TO 31R4-2GRN31-6WC-1
1 MAY 2006 CHANGE 4 23 NOVEMBER 2011
DISTRIBUTION STATEMENT C - Distribution authorized to U S. Government agencies and their contractors for administrative or operational use, (1 April 2011). Refer other requests for this document to OC-ALC/GKAAB, Tinker AFB, Oklahoma 73145-9155.
WARNING - This document contains technical data whose export is restricted by the Arms Export Control Act (Title 22, U.S.C. 2751 et seq.) or Executive Order 12470. Violations of these export laws are subject to severe criminal penalties. Disseminate in accordance with provisions of DoD Directive 5230.25.
HANDLING AND DESTRUCTION NOTICE - Handle in compliance with distribution statement and destroy by any method that will prevent disclosure of the contents or reconstruction of the document.
Published under the authority of the Secretary of the Air Force.
SCHEDULED PERIODIC INSPECTION WORKCARDS
RADIO TRANSMITTING SET (GLIDESLOPE STATION) AN/GRN-31(V)
PART NO. 098302-0100/0300 (NSN 5825-01-046-9975)
WITH TRAINER
PART NO. 098302-0200 (NSN 5825-01-046-8596)
A CHANGE 4
LIST OF EFFECTIVE CARDS
Insert latest change card and destroy superseded cards.
NOTE: The portions of the text affected by the changes are indicated by a vertical line in the outer margin of the card. Changes to illustrations are indi-cated by miniture pointing hands.
DATES OF ISSUE FOR ORIGINAL AND CHANGED CARDS ARE:
The total number of cards in this publication is 27, consisting of the following:
Title A I-01 - I-02 I-03 1-001 1-002
1-003 - 1-004 1-005 1-006 - 1-007 1-008 1-009 1-010 - 1-013
1-014 1-015 2-001 - 2-006 5-001 - 5-002
Original . . . . . . . . . . . 0 . . . . . . . . . . . . 1 May 2006 Change . . . . . . . . . . . . 3 . . . . . . . . . . . . 1 April 2011
Change . . . . . . . . . . . . .1. . . . . . . . . . . . . . 4 July 2009 Change . . . . . . . . . . . . .4. . . . . . . . 23 November 2011
Change . . . . . . . . . . . . 2. . . . . . . . . 24 February 2011
PAGE NO. CHANGE NO. PAGE NO. CHANGE NO. PAGE NO. CHANGE NO.
PUBLICATION NUMBER
INSPECTION REQUIREMENTS
TABLE OF CONTENTS
FIGURE CHANGE NO. CARD NO.
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I-02
1 INSPECTION REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-001
A 56 DAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-002 B 84 DAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-009 C 168 DAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-010 D 336 DAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-014
2 SERVICE AND LUBE REQUIREMENTS (84 AND 168 DAY) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-001
3 SPECIAL INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N/A
4 TIME REPLACEMENT ITEMS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N/A
5 REPAIR RESTRICTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-001
I-01
INSPECTION REQUIREMENTS
INTRODUCTION
FIGURE CHANGE NO. CARD NO.
I-02
GENERAL INFORMATION
1. THESE WORKCARDS CONTAIN ALL REQUIREMENTS FOR ACCOMPLISHING SCHEDULED MAINTENANCE ON GROUND ELEC- TRONIC (C-E) EQUIPMENT DURING ITS ENTIRE SERVICE LIFE. IT ESTABLISHES INSPECTION, ACCESSORY REPLACEMENT, DEPOT LEVEL, AND BASE LEVEL REPAIR REQUIREMENT/RESTRICTIONS. THESE REQUIREMENTS ARE PRIMARILY TECHNI- CAL IN NATURE AND THE CONDITIONS LISTED ARE INTENDED TO DIRECT ATTENTION TO KNOWN PROBLEM AREAS. THESE REQUIREMENTS ARE DEVELOPED FOR NEW C-E EQUIPMENT THROUGH MAINTENANCE ENGINEERING AND COMPARISON OF SIMILAR INSTALLATIONS, OR IN-SERVICE C-E EQUIPMENT. THE INTERVAL BETWEEN THE ACCOMPLISHMENT OF A REQUIREMENT IS INTENDED TO BE THE LONGEST PERIOD OF TIME THAT AN ITEM OR COMPONENT CAN SAFELY OPERATE WITHOUT AN INSPECTION OR OBSERVATION. THESE REQUIREMENTS AND INSPECTION INTERVALS ARE THE MAXIMUM AND SHOULD NEVER BE EXCEEDED. LOCAL CONDITIONS (TYPE OF MISSION, SPECIAL UTILIZATION, GEOGRAPHICAL LOCA- TION, ETC), MAY DICTATE MORE FREQUENT INSPECTIONS, REPLACEMENT OR MORE THOROUGH INSPECTIONS; THERE- FORE, COMMANDS, LOCAL COMMANDERS, AND THEIR MAINTENANCE OFFICERS HAVE THE PREROGATIVE TO INCREASE THE FREQUENCY OR SCOPE OF ANY REQUIREMENT, AND ARE EXPECTED TO EXERCISE THIS PREROGATIVE.
2. THE INSPECTIONS PRESCRIBED BY THESE WORKCARDS WILL BE ACCOMPLISHED AT SPECIFIED PERIODS BY AIR FORCE ORGANIZATIONAL ACTIVITIES WITH ASSISTANCE PROVIDED BY AFETS AND SMTS WHEN REQUIRED. COMPLIANCE WITH THE PROVISIONS OF THESE WORKCARDS IS REQUIRED TO ASSURE THAT LATENT DEFECTS ARE DISCOVERED AND COR-
RECTED BEFORE MALFUNCTIONING OR SERIOUS TROUBLE RESULTS.
INSPECTION REQUIREMENTS
INTRODUCTION
FIGURE CHANGE NO. CARD NO.
I-02
NOTE
SHOULD THE PARAMETER BEING MEASURED APPROACH THE ESTABLISHED LIMITS, ACTION SHOULD BE
TAKEN TO CORRECT THE MARGINAL CONDITION.
3. THE INSPECTION REQUIREMENTS ARE STATED IN SUCH A MANNER AS TO ESTABLISH WHAT EQUIPMENT IS TO BE INSPECTED, WHEN IT IS TO BE INSPECTED, AND WHAT CONDITIONS ARE TO BE SOUGHT. IN SCOPE, THE REQUIREMENTS ARE DESIGNED TO DIRECT THE ATTENTION OF MAINTENANCE PERSONNEL TO COMPONENTS AND AREAS WHERE DEFECTS MAY EXIST AS A RESULT OF USAGE UNDER NORMAL OPERATING CONDITIONS. THEY ARE NOT INTENDED TO PROVIDE COVERAGE FOR ROUTINE CLEANING, WASHING, ETC., NOR ARE THEY DESIGNED TO LEAD TO THE DETECTION OF ISOLATED DISCREPANCIES THAT MAY OCCUR ON A ONE-TIME BASIS, OR DISCREPANCIES THAT ARE THE RESULT OF CARE- LESSNESS, ABUSE OR POOR MAINTENANCE PRACTICES. DURING ACCOMPLISHMENT OF THE SPECIFIC REQUIREMENTS DIRECTED BY THESE WORKCARDS, MAINTENANCE PERSONNEL SHOULD OBSERVE BOTH THE EQUIPMENT BEING INSPECTED AND THE COMPONENTS IN THE SURROUNDING AREA FOR DEFECTS OR IRREGULARITIES NOT WITHIN THE SCOPE OF THE REQUIREMENTS. REQUIREMENTS REQUIRING THE USE OF ELECTRICAL POWER FOR ACCOMPLISHMENT ARE IDENTIFIED BY A COMMERCIAL “@” SYMBOL PRECEDING THE PARAGRAPH NUMBER FOR THE REQUIREMENTS.
4. THE REPLACEMENT SCHEDULE DIRECTS REPLACEMENT OF ITEMS AT A SPECIFIC TIME WHEN A FAILURE WOULD COMPRO- MISE SAFETY OR OPERATION BEYOND REASONABLE LIMITS OR DEFINITELY CAUSE A MISSION FAILURE. ALSO CONSID- ERED ARE ANY HIGH COST ITEMS WHO’S FAILURE WOULD RESULT IN CONDEMNATION AND ANY SHORT LIFE ITEMS WHICH WOULD REQUIRE FREQUENT UNSCHEDULED MAINTENANCE. ITEMS NOT LISTED WILL BE KNOWN AS “CONDITION ITEMS”
AND WILL BE REPLACED ONLY WHEN NECESSARY.
INSPECTION REQUIREMENTS
INTRODUCTION
FIGURE CHANGE NO. CARD NO.
2 I-03
5. BASE LEVEL REPAIR RESTRICTIONS DESCRIBES THE REPAIRS WHICH ARE NOT AUTHORIZED AT BASE LEVEL.
6. THE TIME IN MAN-MINUTES FOR ACCOMPLISHMENT OF REQUIREMENTS REFLECTS ONLY THE TIME REQUIRED FOR INSPECTION OR REPLACEMENT. THIS TIME DOES NOT INCLUDE TIME REQUIRED TO GAIN ACCESS TO THE EQUIPMENT TO FACILITATE ACCOMPLISHMENT. THOSE FACTORS (PERSONNEL AND EQUIPMENT SHORTAGES, LACK OF PARTS, ADVERSE WORKING CONDITIONS, AND QUALIFICATIONS OF PERSONNEL) WHICH WILL DIRECTLY AFFECT THE LENGTH OF TIME OF ANY SCHEDULED MAINTENANCE ACTION ARE NOT INCLUDED BECAUSE THEY CANNOT BE ACCURATELY PREDICTED.
7. THESE WORKCARDS DO NOT CONTAIN DETAILED INSTRUCTIONS FOR TROUBLESHOOTING TO FIND CAUSES FOR MAL- FUNCTIONS, NOR DO THEY CONTAIN INSTRUCTIONS FOR REPAIR, ADJUSTMENT, OR OTHER MEANS OF RECTIFYING DEFECTIVE CONDITIONS. PROPER INSTALLATION OF A PIECE OF EQUIPMENT OR ACCESSORY IS NOT NECESSARILY WITHIN THE SCOPE OF THESE WORKCARDS AS ADEQUACY AND COMPLETENESS OF INSTALLATION WILL HAVE BEEN DETERMINED AT THE TIME OF INSTALLATION. APPLICABLE PORTIONS OF THE APPROPRIATE MAINTENANCE MANUAL SHOULD BE CONSULTED TO OBTAIN “HOW TO” MAINTENANCE INSTRUCTIONS AS THEY ARE BEYOND THE SCOPE OF THESE
WORKCARDS.
8. FOR THE PURPOSE OF CLARIFICATION OF TERMS USED IN THESE WORKCARDS, THE FOLLOWING DEFINITIONS ARE GIVEN:
SPECIFIED- REFERS TO A DEFINITE AMOUNT, OPERATION, OR LIMITATION WHICH HAS BEEN ESTABLISHED AND IS CON- TAINED IN APPLICABLE DIRECTIVES. EVIDENCE- PROOF OF A SUSPECTED OR EXISTING UNSATISFACTORY CONDITION.
SECURE-MEANS THE COMPONENT IS PROPERLY MOUNTED OR ATTACHED TO RELATED EQUIPMENT, INCLUDING APPLICA- BLE SAFETYING. ACCESSIBLE- THE TERM APPLIED TO EQUIPMENT THAT MAY BE INSPECTED WITHOUT FURTHER DISAS- SEMBLY OR REMOVAL OF COVERS, CLOSURES, PANELS, ETC., OTHER THAN THOSE REQUIRED TO ACCOMPLISH THE MORE
SPECIFIC REQUIREMENTS APPLICABLE TO THE PARTICULAR INSPECTIONS.
INSPECTION REQUIREMENTS
INTRODUCTION
FIGURE CHANGE NO. CARD NO.
2 I-03
9. CHANGES AND REVISIONS TO THESE WORKCARDS WILL BE PUBLISHED WHEN NECESSARY TO ADD, DELETE, OR CHANGE FREQUENCY OR SCOPE OF REQUIREMENTS. SUCH CHANGES WILL BE BASED ON FACTUAL DATA ACCUMULATED AS A RESULT OF MAINTENANCE EXPERIENCE WITH THE EQUIPMENT. RECOMMENDATIONS PROPOSING CHANGES TO THESE WORKCARDS SHOULD BE SUBMITTED ON AFTO FORM 22 IN ACCORDANCE WITH TO 00-5-1 TO THE USING COMMAND HEAD-
QUARTERS.
NOTE
ALL CORROSION WILL BE TREATED IN ACCORDANCE WITH TO 1-1-700.
MAN
MIN
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB INTRODUCTION 1-001
INSPECTION REQUIREMENTS
1. THESE INSPECTION WORKCARDS PROVIDE THE REQUIREMENTS FOR INSPECTION AND WILL BE USED AS A GUIDE IN PERFORMING THE INSPECTION TO ENSURE THAT NO ITEM IS OVERLOOKED.
THE CARD SIZE AFFORDS CONVENIENT HANDLING BY MAINTENANCE PERSONNEL WHILE PER-
FORMING AN INSPECTION.
2. DETAILED INSTRUCTIONS FOR THE USE OF THESE CARDS AND THE DESCRIPTION AND APPLICA-
TION OF OTHER FORMS AND CHARTS TO BE USED IN CONJUNCTION WITH THESE CARDS ARE
CONTAINED IN 00 -20 SERIES TECHNICAL ORDERS.
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
CHANGE NO.
1-001
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 56 DAY ON OUT 1-002
@ TRANSMITTER WAVESHAPES (AUDIO PHASE)
1. EQUIPMENT REQUIRED.
A. OSCILLOSCOPE
B. TWO TEST CABLES, BNC TO PHONE JACK
AB AB0 2. OPEN CONTROL UNIT. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO. 1
AND SET MONITOR BYPASS/NORMAL SWITCH TO BYPASS.
AB AE0 3. MEASURE AND RECORD CARRIER, SIDEBAND, AND CLEARANCE TRANSMITTED OUTPUT POW-
ERS USING REFERENCE WATT ELEMENTS.
AB AD0 4. CONNECT OSCILLOSCOPE EXTERNAL SYNC TO ON AIR TRANSMITTER 60 HZ SYNC JACK WITH
ONE TEST CABLE.
AB AD0 5. CONNECT OSCILLOSCOPE VERTICAL INPUT TO ON AIR TRANSMITTER CSB TEST JACK WITH
OTHER TEST CABLE.
NOTE
ENSURE OSCILLOSCOPE VERTICAL INPUT IS SET TO INPUT DC.
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
1-002 4
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 56 DAY ON OUT 1-002
AB AD0 6. OBTAIN WAVESHAPE ON OSCILLOSCOPE AND COMPARE TO FIGURE W1-001. ENSURE WAVE-
SHAPE IS CORRECT.
NOTE
ADJUST SIGNAL TRACE OF OSCILLOSCOPE TO GROUND REFERENCE ON BOTTOM
GRATICULE.
AB AD0 7. SWITCH TEST CABLE IN STEP 5 TO THE SBO TEST JACK. OBTAIN WAVESHAPE ON OSCILLO-
SCOPE AND COMPARE TO FIGURE W1-002. ENSURE WAVESHAPE AND PERCENT OF MODULA-
TION ARE CORRECT. OVER MODULATION OF THE SBO SIGNAL IS INDICATED BY THE BOTTOM
OF THE WAVE FORM BEING FLATTENED.
AB AB0 8. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO.2 AND REPEAT STEPS 3-7.
AB 000 9. RETURN SYSTEM TO NORMAL OPERATING CONFIGURATION.
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 56 DAY ON OUT 1-003W1-001
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
1-003
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 56 DAY ON OUT 1-004W1-002
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
1-004
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 56 DAY ON OUT 1-005
@ TRANSMITTER PERCENTAGE OF MODULATION AND MODULATION BALANCE TEST
1. EQUIPMENT REQUIRED:
A. PORTABLE ILS RECEIVER (PIR).
B. SNIFFER ASSEMBLY.
C. ONE 6 FT LENGTH RG-223 OR EQUIVALENT TEST CABLE WITH BNC CONNECTORS.
D. 50 OHM BIRD 80M DUMMY LOADS.
E. 50 OHM BIRD 80F DUMMY LOADS.
NOTE
THIS PROCEDURE REQUIRES EQUIPMENT DOWNTIME. ENSURE THE APPROPRIATE
PARTIES ARE ADVISED BEFORE THIS PROCEDURE IS ACCOMPLISHED.
AB AB0 2. OPEN CONTROL UNIT. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO. 1 AND
SET MONITOR BYPASS/NORMAL SWITCH TO BYPASS.
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
1-005 4
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 56 DAY ON OUT 1-005
AB AE0 3. TURN OFF TRANSMITTER NO. 1. OPEN CHANGEOVER UNIT, DISCONNECT SIDEBAND OUT
CABLE, DUMMY LOAD CABLE AND PORT. TURN ON TRANSMITTER NO. 1.
AB AD0 4. CONNECT TEST EQUIPMENT AS SHOWN IN FIGURE W1-003.
AB AD0 5. INSERT THE SNIFFER INTO THE CARRIER THRU-LINE BODY.
AB AD0 6. SET PIR TO READ MOD, VERIFY MODULATION BALANCE, PIR SHOULD INDICATE 0.000 DDM
±0.005 DDM.
AB AD0 7. SET PIR TO READ 90 HZ ONLY.
AB AD0 8. VERIFY 90 HZ MODULATION, PIR SHOULD INDICATE REF ±2%.
AB AD0 9. SET PIR TO READ 150 HZ ONLY.
AB AD0 10. VERIFY 150 HZ MODULATION, DIGITAL PIR SHOULD INDICATE REF ±2%.
AB AB0 11. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO.2 AND REPEAT STEPS 6-10.
AB 000 12. RETURN SYSTEM TO NORMAL OPERATING CONFIGURATION.
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 56 DAY ON OUT 1-006W1-003
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
1-006
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 56 DAY ON OUT 1-007
@ GROUND PHASING CHECK
AB 000 1. EQUIPMENT REQUIRED:
A. PORTABLE ILS RECEIVER (PIR).
B. 90º PHASING TEST CABLE.
C. ONE 4 FOOT LENGTH, RG-223 TEST CABLE WITH BNC CONNECTORS.
D. ADAPTERS (AS REQUIRED).
E. APPROPRIATE WATT ELEMENTS (SITE SPECIFIC).
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
1-007
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 56 DAY ON OUT 1-007
NOTE
PRIOR TO PROCEEDING, IF FAR FIELD MONITOR IS INSTALLED, INSURE THE FAR FIELD
MONITOR BYPASS SWITCH AT THE LOCALIZER IS IN THE BYPASS POSITION. YOU WILL
NEED TWO PERSONNEL TO COMPLETE THE FOLLOWING STEPS WITH RADIO CONTACT
BETWEEN GLIDESLOPE SITE AND PERSONNEL IN FAR FIELD.
AB AB0 2. OPEN CONTROL UNIT AND SET MONITOR NORMAL/BYPASS SWITCH TO BYPASS.
AB AD0 3. SET ALL TRANSMITTER POWER SWITCHES TO OFF.
AB AE0 4. OPEN CHANGE OVER UNIT. DISCONNECT SBO OUTPUT CABLE W2 FROM THRU-LINE BODY.
AB AE0 5. INSERT 90º PHASING CABLE BETWEEN THRU-LINE BODY AND SBO OUTPUT CABLE W2.
AB AD0 6. AT THE ESTABLISHED GLIDESLOPE PHASING POINT, USE PIR TO MEASURE DDM.
A. IF USING FAR FIELD MONITOR, OPEN CABINET DOOR AND SLIDE OUT RECEIVER DRAWER.
DISCONNECT FFM INPUT CABLE FROM RECEIVER ASSEMBLY A3J1P-1 AND CONNECT PIR
TO CABLE W-1 USING 4 FT TEST CABLE AND ADAPTORS. SET PIR TO MEASURE DDM.
B. IF FAR FIELD MONITOR IS NOT INSTALLED, PIR WILL BE PLACED ON ESTABLISHED GLIDE-
SLOPE PHASING POINT. USE PIR GLIDESLOPE ANTENNA CONNECTED TO PIR SET TO MEA-
SURE DDM.
AB AB0 7. HAVE SITE PERSONNEL SELECT TRANSMITTER NO. 1 AS MAIN AND SET TRANSMITTER POWER
SWITCHES ON.
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 56 DAY ON OUT 1-008
AB AD0 8. OBSERVE PIR INDICATION. READINGS SHOULD BE WITHIN ±20 DDM OF FACILITY REFERENCE
DATA. IF READINGS ARE NOT IN TOLERANCE THEN MAINTENANCE IS REQUIRED.
AB AB0 9. HAVE SITE PERSONNEL SELECT TRANSMITTER NO. 2 AS MAIN AND REPEAT STEP 8.
AB 000 10. RETURN SYSTEM TO NORMAL OPERATING CONFIGURATION.
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
1-008 4
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 84 DAY OFF OUT 1-009
@ CORROSION PREVENTION AND CONTROL
• ENSURE ALL POWER TO THE UNIT UNDER INSPECTION IS OFF BEFORE PROCEED-
ING WITH STEP 1.
• ELECTROLYTE IS A SULFURIC ACID SOLUTION AND IS TOXIC. AVOID EYE AND SKIN
CONTACT AND BREATHING OF FUMES. WEARING OF FULL FACE SHIELD, RUBBER
GLOVES AND APRON, IS REQUIRED.
NOTE
CORRECTIVE ACTION WILL BE INITIATED IMMEDIATELY WHEN CORROSION IS FOUND
TO PREVENT FURTHER DETERIORATION OF THE EQUIPMENT. CORROSION IS THE
DETERIORATION OF A MATERIAL BY CHEMICAL OR ELECTRO-CHEMICAL REACTION
WITH ITS ENVIRONMENT.
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
21-009
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 84 DAY OFF OUT 1-009
AB 000 1. VISUALLY INSPECT THE COMPLETE SYSTEM (INCLUDING BATTERY TERMINALS) FOR EVIDENCE
OF CORROSION. PROCEDURES FOR IDENTIFICATION, ISOLATION AND CONTROL OF CORRO-
SION ARE IDENTIFIED IN THE FOLLOWING TECHNICAL ORDERS.
A. TO 1-1-8 APPLICATION AND REMOVAL OF ORGANIC COATINGS, AEROSPACE AND NON-
AEROSPACE EQUIPMENT.
B. TO 1-1-700 CORROSION PREVENTION AND CONTROL, GROUND COMMUNICATIONS-ELEC-
TRONIC EQUIPMENT (C-E).
C. TO 31Z-10-37 GENERAL ENGINEERING TECHNICAL MANUAL—CORROSION PREVENTION
AND DETECTION.
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 168 DAY ON OUT 1-010
@ MONITOR DIGITAL READOUT INDICATIONS AND UPPER/LOWER ALARM LIMITS
NOTE
NOTIFY PERSONNEL AT THE REMOTE CONTROL/DISPLAY UNIT THAT CHECKS ARE
BEING MADE THAT MAY CAUSE ABNORMAL INDICATIONS.
AB AB0 1. OPEN CONTROL UNIT. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO. 1 AND
SET MONITOR BYPASS/NORMAL SWITCH TO BYPASS.
AB AC0 2. OBSERVE AND RECORD MONITORS NO. 1 AND NO. 2 DIGITAL READOUT NORMAL INDICATIONS
OF DISPLAY SELECTOR SWITCH. OBSERVE LOWER AND UPPER LIMIT INDICATIONS UTILIZING
MONITOR ALARM TEST SWITCH (REF FIGURE W1-004).
AB AB0 3. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO. 2 AND REPEAT STEP 2.
AB 000 4. RETURN SYSTEM TO NORMAL OPERATING CONFIGURATION.
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
1-010
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 168 DAY ON OUT 1-011W1-004
SWITCH POSITION NORMAL LOWER UPPER
TEST DDM 0.500 ± 0.040 0.426 ± 0.040 0.557 ± 0.040
PATH DDM (INT MON) 0.000 ± 0.050 N/A 0.050
PATH DDM (NEAR FIELD) 0.000 ± 0.050 N/A 0.050
WIDTH DDM 0.175 TO 0.020 0.155 0.195
RF LEVEL (% NORMAL 100.0 +15.0/-10.0 90.0 N/A
% MOD FACILITY REF ± 4.0% 4.0 BELOW REF 4.0 ABOVE REF
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
1-011
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 168 DAY ON OUT 1-012
@ VSWR CHECK
1. EQUIPMENT REQUIRED:
A. VECTOR VOLTMETER (VVM).
B. BIDIRECTIONAL COUPLER.
C. TEST CABLE, 4 FT RG-214 WITH N-TYPE MALE AND N-TYPE FEMALE CONNECTORS.
D. DUMMY LOAD, 1 EACH BIRD 80M AND BIRD 80F.
AB AB0 2. OPEN CONTROL UNIT. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO. 1 AND
SET MONITOR BYPASS/NORMAL SWITCH TO BYPASS.
AB AD0 3. DECREASE TRANSMITTER NO. 1 OUTPUT POWER TO ZERO (FULLY CCW) AND SET TRANSMIT-
TER POWER SWITCH TO OFF.
AB AE0 4. OPEN CHANGEOVER UNIT AND DISCONNECT THE CARRIER OUTPUT CABLE W1 FROM THRU-
LINE BODY. DUMMY LOAD SBO OUTPUT CABLE AND PORT.
AB AD0 5. CONNECT TEST EQUIPMENT AS SHOWN IN FIGURE W1-005.
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
1-012
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 168 DAY ON OUT 1-012
NOTE
PLACE VVM dB SWITCH TO +10 dB TO PREVENT POSSIBLE DAMAGE TO VVM.
AB AD0 6. SET TRANSMITTER NO. 1 POWER SWITCH TO ON AND ADJUST POWER OUTPUT CONTROL TO OBTAIN 0 dB ON CHANNEL “A” OF THE VVM.
AB C00 7. MEASURE dB DIFFERENCE IN VVM CHANNEL “A” AND CHANNEL “B” INDICATIONS. IT MUST BE AT LEAST -20.8 dB OR GREATER WHICH CORRESPONDS TO A VSWR OF 1.2:1 OR LESS.
AB AD0 8. SET TRANSMITTER NO. 1 POWER SWITCH TO OFF.
AB C00 9. DISCONNECT CABLE W1 FROM BIDIRECTIONAL COUPLER AND CONNECT CABLE W2 TO THE
BIDIRECTIONAL COUPLER. DUMMY LOAD CABLE W1.
AB AD0 10. SET TRANSMITTER NO. 1 POWER SWITCH TO ON.
AB C00 11. MEASURE dB DIFFERENCE IN VVM CHANNEL “A” AND CHANNEL “B” INDICATIONS. IT MUST BE AT
LEAST -20.8 dB OR GREATER WHICH CORRESPONDS TO A VSWR OF 1.2:1 OR LESS.
AB AD0 12. SET TRANSMITTER NO. 1 POWER SWITCH TO OFF.
AB 000 13. RETURN SYSTEM TO NORMAL OPERATIING CONFIGURATION.
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 168 DAY ON OUT 1-013W1-005
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
1-013
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 336 DAY ON OUT 1-014
1. ACCOMPLISH 336 DAY PMI IN ACCORDANCE WITH 31R4-2GRN31-2, CHAPTER 6, TABLE 6-15, PAGES 6-146 THRU 6-154 “NULL REFERENCE GLIDESLOPE FACILITY 336 DAY PMI PROCE-
DURES.”
2. ALL PMI DATA WILL BE DOCUMENTED ON AFTO 295 GLIDESLOPE REFERENCE DATA SHEET.
NOTE
TABLE 6-15, 336 DAY PMI, INCLUDES THE 56, 84, AND 168 DAY PMI INTERVALS. AFTER
COMPLETION OF ANNUAL PMI, THE WORKCENTER WILL RESET THE 56, 84, AND 168
DAY INSPECTION DUE DATES ON PMI SCHEDULE TO CORRELATE WITH 336 DAY PMI.
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
1-014 4
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 336 DAY ON OUT 1-014
@ BATTERY PERFORMANCE TEST.
LETHAL VOLTAGE IS USED IN THE OPERATIONAL CHECKOUT OF THIS UNIT. DEATH ON
CONTACT MAY RESULT IF PERSONNEL FAIL TO OBSERVE THE FOLLOWING SAFETY
PRECAUTIONS. REMOVE WATCHES AND RINGS AND EXERCISE EXTREME CAUTION
WHEN WORKING INSIDE THE EQUIPMENT THROUGHOUT THE REMAINDER OF THIS
PROCEDURE.
AB G00 1. CHECK BATTERY BOX AIR BLOWER FOR PROPER OPERATION.
AB G00 2. CHECK ALL VENTS TO MAKE SURE THEY ARE CLEAN AND NOT CLOGGED.
AB G00 3. OPEN BATTERY CHARGER CIRCUIT BREAKERS 11CB4 AND 11CB5.
AB G00 4. OBSERVE THE EQUIPMENT OPERATES NORMALLY FOR 30 MINUTES.
AB 000 5. COMPLETETY POWER SYSTEM DOWN TO RESTART THE BATTERY CHARGING SYSTEM.
AB 000 6. RETURN SYSTEM TO NORMAL OPERATING CONFIGURATION.
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 336 DAY ON OUT 1-015
@ SYSTEM TRANSFER/SHUT DOWN TEST
AB AD0 1. OPEN THE ON-AIR TRANSMITTER AND PLACE EITHER 90HZ OR 150 HZ SWITCH TO THE OFF
POSITION. ENSURE SYSTEM CYCLES TO THE STAND-BY TRANSMITTER.
AB AD0 2. OPEN THE STAND-BY TRANSMITTER AND PLACE EITHER 90 HZ OR 150 HZ SWITCH TO THE OFF
POSITION. ENSURE SYSTEM SHUTS DOWN.
AB 000 3. RETURN SYSTEM TO NORMAL OPERATING CONFIGURATION.
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
1-015
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB INTRODUCTION 2-001
SERVICING AND LUBRICATION
1. THESE INSPECTION WORKCARDS PROVIDE THE REQUIREMENTS FOR SERVICING/LUBRICA-
TION AND WILL BE USED AS A GUIDE IN PERFORMING THE INSPECTION TO ENSURE THAT NO
ITEM IS OVERLOOKED. THE CARD SIZE AFFORDS CONVENIENT HANDLING BY MAINTENANCE
PERSONNEL WHILE PERFORMING AN INSPECTION.
2. DETAILED INSTRUCTIONS FOR THE USE OF THESE CARDS AND THE DESCRIPTION AND APPLI-
CATION OF OTHER FORMS AND CHARTS TO BE USED IN CONJUNCTION WITH THESE CARDS
ARE CONTAINED IN 00-20 SERIES TECHNICAL ORDERS.
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
2-001
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 84 DAY OFF OUT 2-002
@ GENERAL CLEANING.
AB G00 1. USE VACUUM CLEANER AND BLOWER ATTACHMENT TO CLEAN EQUIPMENT, BATTERY
CHARGER, HEATER, AND AIR VENTS.
2. VACUUM FLOOR, WALLS, WORKBENCH, AND TOP OF ALL EQUIPMENT CABINETS AND/OR
PANELS.
AB G00 3. USE VACUUM CLEANER AND BLOWER ATTACHMENT TO REMOVE DUST AND DEBRIS FROM
EQUIPMENT DRAWERS.
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
2-002
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 168 DAY ON IN 2-003
@ AIR CONDITIONER FILTER CLEANING.
1. REMOVE FILTER FROM GRILLE ASSEMBLY.
AB G00 2. REMOVE TRAPPED DUST AND DIRT FROM FILTER.
AB G00 3. IF, AFTER THOROUGH CLEANING, FILTER REMAINS CLOGGED, DISCARD AND REPLACE IT.
AB G00 4. PLACE FILTER INTO GRILLE ASSEMBLY. SECURE IN PLACE WITH SCREWS AND WASHERS.
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
2-003
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 168 DAY SERVICE ON IN 2-004
@ VENTILATOR INLET INTERIOR (RFI) FILTER.
AB G00 1. CLEAN VENTILATOR INLET INTERIOR FILTER BY USING A VACUUM CLEANER WITH A NARROW
TOOL INSERTED BETWEEN VENT HOOD AND INSERT SCREEN.
AB G00 2. IF NECESSARY, USE A STIFF-BRISTLED BRUSH TO LOOSEN TRAPPED PARTICLES FROM INSERT
SCREEN.
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
2-004
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 168 DAY SERVICE ON IN 2-005
@ VENTILATOR INLET EXTERIOR (AIR) FILTER.
AB G00 1. REMOVE FILTER AND CLEAN WITH A VACUUM CLEANER.
AB G00 2. IF, AFTER THOROUGH CLEANING, FILTER REMAINS CLOGGED, DISCARD AND REPLACE IT.
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
2-005
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 168 DAY ON IN 2-006
@ VENTILATOR OUTLET INTERIOR FILTER
AB G00 1. REMOVE FILTER AND CLEAN WITH A VACUUM CLEANER.
AB G00 2. IF, AFTER THOROUGH CLEANING, FILTER REMAINS CLOGGED, DISCARD AND REPLACE IT.
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
2-006
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 5-001REPAIR RESTRICTIONS
REPAIR RESTRICTIONS
1. BASE LEVEL REPAIR RESTRICTIONS.
A. REPAIRS REQUIRED TO RETURN THE ITEM TO A SERVICEABLE CONDITION WILL BE ACCOM-
PLISHED AT BASE LEVEL CONSISTENT WITH THE AUTHORIZATIONS (SMR CODES) FOR
REPAIR LEVEL CONTAINED IN THE APPROPRIATE ILLUSTRATED PARTS BREAKDOWN MAN-
UAL.
B. REPAIR RESTRICTIONS WILL BE REVIEWED PERIODICALLY BY UTILIZING MAINTENANCE
DATA AND SUPPLY INFORMATION TO DETERMINE WHETHER BASE LEVEL REPAIR AUTHORI-
ZATIONS CAN BE EXTENDED.
C. FOR MAINTENANCE DATA REPORTING PURPOSES NRTS CODE 1 (REPAIR NOT AUTHO-
RIZED) WILL BE USED ONLY WHEN REPAIRS REQUIRED TO MAKE THE ITEM SERVICEABLE
INCLUDE ONE OR MORE OF THE CONDITIONS LISTED IN THIS SECTION FOR THAT PARTICU-
LAR ITEM.
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
5-001
WORK
AREA
WORK UNIT CODE
INSPECTION
REQUIREMENTS
ELECTRICAL POWER SERVICE FIGURE CARD NO.
SYS SUB 5-002REPAIR RESTRICTIONS
ALL REPAIRS ON PRINTED CIRCUIT BOARDS WILL BE RESTRICTED TO THE TECHNICAL REPAIR
CENTER (TRC). CONSULT APPLICABLE TO FOR ADDITIONAL REPAIR RESTRICTIONS.
CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER
TO 31R4-2GRN31-6WC-1
5-002
| SCHEDULED PERIODIC INSPECTION WORKCARDS |
| RADIO TRANSMITTING SET (GLIDESLOPE STATION) AN/GRN-31(V) |
| Part no. 098302-0100/0300 (nsn 5825-01-046-9975) WITH TRAINER PART NO. 098302-0200 (NSN 5825-01-046-8596) |
| 1. THESE INSPECTION WORKCARDS PROVIDE THE REQUIREMENTS FOR INSPECTION AND WILL BE USED AS A GUIDE IN PERFORMING THE INSPECTION T... |
| 2. DETAILED INSTRUCTIONS FOR THE USE OF THESE CARDS AND THE DESCRIPTION AND APPLICATION OF OTHER FORMS AND CHARTS TO BE USED IN CONJUNCTION WITH THESE CARDS ARE CONTAINED IN 00 -20 SERIES TECHNICAL ORDERS. |