This document is a Preventive Maintenance (PM) inspection report for Constant Current Regulators (CCRs) located at an electrical vault/substation at coordinates 37.079141, -76.355321 in Virginia, dated April 24, 2026. The report documents maintenance and testing activities performed on airfield lighting equipment, specifically CCRs used for runway approach lighting systems.

The inspection covers 27 CCR units across multiple circuits including PAPI (Precision Approach Path Indicator), runway, approach, and taxiway lighting systems. Key maintenance activities completed include CCR calibration, cleaning, local and remote operational testing, and feedback verification. However, output waveforms were not analyzed and hotspot checks were not performed on the units. The inspection identified firmware versions across the units: CCR Firmware 38A.04, ACE Firmware 28A.07, and IRMS Firmware 32A.04 (with some variations). Detailed measurement data in three appendices provide specific current outputs (I-out) at various step levels (B1 through B5/B100), voltage outputs (V-out), and volt-ampere outputs (VA-out) for each CCR unit, including spare units and empty cells. Notes, conclusions, and recommendations are referenced in an accompanying trip report. Several spare units showed zero output readings, indicating they are not currently operational or in inventory.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CCR PMA - Measurements and Data collection

Date 24/04/26 Page 1 / 1

1. Site information

Electrical Vault/substation name Vault 1

Location [{coordinates=37.079141;-76.355321;-32.600002;ellipsoid;42.5, alt=-32.600002, accuracy=42.5, locationPickerIndex=0, lat=37.079141, long=-76.355321, altRefSys=ellipsoid}]

2. CCRs data

CCRs measurements (See Appendix A)

3. CCR PM

CCR Calibrated Yes No

Output waveforms analyzed Yes No

CCR checked for hotspots Yes No

CCR Cleaned Yes No

Local Operational test Yes No

Remote Operational Test Yes No

Feedbacks verified Yes No

4. General Observations

Notes and observations See trip report

Conclusions and recommendations See trip report

Recommended Spare parts See trip report

ADB_Safegate - - - -

Appendix A - CCRs measurements Date 24/04/26 Page 1 / 3

CCR/Circu it Name

Model Serial Number

Number of Steps

B1 I-out B2 I-out B3/B10 I-out

B4/B30 I-out

B5/B100 I-out

B5/B100 V-out

B5/B100 VA-out

CCR

Firmware

ACE

Firmware

IRMS

Firmware

Notes

PAPI 26 PSF6604/

20180508 00013

5 2.8 3.4 4.1 5.2 6.6 330 2100 38A.04 28A.07 32A.04

Runway R2

PSF6630/

20180508 00004

5 2.8 3.4 4.1 5.2 6.6 2300 15000 38A.04 28A.07 32A.04

Approach 26B

PSF6620/

20180508 00008

5 2.8 3.4 4.1 5.2 6.6 2300 15000 38A.04 28A.07 32A.04

Approach 26A

PSF6620/

20180508 00009

5 2.8 3.4 4.1 5.2 6.6 2000 13000 38A.04 28A.07 32A.04

Approach 26C

PSF6620/

20180508 00006

5 2.8 3.4 4.1 5.2 6.6 2000 13000 38A.04 28A.07 32A.04

Approach 26D

PSF6620/

20180508 00007

5 2.8 3.4 4.1 5.2 6.6 2000 13000 38A.04 28A.07 32A.04

TWY A

East, M, D

PSF6607/

20180508 00012

3 4.8 5.5 6.6 0 0 370 2440 38A.04 28A.07 32A.04

TWY E, F PSF6607/

20180606 00199

3 4.8 5.5 6.6 0 0 170 1140 38A.04 28A.07 32A.04

Spare 2 PSF6620/

20180508 00010

3 4.8 5.5 6.6 0 0 0 0 38A.04 28A.07 32A.04

Spare 1 PSF6630/

20180508 00005

5 2.8 3.4 4.1 5.2 6.6 0 0 38A.04 28A.07 32A.04

Runway R1

PSF6630/

20180606 00191

5 2.8 3.4 4.1 5.2 6.6 2500 16300 38A.04 28A.07 32A.04

Appendix B - CCRs measurements Date 24/04/26 Page 2 / 3 it Name

Model Serial Number

Number of Steps

B1 I-out B2 I-out B3/B10 I-out

B4/B30 I-out

B5/B100 I-out

B5/B100 V-out

B5/B100 VA-out

CCR

Firmware

ACE

Firmware

IRMS

Firmware

Notes

PAPI 08 PSF6604/

20180606 00200

5 2.8 3.4 4.1 5.2 6.6 350 2300 38A.04 28A.07 32A.04

Approach 08 A

PSSF6620

/535

20200318 00015

5 2.8 3.4 4.1 5.2 6.6 1800 12200 38A.04 28A.07 32A.04

Approach 08 B

PSF6630/

20180606 00192

5 2.8 3.4 4.1 5.2 6.6 3000 19000 38A.04 28A.07 32A.04

Approach 08 C

PSSF6620

/535

20200318 00014

5 2.8 3.4 4.1 5.2 6.6 2400 16100 38A.04 28A.07 32A.04

Approach 08 D

PSSF6620

/535

20200318 00012

5 2.8 3.4 4.1 5.2 6.6 2000 12900 38A.04 28A.07 32A.04

Taxiway A West, H

PSF6607/

20180522 00921

3 4.8 5.5 6.6 0 0 450 2900 38A.04 28A.07 32A.04

Taxiway B, C

PSF6607/

20180522 00922

3 4.8 5.5 6.6 0 0 200 1400 38A.04 28A.07 32A.04

Taxiway K PSF6607/

20180522 00923

3 4.8 5.5 6.6 0 0 190 1200 38A.04 28A.07 32A.04

Spare 3 NA NA 1 0 0 0 0 0 0 0 38A.04 28A.07 NA Empty Cell

Empty C-

PSF2020/

20180606 00195

5 8.5 10.3 12.4 15.8 20.0 0 0 NA 28A.07 32A.04

Empty C-

PSF2020/

20180606 00193

5 0 0 0 0 0 0 0 38A.04 28A.07 32A.04

Appendix C - CCRs measurements Date 24/04/26 Page 3 / 3 it Name

Model Serial Number

Number of Steps

B1 I-out B2 I-out B3/B10 I-out

B4/B30 I-out

B5/B100 I-out

B5/B100 V-out

B5/B100 VA-out

CCR

Firmware

ACE

Firmware

IRMS

Firmware

Notes

Spare 6 PSF6620/

20180508 00011

3 0 0 0 0 0 0 0 38A.04 28A.07 32A.04

Empty C-

PSF2020/

20180606 00196

5 0 0 0 0 0 0 0 38A.04 28A.07 32A.04

Spare 4 PSF6620/

20180606 00197

3 0 0 0 0 0 0 0 38A.04 28A.07 32A.04

Spare 5 PSSF6620 /535

20200318 00013

5 0 0 0 0 0 0 0 38A.04 28A.07 32A.04

File details come from the government source that posted it. Updated .