AMOS_HVAC_Filters.pdf

PDF 95 KB Posted

Attached to
Maui BOS Solicitation Federal contract opportunity
Solicitation number
FA5215-16-R-0002
Issued by
Department of the Air Force Materiel Command Installation and Mission Support Center Installation Contracting Agency

About this file

This document was inadvertently left out in the last amendment. It will help with questions 62 and 70 regarding HVAC filters.

View the file

Other files for this federal contract opportunity

Other files attached to Maui BOS Solicitation, newest first.
File Type Posted
FAR_51.2-_Ktr_use_of_GOVs_Answer_to_83.pdf PDF
Repair_Workload_Data_Answer_to_54_(Fire_Sys).pdf PDF
Amendment_0005.pdf PDF
DET_15_GSA_Vehicle_Fleet_-_Answer_to_80.pdf PDF
Repair_Workload_Data_Answer_to_54_(HVAC).pdf PDF
Repair_Workload_Data_Answer_to_54_(Solar_PV).pdf PDF
Answer_to_Question_31.pdf PDF
WD_2005-2153_Rev_2_(08-11-2016).pdf PDF
Construction_Wage_Rates_(10-14-2016).pdf PDF
Repair_Workload_Data_Answer_to_54_(Access_Ctrl).pdf PDF
Amendment_0004.pdf PDF
FA5215-16-R-0002-0003.pdf PDF
Site_Visit_Address_Confirmation.docx DOCX document
FA5215-16-R-0002-0002.pdf PDF
AMENDMENT_0002.pdf PDF
Attachment_2_-_Price_Schedule.xlsx XLSX spreadsheet
Attachment_6_-_Construction_Wage_Rates.pdf PDF
Attachment_9_-_GFP.pdf PDF
Attachment_10_-_FBO_-_Site_Visit_Registration_Form.pdf PDF
Attachment_3_-_PPQ_Ltr_Questionnaire.pdf PDF
Attachment_5_-_WD_2005-2153_Rev_21.pdf PDF
Attachment_7_-_Clauses_Particular_to_Over_and_Above_CLINS.pdf PDF
Attachment_8_-_CBA.pdf PDF
Attachment_4_-_DD254.pdf PDF
FA5215-16-R-0002-0001_(Maui_BOS)__.pdf PDF
FA5215-16-R-0002_(Maui_BOS).pdf PDF
Attachment_1_-_PWS_Dated_26_July_16_v3_FINAL.pdf PDF
Show all 27

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TSP

IN

HP V/PH/HZ Pleated Filter # Bag Filter # Belt Size # Bottle Type

AHU‐1 Coude Access L‐1 Ceiling

2.5 1.5 460/3/60 20"x20"x2" 2 No AX48 1 No AHUs highlighted in blue require HEPA filters

AHU‐2 Optics RM 1 Assem Area 125 2.5 2.0 460/3/60 20"x20"x2" 2 No AX48 1 No

AHU‐3 Exp. RM 1 L‐2 Ceiling 2.5 5.0 460/3/60 16"x20"x2" 6 No BX35 1 No

AHU‐4 Optics RM 2 L‐1 Ceiling 2.5 2.0 460/3/60 20"x20"x2" 2 No AX48 1 No

AHU‐5 Exp. RM 2 L‐2 Ceiling 2.5 5.0 460/3/60 16"x20"x2" 6 No BX35 1 No

AHU‐6 Optics RM 3 L‐1 Ceiling 2.5 2.0 460/3/60 20"x20"x2" 2 No AX48 1 No

AHU‐7 Exp. RM 3 L‐2 Ceiling 2.5 5.0 460/3/60 16"x20"x2" 6 No BX35 1 No

AHU‐8 Optics RM 4 L‐1 Ceiling 2.5 2.0 460/3/60 20"x20"x2" 2 No AX48 1 No

AHU‐9 Exp. RM 4 L‐2 Ceiling 2.5 5.0 460/3/60 16"x20"x2" 6 No BX35 1 No

AHU‐10 Optics RM 5 L‐1 Ceiling 2.5 2.0 460/3/60 20"x20"x2" 2 No AX48 1 No

AHU‐11 Exp. RM 5 L‐2 Ceiling 2.5 5.0 460/3/60 16"x20"x2" 6 No BX35 1 No

AHU‐12 Optics RM 6 L‐1 Ceiling 2.5 2.0 460/3/60 20"x20"x2" 2 No AX48 1 No

AHU‐13 Exp. RM 6 L‐2 Ceiling 2.5 5.0 460/3/60 16"x20"x2" 6 No BX35 1 No

AHU‐14 Optics RM 7 L‐1 Ceiling 2.5 2.0 460/3/60 20"x20"x2" 2 No AX48 1 No

AHU‐15 Exp. RM 7 L‐2 Ceiling 2.5 1.5 460/3/60 20"x20"x2" 2 No AX48 1 No

AHU‐16 Assembly Area L‐2 Ceiling 2.5 1.5 460/3/60 20"x24"x2" 1 20"x24"x12" 1 AX41 1 No

16"x25"x2" 8 20"x25"x2" 2 20"x25"x2" 2

20"x25"x2" 6

AHU‐26 L‐2 Corridor L‐2 Ceiling 2.5 1.5 460/3/60 20"x24"x2" 1 20"x24"x12" 1 AX41 1 No

AHU‐27 Outside Air L‐1 Ceiling 4.0 3.0 460/3/60 20"x24"x2" 4 20"x24"x12" 4 AX52 1 No

AHU‐28 Outside Air L‐2 Ceiling 2.5 1.5 460/3/60 20"x20"x2" 2 20"x20"x12" 2 AX50 1 No

AHU‐29 DOME L‐3 Ceiling 3.0 10.0 460/3/60 24"x24"x2" 6 24"x24"x12" 6 BX85 1 No

AHU‐30 DOME L‐3 Ceiling 3.0 10.0 460/3/60 24"x24"x2" 6 24"x24"x12" 6 BX85 1 No

AIR HANDLING UNITS (AHU) AEOS

AHU‐24 Rm 220 L‐2 Ceiling 3.0 7.5 460/3/60 No Yes 621

DESIGNATION SERVICE LOCATION

FAN MOTOR 5

Yes 6217.5 460/3/60 NO

2AX59

AX59 2AHU‐25 Rm 220 L‐2 Ceiling 3.0

AHU‐31 DOME L‐3 Ceiling 3.0 10.0 460/3/60 24"x24"x2" 6 24"x24"x12" 6 BX85 1 No

AHU‐32 DOME L‐3 Ceiling 2.5 10.0 460/3/60 24"x24"x2" 6 24"x24"x12" 6 BX85 1 No

AHU‐40 & 41 2 Floor Offices L‐2 Ceiling 2.5 2.0 460/3/60 20"x20"x2" 2 20"x20"x12" 2 AX52 1 No

AHU‐34 L‐1 Corridor L‐1 Ceiling 2.5 1.5 460/3/60 20"x24"x2" 1 20"x24"x12" 1 AX41 1 No

AHU‐35 L‐2 Corridor L‐2 Ceiling 2.5 1.5 460/3/60 20"x24"x2" 1 20"x24"x12" 1 AX42 1 No

20"x24"x12" 1 20"x24"x12" 2 24"x24"x2" 2 24"x24"x12" 1 12"x20"x2" 1 12"x20"x12" 2 12"x24"x2" 2 12"x24"x12" 1

AHU‐37 Machine Shop Machine Shop 2.5 1.5 460/3/60

AHU‐38 Maint. Shop Maint. Shop 2.5 1.5 460/3/60

AHU‐39 Level 1 ELEC. Rm 2.5 1.5 460/3/60 20"x20"x2" 2 20"x20"x12" 2 AX44 1 No AHU‐40 Level 3 Mirror Purge 12"x20"x2" 1 NO No No AHU‐41 Level 2 Offices 16"x20"2" 4 NO AX45 1 No AHU‐42 Level 2 Offices 16"x20"2" 4 NO AX45 1 No AHU‐43 Level 2 Offices 16"x20"2" 2 NO AX6/ 1 No EFU‐1 Level 1 Rm 108 NO 3L390 1 No EFU‐2 Level 1 Rm 101 NO 3VX560 4 No EFU‐3 Level 1 Rm 109 NO AX52 1 No

TSP

IN

HP V/PH/HZ Pleated Filter # Bag Filter # Belt Size # Bottle Type

AHU‐1 RM 40 20"x25"x4" 2 No BX38 2 Yes 202

The units highlighted in orange are in mothballed status; and currently only require an annual startup and operational check.

AHU‐2 RM 40 20"x25"x4" 2 No BX38 2 Yes 202 AHU‐3 RM 40 20"x25"x4" 2 No BX38 2 Yes 202 AHU‐4 RM 71 20"x25"x4" 2 No BX38 2 Yes 202

3rd Floor L‐3 Ceiling 2.5 1 No5.0 460/3/60 BX57

AIR HANDLING UNITS (AHU) MSSS

DESIGNATION SERVICE LOCATION

FAN MOTOR 5

AHU‐36

AHU‐5 RM 44 20"x25"x4" 2 No BX38 2 Yes 202 AHU‐6 RM 25 Men's Bathroom 20"x25"x4" 2 No BX38 2 Yes 202 AHU‐16 RM 70 20"x20"x4" 2 No AX31 1 Yes 204 AHU‐17 RM 66 16"x25"x2" 1 No AX28 1 Yes 204 AHU‐18 RM 67 Pit 20"x20"x4" 2 No AX30 1 No AHU‐19 RM 68 20"x20"x4" 2 No AX30 1 Yes 204

24"x24"x4" 2 12"x24"x4" 1

AHU‐21 RM 69 24"x24"x4" 2 No AX36 1 No AHU ? RM 44 20"x20"x4" 1 No AX39 1 Yes 102

AHU ? RM 44 20"x20"x4" High Eff. 2 No AX39 1 No

AHU ? RM 42 16"x20"x4" High Eff. 2 No AX39 1 Yes 102

AHU RM 27 Clean Room 19"x23"x1" 5 No AX35 2 No SF‐1 RM 42 12"x24"x2" 1 No No No SF‐2 RM 05 12"x24"x2" 1 No No No SF‐3 RM 11 12"x24"x2" 1 No No No FCU‐5 RM 39 Comm Room 9"x34"x1" 1 No No No FCU‐6 RM 72A 20"x20"x2" 1 No AX40 1 Yes 104 EFU‐1 RM 72A No No AX28 1 No EFU‐1 RM 44 No No No No EFU‐4 RM 1D No No No No

TSP

IN

HP V/PH/HZ Pleated Filter # Bag Filter # Belt Size # Bottle Type

AHU‐8 GEODSS Tower 1 24"x24"x2" 1 No BX40 1 Yes 202 AHU‐10 GEODSS Tower 2 24"x24"x2" 1 No BX40 1 Yes 202 AHU‐12 GEODSS Tower 3 24"x24"x2" 1 No BX40 1 Yes 202 AHU‐13 GEODSS RM 115 24"x24"x4" 2 No AX31 1 No

20"x25"x4" 2 16"x25"x4" 2 16"x20"x4" 2 16"x25"x4" 4 16"x20"x4" 2 16"x25"x4" 4 14"x20"x1" 1 20"x20"x1" 2 14"x20"x1" 1 20"x20"x1" 1

AX41 1 NoAHU‐20 RM 18 No

AHU‐14 GEODSS RM 117

AHU‐22 GEODSS RM 119

AIR HANDLING UNITS (AHU) GEODSS

DESIGNATION SERVICE LOCATION

FAN MOTOR 5

FCU‐3 GEODSS RM 122

AHU‐23 GEODSS RM 119

FCU‐2 GEODSS RM 123

No BX45 2 Yes

No BX45 2 Yes 411

No BX38 2 Yes

No No No

No No No

14"x20"x1" 1 20"x20"x1" 1

EFU‐3 GEODSS RM 104 No No No No

TSP

IN

HP V/PH/HZ Pleated Filter # Bag Filter # Belt Size # Bottle Type

18"x18"x2" 1 20"x20"x1" 1 18"x18"x2" 1 20"x20"x1" 1 18"x18"x2" 1 20"x20"x1" 1 18"x18"x2" 1 16"x20"x1" 1

TSP

IN

HP V/PH/HZ Pleated Filter # Bag Filter # Belt Size # Bottle Type

CRU‐2 RM 112 Outside Door 24"x24"x4" 4 No BX42 2 Yes 153310P2 CRU‐1 RM 109 Men's Bath 24"x24"x4" 4 No BX46 2 Yes 153310P2 Vent Make‐up Air 11"x12"x1/2" 1 No No No

Building 550 Lipoa has 2 primary Air Handling Units that require filter changes. Each unit requires 18 filters; 12 each 20x20x2 MERV 7 and 6 20x25x2 MERV 7.

Building 550 Lipoa also has 5 Computer Room Air Handling (CRAH) units. Each CRAH uses 8 filters, Size = 18x24x4 pleated filter, part # 5W518.

FCU‐4 GEODSS RM 121 No No No

VAV TU1‐01 Butler Bldg. RM 107

AIR HANDLING UNITS (AHU) Butler Building

DESIGNATION SERVICE LOCATION

FAN MOTOR 5

Yes 607No No

No NoVAV TU2‐02 Butler Bldg. RM 204 Yes 303

No No

No No

AIR HANDLING UNITS (AHU) RME

DESIGNATION SERVICE LOCATION

FAN MOTOR 5

Yes 303

Yes 303VAV TU2‐03 Butler Bldg. RM 204

VAV TU2‐01 Butler Bldg. RM 204