This document contains a set of Questions and Answers related to Solicitation Number FA8604-24-R-B005 for a Storage Aids System at JB Charleston, South Carolina. The solicitation is a 100% small business set-aside with a NAICS code of 333922 and a size standard of 500 employees.
The key details from the Questions and Answers are:
- Mounting light fixtures for aisle lighting on a single beam at the top of the upright frames on the mobile aisle system is acceptable.
- Dunnage is not required for this project.
- The quantity and configuration of the modular cabinets will be determined at the Post Award Technical Information Meeting (PATIM), with a total of 54 cabinets required as stated in the specifications.
The overall solicitation is for the performance, design, fabrication, installation, and test requirements for a Storage Aids System at Building 79 at JB Charleston, South Carolina. Proposals are due by 4:00 PM ET on 19 April 2024, with a contract completion required within 300 days from date of award. The evaluation will be based on Lowest Price Technically Acceptable (LPTA).
View the file
Other files for this federal contract opportunity
Show all 34
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FA8604‐24‐R‐B005
JB Charleston, SC Questions/Answers Set 1 Date 28 March 2024
Questions/Answers:
1. Wan ng to make sure you are OK with moun ng the light fixtures for the aisle ligh ng on the mobile aisle system(s) on a single beam at the top of the upright frames. This is standard when using pallet rack on a mobile system with aisle ligh ng, but it does reduce OH access on the top level of rack affected.
Yes, a mounting the light fixtures on a single beam at the top of the upright frames on the mobile aisle is acceptable.
2. RE: Dunnage for “463L” pallet rack – App F – 3.2.1. men ons “(3) pieces of dunnage (if applicable)” There are no other dimensional requirements or actual request to provide – is dunnage part of the quote? Or is this GFE?
Dunnage is not required for this project.
3. Ques on on the mini mezz configura ons –
“Modular cabinet detail is showing (2) configura ons – “G” with 8 drawers, and “H” with 6 drawers – both showing OH shelf units.
View A & B are showing the lower-level cabinets W/O shelf units other than the (4) per mezz at the staircases – and both show 9 drawers in the cabinets.
Can you confirm how you are wan ng this laid out? Which cabinets are on the floor, and which are stacked?
3.2.1.5.7. drawer configura on shows a total of 104 type “G” & 34 type “H” – which isn’t making sense either”.
All upper-level cabinets and the two lower-level cabinets at each staircase will have overhead cabinets, hence only 54 cabinets. As stated in Appendix D section 3.2.2. “Placement of modular cabinet types by drawer configuration into the mini-mezzanine systems shall be determined by base personnel at the Post Award Technical Information Meeting (PATIM).” Quantity of modular cabinets required is stated in section 3.2.1.5.7.
The cabinets show in View A are just representa ve, they are not meant to show the actual quan ty of cabinets required, that is listed in the spec.