMBINATION INSIDE ROOM #18063-S FAIL NO POWER TO ACTUATOR
Bldg-1
Main SD-19-005 SMOKE 19th FLOOR MECHANICAL ROOM FAIL NO POWER TO ACUTATOR
Bldg-1
Main
SD-19-006 SMOKE INSIDE AHU#11 FAIL NO POWER TO ACUTATOR
Bldg-1
Main
SD-19-007 SMOKE INSIDE AHU#11 FAIL NO POWER TO ACUTATOR
Bldg-1
Main
SD-19-008 SMOKE INSIDE AHU#11 FAIL NO POWER TO ACUTATOR
Bldg-1
Main
SD-19-009 SMOKE INSIDE AHU#12 FAIL NO POWER TO ACUTATOR
Bldg-1
Main
SD-19-015 SMOKE INSIDE AHU#12 FAIL NO POWER TO ACUTATOR
Bldg-1
Main
SD-19-016 SMOKE INSIDE AHU#12 FAIL NO POWER TO ACUTATOR
Bldg-1
Main
SD-19-018 SMOKE INSIDE AHU#13 FAIL NO POWER TO ACUTATOR
Bldg-1
Main
SD-19-019 SMOKE INSIDE AHU#13 FAIL NO POWER TO ACUTATOR
Bldg-1
Main SD-19-021 SMOKE ROOF ON FRONT WEST SIDE FAIL NOT REQ. DUCT NOT IN USE - NOT REQUIRED
Bldg-6
OPC
FD-5-096 FIRE 5th FLOOR I.B.S. FAIL
DAMPER BROKEN, BOUND IN
TRACKS(RACKING), BROKEN SPRINGS
Bldg-1
Main
FD-11-074 FIRE ABOVE FIRE EQUIPMENT CLOSET #11128-N CONSTR. AREA CONST. AREA
INSIDE CONSTRUCTION AREA - TO BE
COMPLETED BY OTHERS
Bldg-1
Main
FD-11-075 FIRE INSIDE STORAGE ROOM #11130-N CONSTR. AREA CONST. AREA
INSIDE CONSTRUCTION AREA - TO BE
COMPLETED BY OTHERS
Bldg-1
Main
FD-18-042 FIRE
ABOVE DOUBLE DOOR NORTH WING AIDS
RESEARCH
CONSTR. AREA CONST. AREA
INSIDE CONSTRUCTION AREA - TO BE
COMPLETED BY OTHERS
Bldg-1
Main
FD-18-043 FIRE
ABOVE DOUBLE DOOR NORTH WING AIDS
RESEARCH
CONSTR. AREA CONST. AREA
INSIDE CONSTRUCTION AREA - TO BE
COMPLETED BY OTHERS
Bldg-1
Main
FD-1-334 FIRE INSIDE DAY CARE OFFICE NOT REQUIRED NOT REQ.
NO DAMPER DUE TO MODIFICATION OF
DUCTLESS SPLIT
Bldg-6
OPC
FD-G-277 FIRE INSIDE S.P.O. NOT FOUND NOT FOUND NO DAMPER FOUND
Bldg-6
OPC
FD-G-278 FIRE IN CORRIDOR OUTSIDE OUTPATIENT A.B.C. NOT FOUND NOT FOUND NO DAMPER FOUND
Bldg-6
OPC
FD-2-263 FIRE INSIDE LAUNDRY CHUTE NOT FOUND RECHECK NEED TO RECHECK
Bldg-6
OPC
FD-5-129 FIRE 5th FLOOR I.B.S. NOT FOUND RECHECK NEED TO RECHECK
Bldg-6
OPC
FD-5-162 FIRE 5th FLOOR I.B.S. NOT FOUND RECHECK NEED TO RECHECK
IN CONSTRUCTION AREA
NOT REQUIRED
NOT FOUND
FAILED
DISABLED
DAMPER STATUS BEFORE 06/24
INACCESSIBLE 39 PASSED 21
INACCESSIBLE 17
IN CONSTR. AREA (INCLUDED IN
CONST. AREA TOTAL BELOW)
HIGH VELOCITY 12
P.I.R. 2
RECHECK 2
NEEDS LARGER ACCESS DOOR 1
FAILED 19 PASSED 1
FAILED 17
NOT REQ. (INCLUDED IN NOT REQ.
TOTAL BELOW)
BROKEN DAMPER 1
PROBLEM WITH ACTUATOR 16
IN CONSTR. AREA 4 5
NOT REQ. 1 2
NOT FOUND 5 5
DISABLED 8 8
TOTAL NOT PASSED 76 54
FAILED DAMPERS - BREAKDOWN
AFTER 06/24
DAMPER REPORT SUMMARY 07/01/14
INACCESSIBLE DAMPERS - BREAKDOWN