TO 31R4-2GRN30-6WC-1 SCHEDULED PERIODIC INSPECTION WORKCARDS RADIO TRANSMITTING SET (DUAL FREQUENCY LOCALIZER STATION) AN/GRN-30(V)

View the file

Other files

File Type Posted
Amendment 01.pdf PDF
31Z3-822-2 .pdf PDF
MIL-STD-188-124B.pdf PDF
31R4-2GRN31-2.pdf PDF
31R4-2GRN29-6WC-1.pdf PDF
31R2-2GRT-102-WA-1.pdf PDF
31R2-2GRT-104.pdf PDF
31R4-2FRN45-2-33FI-1.pdf PDF
31R4-2GRN31-3.pdf PDF
31R4-2GRN30-2-1.pdf PDF
31R4-2GRN30-3.pdf PDF
31R2-2GRR-116WC-1.pdf PDF
31R4-2FRN45-6WC-1.pdf PDF
31R4-2GRN29-4.pdf PDF
31R2-2GRR-112BA_CHG18.pdf PDF
31R4-2FRN45-2-33SD-1.pdf PDF
31R4-2GRN29-2 CHG 1.pdf PDF
31R4-2FRN45-2-33GE-1.pdf PDF
31R2-2GRR-114B_CHG7.pdf PDF
31R4-2GRN30-4 CHG 3.pdf PDF
31R4-2FRN45-2-33JG-1.pdf PDF
31R4-2GRN29-3 CHG 1.pdf PDF
31R4-2FRN45-4-33PL-1 CHG 4.pdf PDF
TO 31R4-2GRN31-4.pdf PDF
31R4-2GRN31-6WC-1.pdf PDF
31R4-2FRN-41 CHANGE 6.pdf PDF
31R4-2FRN45-2-33GS-1.pdf PDF
31R2-2GRT-106WC-1.pdf PDF
FA4486 12 R 012 GATR NAVAID RFP.pdf PDF
Lajes Field SON GATR Longhaul Upgrade 17 may 12.pdf PDF
Lajes Field MHDS for Longhaul Project.pdf PDF
PP Questionnaire.pdf PDF
Blanket Waiver ATCALS Shelter Fiber Equipment Installation.pdf PDF
Subcontractor Consent Form.pdf PDF
AF Form 3000.xls XLS spreadsheet
Synopsis - Longhaul upgrade.doc DOC document
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TO 31R4-2GRN30-6WC-1

1 SEPTEMBER 2006 CHANGE 4 28 SEPTEMBER 2011

DISTRIBUTION STATEMENT C - Distribution authorized to U S. Government agencies and their contractors for administrative or operational use, (31 March 2011). Refer other requests for this document to OC-ALC/GKAAB, Tinker AFB, Oklahoma 73145-9155.

WARNING - This document contains technical data whose export is restricted by the Arms Export Control Act (Title 22, U.S.C. 2751 et seq.) or Executive Order 12470. Violations of these export laws are subject to severe criminal penalties. Disseminate in accordance with provisions of DoD Directive 5230.25.

HANDLING AND DESTRUCTION NOTICE - Handle in compliance with distribution statement and destroy by any method that will prevent disclosure of the contents or reconstruction of the document.

Published under the authority of the Secretary of the Air Force.

SCHEDULED PERIODIC INSPECTION WORKCARDS

RADIO TRANSMITTING SET (DUAL FREQUENCY LOCALIZER STATION) AN/GRN-30(V)

PART NO. 098303-0100/0300 (NSN 5825-01-219-6243)

PART NO. 098303-0200 (NSN 5825-01-046-9974)

A CHANGE 4

LIST OF EFFECTIVE CARDS

Insert latest change card and destroy superseded cards.

NOTE: The portions of the text affected by the changes are indicated by a vertical line in the outer margin of the card. Changes to illustrations are indi-cated by miniture pointing hands.

DATES OF ISSUE FOR ORIGINAL AND CHANGED CARDS ARE:

The total number of cards in this publication is 30, consisting of the following:

Title A I-01 - I-02 I-03 1-001 1-002 1-003 - 1-004

1-005 1-006 1-007 1-008 1-009 1-010 1-011

1-012 - 1-013 1-014 - 1-016 1-017 1-018 - 1-019 2-001 - 2-006 5-001 - 5-002

Original . . . . . . . . . . . 0 . . . . . . . .1 September 2006 Change . . . . . . . . . . . . 3 . . . . . . . . . . . 21 June 2011

Change . . . . . . . . . . . . .1. . . . . . . . . . 16 October 2009 Change . . . . . . . . . . . . .4. . . . . . . .28 September 2011

Change . . . . . . . . . . . . 2. . . . . . . . . . . 31 March 2011

PAGE NO. CHANGE NO. PAGE NO. CHANGE NO. PAGE NO. CHANGE NO.

PUBLICATION NUMBER

INSPECTION REQUIREMENTS

TABLE OF CONTENTS

FIGURE CHANGE NO. CARD NO.

INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I-02

1 INSPECTION REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-001

A 56 DAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-002 B 84 DAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-009 C 168 DAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-010 D 336 DAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-019

2 SERVICE AND LUBE REQUIREMENTS (84 AND 168 DAY) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-001

3 SPECIAL INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N/A

4 TIME REPLACEMENT ITEMS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N/A

5 REPAIR RESTRICTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-001

I-01

INSPECTION REQUIREMENTS

INTRODUCTION

FIGURE CHANGE NO. CARD NO.

I-02

GENERAL INFORMATION

1. THESE WORKCARDS CONTAIN ALL REQUIREMENTS FOR ACCOMPLISHING SCHEDULED MAINTENANCE ON GROUND ELEC- TRONIC (C-E) EQUIPMENT DURING ITS ENTIRE SERVICE LIFE. IT ESTABLISHES INSPECTION, ACCESSORY REPLACEMENT, DEPOT LEVEL, AND BASE LEVEL REPAIR REQUIREMENT/RESTRICTIONS. THESE REQUIREMENTS ARE PRIMARILY TECHNI- CAL IN NATURE AND THE CONDITIONS LISTED ARE INTENDED TO DIRECT ATTENTION TO KNOWN PROBLEM AREAS. THESE REQUIREMENTS ARE DEVELOPED FOR NEW C-E EQUIPMENT THROUGH MAINTENANCE ENGINEERING AND COMPARISON OF SIMILAR INSTALLATIONS, OR IN-SERVICE C-E EQUIPMENT. THE INTERVAL BETWEEN THE ACCOMPLISHMENT OF A REQUIREMENT IS INTENDED TO BE THE LONGEST PERIOD OF TIME THAT AN ITEM OR COMPONENT CAN SAFELY OPERATE WITHOUT AN INSPECTION OR OBSERVATION. THESE REQUIREMENTS AND INSPECTION INTERVALS ARE THE MAXIMUM AND SHOULD NEVER BE EXCEEDED. LOCAL CONDITIONS (TYPE OF MISSION, SPECIAL UTILIZATION, GEOGRAPHICAL LOCA- TION, ETC), MAY DICTATE MORE FREQUENT INSPECTIONS, REPLACEMENT OR MORE THOROUGH INSPECTIONS; THERE- FORE, COMMANDS, LOCAL COMMANDERS, AND THEIR MAINTENANCE OFFICERS HAVE THE PREROGATIVE TO INCREASE THE FREQUENCY OR SCOPE OF ANY REQUIREMENT, AND ARE EXPECTED TO EXERCISE THIS PREROGATIVE.

2. THE INSPECTIONS PRESCRIBED BY THESE WORKCARDS WILL BE ACCOMPLISHED AT SPECIFIED PERIODS BY AIR FORCE ORGANIZATIONAL ACTIVITIES WITH ASSISTANCE PROVIDED BY AFETS AND SMTS WHEN REQUIRED. COMPLIANCE WITH THE PROVISIONS OF THESE WORKCARDS IS REQUIRED TO ASSURE THAT LATENT DEFECTS ARE DISCOVERED AND COR-

RECTED BEFORE MALFUNCTIONING OR SERIOUS TROUBLE RESULTS.

INSPECTION REQUIREMENTS

INTRODUCTION

FIGURE CHANGE NO. CARD NO.

I-02

NOTE

SHOULD THE PARAMETER BEING MEASURED APPROACH THE ESTABLISHED LIMITS, ACTION SHOULD BE

TAKEN TO CORRECT THE MARGINAL CONDITION.

3. THE INSPECTION REQUIREMENTS ARE STATED IN SUCH A MANNER AS TO ESTABLISH WHAT EQUIPMENT IS TO BE INSPECTED, WHEN IT IS TO BE INSPECTED, AND WHAT CONDITIONS ARE TO BE SOUGHT. IN SCOPE, THE REQUIREMENTS ARE DESIGNED TO DIRECT THE ATTENTION OF MAINTENANCE PERSONNEL TO COMPONENTS AND AREAS WHERE DEFECTS MAY EXIST AS A RESULT OF USAGE UNDER NORMAL OPERATING CONDITIONS. THEY ARE NOT INTENDED TO PROVIDE COVERAGE FOR ROUTINE CLEANING, WASHING, ETC., NOR ARE THEY DESIGNED TO LEAD TO THE DETECTION OF ISOLATED DISCREPANCIES THAT MAY OCCUR ON A ONE-TIME BASIS, OR DISCREPANCIES THAT ARE THE RESULT OF CARE- LESSNESS, ABUSE OR POOR MAINTENANCE PRACTICES. DURING ACCOMPLISHMENT OF THE SPECIFIC REQUIREMENTS DIRECTED BY THESE WORKCARDS, MAINTENANCE PERSONNEL SHOULD OBSERVE BOTH THE EQUIPMENT BEING INSPECTED AND THE COMPONENTS IN THE SURROUNDING AREA FOR DEFECTS OR IRREGULARITIES NOT WITHIN THE SCOPE OF THE REQUIREMENTS. REQUIREMENTS REQUIRING THE USE OF ELECTRICAL POWER FOR ACCOMPLISHMENT ARE IDENTIFIED BY A COMMERCIAL “@” SYMBOL PRECEDING THE PARAGRAPH NUMBER FOR THE REQUIREMENTS.

4. THE REPLACEMENT SCHEDULE DIRECTS REPLACEMENT OF ITEMS AT A SPECIFIC TIME WHEN A FAILURE WOULD COMPRO- MISE SAFETY OR OPERATION BEYOND REASONABLE LIMITS OR DEFINITELY CAUSE A MISSION FAILURE. ALSO CONSID- ERED ARE ANY HIGH COST ITEMS WHO’S FAILURE WOULD RESULT IN CONDEMNATION AND ANY SHORT LIFE ITEMS WHICH WOULD REQUIRE FREQUENT UNSCHEDULED MAINTENANCE. ITEMS NOT LISTED WILL BE KNOWN AS “CONDITION ITEMS”

AND WILL BE REPLACED ONLY WHEN NECESSARY.

INSPECTION REQUIREMENTS

INTRODUCTION

FIGURE CHANGE NO. CARD NO.

3 I-03

5. BASE LEVEL REPAIR RESTRICTIONS DESCRIBES THE REPAIRS WHICH ARE NOT AUTHORIZED AT BASE LEVEL.

6. THE TIME IN MAN-MINUTES FOR ACCOMPLISHMENT OF REQUIREMENTS REFLECTS ONLY THE TIME REQUIRED FOR INSPECTION OR REPLACEMENT. THIS TIME DOES NOT INCLUDE TIME REQUIRED TO GAIN ACCESS TO THE EQUIPMENT TO FACILITATE ACCOMPLISHMENT. THOSE FACTORS (PERSONNEL AND EQUIPMENT SHORTAGES, LACK OF PARTS, ADVERSE WORKING CONDITIONS, AND QUALIFICATIONS OF PERSONNEL) WHICH WILL DIRECTLY AFFECT THE LENGTH OF TIME OF ANY SCHEDULED MAINTENANCE ACTION ARE NOT INCLUDED BECAUSE THEY CANNOT BE ACCURATELY PREDICTED.

7. THESE WORKCARDS DO NOT CONTAIN DETAILED INSTRUCTIONS FOR TROUBLESHOOTING TO FIND CAUSES FOR MAL- FUNCTIONS, NOR DO THEY CONTAIN INSTRUCTIONS FOR REPAIR, ADJUSTMENT, OR OTHER MEANS OF RECTIFYING DEFECTIVE CONDITIONS. PROPER INSTALLATION OF A PIECE OF EQUIPMENT OR ACCESSORY IS NOT NECESSARILY WITHIN THE SCOPE OF THESE WORKCARDS AS ADEQUACY AND COMPLETENESS OF INSTALLATION WILL HAVE BEEN DETERMINED AT THE TIME OF INSTALLATION. APPLICABLE PORTIONS OF THE APPROPRIATE MAINTENANCE MANUAL SHOULD BE CONSULTED TO OBTAIN “HOW TO” MAINTENANCE INSTRUCTIONS AS THEY ARE BEYOND THE SCOPE OF THESE

WORKCARDS.

8. FOR THE PURPOSE OF CLARIFICATION OF TERMS USED IN THESE WORKCARDS, THE FOLLOWING DEFINITIONS ARE GIVEN:

SPECIFIED- REFERS TO A DEFINITE AMOUNT, OPERATION, OR LIMITATION WHICH HAS BEEN ESTABLISHED AND IS CON- TAINED IN APPLICABLE DIRECTIVES. EVIDENCE- PROOF OF A SUSPECTED OR EXISTING UNSATISFACTORY CONDITION.

SECURE-MEANS THE COMPONENT IS PROPERLY MOUNTED OR ATTACHED TO RELATED EQUIPMENT, INCLUDING APPLICA- BLE SAFETYING. ACCESSIBLE- THE TERM APPLIED TO EQUIPMENT THAT MAY BE INSPECTED WITHOUT FURTHER DISAS- SEMBLY OR REMOVAL OF COVERS, CLOSURES, PANELS, ETC., OTHER THAN THOSE REQUIRED TO ACCOMPLISH THE MORE

SPECIFIC REQUIREMENTS APPLICABLE TO THE PARTICULAR INSPECTIONS.

INSPECTION REQUIREMENTS

INTRODUCTION

FIGURE CHANGE NO. CARD NO.

3 I-03

9. CHANGES AND REVISIONS TO THESE WORKCARDS WILL BE PUBLISHED WHEN NECESSARY TO ADD, DELETE, OR CHANGE FREQUENCY OR SCOPE OF REQUIREMENTS. SUCH CHANGES WILL BE BASED ON FACTUAL DATA ACCUMULATED AS A RESULT OF MAINTENANCE EXPERIENCE WITH THE EQUIPMENT. RECOMMENDATIONS PROPOSING CHANGES TO THESE WORKCARDS SHOULD BE SUBMITTED ON AFTO FORM 22 IN ACCORDANCE WITH TO 00-5-1 TO THE USING COMMAND HEAD-

QUARTERS.

NOTE

ALL CORROSION WILL BE TREATED IN ACCORDANCE WITH TO 1-1-700.

MAN

MIN

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

INTRODUCTION

1. THESE INSPECTION WORKCARDS PROVIDE THE REQUIREMENTS FOR INSPECTION AND WILL BE

USED AS A GUIDE IN PERFORMING THE INSPECTION TO ENSURE THAT NO ITEM IS OVERLOOKED.

THE CARD SIZE AFFORDS CONVENIENT HANDLING BY MAINTENANCE PERSONNEL WHILE PER-

FORMING AN INSPECTION.

2. DETAILED INSTRUCTIONS FOR THE USE OF THESE CARDS AND THE DESCRIPTION AND APPLICA-

TION OF OTHER FORMS AND CHARTS TO BE USED IN CONJUNCTION WITH THESE CARDS ARE

CONTAINED IN 00-20 SERIES TECHNICAL ORDERS.

1-001

INSPECTION REQUIREMENTS 1-001

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

@ TRANSMITTER WAVESHAPES (AUDIO PHASE)

1. EQUIPMENT REQUIRED.

A. OSCILLOSCOPE

B. TWO TEST CABLES, BNC TO PHONE JACK

AA AB0 2. OPEN CONTROL UNIT. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO. 1

AND SET MONITOR BYPASS/NORMAL SWITCH TO BYPASS.

AA AD0 3. MEASURE AND RECORD COURSE AND CLEARANCE CSB AND SBO TRANSMITTER OUTPUT

POWER USING REFERENCE WATT ELEMENTS. (FACILITY REF CARRIER ± .5W, SBO ± 1mW)

AA AD0 4. CONNECT OSCILLOSCOPE EXTERNAL SYNC TO ON AIR TRANSMITTER 60 HZ SYNC JACK WITH

ONE TEST CABLE.

AA AD0 5. CONNECT OSCILLOSCOPE VERTICAL INPUT TO ON AIR TRANSMITTER CSB TEST JACK WITH

OTHER TEST CABLE.

56 DAY ON OUT 1-002

1-002

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

NOTE

ENSURE OSCILLOSCOPE VERTICAL INPUT IS SET TO INPUT DC.

AA AD0 6. OBTAIN WAVESHAPE ON OSCILLOSCOPE AND COMPARE TO FIGURE W1-001. ENSURE WAVE-

SHAPE IS CORRECT.

NOTE

ADJUST SIGNAL TRACE OF OSCILLOSCOPE TO GROUND REFERENCE ON BOTTOM

GRATICULE.

AA AD0 7. SWITCH TEST CABLE IN STEP 5 TO THE SBO TEST JACK. OBTAIN WAVESHAPE ON OSCILLO-

SCOPE AND COMPARE TO FIGURE W1-002. ENSURE WAVESHAPE AND PERCENT OF MODULA-

TION ARE CORRECT. OVER MODULATION OF THE SBO SIGNAL IS INDICATED BY THE BOTTOM

OF THE WAVE FORM BEING FLATTENED.

AA AD0 8. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO.2 AND REPEAT STEPS 3-7.

AA BC0 9. REPEAT STEPS 2 - 8 FOR BOTH CLEARANCE TRANSMITTERS.

AA 000 10. RETURN SYSTEM TO NORMAL OPERATING CONFIGURATION.

56 DAY ON OUT 1-002

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

56 DAY ON OUT 1-003

1-003

W1-001

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

1-004

56 DAY ON OUT 1-004W1-002

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

@ TRANSMITTER PERCENTAGE OF MODULATION AND MODULATION BALANCE TEST

1. EQUIPMENT REQUIRED:

A. PORTABLE ILS RECEIVER (PIR).

B. SNIFFER ASSEMBLY.

C. ONE 6 FT LENGTH RG-223 OR EQUIVALENT TEST CABLE WITH BNC CONNECTORS.

D. 50 OHM BIRD 80M DUMMY LOADS.

E. 50 OHM BIRD 80F DUMMY LOADS.

F. 50 WATT, BIRD 8085 DUMMY LOADS.

NOTE

THIS PROCEDURE REQUIRES EQUIPMENT DOWNTIME. ENSURE THE APPROPRIATE

PARTIES ARE ADVISED BEFORE THIS PROCEDURE IS ACCOMPLISHED.

56 DAY ON OUT 1-005

1-005

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

AA AB0 2. OPEN CONTROL UNIT. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO. 1 AND

SET MONITOR BYPASS/NORMAL SWITCH TO BYPASS. SET COURSE TRANSMITTER KEYER

SWITCHES TO OFF.

AA AE0 3. SET ALL TRANSMITTER POWER SWITCHES TO OFF.

AA BC0 4. OPEN COURSE CHANGEOVER UNIT. DISCONNECT SIDEBAND OUT CABLE, DUMMY LOAD CABLE

AND PORT.

AA AD0 5. CONNECT TEST EQUIPMENT AS SHOWN IN FIGURE W1-003.

AA AD0 6. INSERT THE SNIFFER INTO THE COURSE CARRIER THRU-LINE BODY.

AA AD0 7. TURN ON SELECTED COURSE TRANSMITTER ONLY.

AA AD0 8. SET PIR TO MEASURE DMM USING BOTH TONES. VERIFY MODULATION BALANCE, PIR SHOULD

INDICATE FACILITY REFERENCE DATA ±0.010 DDM.

AA AD0 9. SET PIR TO MEASURE 90 HZ PERCENT OF MODULATION.

AA AD0 10. VERIFY 90 HZ MODULATION, PIR SHOULD INDICATE FACILITY REFERENCE DATA ±2%.

AA AD0 11. SET PIR TO MEASURE 150 HZ PERCENT OF MODULATION.

AA AD0 12. VERIFY 150 HZ MODULATION, DIGITAL PIR SHOULD INDICATE FACILITY REFERENCE DATA ±2%.

AA AB0 13. SET ALL TRANSMITTER POWER SWITCHES TO OFF.

56 DAY ON OUT 1-005

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

AA AD0 14. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO.2 AND REPEAT STEPS 7-13 FOR

COURSE TRANSMITTER NO. 2.

AA AE0 15. OPEN CLEARANCE CHANGEOVER UNIT. DISCONNECT SIDEBAND OUT (W2) CABLE, DUMMY

LOAD CABLE AND PORT. DISCONNECT COURSE CARRIER OUTPUT CABLE W1 FROM CHANGE-

OVER UNIT AND DUMMY LOAD CABLE AND PORT. ENSURE 50 WATT DUMMY LOAD IS USED FOR

PORT. ENSURE ALL COURSE AND CLEARANCE SIDEBAND OUT (W2) CABLES AND PORTS ARE

DUMMY LOADED.

AA AB0 16. CYCLE CONTROL UNIT MAIN SELECT TO TRANSMITTER NO. 1.

AA AD0 17. REMOVE SNIFFER FROM COURSE CARRIER THRU-LINE BODY AND INSERT SNIFFER INTO THE

CLEARANCE CARRIER THRU-LINE BODY. TURN ON SELECTED TRANSMITTER NO. 1 POWER

SWITCHES.

AA BC0 18. REPEAT STEPS 8-13 FOR CLEARANCE TRANSMITTER NO. 1.

AA AB0 19. CYCLE CONTROL UNIT MAIN SELECT SWITCH TO TRANSMITTER NO.2. TURN ON SELECTED

TRANSMITTER NO. 2 POWER SWITCHES AND REPEAT STEPS 8-13 FOR CLEARANCE TRANSMIT-

TER NO. 2.

AA AD0 20. ENSURE ALL TRANSMITTER POWER SWITCHES ARE SET TO OFF.

1-006

56 DAY ON OUT 1-006

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

AA 000 21. RETURN SYSTEM TO NORMAL OPERATING CONFIGURATION.

56 DAY ON OUT 1-006

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

1-007

56 DAY ON OUT 1-007W1-003

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

@ GROUND CHECK PROCEDURES (RECORD GROUND CHECK READINGS ON APPROPRIATE FORMS).

AA 000 1. EQUIPMENT REQUIRED:

A. PORTABLE ILS RECEIVER (PIR) WITH UNIPOD.

AA AB0 2. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO. 1.

AA AD0 3. PERFORM NEAR-FIELD GROUND CHECK AT THE FOLLOWING SURVEYED GROUND CHECK

MARKERS USING PIR: HALF WIDTH POINTS, CENTERLINE, AND 10 AND 20 DEGREE POINTS.

AA AD0 4. RECORD AND COMPARE READINGS TO THOSE RECORDED AFTER THE REFERENCE FLIGHT

INSPECTION. MAINTENANCE IS REQUIRED IF READINGS SHOW EVIDENCE OF EQUIPMENT

DETERIORATION. THE FOLLOWING TOLERANCES APPLY:

CENTERLINE - REF ± 5 DDM (0.005)

HALF WIDTHS - REF ± 10 DDM (0.010)

ALL OTHERS - REF ± 20 DDM (0.020)

AA AB0 5. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO. 2 AND REPEAT STEPS 3 AND 4.

AA 000 6. RETURN SYSTEM TO NORMAL OPERATING CONFIGURATION.

1-008

56 DAY ON OUT 1-008

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

@ CORROSION PREVENTION AND CONTROL

• ENSURE ALL POWER TO THE UNIT UNDER INSPECTION IS OFF BEFORE PROCEED-

ING WITH STEP 1.

• ELECTROLYTE IS A SULFURIC ACID SOLUTION AND IS TOXIC. AVOID EYE AND SKIN

CONTACT AND BREATHING OF FUMES. WEARING OF FULL FACE SHIELD, RUBBER

GLOVES AND APRON, IS REQUIRED.

NOTE

CORRECTIVE ACTION WILL BE INITIATED IMMEDIATELY WHEN CORROSION IS FOUND

TO PREVENT FURTHER DETERIORATION OF THE EQUIPMENT. CORROSION IS THE

DETERIORATION OF A MATERIAL BY CHEMICAL OR ELECTRO-CHEMICAL REACTION

WITH ITS ENVIRONMENT.

1-009

84 DAY OFF OUT 1-009

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

AB 000 1. VISUALLY INSPECT THE COMPLETE SYSTEM (INCLUDING BATTERY TERMINALS) FOR EVIDENCE

OF CORROSION. PROCEDURES FOR IDENTIFICATION, ISOLATION AND CONTROL OF CORRO-

SION ARE IDENTIFIED IN THE FOLLOWING TECHNICAL ORDERS.

A. TO 1-1-8 APPLICATION AND REMOVAL OF ORGANIC COATINGS, AEROSPACE AND NON-

AEROSPACE EQUIPMENT.

B. TO 1-1-700 CORROSION PREVENTION AND CONTROL, GROUND COMMUNICATIONS-ELEC-

TRONIC EQUIPMENT (C-E).

C. TO 31Z-10-37 GENERAL ENGINEERING TECHNICAL MANUAL—CORROSION PREVENTION

AND DETECTION.

84 DAY OFF OUT 1-009

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

@ GROUND TO SIDEBAND IN-LINE PHASING CHECK.

1. EQUIPMENT REQUIRED:

A. PORTABLE ILS RECEIVER (PIR).

B. TWO 50 OHM, BIRD 80F DUMMY LOADS.

C. ONE 50 OHM, BIRD 80M DUMMY LOAD.

D. ONE 50-WATT, BIRD 8085 DUMMY LOAD.

E. ONE 6 FOOT BNC TO AUDIO PLUG TEST CABLE.

AA AE0 2. MEASURE AND RECORD COURSE AND CLEARANCE CARRIER AND SBO TRANSMITTER OUTPUT POWER USING REFERENCE WATT ELEMENTS. (FACILITY REF CARRIER ±.5W, SBO ±1mW).

AA AB0 3. OPEN CONTROL UNIT. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO. 1 AND

SET MONITOR BYPASS/NORMAL SWITCH TO BYPASS.

AA BC0 4. SET BOTH CLEARANCE TRANSMITTER POWER SWITCHES TO OFF.

AA AD0 5. CONNECT TEST EQUIPMENT AS SHOWN IN FIGURE W1-004.

AA AD0 6. SET PIR TO READ DDM.

1-010

168 DAY ON OUT 1-010

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

AA AD0 7. OBSERVE PIR DDM INDICATION. READINGS SHOULD BE WITHIN ±20 DDM OF FACILITY REFER-

ENCE DATA. IF READINGS ARE NOT IN TOLERANCE THEN MAINTENANCE IS REQUIRED.

AA AB0 8. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO. 2 AND REPEAT STEPS 6 AND 7.

AA BC0 9. SET ALL TRANSMITTER POWER SWITCHES TO OFF.

AA AE0 10. OPEN THE COURSE CHANGEOVER UNIT AND DISCONNECT THE CARRIER W1 AND SBO W2

OUTPUT CABLES AND DUMMY LOAD THE CABLES AND PORTS. ENSURE THAT THE 50 WATT

LOAD IS USED ON THE CARRIER OUTPUT OF THE COURSE CHANGEOVER UNIT.

AA AD0 11. SET ALL TRANSMITTER POWER SWITCHES TO ON.

AA AB0 12. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO. 1 AND REPEAT STEPS 6 AND 7

FOR CLEARANCE TRANSMITTER NO. 1.

AA AB0 13. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO. 2 AND REPEAT STEPS 6 AND 7

FOR CLEARANCE TRANSMITTER NO. 2.

AA AD0 14. SET ALL TRANSMITTER POWER SWITCHES TO OFF.

AA AE0 15. DISCONNECT DUMMY LOADS FROM COURSE CARRIER AND SBO CABLES AND PORTS AND

RECONNECT CABLES TO PORTS.

AA 000 16. RETURN SYSTEM TO NORMAL OPERATING CONFIGURATION.

168 DAY ON OUT 1-010

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

1-011

168 DAY ON OUT 1-011W1-004

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

@ GROUND CHECK PROCEDURES (RECORD GROUND CHECK READINGS ON APPROPRIATE FORMS).

1. EQUIPMENT REQUIRED:

A. PORTABLE ILS RECEIVER (PIR) WITH UNIPOD.

B. TWO 50 OHM, BIRD 80F DUMMY LOADS.

C. ONE 50 OHM, BIRD 80M DUMMY LOAD.

D. ONE 50-WATT, BIRD 8085 DUMMY LOAD.

AA AB0 2. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO. 1.

AA AD0 3. PERFORM A COMPLETE NEAR-FIELD GROUND CHECK AT THE FOLLOWING SURVEYED

GROUND CHECK MARKERS (0-35 DEGREES, 150 HZ AND 90 HZ) USING PIR.

1-012

168 DAY ON OUT 1-012

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

AA AD0 4. RECORD AND COMPARE READINGS TO THOSE RECORDED AFTER THE REFERENCE FLIGHT

INSPECTION. MAINTENANCE IS REQUIRED IF READINGS SHOW EVIDENCE OF EQUIPMENT

DETERIORATION. THE FOLLOWING TOLERANCES APPLY:

CENTERLINE - REF ± 5 DDM (0.005)

HALF WIDTHS - REF ± 10 DDM (0.010)

ALL OTHERS - REF ± 20 DDM (0.020)

AA AB0 5. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO. 2 AND REPEAT STEPS 3 AND 4.

AA AD0 6. PERFORM FAR-FIELD GROUND CHECK AT THE FOLLOWING SURVEYED GROUND CHECK MARK-

ERS USING PIR; CENTERLINE AND HALF WIDTH POINTS.

AA AD0 7. RECORD AND COMPARE READINGS TO THOSE RECORDED AFTER THE REFERENCE FLIGHT

INSPECTION. MAINTENANCE IS REQUIRED IF READINGS SHOW EVIDENCE OF EQUIPMENT

DETERIORATION. THE FOLLOWING TOLERANCES APPLY:

CENTERLINE - REF ± 5 DDM (0.005)

HALF WIDTHS - REF ± 10 DDM (0.010)

AA AB0 8. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO.1 AND REPEAT STEPS 6 AND 7.

AA AD0 9. SET ALL TRANSMITTER POWER SWITCHES TO OFF.

168 DAY ON OUT 1-012

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

AA AE0 10. OPEN THE COURSE CHANGEOVER UNIT AND DISCONNECT THE CARRIER W1 AND SBO W2

OUTPUT CABLES AND DUMMY LOAD THE CABLES AND PORTS. ENSURE THAT THE 50 WATT

LOAD IS USED ON THE CARRIER OUTPUT OF THE COURSE CHANGEOVER UNIT.

AA AD0 11. SET ALL TRANSMITTER POWER SWITCHES TO ON.

AA BC0 12. PERFORM CLEARANCE ONLY FAR-FIELD GROUND CHECK AT THE FOLLOWING SURVEYED

GROUND CHECK MARKERS USING PIR; CENTERLINE AND 2 DEGREES MARKER.

AA BC0 13. RECORD AND COMPARE READINGS TO THOSE RECORDED AFTER THE REFERENCE FLIGHT

INSPECTION. MAINTENANCE IS REQUIRED IF READINGS SHOW EVIDENCE OF EQUIPMENT

DETERIORATION. THE FOLLOWING TOLERANCES APPLY:

CENTERLINE - REF ± 20 DDM (0.020)

2 DEGREE MARKERS - REF ± 20 DDM (0.020)

AA AB0 14. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO.2 AND REPEAT STEPS 12 AND 13.

AA AD0 15. SET ALL TRANSMITTER POWER SWITCHES TO OFF.

1-013

168 DAY ON OUT 1-013

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

AA AE0 16. DISCONNECT DUMMY LOADS FROM COURSE CARRIER AND SBO CABLES AND PORTS AND

RECONNECT CABLES TO PORTS.

AA 000 17. RETURN SYSTEM TO NORMAL OPERATING CONFIGURATION.

168 DAY ON OUT 1-013

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

@ MONITOR DIGITAL READOUT INDICATIONS AND UPPER/LOWER ALARM LIMITS

NOTE

NOTIFY PERSONNEL AT THE REMOTE CONTROL/DISPLAY UNIT THAT CHECKS ARE

BEING MADE THAT MAY CAUSE ABNORMAL INDICATIONS.

AA ABO 1. OPEN CONTROL UNIT. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO. 1 AND

SET MONITOR BYPASS/NORMAL SWITCH TO BYPASS.

AA AC0 2. OBSERVE AND RECORD COURSE MONITORS NO. 1 AND NO. 2 DIGITAL READOUT NORMAL INDI-

CATIONS OF DISPLAY SELECTOR SWITCH. OBSERVE LOWER AND UPPER LIMIT INDICATIONS

UTILIZING MONITOR ALARM TEST SWITCH (REF FIGURE W1-005).

AA AC0 3. OBSERVE AND RECORD CLEARANCE MONITORS NO. 1 AND NO. 2 DIGITAL READOUT NORMAL

INDICATIONS FOR THE FOLLOWING POSITIONS OF DISPLAY SELECTOR SWITCH. OBSERVE

LOWER AND UPPER LIMIT INDICATIONS UTILIZING MONITOR ALARM TEST SWITCH (REF FIGURE W1-006).

AA AB0 4. CYCLE CONTROL UNIT MAIN SEL SWITCH TO TRANSMITTER NO.2 AND REPEAT STEPS 2 AND 3.

AA 000 5. RETURN SYSTEM TO NORMAL OPERATING CONFIGURATION.

1-014

168 DAY ON OUT 1-014

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

COURSE MONITORS

SWITCH POSITION NORMAL LOWER UPPER

TEST DDM 0.500 ± 0.040 0.426 ± 0.040 0.557 ± 0.040

COURSE DDM 0.000 ± 0.011 N/A 0.011

WIDTH DDM 0.141 TO 0.175 0.141 0.175

RF LEVEL (% NORMAL 100.0 +15.0/-10.0 90.0 N/A

% MOD FACILITY REF ± 4.0% 4.0 BELOW REF 4.0 ABOVE REF

IDENT % MOD 005.0 ± 2.0 3.0 018.4 ± 003.0

1-015

168 DAY ON OUT 1-015W1-005

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

CLEARANCE MONITORS

SWITCH POSITION NORMAL LOWER UPPER

TEST DDM 0.500 ± 0.040 0.426 ± 0.040 0.557 ± 0.040

COURSE DDM 0.000 ± 0.026 N/A 0.026

WIDTH DDM 0.129 TO 0.181 0.129 0.181

RF LEVEL (% NORMAL 100.0 +15.0/-10.0 90.0 N/A

% MOD FACILITY REF ± 4.0% 4.0 BELOW REF 4.0 ABOVE REF

IDENT % MOD 005.0 ± 2.0 3.0 018.4 ± 3.0

FREQ SEP (KHZ) 9.5 ± 4.5 5.0 14.0

1-016

168 DAY ON OUT 1-016W1-006

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

1. ACCOMPLISH 336 DAY PMI IN ACCORDANCE WITH 31R4-2GRN30-2, CHAPTER 6, TABLE 6-21, PAGES 6-196 THRU 6-212 FOR DUAL FREQUENCY LOCALIZER 336 DAY PMI PROCEDURES OR

TABLE 6-22, PAGES 6-213 THRU 6-222 FOR SINGLE FREQUENCY LOCALIZER 336 DAY PMI PRO-

CEDURES.

2. ALL PMI DATA WILL BE DOCUMENTED ON AFTO 296, LOCALIZER REFERENCE DATA SHEET.

NOTE

TABLE 6-21, DUAL FREQUENCY LOCALIZER 336 DAY PMI, AND TABLE 6-22, SINGLE FRE-

QUENCY LOCALIZER 336 DAY PMI, INCLUDES THE 56, 84, AND 168 DAY PMI INTERVALS.

AFTER COMPLETION OF ANNUAL PMI, THE WORKCENTER WILL RESET THE 56, 84, AND

168 DAY PMI INSPECTION DUE DATES ON THE PMI SCHEDULE TO CORRELATE WITH

THE 336 DAY PMI.

OUT

1-017

1-017ON336 DAY

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

@ BATTERY PERFORMANCE TEST.

LETHAL VOLTAGE IS USED IN THE OPERATIONAL CHECKOUT OF THIS UNIT. DEATH ON

CONTACT MAY RESULT IF PERSONNEL FAIL TO OBSERVE THE FOLLOWING SAFETY

PRECAUTIONS. REMOVE WATCHES AND RINGS AND EXERCISE EXTREME CAUTION

WHEN WORKING INSIDE THE EQUIPMENT THROUGHOUT THE REMAINDER OF THIS

PROCEDURE.

AA D00 1. CHECK BATTERY BOX AIR BLOWER FOR PROPER OPERATION.

AA D00 2. CHECK ALL VENTS TO MAKE SURE THEY ARE CLEAN AND NOT CLOGGED.

AA D00 3. OPEN BATTERY CHARGER CIRCUIT BREAKERS 11CB4 AND 11CB5.

AA D00 4. OBSERVE THAT THE EQUIPMENT OPERATES NORMALLY FOR 30 MINUTES.

AA 000 5. COMPLETELY POWER SYSTEM DOWN TO RESTART THE BATTERY CHARGING SYSTEM.

AA 000 6. RETURN SYSTEM TO NORMAL OPERATING CONFIGURATION.

336 DAY ON OUT 1-018

1-018

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

@ SYSTEM TRANSFER/SHUT DOWN TEST

AA AD0 1. OPEN THE ON-AIR TRANSMITTER AND PLACE EITHER 90 HZ OR 150 HZ SWITCH TO THE OFF

POSITION. ENSURE SYSTEM CYCLES TO THE STAND-BY TRANSMITTER.

AA AD0 2. OPEN THE STAND-BY TRANSMITTER AND PLACE EITHER 90 HZ OR 150 HZ SWITCH TO THE OFF

POSITION. ENSURE SYSTEM SHUTS DOWN.

AA 000 3. RETURN SYSTEM TO NORMAL OPERATING CONFIGURATION.

AA AD0 4. PLACE THE ON-AIR TRANSMITTER KEYER SWITCH (S2) IN THE OFF POSITION. ENSURE SYS-

TEM CYCLES TO THE STAND-BY TRANSMITTER.

AA AD0 5. PLACE THE STAND-BY TRANSMITTER KEYER SWITCH (S2) IN THE OFF POSITION. ENSURE SYS-

TEM SHUTS DOWN.

AA 000 6. RETURN SYSTEM TO NORMAL OPERATING CONFIGURATION.

AA AD0 7. PLACE ON-AIR TRANSMITTER KEYER SWITCH (S2) IN THE CONTINUOUS POSITION. ENSURE

SYSTEM CYCLES TO THE STAND-BY TRANSMITTER.

AA AD0 8. PLACE THE STAND-BY TRANSMITTER KEYER SWITCH (S2) IN THE CONTINUOUS POSITION.

ENSURE SYSTEM SHUTS DOWN.

AA 000 9. RETURN SYSTEM TO NORMAL OPERATING CONFIGURATION.

336 DAY OUT 1-019

1-019

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

SERVICING AND LUBRICATION

1. THESE INSPECTION WORKCARDS PROVIDE THE REQUIREMENTS FOR SERVICING/LUBRICA-

TION AND WILL BE USED AS A GUIDE IN PERFORMING THE INSPECTION TO ENSURE THAT NO

ITEM IS OVERLOOKED. THE CARD SIZE AFFORDS CONVENIENT HANDLING BY MAINTENANCE

PERSONNEL WHILE PERFORMING AN INSPECTION.

2. DETAILED INSTRUCTIONS FOR THE USE OF THESE CARDS AND THE DESCRIPTION AND APPLI-

CATION OF OTHER FORMS AND CHARTS TO BE USED IN CONJUNCTION WITH THESE CARDS

ARE CONTAINED IN 00-20 SERIES TECHNICAL ORDERS.

INTRODUCTION 2-001

2-001

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

@ GENERAL CLEANING.

NOTE

THE ACCOMPLISHMENT OF THIS INSPECTION REQUIRES THE REMOVAL OF THE

LOCALIZER FROM SERVICE. ALL NECESSARY PERSONNEL WILL BE NOTIFIED THE

FACILITY WILL BE OUT OF SERVICE.

AA D00 1. USE VACUUM CLEANER AND BLOWER ATTACHMENT TO CLEAN EQUIPMENT, BATTERY

CHARGER, HEATER, AND AIR VENTS.

AA D00 2. VACUUM FLOOR, WALLS, WORKBENCH, AND TOP OF ALL EQUIPMENT CABINETS AND/OR

PANELS.

AA D00 3. USE VACUUM CLEANER AND BLOWER ATTACHMENT TO REMOVE DUST AND DEBRIS FROM

EQUIPMENT DRAWERS.

84 DAY SERVICE OFF OUT 2-002

2-002

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

@ AIR CONDITIONER FILTER CLEANING.

AA D00 1. REMOVE FILTER FROM GRILLE ASSEMBLY.

AA D00 2. REMOVE TRAPPED DUST AND DIRT FROM FILTER.

AA D00 3. IF, AFTER THOROUGH CLEANING, FILTER REMAINS CLOGGED, DISCARD AND REPLACE IT.

AA D00 4. PLACE FILTER INTO GRILLE ASSEMBLY. SECURE IN PLACE WITH SCREWS AND WASHERS.

168 DAY SERVICE ON IN

2-003

2-003

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

@ VENTILATOR INLET INTERIOR (RFI) FILTER.

AA D00 1. CLEAN VENTILATOR INLET INTERIOR FILTER BY USING A VACUUM CLEANER WITH A NARROW

TOOL INSERTED BETWEEN VENT HOOD AND INSERT SCREEN.

AA D00 2. IF NECESSARY, USE A STIFF-BRISTLED BRUSH TO LOOSEN TRAPPED PARTICLES FROM INSERT

SCREEN.

168 DAY SERVICE ON IN 2-004

2-004

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

@ VENTILATOR INLET EXTERIOR (AIR) FILTER.

AA D00 1. REMOVE FILTER AND CLEAN WITH A VACUUM CLEANER.

AA D00 2. IF, AFTER THOROUGH CLEANING, FILTER REMAINS CLOGGED, DISCARD AND REPLACE IT.

2-005

168 DAY SERVICE ON IN 2-005

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

@ VENTILATOR OUTLET INTERIOR FILTER.

AA D00 1. REMOVE FILTER AND CLEAN WITH A VACUUM CLEANER.

AA D00 2. IF, AFTER THOROUGH CLEANING, FILTER REMAINS CLOGGED, DISCARD AND REPLACE IT.

2-006

168 DAY SERVICE ON IN 2-006

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

REPAIR RESTRICTIONS

1. BASE LEVEL REPAIR RESTRICTIONS.

A. REPAIRS REQUIRED TO RETURN THE ITEM TO A SERVICEABLE CONDITION WILL BE ACCOM-

PLISHED AT BASE LEVEL CONSISTENT WITH THE AUTHORIZATIONS (SMR CODES) FOR

REPAIR LEVEL CONTAINED IN THE APPROPRIATE ILLUSTRATED PARTS BREAKDOWN MAN-

UAL.

B. REPAIR RESTRICTIONS WILL BE REVIEWED PERIODICALLY BY UTILIZING MAINTENANCE

DATA AND SUPPLY INFORMATION TO DETERMINE WHETHER BASE LEVEL REPAIR AUTHORI-

ZATIONS CAN BE EXTENDED.

C. FOR MAINTENANCE DATA REPORTING PURPOSES NRTS CODE 1 (REPAIR NOT AUTHO-

RIZED) WILL BE USED ONLY WHEN REPAIRS REQUIRED TO MAKE THE ITEM SERVICEABLE

INCLUDE ONE OR MORE OF THE CONDITIONS LISTED IN THIS SECTION FOR THAT PARTICU-

LAR ITEM.

INTRODUCTION 5-001

5-001

WORK

AREA

WORK UNIT CODE

INSPECTION

REQUIREMENTS

ELECTRICAL POWER SERVICE FIGURE CARD NO.

SYS SUB

CARD NO. WORK AREA(S) TYPE MECH RQR MECH NO CARD TIME PUBLICATION NUMBER

TO 31R4-2GRN30-6WC-1

CHANGE NO.

ALL REPAIRS ON PRINTED CIRCUIT BOARDS WILL BE RESTRICTED TO THE TECHNICAL REPAIR

CENTER (TRC). CONSULT APPLICABLE TO FOR ADDITIONAL REPAIR RESTRICTIONS.

REPAIR INSTRUCTIONS 5-002

5-002

Title
List of Effective Cards
Table of Contents
Introduction
Inspection Requirements
Servicing and Lubrication
Repair Restrictions