QuestionsAnswers Set 2_Charleston_01Apr24.pdf
PDF 352 KB Posted
- Attached to
- FA8604 Storage Aids System/JB Charleston, South Carolina MMHS Federal contract opportunity
- Solicitation number
- FA860424RB005
About this file
This document is a set of questions and answers related to Solicitation Number FA8604-24-R-B005 for a Storage Aids System at JB Charleston, South Carolina.
The solicitation is a 100% small business set-aside with a NAICS code of 333922 and a small business size standard of 500 employees. It requires the performance, design, fabrication, installation, and testing of a Storage Aids System for Building 79 at JB Charleston. Key details include the availability of a loading dock, no requirement for PE-stamped drawings except for the fire suppression system, the proximity of electrical panels, and specifications for the pallet scale such as a 5-pound readability and 10,000-pound capacity. The solicitation has 14 line items, and the work must be completed within 300 days of award. Proposals are due by 4:00 PM ET on 19 April 2024, and the evaluation will be based on Lowest Price Technically Acceptable (LPTA).
View the file
Other files for this federal contract opportunity
Show all 34
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FA8604‐24‐R‐B005
JB Charleston, SC Questions/Answers Set 2 Date 01 April 2024
Questions/Answers:
1. Can you please tell us if there is a dock available for unloading or a portable ramp?
Yes, there will be a dock available for unloading.
2. Could you also please verify that PE Stamped drawings are not required? Seismic condi�ons were listed, but we did not see anything about PE Stamped drawings being required.
PE drawings are not required for seismic conditions. However, for the fire suppression system under the mezzanine Appendix E section 3.2.1.12. states that the fire suppression design and hydraulic calculations shall be sealed by a qualified registered Professional Engineer or a R.M.E.
(NICET Level IV) technician.
3. Is there an electrical panel within 100’ of the scale, mezzanine and mobile aisle since all require electricity?
There is an electric panel within 100’ of the scale and mezzanine. The distance has been increased to 200’ for the mobile aisle with anticipated distance around 170’. The location of the electrical room has been added to the drawing. The revised Appendix B (REV 1) and drawing are attached.
4. Pallet Scale for 463L- Is there a 110 volt outlet near where the scale will be placed? If not and we need to run one, how far away is the closest panel?
There will be a 110-volt outlet available in the area of the pallet scale.
5. Pallet Scale for 463L- Does the scale need to be “legal for trade”?
No, the scale does not need to be “legal for trade”. It does need to comply with the certification and calibration requirements in reference Appendix F section 3.2.10.
6. Pallet Scale for 463L- How big is the overhead door shown in the drawing below?
Questions/Answers Set 2 Date 01 April 2024
20’ W x 15’ H
7. Pallet Scale for 463L- Do you want guard on just the long loading side, or the 3 sides not against the wall?
Guards shall be placed on the 3 sides not against the wall. Appendix F section 3.2.10. and the drawing have been revised.
8. Pallet Scale for 463L- What is the total capacity required for the scale and maximum weight of pallet?
Appendix F section 3.2.10.2. states the scale shall have a minimum capacity of 10,000 pounds. Maximum weight of a pallet can be 10,000 pounds.
9. Pallet Scale for 463L- Readability, or grad size - this is how the scale increments. For example on a scale that has a 1 pound readability, you would see every 1 pound applied to the pla�orm. On a scale the has 2 pound readability, you would see every 2 pounds applied to the pla�orm. On a scale the has 5 pound readability, you would see every 5 pounds applied to the pla�orm.
Example:
1 pound readability -- 0,1,2,3,4,5,6,7,8,9,10 etc.
2 pound readability -- 0,2,4,6,8,10 etc.
5 pound readability -- 0,5,10,15 etc.
I would expect at least a 2 pound or 5 pound readability on a scale that size, but wanted to be sure of exactly they're expec�ng.
The scale shall have a 5 pound readability. Appendix F section 3.2.10.1. has been revised.
10. RE: Row spacers in the pallet rack –
3.2.8. appendix A asks for (3) RS per pair of frames – I believe we will only need (3) in the “A” rack (14’ tall) and then (2) in the rest of the configura�ons – am I correct?
Questions/Answers Set 2 Date 01 April 2024
Yes, 3 row spacers for 14’H pallet rack and 2 row spacers for 7’H pallet rack would be acceptable. The revised Appendix A (section 3.2.8.) is attached.
11. Also – in the flue space where we are straddling a building column – do you want row spacers there? If so I can es�mate the length needed.
Row spacers are not required where the pallet rack is straddling the building column.