Attch 13 LAFB PremisesDistributionSpecs - Revised June10.docx

DOCX document 44 KB Posted

Attached to
Multiple Award Construction Contract (MACC) at Langley AFB/Ft Eustis AB, VA Federal contract opportunity
Solicitation number
FA4800-11-R-0002
Issued by
Department of the Air Force Air Combat Command

About this file

Attachment 13 LAFB Premises Distribution System Specification

View the file

Other files for this federal contract opportunity

Other files attached to Multiple Award Construction Contract (MACC) at Langley AFB/Ft Eustis AB, VA, newest first.
File Type Posted
Attch 23 - 28 31 65 Addressable System.docx DOCX document
Test Hole Locations pdf.zip ZIP file
Attch 17 RFP Amend 03.docx DOCX document
Attch 24 - 28 31 66 Conventional System.docx DOCX document
Amendment 0005.doc DOC document
Attch 25 UFC 1-300-02 Unified Facilities Guide Specs.pdf PDF
QUESTIONS AND ANSWERS 320 -339.docx DOCX document
Attch 22 - 27 10 10 BUILDING TELECOMMUNICATIONS WIRING.docx DOCX document
QUESTIONS AND ANSWERS 1-339.docx DOCX document
BASE-H09125H-01SNew.dwg DWG drawing
LAFB-Plans-35 -Submittal.dwg DWG drawing
Test-Hole-Locations.dwg DWG drawing
LAFB-Plans-35 -Submittal-Cover.dwg DWG drawing
Attch 20 QUESTIONS AND ANSWERS 305 - 319.docx DOCX document
Attch 20 QUESTIONS AND ANSWERS 284-304.docx DOCX document
Test-Hole-Locations.dwg DWG drawing
Bldg 333a.pdf PDF
Bldg 366a.pdf PDF
Bldg 337.pdf PDF
Bldg 325a.pdf PDF
Bldg 338a.pdf PDF
bldg 338b.pdf PDF
Bldg 333.pdf PDF
bldg 366b.pdf PDF
Bldg 366c.pdf PDF
Bldg 337b.pdf PDF
Bldg 325.pdf PDF
Bldg 366f.pdf PDF
Bldg 366e.pdf PDF
Bldg 337a.pdf PDF
Attch 20 Question Answers Cont.docx DOCX document
Attch 17 RFP Amend 02.docx DOCX document
SF 30 Amendment 0004.doc DOC document
Amendment 0002.doc DOC document
AutoCAD 2000.zip ZIP file
Amendment 0001.pdf PDF
Attch 06 Teaming List.doc DOC document
RFP Design Build SoW 06-4088.docx DOCX document
Attch 02 Financial_Information_Request.docx DOCX document
Attch 03 Bonding_Information_Request.docx DOCX document
Attch 08 AF 3064 Progress Sched.xfd —
Attch 07 AF 3052 Construction Cost Estimate.xls XLS spreadsheet
Attch 15 General Provisions for MACC.docx DOCX document
Attch 05 ClientAuthorizationLetter.doc DOC document
FA4800-11-R-0002 MACC Solicitation.doc DOC document
Attch 11 Section 01 12 00.docx DOCX document
Attch 01B PastPeformanceInformationSheet.doc DOC document
Attch 14 Ft Eustis Specific Instructions.docx DOCX document
Attch 10 LAFB 01 06 00 Regulatory Requirements.docx DOCX document
Attch 09 LAFB Section 01 11 00 - 09Aug2010.docx DOCX document
Show all 50

Multiple Award Construction Contract (MACC) at Langley AFB/Ft Eustis AB, VA has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SOLICITATION NO.: FA4800-11-R-0002

ATTACHMENT 13

633d COMM SQUADRON/LAFB

PREMISES DISTRIBUTION SYSTEM SPECIFICATIONS

NOV 2003

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by basic designation only.

ELECTRONIC INDUSTRIES ASSOCIATION (EIA)

EIA ANSI/TIA/EIA-568-b.1(2001) Commercial Building Telecommunications Cabling Standard, Part 1, General Requirements
EIA ANSI/TIA/EIA-568-b.2(2001) Commercial Building Telecommunications Cabling Standard, Part 2, Balanced Twisted-Pair Cabling Components
EIA ANSI/TIA/EIA-568-b.3(2001) Commercial Building Telecommunications Cabling Standard, Part 3, Optical Fiber Cabling Components Standard
EIA ANSI/TIA/EIA-569-A(1998) Commercial Building Standard for Telecommunications Pathways and Spaces
EIA ANSI/TIA/EIA-606(1993) Administration Standard for the Telecommunications Infrastructure of Commercial Buildings
EIA ANSI/TIA/EIA-607(1994) Commercial building Grounding and Bonding Requirements for Telecommunications
EIA TSB 67(1995) Transmission Performance Specifications for Field Testing of Unshielded Twisted Pair Cabling Systems
EIA TSB 75(1996) Additional Horizontal Cabling Practices for Open Offices

INSULATED CABLE ENGINEERS ASSOCIATION (ICEA)

ICEA S-8O-576 (1994) Communications Wire and Cable for Wiring of Premises

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 70 (1999) National Electrical Code

1.2 SYSTEM DESCRIPTION

The premises distribution system shall consist of inside-plant horizontal, riser and backbone cables and connecting hardware to transport telephone and data (Local Area Network) signals between equipment items in a building. This will be a complete system, to include full telecommunication room (TR) wire pathway support from entry into TR and wire management system on equipment racks. This will also include complete grounding/bonding backbone system. Entire premises distribution system will be in accordance with above listed commercial specifications.

1.3 ENVIRONMENTAL REQUIREMENTS

Connecting hardware shall be rated for operation under ambient conditions of 32 to 140 degrees F and in the range of 0 to 95 percent relative humidity, non condensing. The optimal temperature range for each TR shall be 65 – 77 degrees F to support Network accreditation requirements.

1.4 QUALIFICATIONS

1.4.1 Minimum Contractor Qualifications

All work under this section shall be performed by and all equipment shall be furnished and installed by a certified Telecommunications Contractor, hereafter referred to as the Contractor. The Contractor shall have the following qualifications in the Telecommunications Systems installation:

a. Contractor shall have a minimum of 3 years experience in the application, installation and testing of the specified systems and equipment to be installed. Contractor shall have all design proposals certified as compliant with Building Industry Consulting Services International (BICSI) design practices by a Registered Communications Distribution Designer (RCDD).

b. All supervisors assigned to the installation of this system or any of its components shall have a minimum Level 2 Installer certification from BICSI and installers assigned to the installation of this system or any of its components shall have a minimum Level 1 Installer certification from BICSI. All supervisors and installers shall have factory certification from each equipment manufacturer that they are qualified to install and test the provided products. General electrical trade staff (electricians) shall not be used for the installation of the premises distribution system cables and associated hardware unless they are certified BICSI installers.

c. All installers assigned to the installation of this system or any of its components shall have a minimum of 3 years experience in the installation of the specified copper and fiber optic cable and their components.

1.4.2 Minimum Manufacturer Qualifications

The equipment and hardware provided under this contract shall be from manufacturers that have a minimum of 3 years experience in producing the types of systems and equipment specified.

1.5 SUBMITTALS

Government approval is required for submittals. The following shall be submitted to the 633D Communications Squadron (633D CS/SCXP) Plans and Implementation section for review:

1.5.1 Data

1.5.1.1 Spare Parts;

Spare parts, tools, and test equipment provided under this contract shall be submitted to 633D CS/SCXP along with an inventory of these spare parts, tools, and test equipment. The inventory data shall include a complete list of parts and supplies, with current unit prices and source of supply, and a list of spare parts recommended for stocking.

1.5.2 Drawings

1.5.2.1 Premises Distribution System;

Detail drawings, size E drawing format, including a complete list of equipment and material. Detail drawings shall contain complete wiring and schematic diagrams and other details required to demonstrate that the system has been coordinated and will function properly as a system. Drawings shall include vertical riser diagrams, equipment rack details (to include complete wire management support systems in Telecommunications Room), elevation drawings of telecommunications room wall, outlet face plate details for all outlet configurations, size and types of cables, conduits, and cable trays. Drawings shall show proposed layout and anchorage of equipment and appurtenances and equipment relationship to other parts of the work including clearance for maintenance and operation.

1.5.2.2 Record Drawings;

Record drawings for the installed wiring system infrastructure per EIA ANSI/TIA/EIA-606. The drawings shall show the location of all cable terminations and location and routing of all backbone and horizontal cables. The identifier for each termination and cable shall appear on the drawings.

1.5.3 Instructions

1.5.3.1 Manufacturer’s Recommendations;

Where installation procedures, or any part thereof, are required to be in accordance with the recommendations of the manufacturer of the material being installed, printed copies of these recommendations, prior to installation shall be provided. Installation of the item will not be allowed to proceed until the recommendations are received and approved.

1.5.4 Statements

1.5.4.1 Test Plan;

Test plan defining the tests required to ensure that the system meets technical, operational and performance specifications, 60 days prior to the proposed test date. The test plan must be approved before the start of any testing. The test plan shall identify the capabilities and functions to be tested, and include detailed instructions for the setup and execution of each test and procedures for evaluation and documentation of the results.

1.5.4.2 Qualifications;

The qualifications of the Manufacturer, Contractor and the Installer to perform the work specified herein. This shall include proof of the minimum qualifications specified herein.

1.5.5 Reports

1.5.5.1 Test Reports;

Test reports in booklet form with witness signatures verifying execution of tests. Reports shall show the field tests performed to verify compliance with the specified performance criteria. Test reports shall include record of the physical parameters verified during testing. Test reports shall be submitted within 7 days after completion of testing to the 633D Communications Squadron for Quality Assurance Inspection purposes.

1.5.6 Certificates

1.5.6.1 Premises Distribution System;

Written certification that the premises distribution system complies with the EIA ANSI/TIA/EIA-568-b.1,b.2,b.3, EIA ANSI/TIA/EIA-569-A, EIA ANSI/TIA/EIA-606 standards, and EIA ANSI/TIA/EIA-607 standards.

1.5.6.2 Materials and Equipment;

Where materials and equipment are specified to conform, be constructed, or tested to meet specific requirements, certification that the items conform to such requirements must be provided. Certification by a nationally recognized testing laboratory that a representative sample has been tested to meet the requirements, or a published catalog specification statement to the effect that the item meets the referenced standard, will be acceptable as evidence that the item conforms. Compliance with these requirements does not relieve the Contractor from compliance with other requirements of the specification.

1.5.6.3 Installers;

The Contractor shall submit certification to the Contracting Officer (633D CES/LGCB) that all the installers are factory certified to install and test the provided products.

1.5.7 Records

1.5.7.1 Record keeping and Documentation;

Documentation on cables and termination hardware shall be provided in accordance with ANSI TIA/EIA-606.

1.6 DELIVERY AND STORAGE

Equipment delivered and placed in storage shall be stored with protection from the weather, humidity and temperature variation, dirt and dust, or other contamination.

1.7 OPERATION AND MAINTENANCE MANUALS

Commercial off the shelf manuals shall be furnished for operation, installation, configuration, and maintenance for all products provided as a part of the premises distribution system. Specification sheets for all cable, connectors, and other equipment shall be provided.

1.8 RECORD KEEPING AND DOCUMENTATION

1.8.1 Cables

The Contractor shall be responsible for recording and providing, to the Contracting Officer, all test data within 7 days of system final testing. A record of all installed cable shall be provided in hard copy format per ANSI TIA/EIA-606. The cable records shall include the required data fields for each cable and complete end-to-end circuit report for each complete circuit from the assigned outlet to the entry facility per ANSI TIA/EIA-606. For all fiber optic cables, power meter test results shall be provided in a hard copy format. All twisted pair copper cables shall have a disk copy output of the test results with station ID assigned.

1.8.2 Termination Hardware

A record of all installed patch panels and outlets shall be provided in hard copy format per ANSI TIA/EIA-606. The hardware records shall include only the required data fields per ANSI TIA/EIA-606.

PART 2 PRODUCTS

2.1 MATERIALS AND EQUIPMENT

Materials and equipment shall be the standard products of a manufacturer regularly engaged in the manufacture of the products and shall be the manufacturer’s latest standard design that has been in satisfactory use for at least 1 year prior to installation. Materials and equipment shall conform to the respective publications and other requirements specified below and to the applicable requirements of NFPA 70.

2.2 UNSHIELDED TWISTED PAIR CABLE SYSTEM

2.2.1 Cable Insulation

For each individual Category 5e cable, the insulation, material used on each pair shall be exactly the same in all physical, electrical and chemical respects. The use of Teflon insulated plenum rated category 5e cable is required for both plenum and non-plenum environments. Plenum rated cable shall be type 4x0, where all four pairs are Teflon insulated. Type 3x1 and 2x2 are not acceptable.

2.2.2 Riser Cable

Riser cable shall meet the requirements of ICEA S-80-576 and ANSI/TIA/EIA-568-b.1 for Category 3 unshielded twisted pair cable. Cable shall be label-verified. Cable jacket shall be factory marked at regular intervals indicating verifying organization and performance level. Conductors shall be solid untinned copper 24 AWG. Cable shall be rated CMP per NFPA 70.

2.2.3 Horizontal Cable

Horizontal cable shall meet the requirements of EIA ANSI/TIA/EIA-568-b.1 for Category 5e horizontal cable. Cable shall be label-verified. Cable jacket shall be factory marked at regular intervals indicating verifying organization and performance level. Conductors shall be solid untinned copper 24 AWG. Cable shall be 4 pair. Cable shall be rated to support minimum 350 MHz. Cable shall be rated CMP per NFPA 70. All horizontal cables to be installed on any particular installation will be from the same manufacturer. Cable color will be the same throughout the particular facility. The only exception to this will be, if multiple comm. closets are to be installed in a particular facility, these closet distribution cables may be separate colors to differentiate the difference of comm. closet distribution. Recommended colors for distribution cables are white, gray or blue.

2.2.4 Connecting Hardware

Connecting and cross-connecting hardware shall be the same category as the cable it serves, as well as type 110 insulation displacement connection termination. Hardware shall be in accordance with and EIA ANSI/TIA/EIA-568-b.2.

2.2.4.1 Telecommunications Outlets

Wall and desk outlet plates shall come equipped as indicated and be labeled according to the Langley AFB standard labeling scheme. Modular jacks shall be the same category as the cable they terminate and shall meet the requirements of EIA ANSI/TIA/EIA-568-b.2. Modular jack pin/pair configuration shall be T568A per EIA ANSI/TIA/EIA-568-b.1. Termination shall be type 110 insulation displacement connection. Modular jacks shall be unkeyed. Faceplates shall be provided and coincide with the surrounding decor. Outlet assemblies used in the premises distribution system shall consist of modular jacks assembled in a quadra-plex outlet assemblies in single gang covers as indicated on the drawings. The modular jacks shall conform to the requirements of EIA ANSI/TIA/EIA-568-b.2, Category 5e. Outlets will be placed in a flood wire configuration (approx. one outlet every 10 feet) for facility installation/renovation for wall-mounted outlets. In areas where floor mounted boxes are installed, one quad outlet will be provided for each workstation to be placed in the facility. Any deviation from the above configurations requires approval from 633D Communications Squadron, Plans and Programs section (633D CS/SCXP).

2.2.4.2 Patch Panels

Patch panels shall be rated category 5e and not be more than 48 port, shall consist of eight-position modular jacks, with rear mounted type 110 (IDC) insulation displacement connection, arranged in rows on 19 inch rack mounted panels. Jack pin/pair configuration shall be T568A per ANSI/TIA/EIA-568-b1. Jacks shall be unkeyed. Panels shall be labeled in accordance with Langley AFB standard labeling scheme.

2.2.4.3 Patch Cords

Patch cords shall be cable assemblies consisting of flexible, twisted pair wire with eight-position plugs. Cable shall be label-verified. Cable jacket shall be factory marked at regular intervals indicating verifying organization and performance level. Patch cords shall be wired straight through; pin numbers shall be identical at each end and shall be paired to match T568A patch panel jack wiring per EIA ANSI/TIA/EIA-568-b.1. Patch cords shall be category 5e rated, keyed (non-booted) and factory assembled. Two patch cords shall provided for every port: one (1) sixteen foot patch cord (stranded with eight-position plugs at each end and gray in color) used for connectivity from the jack to the device, and one (1) seven foot patch cord (half shall be stranded with eight-position plugs at each end and gray in color; and half shall be solid conductor with an eight-position plug on at least one end and blue in color) used for LAN and Telephone connectivity at the patch panel.

2.2.4.4 Terminal Blocks

Rack mounted: Terminal blocks shall be rack mounted wire termination units consisting of insulation displacement connectors mounted in plastic blocks, frames or housings. Blocks shall be type 110 IDC that meet the requirements of ANSI/TIA/EIA-568-b.2 for category 5e, typically used to terminate backbone cables to equipment racks. Blocks shall include cable management hardware. Insulation displacement connectors shall terminate 22 or 24 AWG solid copper wire as a minimum, and shall be connected in pairs so that horizontal cable and connected jumper wires are on separate connected terminals.

Wall mounted: Terminal blocks shall be wall mounted wire termination units consisting of insulation displacement connectors mounted in plastic blocks, frames or housings. Blocks shall be type 66 split 50 blocks, typically mounted on a communications backboard to allow interface to voice service demarcations. In certain applications, type 110 IDC blocks may be used, meeting the requirements of ANSI/TIA/EIA-568-b.2 for category 5e, and shall be specifically identified by 633D CS/SCMX personnel. Blocks shall include cable management hardware. Insulation displacement connectors shall terminate 22 or 24 AWG solid copper wire as a minimum, and shall be connected in pairs so that horizontal cable and connected jumper wires are on separate connected terminals.

2.3 FIBER OPTIC CABLE SYSTEM

2.3.1 Backbone Cable

2.3.1.1 Multimode

Multimode fiber optic backbone cable shall be run from Main Distribution Frame (MDF) to Intermediate Distribution Frame (IDF) for networking connectivity to government identified demarcation point. Fiber optic backbone cable will meet the requirements of EIA ANSI/TIA/EIA-568-b.1 and ICEA S-83-596 for 12 strand, 62.5/125 micrometer multimode graded index optical fiber cable. Numerical aperture for each fiber shall be a minimum of 0.275. Cable construction shall be tight-buffered type. Individual fibers shall be color coded for identification. Cable shall be imprinted with fiber count and aggregate length at regular intervals. Cable shall be rated OFNP per NFPA 70.

2.3.2 Connecting Hardware

2.3.2.1 Connectors

Connectors shall be ST type for termination for connectivity in patch panels, with ceramic ferrule material with a maximum insertion loss of .5 db. Connectors shall meet performance requirements of EIA ANSI/TIA/EIA-526-14A Connectors shall be field installable. Connectors shall utilize adhesive for fiber attachment to ferrule. Connectors shall terminate fiber sizes as required for service.

2.3.2.2 Patch Panels

Patch panels shall be a complete system of components by a single manufacturer, and shall provide termination, splice storage, routing, radius limiting, cable fastening, storage, and cross-connection. Patch panels shall be 19 inch rack mounted panels. Patch panels shall provide strain relief for cables. Panels shall be labeled per Langley Air Force Base standards. Patch panel connectors and couplers shall be SC type for termination for connectivity in patch panels, with ceramic ferrule material with a maximum insertion loss of .5 db. Connectors shall meet performance requirements of EIA ANSI/TIA/EIA-568-b.3.

2.4 EQUIPMENT RACKS

2.4.1 Floor Mounted Open Frame

Floor mounted equipment racks shall be standard 19-inch aluminum relay racks, uprights shall be 3 inches deep, 1¼ inches wide, drilled and tapped 12-24 in a half inch pattern. Racks shall be provided with a standard top cross member, and predrilled base plate to allow floor fastening. Open frame equipment racks shall be 7 feet in height and clear coated. AC outlets shall be provided in the equipment rack to prevent tripping, one quad outlet dedicated 20 Amp line assembly, per every two equipment racks provided.

2.4.2. Wall Mounted Swing Frame

2.4.3 Cable Management

Cable management shall be specifically manufactured for the purpose of routing cables, wires and patch cords horizontally and vertically on standard 19-inch equipment racks. Cable management shall consist of ring or bracket-like devices mounted on rack panels for front horizontal use or of a type that utilizes duct fingers with snap on covers. Cable management shall mount to racks by screws and/or nuts and lock washers. Cable management shall be provided above, below and to both sides of each patch panel on the standard 19-inch equipment rack(s). Vertical cable management will be provided between and to the ends of equipment racks, and provide front and rear vertical cable management. Vertical Cable management shall be of a type that utilizes duct fingers with snap on covers. Cable management will be provided in the rear of the rack, utilizing duct fingers with snap on cover style, or standoff bars. Velcro ties shall be utilized for binding of horizontal distribution wires within the telecommunications room trays and wire management systems.

2.5 EQUIPMENT MOUNTING BACKBOARD

Plywood backboards, 4 feet by 8 feet by ¾ inch and void free, grade A, shall be provided covering no less than 2 walls, painted with gray colored fire resistive paint.

2.6 TELECOMMUNICATIONS OUTLET BOXES

Electrical boxes for telecommunication outlets shall be 4-11/16 inch square by 2⅛ inches deep with minimum ⅛ inch deep single or two-gang plaster ring as shown in provided design drawings. Provide a minimum 1-inch conduit. All outlet boxes are to receive Quad jack installation.

2.7 TELECOMMUNICATIONS ROOM REQUIREMENTS

Telecommunication rooms must be an appropriate size to accommodate the proposed cable/LAN distribution system and associated connectivity equipment for any given facility and/or facility floor. The minimum size telecommunications room for system installation is 8 foot by 10 foot. This would support a two-equipment rack configured system. If any additional equipment/racks are placed in a comm. room, the comm. room must be enlarged to meet the requirement of having a full 36 inches of space between the communications rack assembly and the nearest wall. The entrance door must swing outward into the hallway, or additional room square footage must be added to the floor space to accommodate interior door swing. Minimum distance of 3’ feet separation from wall shall be maintained. Dedicated Ventilation Air Conditioning (VAC) systems support must be provided for each telecommunications room. Systems must be of an appropriate capacity to self-support the room per proposed equipment installation requirements. VAC systems must not take up any floor space within the comm. room. A dedicated 20 Amp circuit for the use of (VAC) system. Telecommunications room placement preference is towards the center of any given facility. If facility is multiple stories, preference is for stacked telecommunications room placement, facilitating easy interconnectivity between telecommunication rooms.

PART 3 EXECUTION

3.1 INSTALLATION

System components and appurtenances shall be installed in accordance with NFPA 70, manufacturer’s instructions and as shown. Necessary interconnections, services and adjustments required for a complete and operable signal distribution system, from the facility’s government provided outside plant demarcation point, shall be provided. Components shall be labeled in accordance with EIA ANSI/TIA/EIA-606 and Langley AFB standards. Penetrations in fire-rated construction shall be fire stopped in accordance with specifications. Conduits, outlets and raceways shall be installed in accordance with EIA ANSI/TIA/EIA-569-A, Telecommunications Pathways and Spaces. Wiring shall be installed in accordance with EIA ANSI/TIA/EIA-568-b.1, b.2. Wiring, and terminal blocks and outlets shall be marked in accordance with EIA ANSI/TIA/EIA-606. Cables shall not be installed in the same cable tray, utility compartment, or floor trench compartment with AC power cables. Cables not installed in conduit or wire ways shall be properly secured, per industry standard, and neat in appearance and, if installed in plenums or other spaces used for environmental air, shall comply with NFPA 70 requirements for this type of installation. Cable tray installation will be provided for complete wire support within the telecommunications room, from room entrance to overhead rack area, providing complete cable support, when overhead wire installation methods are utilized.

3.1.1 Horizontal Distribution Cable

The rated cable pulling tension shall not be exceeded. Cable shall not be stressed such that twisting, stretching or kinking occurs. Cable shall not be spliced. Cables shall be installed in conduit, cable trays, or other industry approved hanger assemblies as EIA ANSI/TIA/EIA-568-b.2 recommends. Cable shall not be run through structural members or in contact with pipes, ducts, or other potentially damaging items. Placement of cable parallel to power conductors shall be avoided, if possible; a minimum separation of 12 inches shall be maintained when such placement cannot be avoided. Cables shall be terminated; no cable shall contain un-terminated elements. Minimum bending radius shall not be exceeded during installation or once installed. Cable ties shall not be excessively tightened such that the transmission characteristics of the cable are altered. Cable 6 feet long shall be neatly coiled not less than 12 inches in diameter below each feed point in raised floor areas, if applicable.

3.1.2 Riser and Backbone Cable

Vertical cable support intervals shall be in accordance with manufacturers’ recommendations. Cable bend radius shall not be less than ten times the outside diameter of the cable during and after installation. Maximum tensile strength rating of the cable shall not be exceeded. Cable shall not be spliced. Maintenance loop or slack required for modification or re-termination of backbone cabling shall be no less than 3 meters (ten feet), at both ends of termination.

3.1.3 Telecommunication Outlets

3.1.3.1 Faceplates

As a minimum, each jack shall be labeled as to its function and a unique number to identify cable link, as per Langley AFB standard.

3.1.3.2 Cables

Maintenance loop or slack required for modification or re-termination of horizontal cabling shall be no less than 3 meters (ten feet), at the distribution closet and no less than 30 centimeters (24 inches) at the outlet. Slack at the user termination shall not be placed in the outlet box, but shall be installed at the nearest practical point to the outlet box. (I.e. above the ceiling prior to entering the wall).

3.1.3.3 Pull Cords

Pull cords shall be installed in all conduits serving telecommunications outlets, which do not initially have fiber optic cable installed.

3.1.3.4 Outlet Location

Outlet locations, when placed on a fixed wall, shall be located 18” Above Finished Floor (AFF) or at a height equal to existing electrical outlets in the room, when applicable. When placing outlets in a raised floor setting, jacks shall be placed in recessed floor gang boxes that provide appropriate accessibility and protection of outlets.

3.1.4 Terminal Blocks

Terminal blocks shall be mounted on orderly rows and columns. Adequate vertical and horizontal wire routing areas shall be provided between groups of blocks. Industry standard wire routing guides shall be utilized. Rack mounted 110 IDC terminal blocks will be used at the Intermediate Distribution Frame (IDF) point (Patch Panel end) for copper backbone cable cross connects. Wall mounted 66-type terminal blocks shall be utilized at the Main Distribution Frame (MDF) or Demarcation Point for outside plant copper cross connect capability.

3.1.5 Unshielded Twisted Pair Patch Panels

Patch panels shall be mounted in equipment racks with sufficient modular jacks to accommodate the installed cable plant plus 25 percent spares for future expansion. Cable management will be provided above, below, between, and to both sides of each panel, to include the front and rear of rack, and patch Panel assembly.

3.1.6 Fiber Optic Patch Panels

Patch panels shall be mounted in equipment racks with sufficient ports to accommodate the installed cable plant plus 25 percent spares. A slack loop of fiber shall be provided within each panel. Loop shall be 3 feet in length or longer if recommended by the manufacturer. The outer jacket of each cable entering a patch panel shall be secured to the panel to prevent movement of the fibers within the panel, using clamps or brackets specifically manufactured for that purpose. ST type connectors will be utilized for fiber termination.

3.1.7 Equipment Racks

Open frame equipment racks shall be bolted to the floor. Cable management shall be bolted or screwed to racks. Racks shall be installed level, and ganged racks shall be bolted together (with cable management mounted in between racks). Ganged rack cabinets shall have adjacent side panels removed. Open frame equipment racks shall be secured per industry standards to prevent rack from swaying. Wall mounted racks shall be secured to the mounting surface to prevent fully loaded racks from separating from the mounting surface.

3.1.8 Rack Mounted Equipment

Equipment to be rack mounted shall be securely fastened to racks by means of the manufacturers recommended fasteners.

3.2 TERMINATIONS

Cable and conductors shall sweep into termination areas. Cable and conductors shall not bend at right angles. Manufacturers minimum bend radius shall not be exceeded. When there are multiple system type drops to individual workstations, relative position for each system shall be maintained on each system termination block or patch panel. The maximum pulling tensions for 4-pair 24 AWG horizontal UTP cables shall not exceed 25 lbf to avoid stretching the conductors during installation. Cable management precautions shall be observed to include the elimination of cable stress as caused by tension in suspended cable runs and tightly cinched cable bundles. An additional practice that shall be followed to reduce untwisting of pairs, is to strip back only as much cable jacket as required to terminate on connecting hardware. Also, in spaces with UTP terminations, cable bend radius shall not be less than four times the cable diameter for horizontal cable and shall not be less than ten times the cable diameter for multi-pair cable. Care shall be exercised to minimize twisting/kinking of cable during installation. The amount of untwisting in a pair as a result of termination to connecting hardware shall not exceed 0.5 inches for Category 5e cables from IDC.

3.2.1 Unshielded Twisted Pair Cable

Each pair shall be terminated on appropriate outlets, terminal blocks or patch panels. No cable shall be un-terminated or contain un-terminated elements. Pairs shall remain twisted together to within the proper distance from the termination as specified in EIA ANSI/TIA/EIA-568-b.2. Conductors shall not be damaged when removing insulation. Wire insulation shall not be damaged when removing outer jacket.

3.2.2 Fiber Optic Cable

Each fiber shall be terminated to the Contractor supplied patch panel, using ST type connectors. No fiber will be left un-terminated.

3.3 BONDING AND GROUNDING

Bonding and grounding systems shall be configured in the telecommunications entrance facility and in each telecommunications closet (utilizing grounding bus bars with standoff insulators) in accordance with EIA ANSI/TIA/EIA-607. Telecommunications Main Grounding bus bar (TMGB) shall be tied to acceptable ground source with #2 AWG wire and appropriate two-hole compression lug fittings. TMGB with standoff insulators shall be tied to the Telecommunications Ground bus bar (TGB) with #4 AWG wire and appropriate two-hole compression lug fittings. The Equipment Racks shall be bonded together using Compression Lugs and green-jacketed 6 AWG Stranded Copper. Equipment racks shall be connected to the electrical safety ground only if a separate earth ground is not available. Deviations to these standards shall be submitted to 633D CS/SCXP for approval. Bonding and grounding system shall be tested per ANSI/TIA/EIA and NEC standards. Bonding and grounding system shall be labeled per ANSI/TIA/EIA and Langley AFB standards.

3 .4 ADDITIONAL MATERIALS

The Contractor shall provide the following additional materials, required for facility startup, to 633D CS/SCPX:

a. Amount of patch cords to support connectivity of all installed patch panel jacks. Patch cords must be 7 feet in length (half shall be stranded with eight-position plugs at each end and gray in color; and half shall be solid conductor with an eight-position plug on at least one end and blue in color).

b. Amount of line cords to support connectivity at work area outlet for all outlet jacks installed. Patch cords must be 16 feet in length (stranded with eight-position plugs at each end and gray in color).

c. 1 set of any and all special tools required to establish a cross connect and to change and/or maintain a terminal block.

3.5 ADMINISTRATION AND LABELING

3.5.1 Labeling

All labeling shall be done in accordance with Langley AFB standard labeling scheme provided as a technical exhibit to this specification.

3.6 COMMUNICATION CABLING INSPECTION AND TESTING

3.6.1 Inspection

3.6.1.1 System inspection shall be provided through performance of pre-installation, in-progress and final inspections by the Contracting Officer (USAF) or their authorized representative (633D CS/SCXP), at intervals provided below. Contractor is responsible to notify the Contracting Officer and authorized representative (633D CS/SCXP) when installation has reached the below installation phases:

a. (35 Percent) will primarily consist of communication closet set-up, pathways, and spaces, cable support.

b. (50 Percent) will consist of cable handling and pulling techniques, adherence to industry standards, and code compliance.

c. (75 Percent) consists of termination techniques, review of testing procedures and test plan, and documentation. There will be no 100% inspection until all areas up to the 75% inspection have been completed and the inspectors have reviewed testing documentation.

d. (100 Percent) Acceptance Inspection consists of documentation, final testing and test data, discrepancy review, operability testing, and final acceptance.

3.6.1.2 The Contractor may participate in and witness a pre-installation inspection performed by the Contracting Officer (USAF) or his authorized representative, of equipment and materials to be utilized in this project. All items may be verified for compliance with the requirements of the specifications, drawings, and other referenced material.

3.6.1.3 The Contractor and/or the Contracting Officer, shall perform in progress inspections, which shall include visual inspections of equipment condition, wiring, splicing, cabling, mounting and placement of equipment, miscellaneous hardware and adherence to safety procedures. These inspections shall ensure compliance with the specified installation criteria.

3.6.1.4 The Contractor shall conduct a final inspection that encompasses all phases of the installed project. This inspection shall be conducted to verify all phases of the contract have been completed according to the specifications and that proper installation practices have been followed. This inspection shall include a review of the “as-built” drawings provided to the Contracting Officer (USAF) by the Contractor upon completion of the installation. The Contracting Officer or his authorized representative will participate in and witness the final inspection of the communication cabling system.

3.6.1.5 The Contractor shall correct any area of noncompliance of requirements that are revealed by these inspections. Following correction, a re-examination of previous non-compliant items will be conducted at the discretion of the Contracting Officer (USAF).

3.6.1.6. The Contractor shall provide two copies of completed as-built drawings in hardcopy format and one electronic copy on CD-ROM in auto cad format prior to final acceptance. A record of all installed cable shall be provided per ANSI TIA/EIA-606. The as-built drawings shall show the location of all cable terminations, location and routing of all backbone and horizontal cables, and location of outlets. The identifier for each termination, cable and outlet shall appear on the drawings.

3.6.2 CABLE TESTING

The Contractor shall perform the cable tests for all cables specified as follows:

3.6.2.1 The Contractor shall ensure that cables will meet ANSI/TIA/EIA-568-b.1 Commercial Building Telecommunications Cabling Standard during post installation testing or incur the cost of labor for replacing deficient cables.

3.6.2.2 All installed cable shall be tested end to end, determining continuity, shorts, reversed pairs, split pairs and grounds.

3.6.2.3 All installed CAT 5e cable shall be tested for attenuation loss at 100 mega hertz and results reported in dB.

3.6.2.4. All installed CAT 5e cable shall be tested in both directions (TC to outlet, outlet to TC) for near end crosstalk (NEXT) at 100 mega hertz and results reported.

3.6.2.5 All “auto-test” results obtained from the cable tester shall be supplied in both hard copy and on disk to the Contracting Officer and authorized representative. All of the pairs in each installed copper backbone (CMP) cable shall be tested for continuity.

3.6.2.6 All circuit terminations shall be verified for color code consistency.

3.6.2.7 Unshielded Twisted Pair Tests

All metallic cable pairs shall be tested for proper identifications and continuity. All opens, shorts, crosses, grounds, and reversals shall be corrected. Correct color-coding and termination of each pair shall be verified in the communication closet and at the outlet. Horizontal wiring shall be tested from and including the termination device in the communications closet to and including the modular jack in each room. Backbone wiring shall be tested end-to-end, including termination devices, from terminal block to terminal block, in the respective communications closets. These tests shall be completed and all errors corrected before any other tests are started.

3.6.2.8 Category 5e Circuits

All category 5e circuits shall be tested using a test set that meets the Level 2 e requirements of EIA ANSI/TIA/EIA-568-b.2. Testing shall use the Permanent Link Test procedure of EIA ANSI/TIA/EIA-568-b.2. Cables, which contain failed circuits, shall be replaced and retested to verify the standard is met.

3.7 Grounding System

All grounds and bonds shall be tested for continuity according to EIA ANSI/TIA/EIA-607. Resistance to ground testing shall be accomplished on the ground electrode system in accordance with Technical Order 31.10.24, Part two, Chapter 6 and (NEC) sections 250-81, 250-83 and 250-86 and must be no less than five (5) Ohms. This standard shall apply to new and existing facilities. Test results shall be reported in hard copy format. The ground shall be labeled or tagged in accordance with EIA/TIA 606.

3.8 Fiber Optic Cables

3.8.1 All multi-mode fiber optic cable test shall be performed at the 850 nm and 1300 nm windows in both directions. All fiber optic cables shall be tested on the reels prior to installation.

3.8.2 All connectors shall be tested and the loss measured in dB; connectors shall have a loss limit that complies with ANSI/TIA/EIA-526-14A, Commercial Telecommunications Cabling Standard.

3.8.3 All fiber optic links shall be tested and the loss measured in dB/KM.

3.8.4 All fiber optic links shall be tested with a power meter. A copy of the test results shall be provided by the Contractor to the Contracting Officer (USAF) for each fiber, tested in both directions at bandwidths specified in paragraph 3.8.1 above.

3.8.5 All test results shall be documented in accordance with the Contracting Officers instructions and recorded on USAF forms provided by the Contracting Officer.

3.8.6 End to end testing is defined from the equipment end through the cross connect to the terminal end.

3.8.7 After testing is completed, all circuits shall be restored to their pre-test state (i.e. reconnected, re-terminated, etc.)

3.8.8 All fiber optic test results shall be in compliance with ANSI/TIA/EIA-568-b.1, Commercial Building Telecommunications Cabling Standard.

3.9 ACCEPTABILITY

3.9.1 Tolerance Limits

The Contractor shall be responsible for immediate corrections to the communications cabling systems that shall bring it into full compliance with these specifications.

3.10 ADDITIONAL TESTING

3.10.1 The Contracting Officer or his authorized representative or the Contractor may, at his discretion, perform tests in addition to those specified in this document, if there is any reason to question the condition of the material as furnished and installed.

3.10.2 After installation is complete, in addition to any other required testing, and at such times as the Contracting Officer or his authorized representative directs, the Contractor shall conduct an operating test for approval. The installation shall be demonstrated to be in accordance with the requirements of this specification. Any defects revealed shall; be promptly corrected at no cost to the government and the tests re-conducted.

3.10.3 Operational Testing is defined for the following circuit types:

a. Station Cable – Color code compliance, labeling, correct pin termination at outlet location, routing, workmanship, NEXT and attenuation.

b. Backbone Cable (CMR) – Color code compliance, labeling, computer room and distribution closet jumpers, patch cords, grounding/bonding, workmanship, termination block layout and installation, and routing.

c. Fiber Optic Cable – Labeling, patch panel connections, loss measured in Db/km, workmanship, and routing.

d. Ground Cable – Labeling, connections, connectivity, workmanship, and routing.

3.11 TEST REPORTS

3.11.1 The Contractor shall be responsible for recording and providing to the Contracting Officer, all test data. Copies of all test results shall be submitted the Contracting Officer or his authorized representative for review and remain the property of the Government for their records. For all fiber optic cables, power meter test results shall be provided hard copy and correspond to a labeled fiber optic cable. All twisted pair copper cable shall have a disk copy output of the test results with the station ID assigned. All test results shall be provided in hard copy format to the Contracting Officer prior to Quality Assurance Inspection for acceptance of Premises Wire Distribution System installation.

--End of Section--

File details come from the government source that posted it. Updated .