ACCEPTABLE JAPANESE PRODUCT SUBSTITUTES
Any material systems specified by Japanese standards that are considered acceptable equivalents/substitutes for products based on United States (U.S.) Standards as outlined in the Contract Specifications may be used. The following Tables arranged by discipline, are provided as approved Japanese substitutes. If a substitution is not listed in the tables below, documentation of the Contractor’s proposed Japanese material substitute shall be furnished to the Government for approval. The Contractor shall allow at least 10 working days for Government approval of the proposed substitute.
ARCHITECTURAL SUBSTITUTES
Spec Sect Material Description U.S. Standard Japanese Standard
07 72 00 Roof and Deck Insulation ASTM 728 JIS A 9510
ELECTRICAL SUBSTITUTES
Spec Sect Material Description U.S. Standard Japanese Standard
26 20 00 Interior Distribution System
Disconnect Switch NEMA KS1 JIS C 8201
Switch UL 20 JIS C 8304
3-way Switch UL 20 JIS C 8304
EMT Conduit UL 797 JIS C 8305, Type E
EMT Conduit Couplings UL 514B JIS C 8330
EMT Conduit Elbows UL 6 JIS C 8330
Outlet Boxes Metallic UL 514A JIS C 8336
Outlet Boxes Non-Metallic UL 514C JIS C 8435 Cast Metal Hub Type Boxes UL 886 JIS C 8340
Bonding Conductors, Bare Copper, Solid, Hard Drawn
ASTM B 1 JIS C 3101
Bonding Conductors, Bare Copper, Stranded, Hard Drawn
ASTM B 8 JIS C 3105, Class 1, General Use
600V Insulated Wire, 60 Degree C UL 83 JIS C 3307
600V Insulated Wire, 75 Degree C UL 44 JIS C 3317
600V Insulated Wire, 90 Degree C UL 44 JSC 360
Dry-Type Transformer Station NEMA ST 20 JEC-2200/JEM1310
Cable, NM 60 Degree C UL 719 JIS C 3342
Cable, NM 75 Degree C UL 719 JIS C 3605 Type EV or CE
MECHANICAL SUBSTITUTES
Spec Sect Material Description U.S. Standard Japanese Standard
23 07 00 Thermal Insulation for Mechanical Systems
Aluminum Jackets ASTM B 209M JIS H 4000
Atch. 6 to FA5205-15-R-0008-0003 Dated 17 Jun 15
Pipe Insulation, Mineral Fiber ASTM C 547 JIS A 9504
Duct Insulation, Mineral Fiber ASTM C 553 JIS A 9504
23 05 15 Common Piping for HVAC
Steel Pipe, Black ASTM A 53/A 53M, Sch 40
JIS G 3452/JIS G 3454
JIS B 2301
Copper Tubing ASTM B 88M,Type M
JIS H 3300
Copper and Bronze Fittings ASME B16.22
ASTM B 75M
JIS H 3300/JIS H 3401
Gate Valves, Bronze MSS SP-80 JIS B 2011
Check Valves, Bronze MSS SP-80 JIS B 2011
Ball Valve MSS SP-72 or MSS
SP-110
Manufacturer: Kitz, Toyo Valve or approved equal
Pressure Relief Valve ANSI Z21.22 Manufacturer: Venn, Kaneko Sangyo or approved equal
23 07 00 Thermal Insulation for Mechanical Systems
Aluminum Jackets ASTM B 209M JIS H 4000
Pipe Insulation, Mineral Fiber ASTM C 547 JIS A 9504
Duct Insulation, Mineral Fiber ASTM C 553 JIS A 9504
23 82 02.00
Unitary Heating and Cooling Equipment
Fan Coil Units AHRI 700 Manufacturer: Daikin, Mitsubishi or approved equal