11_ME0.4 AMENDED (Amend 1).pdf

PDF 669 KB Posted

Attached to
High Temperature Hot Water System Repair Federal contract opportunity
Solicitation number
FA462624R0009
Issued by
Department of the Air Force Global Strike Command

About this file

This document is an amended design drawing (11_ME0.4 AMENDED (Amend 1).pdf) related to a federal contract opportunity for High Temperature Hot Water (HTHW) System Repair at Malmstrom Air Force Base, Montana.

The key details are:

  • This is a 100% Small Business set-aside solicitation (FA462624R0009) for a firm-fixed price IDIQ contract to repair the HTHW system, including excavation, repair, and replacement of components such as service lines, distribution lines, sump pumps, and valves.
  • The total aggregate order value shall not exceed $4,999,999.99 over the 5-year ordering period.
  • The design drawing provides detailed instructions and requirements for the sump pump system installations, including demolition, electrical, and commissioning work. It references specific manhole locations, piping configurations, and programming requirements to address potential obstructions.

View the file

Other files for this federal contract opportunity

Other files attached to High Temperature Hot Water System Repair, newest first.
File Type Posted
0_Solicitation - FA462624R00090003 Amend 03.pdf PDF
13_QA_13 Aug 2024 (Amend 3).xlsx XLSX spreadsheet
15_ME1.2 AMENDED (Amend 2).pdf PDF
16_M17.3 AMENDED (Amend 2).pdf PDF
0_Solicitation - FA462624R00090002 Amend 02.pdf PDF
14_ME1.3 AMENDED (Amend 2).pdf PDF
11_ME0.4 AMENDED (Amend 2).pdf PDF
5_Blank Bid Sch (Amend 2).xlsx XLSX spreadsheet
6_MT20240066_ 02 Aug 24_Heavy (Amend 2).pdf PDF
13_QA_6 Aug 2024 (Amend 2).xlsx XLSX spreadsheet
0_Solicitation - FA462624R0009 Amend 01.pdf PDF
9_Subcontractor Consent (Amend 1).pdf PDF
7_Sections L and M - HTHW Requirements (updated 072924 Amend 1).pdf PDF
12_M17.4 AMENDED (Amend 1).pdf PDF
13_QA_29 Jul 2024 (Amend 1).xlsx XLSX spreadsheet
10_C1.2 AMENDED (Amend 1).pdf PDF
6_MT20240066 27 Jun 2024_Heavy.pdf PDF
5_Blank Bid Sch.xlsx XLSX spreadsheet
4B_DRAWINGS - Service Lines BLDG 1464.pdf PDF
7_Sections L and M - HTHW Requirements.pdf PDF
4A_Sheet Index - Service Lines Bldg 1464.pdf PDF
2B_Submittal Schedule Service Lines 1464.xlsx XLSX spreadsheet
0_Solicitation - FA462624R0009.pdf PDF
8_Past Performance Questionaire.pdf PDF
3B_DRAWINGS - Sump Pumps.pdf PDF
3A_Sheet Index - Sump Pumps.pdf PDF
2A_Submittal Schedule HTHW Sumps.xlsx XLSX spreadsheet
1B_SPECS Service Lines BLDG 1464.pdf PDF
1A_SPECS - Sump Pumps.pdf PDF
Show all 29

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NOTES:

1. REFER TO SUMP PUMP CONTROLLER DETAIL 1/ME0.2 AND SUMP PUMP INSTALLATION DETAIL 1/ME0.3.

2. HTHW PIPING CROSSES THROUGH MANHOLE PARTIALLY OBSTRUCTING PUMP & LEVEL DETECTOR INSTALLATION. COORDINATE FINAL PLACEMENTS WITH CONTRACTING

OFFICER'S TECHNICAL REPRESENTATIVE. THIS INSTALLATION WILL REQUIRE ADDITIONAL EFFORT TO PROGRAM OUT FALSE ECHO RETURNS (FROM THE PIPING AND NOT

WATER) WITH TRANSDUCER.

3. THIS MANHOLE IS CONSTRUCTED WITH METAL ABOVE GRADE RISER AND MANHOLE COVER.

4. HTHW SERVICE LINE TAKEOFF MANHOLE. DISCHARGE PIPING FOR THIS MANHOLE IS CONFIGURED WITH FLEXIBLE HOSE DUE TO LARGER MANHOLE SIZE AND PRESENCE OF

PIPING. PROVIDE 2" 'GATES 232MB STEAM QUEEN' HOSE OR APPROVED EQUAL, RATED FOR 250 PSIG AND 450°F. HOSE TO BE OF SUFFICIENT LENGTH TO ALLOW PUMP REMOVAL WITHOUT DISCONNECTING HOSE. FOR THESE LARGER VOLUME MANHOLES, PUMP 'ON' SETPOINT SHALL BE 6" ABOVE 'PUMP OFF' SETPOINT.

5. THIS MANHOLE TO RECEIVE NEW SUMP DISCHARGE LINE ROUTED TO EXISTING STORM DRAIN. SEE DETAIL 2/ME1.2.

NUMBER

MANHOLE / VALVE

STATION LOCATION

OR DESIGNATION

CONTROL AND/OR ALARM PANEL CONFIGURATION TRANSFORMER

PIPE SIZE

INCHES

DISTANCE FROM

TOP OF

MANHOLE TO

TOP OF PIPE NOTES

CONTROLLER

ID

POWER FEED

ORIGINATION VOLTAGE HOA

MOTOR

AMP

RATING

MAX

PANEL

AMPS

REMOTE ALARM

LIGHT INPUT

VOLTAGE

OUTPUT

VOLTAGE

REQ'D

Y/N COLOR OUTLET INLET OUTLET INLET

MH-VS480 SPC-480

PEDESTAL

LOAD CENTER

P-493

120/240V

/ 1PH YES 5.3 18.0 YES BLUE 240V/1PH

2W 120/240V

1PH 3W 2 4 2'-0" 7'-11"

MH-VS882 SPC-882

PEDESTAL

LOAD CENTER

P-493

120/240V

/ 1PH YES 5.3 18.0 NO - 240V/1PH

2W 120/240V

1PH 3W - - GRADE 6'-7"

MH-VS1082 SPC-1082 P-G8 120/240V

/ 1PH YES 5.3 18.0 NO 208V/1PH

2W 120/240V

1PH 3W - - NEW,

24" 4'-7"

MH-VS1154 SPC-1154

PARKING LOT

LIGHTING LOAD

CENTER

PEDESTAL

120/240V

/ 1PH YES 5.3 18.0 YES BLUE 240V/1PH

2W 120/240V

1PH 3W 2 4 6" 6'-6"

MH-VS1199 SPC-1199 T-1192 PANEL

P2

120/240V

/ 1PH YES 5.3 18.0 YES BLUE 208V/1PH

2W 120/240V

1PH 3W 2 4 1'-1" 6'-8"

MH-VS1305 SPC-1154

PARKING LOT

LIGHTING LOAD

CENTER

PEDESTAL

120/240V

/ 1PH YES 5.3 18.0 YES BLUE 240V/1PH

2W 120/240V

1PH 3W 2 4 1'-0" 7'-2"

MH-VS2055 SPC-2055 T-1192 PNL P2 120/240V

/ 1PH YES 5.3 18.0 YES BLUE 240V/1PH

2W 120/240V

1PH 3W 2 4 10" 3'-8"

2 3

GLOBAL STRIKE COMMAND

MALMSTROM AIR FORCE BASE, MONTANA

AutoCAD SHX Text GENERAL NOTES: FOR EACH HTHW SUMP PUMP SYSTEM INDICATED, THE FOLLOWING WORK IS REQUIRED: 1. CONTRACTOR SHALL FIELD-VERIFY ALL INVERT ELEVATIONS LISTED IN THE CHART ON THIS SHEET. CONTRACTOR SHALL FIELD-VERIFY ALL INVERT ELEVATIONS LISTED IN THE CHART ON THIS SHEET. LISTED INVERT ELEVATIONS FOR INLET/OUTLET PIPING ARE BASED UPON LASER MEASUREMENT FROM GRADE DURING LIMITED FIELD INVESTIGATION AND ARE FOR REFERENCE ONLY. WHERE INVERT ELEVATIONS ARE NOT LISTED, ACCESS COULD NOT BE GAINED BY THE CONSULTANT DURING DESIGN - ASSUME 10FT DEPTH FOR BIDDING PURPOSES. A INTEGRAL PART OF THIS CONTRACT SHALL BE THE FIELD VERIFICATION AND UPDATES TO ALL DATA FIELDS OF THIS SHEET'S CHART, WHICH SHALL BE SUBMITTED TO THE GOVERNMENT PRIOR TO CONTRACT CLOSEOUT FOR APPROVAL. 2. THE CONTRACTOR IS RESPONSIBLE FOR ALL WATER REMOVAL FROM THE HTHW SUMP BASINS TO THE CONTRACTOR IS RESPONSIBLE FOR ALL WATER REMOVAL FROM THE HTHW SUMP BASINS TO PERFORM THE WORK COVERED BY THIS CONTRACT. 3. FOR EACH PIT, EVERYTHING SHALL BE COMPLETELY REMOVED AS A PART OF DEMOLITION SCOPE. FOR EACH PIT, EVERYTHING SHALL BE COMPLETELY REMOVED AS A PART OF DEMOLITION SCOPE. THIS INCLUDES, BUT IS NOT LIMITED TO THE SUMP PUMP, SUMP PUMP CONTROLLER INCLUDING FOUNDATION/CONDUIT/STRUT SUPPORTS, AUXILIARY SCREEN WALL ALARM LIGHTS, EXISTING HANGARS AND SUPPORTS, CONDUITS, LEVEL DETECTION ASSEMBLIES (FLOATS, RODS, SWITCHES), MISCELLANEOUS JUNCTION BOXES, SIGNAL AND POWER WIRING. THE INTENT OF THIS CONTRACT IS TO COMPLETELY REBUILD THE SUMP PUMPS SYSTEM AND SUPPORTING EQUIPMENT. WHERE FASTENERS ARE ANCHORED INTO CONCRETE, THEY SHALL BE CUT OFF AND GROUND FLUSH WITH THE BASIN WALLS, OR REMOVED AND THE HOLES SEALED WATER TIGHT. WHERE ANCHOR BOLTS ARE CUT OFF FLUSH, THE SURFACE SHALL BE REFINISHED TO MATCH EXISTING. EXISTING SUPPORTS MAY ONLY BE REUSED WHERE SPECIFICALLY PERMITTED BY THE CONTRACTING OFFICER'S REPRESENTATIVE. THE GOVERNMENT RESERVES THE RIGHT TO SALVAGE ANY PROJECT PARTS RESULTANT FROM THIS DEMOLITION SCOPE. ALSO REFER TO SPECIFICATION SECTION 024100 DEMOLITION. 4. FOR EACH PIT, THE CONTRACTOR SHALL CLEAN THE PIT, INFLUENT AND EFFLUENT LINES AS A FOR EACH PIT, THE CONTRACTOR SHALL CLEAN THE PIT, INFLUENT AND EFFLUENT LINES AS A PART OF THE DEMOLITION SCOPE TO PREPARE FOR INSTALLATION OF NEW SYSTEMS. EACH INFLUENT AND EFFLUENT LINE AT EACH LOCATION SHALL BE CAMERA SCOPED 15 FEET DOWN THE LINE TO VERIFY INTEGRITY (WHERE LINE IS LARGE ENOUGH DIAMETER). NOTIFY THE GOVERNMENT IN WRITING OF ANY EXISTING CONDITIONS WHERE LINES ARE DAMAGED AND NEED REPAIR. 5. POWER AND LEVEL TRANSDUCER SIGNAL WIRING SHALL BE INSTALLED INTO THE EXISTING SUMP POWER AND LEVEL TRANSDUCER SIGNAL WIRING SHALL BE INSTALLED INTO THE EXISTING SUMP PITS IN SEPARATE CONDUITS - REFER TO SYSTEM INSTALLATION DETAILS ON PLANS ME0.2/ME0.3. 6. THE NEW SUMP PUMP SYSTEMS (SLIDE RAILS AND PUMP) AND LEVEL TRANSDUCERS SHALL BE THE NEW SUMP PUMP SYSTEMS (SLIDE RAILS AND PUMP) AND LEVEL TRANSDUCERS SHALL BE ARRANGED SUCH THAT THE PUMP CAN BE REMOVED WITHOUT REMOVAL OF THE LEVEL DETECTION TRANSDUCER. THE MANHOLE LID SHALL BE REMOVABLE WITHOUT DISCONNECTION OF POWER OR SIGNAL LEADS TO THE LEVEL TRANSDUCER, AND THE MANHOLE STAIRS (IF PRESENT) SHALL BE USABLE. 7. AT EACH LOCATION OF WORK, THE SUMP PUMP SYSTEM (PUMP, LEVEL DETECTION, CONTROLS, AT EACH LOCATION OF WORK, THE SUMP PUMP SYSTEM (PUMP, LEVEL DETECTION, CONTROLS, ALARMS, ETC) SHALL BE COMMISSIONED AFTER STARTUP. PROVIDE 2 WEEKS NOTICE TO GOVERNMENT PRIOR TO SCHEDULING AND COMMENCING THIS WORK. THE CE HVAC SHOP MUST BE MUST BE BE PRESENT DURING SYSTEM COMMISSIONING. THIS WORK SHALL ENTAIL MEASUREMENT AND VERIFICATION THAT THE SYSTEM OPERATES AS DESIGNED, ADJUSTMENT AND DOCUMENTATION OF INDIVIDUAL SYSTEM SET POINTS, RECORDING AND ADJUSTMENT OF PUMP RUN TIMES, AS WELL AS TESTING OF SYSTEM ALARMS AND ASSOCIATED SETPOINTS. SUBMIT A FIELD COMMISSIONING REPORT TO THE GOVERNMENT PRIOR TO CONTRACT CLOSE-OUT INCLUDING DOCUMENTATION OF EACH WORK TASK COMPLETED AT EACH SUMP PUMP SYSTEM INSTALLATION SITE, ALARM LEVEL SETPOINTS, FINAL INSTALLED PUMP RUN TIME (IE TIME TO PUMP OUT FROM PUMP 'ON' TO 'OFF' SET POINTS), AND DOCUMENTATION OF EXISTING CONDITIONS DIFFERING FROM THE ORIGINAL DESIGN. MINIMUM DIFFERENTIAL BETWEEN PUMP 'ON' AND 'OFF' SHALL BE 6 INCHES FOR THE LARGER HTHW SERVICE LINE MANHOLES, AND 12" FOR THE SMALLER HTHW DISTRIBUTION VALVE STATION MANHOLES. 8. FOR EACH PUMP CONTROL PANEL, INSTALL A LABEL ON THE OUTSIDE OF THE CONTROLS FOR EACH PUMP CONTROL PANEL, INSTALL A LABEL ON THE OUTSIDE OF THE CONTROLS ENCLOSURE WITH: 'MH-XXXX' PER THE NOMENCLATURE ON THIS SHEET'S CHART, AS WELL AS THE SYSTEM POWER SOURCE ORIGINATION POINT. NAMEPLATES TO BE BLACK PHENOLIC, WHITE ENGRAVED LETTERING, 1/4 INCH TEXT HEIGHT. SEE 1/ME0.2 FOR INSTALL LOCATION. 9. ALTHOUGH THE TABLE TO THE LEFT SPECIFICALLY REFERENCES WHICH MH'S HAVE POSSIBLE ALTHOUGH THE TABLE TO THE LEFT SPECIFICALLY REFERENCES WHICH MH'S HAVE POSSIBLE INTERFERENCE (NOTE 2), WHICH MAY INVOLVE PROGRAMMING OUT FALSE POSITIVES, THIS SHALL BE CONSIDERED INCIDENTAL TO ALL MH INSTALLATIONS. ANY PROGRAMMING TO ELIMINATE FALSE ALL MH INSTALLATIONS. ANY PROGRAMMING TO ELIMINATE FALSE MH INSTALLATIONS. ANY PROGRAMMING TO ELIMINATE FALSE POSITIVE READINGS MUST BE DONE BY THE CONTRACTOR, REGARDLESS IF SPECIFICALLY CALLED OUT IN THE TABLE OR NOT. NOTE 2 IN THE TABLE IS A CONVENIENCE FOR KNOWN MH'S THAT KNOWN MH'S THAT MH'S THAT WILL HAVE PROGRAMMING NEEDED. OTHER MH'S MAY ALSO NEED IT, HENCE BEING CONSIDERED INCIDENTAL ON ALL INSTALLATIONS.

AutoCAD SHX Text

LJW

AutoCAD SHX Text

LJW

AutoCAD SHX Text

ME0.4

AutoCAD SHX Text

AutoCAD SHX Text

HTHW SUMP PUMPS WORK SCHEDULE

AutoCAD SHX Text

ATTACHMENT:

AutoCAD SHX Text

REV.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

APPR'D

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

DESIGNED BY

AutoCAD SHX Text

REVIEWED BY

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PLATE

AutoCAD SHX Text

PAGE

AutoCAD SHX Text

OF

AutoCAD SHX Text

PROJECT NUMBERS

AutoCAD SHX Text

ACAD DRAWING NUMBER

AutoCAD SHX Text

RECORD FILE NUMBER

AutoCAD SHX Text

AS NOTED

AutoCAD SHX Text

REPAIR HTHW SUMP PUMPS

AutoCAD SHX Text 1123678

AutoCAD SHX Text 12.23.21

AutoCAD SHX Text

GPD, PC

AutoCAD SHX Text

ME0.4 AMENDED

AutoCAD SHX Text

Sheets and Views
ME0.4

File details come from the government source that posted it. Updated .