TO 31S1-2FYN1-6WC-1
WORK CARDS
SCHEDULED MAINTENANCE
FOR
GLOBAL POSITIONING SYSTEM
INFORMATION NETWORK (GIN)
AN/FYN-1
Space and Missile Systems Center, Global Positioning System Wing/OSG
2SC0491
DISTRIBUTION STATEMENT - E - Distribution authorized to DoD Components only for Administrative or Operational Use, (1 May 2011). Other requests shall be referred to SMC_SLG/GPL - TOMA, 1050 East Stewart Avenue, Peterson AFB, CO 80914-2102.
WARNING - This Document contains technical data whose export is restricted by the Arms Export Control Act (Title 22, USC, Sec 2751et.seq.) or the Export Administration Act of 1979, as amended (Title 50, USC, App 2401et.seq.). Violations of these export laws are subject to severe criminal penalties.
Disseminate in accordance with provisions of DoD Directive 5230.25.
HANDLING AND DESTRUCTION NOTICE - Handle in compliance with the Distribution Statement and destroy by any method that will prevent disclosure of the contents or reconstruction of the document.
Published under authority of the Secretary of the Air Force
1 MAY 2011
LIST OF EFFECTIVE CARDS INSERT LATEST CHANGED CARDS. DESTROY SUPERSEDED CARDS.
NOTE The portion of the text affected by the changes is indicated by a vertical line in the outer margins of the card. Changes to illustrations are indicated by shaded or screened areas, or by miniature pointing hands.
Dates of issue for original and changed cards are:
Original . . . . . . . . . . . . . . . . . . .0 . . . . . . . . . . . . . . . . . . . . . . .1 MAY 2011
TOTAL NO OF CARDS IN THIS PUBLICATION IS 13 CONSISTING OF THE FOLLOWING:
Card *Change Card *Change Card *Change No. No. No. No. No. No.
Title A i - vi A-001 - A-002 B-001 - B-004
*Zero in this column indicates an original card
A USAF
PUBLICATION NUMBER
INSPECTION REQUIREMENTS
TABLE OF CONTENTS
FIGURE CHANGE NO CARD NO.
i
TABLE OF CONTENTS
Section Card
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
SAFETY SUMMARY, GENERAL SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
SAFETY SUMMARY, WARNINGS, CAUTIONS AND NOTES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv
SAFETY SUMMARY, ELECTRICAL POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv
INSPECTION
7-DAY INSPECTION, GIN EQUIPMENT RACK (MCS: 3A69) (AMCS: 3A69) . . . . . . . . . . . . . . . . . . . . . . A-001
7-DAY INSPECTION, GIN WORKSTATIONS (MCS: GPSOC-01 - GPSOC-04, GPSOC-06 - GPSOC-10, GPSOC-12 - GPSOC-15) (AMCS: BGPSOC-01 - BGPSOC-03) . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-002
SERVICING
28-DAY SERVICING, GIN EQUIPMENT RACK (MCS: 3A69) (AMCS: 3A69) . . . . . . . . . . . . . . . . . . . . . . B-001
28-DAY SERVICING, GIN WORKSTATIONS (MCS: GPSOC-01 - GPSOC-04, GPSOC-06 - GPSOC-10, GPSOC-12 - GPSOC-15) (AMCS: BGPSOC-01 - BGPSOC-03) . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-002
84-DAY SERVICING, TAPE DRIVE CLEANING (MCS: 3A69A1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-004
INSPECTION REQUIREMENTS
TABLE OF CONTENTS
FIGURE CHANGE NO CARD NO.
i
INSPECTION REQUIREMENTS
INTRODUCTION
FIGURE CHANGE NO CARD NO.
ii
INTRODUCTION
1. THIS WORK CARD IS A STEP-BY-STEP GUIDE IN ABBREVIATED FORM FOR USE AS A REFERENCE TO ENSURE ACCOMPLISHMENT OF SELECTED TASKS BY A PREDETERMINED SEQUENCE PROCEDURE. THE INTENT OF THIS WORK CARD IS TO ELIMINATE THE PROBABILITY OF OMISSION OF A STEP IN THE ACCOMPLISHMENT OF THE INTENDED TASK. THE PROCEDURES CONTAINED HERE IN ARE PRESENTED IN THE SHORTEST PRACTICAL FORM FOR USE BY QUALIFIED PERSONNEL AND ARE NOT INTENDED TO PROVIDE FULL TECHNICAL INSTRUCTIONS. THIS WORK CARD PROVIDES, IN AN ABBREVIATED FORM, PROCEDURES FOR APPROPRIATE TASKS, INSPECTIONS, ETC. THESE PROCEDURES ARE DERIVED FROM, BUT DO NOT REPLACE, THE DETAILED PROCEDURES CONTAINED IN TECHNICAL ORDERS (TOs). WHENMALFUNCTIONS OCCUR REFERENCE TO THE TO SHALL BE MADE.
2. CHANGES AND REVISIONS TO THESE WORK CARDS WILL BE PUBLISHED WHEN NECESSARY TO ADD, DELETE, REVISE, OR CHANGE REQUIREMENTS. SUCH CHANGES AND REVISIONS WILL BE BASED ON FACTUAL DATA AS A RESULT OF EXPERIENCE WITH EQUIPMENT. DATA WILL BE GATHERED THROUGH AFI 21-116 DATA, FIELD EVALUATION, UNSATISFACTORY REPORTS, AND OTHER FACTUAL/FAILURE DATA.
3. FOR ALL OUT OF SERVICE WORK CARDS, COORDINATE SERVICING TASK WITH JOB CONTROL. FAILURE TO DO SO CAN RESULT
IN LOSS OF MISSION EFFECTIVENESS.
4. RECOMMENDED CHANGES TO THIS SET OF WORK CARDS SHALL BE SUBMITTED ON AFTO FORM 22, THROUGH COMMAND
HEADQUARTERS, IN ACCORDANCE WITH TO 00-5-1.
5. WORK CARDS CONTAINING STEPS REQUIRING THE USE OF ELECTRICAL POWER FOR ACCOMPLISHMENT CAN BE IDENTIFIED BY
THE HEADER DEMARCATION IN THE ELECTRICAL POWER FIELD AS ON OR OFF.
INSPECTION REQUIREMENTS
INTRODUCTION
FIGURE CHANGE NO CARD NO.
ii
6. THEGLOBAL POSITIONING SYSTEM INFORMATIONNETWORK (GIN) EQUIPMENT IS DIVIDED INTO FOURWORKAREAS AS FOLLOWS:
• WORK AREA 1 - GIN EQUIPMENT RACK (3A69) LOCATED IN BUILDING 400, MOD 17A, ROOM 1, SCHRIEVER AFB, CO.
• WORK AREA 2 - GIN WORKSTATIONS (GPSOC-01 - GPSOC-04, GPSOC-06 - GPSOC-10, GPSOC-12 - GPSOC-015) LOCATED IN
BUILDING 400, MOD 11B, ROOM 1, SCHRIEVER AFB, CO.
• WORK AREA 3 - GIN EQUIPMENT RACK (3A69) LOCATED IN BUILDING 23229, ROOM 32, VANDENBERG AFB, CA.
• WORK AREA 4 - GIN WORKSTATIONS (BGPSOC-01 - BGPSOC-03) LOCATED IN BUILDING 23229, ROOM 34, VANDENBERG
AFB, CA.
INSPECTION REQUIREMENTS
SAFETY SUMMARY
FIGURE CHANGE NO CARD NO.
iii
1. GENERAL SAFETY INSTRUCTIONS.
THE FOLLOWING GENERAL SAFETY PRECAUTIONS ARE NOT RELATED TO ANY SPECIFIC PROCEDURE AND THEREFORE DO NOT APPEAR ELSEWHERE IN THIS PUBLICATION. THESE ARE RECOMMENDED PRECAUTIONS THAT PERSONNEL MUST UNDERSTAND AND
APPLY DURING ANY PHASE OF OPERATION AND MAINTENANCE.
1.1. KEEP AWAY FROM LIVE CIRCUITS. OPERATING PERSONNEL MUST AT ALL TIMES OBSERVE ALL SAFETY REGULATIONS. DO NOT REPLACE COMPONENTS WITH THE AC POWER TURNED ON. UNDER CERTAIN CONDITIONS, DANGEROUS POTENTIALS DUE TO CHARGES RETAINED BY CAPACITORS MAY STILL EXIST WHEN THE POWER CONTROL IS SET TO THE OFF POSITION. TO AVOID SEVERE SHOCK OR INJURIES, ALWAYS REMOVE POWER AND DISCHARGE A CIRCUIT TO GROUND BEFORE TOUCHING IT.
1.3. DO NOT SERVICE OR ADJUST ALONE. UNDER NO CIRCUMSTANCES SHOULD ANY PERSON REACH INTO OR ENTER THE ENCLOSURE FOR THE PURPOSE OF SERVICING OR ADJUSTING THE EQUIPMENT, EXCEPT IN THE
PRESENCE OF SOMEONE WHO IS CAPABLE OF RENDERING AID.
1.4. RESUSCITATION. PERSONNEL WORKING WITH OR NEAR HIGH VOLTAGES SHOULD BE FAMILIAR WITH MODERN METHODS OF RESUSCITATION. CARDIOPULMONARY RESUSCITATION PROCEDURES ARE PROVIDED IN TO 31-1-141-1 AND ANNUAL REFRESHER TRAINING REQUIREMENTS ARE OUTLINED IN AIR FORCE OCCUPATIONAL SAFETY AND HEALTH (AFOSH) STANDARD (STD 91-50). OTHER INFORMATION MAY BE OBTAINED FROM BASE MEDICAL SERVICES.
INSPECTION REQUIREMENTS
SAFETY SUMMARY
FIGURE CHANGE NO CARD NO.
iii
1.5. ELECTROSTATIC SENSITIVE DEVICES. IF A CIRCUIT CARD CONTAINS A PART IDENTIFIED AS AN ESD ITEM, APPLICABLE PRECAUTIONS WILL APPEAR IN THIS PUBLICATION. ALL ELECTROSTATICALLY SENSITIVE DEVICES WILL BE MARKED WITH THE SYMBOL . WHEN AN ENTIRE PARAGRAPH, INCLUDING ALL SUBPARAGRAPHS, IS CONSIDERED ESD CRITICAL, THE SYMBOL WILL BE PLACED BETWEEN THE STEP NUMBER AND TITLE. WHEN ALL SUBORDINATE PARAGRAPH AND STEPS ARE NOT RELATED TO HANDLING MAINTENANCE, WHICH COULD DAMAGE ESD PARTS, ONLY THOSE RELATED, WILL BE
ANNOTATED. THE FOLLOWING CAUTION WILL IMMEDIATELY PRECEDE ESD PROCEDURES/STEPS:
INSPECTION REQUIREMENTS
SAFETY SUMMARY
FIGURE CHANGE NO CARD NO.
iv
CAUTION
OBSERVE PRECAUTIONS FOR HANDLING ELECTROSTATIC DISCHARGE SENSITIVE ITEMS. (REFER TO TO 00-25-234)
2. WARNINGS, CAUTIONS AND NOTES.
2.1. DEFINITIONS OF WARNINGS, CAUTIONS, AND NOTES ARE DESCRIBED BELOW.
WARNING
AN OPERATING OR MAINTENANCE PROCEDURE, PRACTICE, CONDITION, STATEMENT, ETC., WHICH, IF NOT
STRICTLY OBSERVED, COULD RESULT IN INJURY TO OR DEATH OF PERSONNEL.
CAUTION
AN OPERATING OR MAINTENANCE PROCEDURE, PRACTICE, CONDITION, STATEMENT, ETC., WHICH, IF NOT STRICTLY OBSERVED, COULD RESULT IN DAMAGE TO, OR DESTRUCTION OF EQUIPMENT OR LOSS OF MISSION EFFECTIVENESS.
NOTE
AN ESSENTIAL OPERATING OR MAINTENANCE PROCEDURE, CONDITION, OR STATEMENT WHICH MUST BE HIGHLIGHTED.
INSPECTION REQUIREMENTS
SAFETY SUMMARY
FIGURE CHANGE NO CARD NO.
iv
3. ELECTRICAL POWER.
3.1. ON. When power is required during the accomplishment of the tasks entered on the card, the word “ON” will be placed in this block.
3.2. OFF. When it is mandatory that power be off during the accomplishment of the tasks entered on the card, the word “OFF” will be placed in this block.
3.3. ON or OFF. When power may be on or off during the accomplishment of the tasks entered on the card, this block will be left blank.
3.4. ON and OFF. When some items require power on but some require it to be off, the words “ON/OFF” will be placed in this block and each power on requirement will be preceded by an “at” (@) symbol in the body of the card.
INSPECTION REQUIREMENTS
WORK AREA DIAGRAM
v
INSPECTION REQUIREMENTS
WORK AREA DIAGRAM
v
INSPECTION REQUIREMENTS
WORK AREA DIAGRAM
vi
INSPECTION REQUIREMENTS
WORK AREA DIAGRAM
vi
CARD NO.
A-001
WORK AREA(S)
1/3
TYPE MECH RQR MECH NO. CARD TIME
01:00
PUBLICATION NUMBER
TO 31S1-2FYN1-6WC-1
CHANGE NO.
MAN
MIN
WORK
AREA
WORK UNIT CODE
SYS SUB 7-DAY INSPECTION
INSPECTION
REQUIREMENTS
ELECTRICAL POWER
ON
SERVICE
IN
FIGURE CARD NO.
A-001
GIN EQUIPMENT RACK (MCS: 3A69) (AMCS: 3A69)
1. PRELIMINARY ACTIONS.
A. REQUIRED EQUIPMENT: NONE.
B. NOTIFY JOB CONTROL THAT THE 7-DAY INSPECTION OF THE EQUIP-
MENT RACK IS ABOUT TO BEGIN.
060 1/3 CA A00 2. EQUIPMENT RACK CLEANLINESS AND AIRFLOW CHECKS.
A. CHECK EXTERIOR OF RACK FOR GENERAL CLEANLINESS.
B. OPEN FRONT AND REAR DOORS OF RACK AND CHECK INTERIORS FOR
CLEANLINESS, DAMAGE, EVIDENCE OF OVERHEATING, AND CORROSION. ENSURE
SIGNAL AND POWER CABLES ARE SECURED.
C. CHECK THAT SIGNAL AND POWER CABLES ARE SECURED.
D. CHECK FANS ON INSIDE OF BACK DOORS OF RACKS FOR DIRT AND DUST.
E. CHECK RACK CABLING AND WIRING FOR DAMAGE, CHAFING, AND WEAR.
3. NOTIFY JOB CONTROL THAT THE 7-DAY INSPECTION OF THE EQUIPMENT RACK IS COMPLETED.
(REVERSE BLANK)
CARD NO.
A-001
WORK AREA(S)
1/3
TYPE MECH RQR MECH NO. CARD TIME
01:00
PUBLICATION NUMBER
CHANGE NO.
INSPECTION REQUIREMENTS
7-DAY INSPECTION
A-001
A-002
WORK AREA(S)
2/4
TYPE MECH RQR MECH NO. CARD TIME
00:30
PUBLICATION NUMBER
TO 31S1-2FYN1-6WC-1
CHANGE NO.
MAN
MIN
WORK
AREA
WORK UNIT CODE
SYS SUB 7-DAY INSPECTION
INSPECTION
REQUIREMENTS
ELECTRICAL POWER
ON
SERVICE
IN
FIGURE CARD NO.
A-002
GIN WORKSTATIONS (MCS: GPSOC-01 - GPSOC-04, GPSOC-06 - GPSOC-10,
GPSOC-12 - GPSOC-15) (AMCS: BGPSOC-01 - BGPSOC-03)
1. PRELIMINARY ACTIONS.
A. REQUIRED EQUIPMENT: NONE.
B. NOTIFY JOB CONTROL THAT THE 7-DAY INSPECTION OF THE WORK-
STATIONS IS ABOUT TO BEGIN.
030 2/4 CW
CW
A00 B00
2. CHECK WORKSTATION COMPUTERS, MONITORS AND KEYBOARDS FOR EXTERNAL
CLEANLINESS, DAMAGE, AND EVIDENCE OF OVERHEATING.
3. NOTIFY JOB CONTROL THAT THE 7-DAY INSPECTION OF THE WORKSTATIONS IS COMPLETED.
(REVERSE BLANK)
CARD NO.
A-002
WORK AREA(S)
2/4
TYPE MECH RQR MECH NO. CARD TIME
00:30
PUBLICATION NUMBER
INSPECTION REQUIREMENTS
7-DAY INSPECTION
A-002
B-001
WORK AREA(S)
1/3
TYPE MECH RQR MECH NO. CARD TIME
01:30
PUBLICATION NUMBER
TO 31S1-2FYN1-6WC-1
CHANGE NO.
MAN
MIN
WORK
AREA
WORK UNIT CODE
SYS SUB 28-DAY SERVICING
INSPECTION
REQUIREMENTS
ELECTRICAL POWER
OFF
SERVICE
OUT
FIGURE CARD NO.
B-001
GIN EQUIPMENT RACK (MCS: 3A69) (AMCS: 3A69)
1. PRELIMINARY ACTIONS.
A. REQUIRED EQUIPMENT:
• ANTISTATIC VACUUM CLEANER
• LINT-FREE CLOTHS
• GENERAL PURPOSE CLEANER
B. NOTIFY JOB CONTROL THAT THE 28-DAY SERVICING OF THE EQUIP-
MENT RACK IS ABOUT TO BEGIN.
090 1/3 CA A00 2. CLEAN EQUIPMENT RACK.
WARNING
ENSURE THE SERVICING CLOTH IS ONLY DAMP. CLEANER MUST NOT RUN
FROM THE CLOTH WHILE WIPING EQUIPMENT. EXCESSIVE MOISTURE WILL
CAUSE ARCING AND SHORTING OF POWER. CLEANING CLOTHS SHALL
BE DISPOSED OF IN PROPER CONTAINER.
A. WIPE OUTSIDE SURFACES OF RACK ASSEMBLY WITH DAMP CLOTH.
B. OPEN REAR DOOR OF RACK.
(CONTINUED ON BACK)
CARD NO.
B-001
WORK AREA(S)
1/3
TYPE MECH RQR MECH NO. CARD TIME
01:30
PUBLICATION NUMBER
MAN
MIN
WORK
AREA
WORK UNIT CODE
SYS SUB 28-DAY SERVICING
INSPECTION
REQUIREMENTS
ELECTRICAL POWER
OFF
SERVICE
OUT
FIGURE CARD NO.
B-001
(CONTINUED FROM FRONT)
C. VACUUM DUST AND DEBRIS FROM REAR OF EQUIPMENT.
D. WIPE DOWN OUTSIDE OF ALL COMPONENTS WITH DAMP CLOTH.
E. VACUUM ANY AIR VENTS ON COMPONENTS IN EQUIPMENT RACK.
F. VACUUM ALL FANS AND GUARDS ON INSIDE OF EQUIPMENT RACK BACK DOOR.
(1) VACUUM ALL FANS AND GUARDS ON OUTSIDE OF EQUIPMENT RACK BACK DOOR.
(2) CLOSE REAR DOOR OF RACK BEING CAREFUL NOT TO PINCH CABLES.
(3) CLOSE FRONT DOORS OF RACK.
3. NOTIFY JOB CONTROL THAT THE 28-DAY SERVICING OF THE EQUIPMENT RACK IS COMPLETED.
B-002
WORK AREA(S)
2/4
TYPE MECH RQR MECH NO. CARD TIME
00:45
PUBLICATION NUMBER
TO 31S1-2FYN1-6WC-1
CHANGE NO.
MAN
MIN
WORK
AREA
WORK UNIT CODE
SYS SUB 28-DAY SERVICING
INSPECTION
REQUIREMENTS
ELECTRICAL POWER
OFF
SERVICE
OUT
FIGURE CARD NO.
B-002
GIN WORKSTATIONS (MCS: GPSOC-01 - GPSOC-04, GPSOC-06 - GPSOC-10,
GPSOC-12 - GPSOC-15) (AMCS: BGPSOC-01 - BGPSOC-03)
1. PRELIMINARY ACTIONS.
A. REQUIRED EQUIPMENT:
• ANTISTATIC VACUUM CLEANER
• LINT-FREE CLOTHS
• GENERAL PURPOSE CLEANER
B. NOTIFY JOB CONTROL THAT THE 28-DAY SERVICING OF THE WORK-
STATIONS IS ABOUT TO BEGIN.
005 2/4 CW AD0 2. CLEAN THE MOUSE.
WARNING
ENSURE THE SERVICING CLOTH IS ONLY DAMP. CLEANER MUST NOT RUN
FROM THE CLOTH WHILE WIPING EQUIPMENT. EXCESSIVE MOISTURE WILL
CAUSE ARCING AND SHORTING OF POWER. CLEANING CLOTHS SHALL
BE DISPOSED OF IN PROPER CONTAINER.
CW BD0 A. DAMPEN A LINT-FREE CLOTH WITH GENERAL PURPOSE CLEANER.
(CONTINUED ON BACK)
CARD NO.
B-002
WORK AREA(S)
2/4
TYPE MECH RQR MECH NO. CARD TIME
00:45
PUBLICATION NUMBER
MAN
MIN
WORK
AREA
WORK UNIT CODE
SYS SUB 28-DAY SERVICING
INSPECTION
REQUIREMENTS
ELECTRICAL POWER
OFF
SERVICE
OUT
FIGURE CARD NO.
B-002
(CONTINUED FROM FRONT)
B. WIPE DOWN EXTERIOR SURFACES OF MOUSE.
010 2/4 CW AB0 3. CLEAN MONITOR.
CW BB0 A. ENSURE POWER IS OFF BY DEPRESSING THE POWER BUTTON ON THE
FRONT OF THE LCD MONITOR.
WARNING
ENSURE THE SERVICING CLOTH IS ONLY DAMP. CLEANER MUST NOT RUN
FROM THE CLOTH WHILE WIPING EQUIPMENT. EXCESSIVE MOISTURE WILL
CAUSE ARCING AND SHORTING OF POWER. CLEANING CLOTHS SHALL
BE DISPOSED OF IN PROPER CONTAINER.
B. DAMPEN A LINT-FREE CLOTH WITH GENERAL PURPOSE CLEANER.
C. WIPE DOWN SCREEN FIRST.
D. WIPE DOWN EXTERIOR SURFACES OF MONITOR.
E. RETURN POWER TO THE MONITOR.
010 2/4 CW AE0 4. CLEAN KEYBOARD.
CW BE0 A. VACUUM DUST AND DEBRIS FROM KEYS.
B. DAMPEN A LINT-FREE CLOTH WITH GENERAL PURPOSE CLEANER.
C. WIPE DOWN KEY BOARD AND REMOVE ALL STAINS.
010 2/4 CW AA0 5. CLEAN COMPUTER.
CW BA0 A. VACUUM DUST AND DEBRIS FROM AIR INTAKES ON COMPUTER.
B. DAMPEN A LINT-FREE CLOTH WITH GENERAL PURPOSE CLEANER.
(CONTINUED ON NEXT CARD)
B-003
WORK AREA(S)
2/4
TYPE MECH RQR MECH NO. CARD TIME
00:45
PUBLICATION NUMBER
TO 31S1-2FYN1-6WC-1
CHANGE NO.
MAN
MIN
WORK
AREA
WORK UNIT CODE
SYS SUB 28-DAY SERVICING
INSPECTION
REQUIREMENTS
ELECTRICAL POWER
OFF
SERVICE
OUT
FIGURE CARD NO.
B-003
(CONTINUED FROM PREVIOUS CARD
C. WIPE DOWN COMPUTER AND REMOVE ALL STAINS.
010 2/4 CW
CW
A00 B00
6. VACUUM DUST AND DEBRIS FROM DESK TOP AND FLOOR AROUND WORKSTATION.
7. REPEAT STEPS 2 THROUGH 6 FOR REMAINING WORKSTATIONS.
8. NOTIFY JOB CONTROL THAT THE 28-DAY SERVICING OF THE WORKSTATION IS COMPLETED.
(REVERSE BLANK)
CARD NO.
B-003
WORK AREA(S)
2/4
TYPE MECH RQR MECH NO. CARD TIME
00:45
PUBLICATION NUMBER
INSPECTION REQUIREMENTS
28-DAY SERVICING
B-003
B-004
WORK AREA(S)
TYPE MECH RQR MECH NO. CARD TIME
00:15
PUBLICATION NUMBER
TO 31S1-2FYN1-6WC-1
CHANGE NO.
MAN
MIN
WORK
AREA
WORK UNIT CODE
SYS SUB 84-DAY SERVICING
INSPECTION
REQUIREMENTS
ELECTRICAL POWER
ON
SERVICE
IN
FIGURE CARD NO.
B-004
TAPE DRIVE CLEANING (MCS: 3A69A1)
1. PRELIMINARY ACTIONS.
A. REQUIRED EQUIPMENT:
• UNIVERSAL CLEANING CARTRIDGE
B. NOTIFY JOB CONTROL THAT THE 84-DAY SERVICING OF THE TAPE DRIVE IS ABOUT TO BEGIN.
015 1 CA AA0 2. CLEAN TAPE DRIVE.
CAUTION
CLEANING CARTRIDGE IS GOOD FOR 50 CLEANINGS. IF ERROR CODE 7 IS
DISPLAYED ON TAPE DRIVE, REPLACE CARTRIDGE WITH A NEW CARTRIDGE
FAILURE TO COMPLY MAY DAMAGE TAPE DRIVE.
A. INSERT A CLEANING CARTRIDGE INTO THE TAPE DRIVE. THE TAPE DRIVE
PERFORMS THE CLEANING AUTOMATICALLY.
B. TAPE DRIVE EJECTS THE CARTRIDGE WHEN CLEANING IS FINISHED.
C. REMOVE CLEANING CARTRIDGE FROM THE TAPE DRIVE.
3. NOTIFY JOB CONTROL THAT THE 84-DAY SERVICING OF THE TAPE DRIVE IS COMPLETED.
(REVERSE BLANK)
CARD NO.
B-004
WORK AREA(S)
TYPE MECH RQR MECH NO. CARD TIME
00:15
PUBLICATION NUMBER
INSPECTION REQUIREMENTS
84-DAY SERVICING
B-004
| toc |
| SCHEDULED MAINTENANCE |
| INTRODUCTION |
| 1.GENERAL SAFETY INSTRUCTIONS. |
| 1.1.KEEP AWAY FROM LIVE CIRCUITS. OPERATING PERSONNEL MUST AT AL |
| 1.3.DO NOT SERVICE OR ADJUST ALONE. UNDER NO CIRCUMSTANCES SHOUL |
| 1.4.RESUSCITATION. PERSONNEL WORKING WITH OR NEAR HIGH VOLTAGES |
| 1.5.ELECTROSTATIC SENSITIVE DEVICES. IF A CIRCUIT CARD CONTAINS |
| 2.WARNINGS, CAUTIONS AND NOTES. |
| 2.1.DEFINITIONS OF WARNINGS, CAUTIONS, AND NOTES ARE DESCRIBED B |
| 3.ELECTRICAL POWER. |
| 3.1.ON. When power is required during the accomplishment of the |
| 3.2.OFF. When it is mandatory that power be off during the accom |
| 3.3.ON or OFF. When power may be on or off during the accomplish |
| 3.4.ON and OFF. When some items require power on but some requir |
| GIN EQUIPMENT RACK (MCS: 3A69) (AMCS: 3A69) |
| GIN WORKSTATIONS (MCS: GPSOC-01 - GPSOC-04, GPSOC-06 - GPSOC-10, |
| GIN EQUIPMENT RACK (MCS: 3A69) (AMCS: 3A69) |
| GIN WORKSTATIONS (MCS: GPSOC-01 - GPSOC-04, GPSOC-06 - GPSOC-10, |
| TAPE DRIVE CLEANING (MCS: 3A69A1) |