09 90 00 PAINTS AND COATINGS.doc
DOC document 1 MB Posted
- Solicitation number
- FA3016-17-R-0025
About this file
SOW Appendix A, Specifications, FA3016-17-R-0025
View the file
Other files
Show 40 more
Latest 50 of 63 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FA3089-12-R-XXXX
Attachment 2 to Section J
DIVISION 09 - FINISHES
SECTION 09 90 00
PAINTS AND COATINGS
SECTION 09 90 00
Revision Date: 24 Jan 11
PART 1 - GENERAL
1.2 The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN CONFERENCE OF GOVERNMENTAL INDUSTRIAL HYGIENISTS (ACGIH)
ACGIH 0100Doc (2005) Documentation of the Threshold Limit Values and Biological Exposure Indices
ASME INTERNATIONAL (ASME)
ASME A13.1 (2007) Scheme for the Identification of Piping Systems
ASTM INTERNATIONAL (ASTM)
ASTM C 669 (2000) Glazing Compounds for Back Bedding and Face Glazing of Metal Sash
ASTM C 920 (2008) Standard Specification for Elastomeric Joint Sealants
ASTM D 2092 (1995; R 2001e1) Standard Guide for Preparation of Zinc-Coated (Galvanized) Steel Surfaces for Painting
ASTM D 235 (2002; R 2008) Mineral Spirits (Petroleum Spirits) (Hydrocarbon Dry Cleaning Solvent)
ASTM D 2824 (2006) Aluminum-Pigmented Asphalt Roof Coatings, Non-Fibered, Asbestos Fibered, and Fibered without Asbestos
ASTM D 4214 (2007) Standard Test Method for Evaluating the Degree of Chalking of Exterior Paint Films
ASTM D 4263 (1983; R 2005) Indicating Moisture in Concrete by the Plastic Sheet Method
ASTM D 4444 (2008) Use and Calibration of Hand-Held Moisture Meters
ASTM D 523 (2008) Standard Test Method for Specular Gloss
ASTM E 2129 (2005) Standard Practice for Data Collection for Sustainability Assessment of Building Products
ASTM F 1869 (2004) Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride
MASTER PAINTERS INSTITUTE (MPI)
MPI 1 (Jan 2004) Aluminum Paint
MPI 10 (Jan 2004) Exterior Latex, Flat, MPI Gloss Level 1
MPI 101 (Jan 2004) Epoxy Anti-Corrosive Metal Primer
MPI 107 (Jan 2004) Rust Inhibitive Primer (Water-Based)
MPI 108 (Jan 2004) High Build Epoxy Coating, Low Gloss
MPI 11 (Jan 2004) Exterior Latex, Semi-Gloss, MPI Gloss Level 5
MPI 113 (Jan 2004) Exterior Pigmented Elastomeric Coating (Water Based)
MPI 116 (Jan 2004) Epoxy Block Filler
MPI 119 (Jan 2004) Exterior Latex, Gloss
MPI 13 (Jan 2004) Exterior Solvent-Based Semi-Transparent Stain
MPI 134 (Jan 2004) Galvanized Primer (Waterbased)
MPI 138 (Jan 2004) Interior High Performance Latex, MPI Gloss Level 2
MPI 139 (Jan 2004) Interior High Performance Latex, MPI Gloss Level 3
MPI 140 (Jan 2004) Interior High Performance Latex, MPI Gloss Level 4
MPI 141 (Jan 2004) Interior High Performance Latex MPI Gloss Level 5
MPI 144 (Jan 2004) Institutional Low Odor / VOC Interior Latex, MPI Gloss Level 2
MPI 145 (Jan 2004) Institutional Low Odor / VOC Interior Latex, MPI Gloss Level 3
MPI 146 (Jan 2004) Institutional Low Odor/VOC Interior Latex, MPI Gloss Level 4
MPI 147 (Jan 2004) Institutional Low Odor / VOC Interior Latex, Semi-Gloss, MPI Gloss Level 5
MPI 151 (Jan 2006) Interior W.B. Light Industrial Coating, MPI Gloss Level 3
MPI 153 (Jan 2006) Interior W.B. Light Industrial Coating, Semi-Gloss, MPI Gloss Level 5
MPI 154 (Jan 2006) Interior W.B. Light Industrial Coating, Gloss, MPI Gloss Level 6
MPI 16 (Jan 2004) Exterior Latex-Based Solid Hide Stain
MPI 161 (Jan 2006) Exterior W.B. Light Industrial Coating, MPI Gloss Level 3
MPI 163 (Jan 2006) Exterior W.B. Light Industrial Coating, Semi-Gloss, MPI Gloss Level 5
MPI 164 (Jan 2006) Exterior W.B. Light Industrial Coating, Gloss, MPI Gloss Level 6
MPI 19 (Jan 2004) Inorganic Zinc Rich Primer
MPI 2 (Jan 2004) Aluminum Heat Resistant Enamel (up to 427 C and 800 F
MPI 21 (Jan 2004) Heat Resistant Enamel, Gloss (up to 205 degrees C and 400 degrees F), MPI Gloss Level 6
MPI 22 (Jan 2004) Aluminum Paint, High Heat (up to 590 degrees C and 1100 degrees F.
MPI 23 (Jan 2004) Surface Tolerant Metal Primer
MPI 26 (Jan 2004) Cementitious Galvanized Metal Primer
MPI 27 (Jan 2004) Exterior / Interior Alkyd Floor Enamel, Gloss
MPI 31 (Jan 2004) Polyurethane, Moisture Cured, Clear Gloss
MPI 39 (Jan 2004) Interior Latex-Based Wood Primer
MPI 4 (Jan 2004) Interior/Exterior Latex Block Filler
MPI 42 (Jan 2004) Latex Stucco and Masonry Textured Coating
MPI 44 (Jan 2004) Interior Latex, MPI Gloss Level 2
MPI 45 (Jan 2004) Interior Alkyd Primer Sealer
MPI 46 (Jan 2004) Interior Enamel Undercoat
MPI 47 (Jan 2004) Interior Alkyd, Semi-Gloss, MPI Gloss Level 5
MPI 48 (Jan 2004) Interior Alkyd, Gloss, MPI Gloss Level 6
MPI 49 (Jan 2004) Interior Alkyd, Flat, MPI Gloss Level 1
MPI 5 (Jan 2004) Exterior Alkyd Wood Primer
MPI 50 (Jan 2004) Interior Latex Primer Sealer
MPI 51 (Jan 2004) Interior Alkyd, Eggshell, MPI Gloss Level 2
MPI 52 (Jan 2004) Interior Latex, MPI Gloss Level 3
MPI 54 (Jan 2004) Interior Latex, Semi-Gloss, MPI Gloss Level 5
MPI 56 (Jan 2004) Interior Oil Modified Urethane Clear Gloss
MPI 57 (Jan 2004) Interior Oil Modified Urethane Clear Satin
MPI 59 (Jan 2004) Interior/Exterior Floor Enamel, Low Gloss
MPI 6 (Jan 2004) Exterior Latex Wood Primer
MPI 60 (Jan 2004) Interior/Exterior Latex Floor Paint, Low Gloss
MPI 68 (Jan 2004) Interior/Exterior Latex Floor Enamel, Gloss
MPI 7 (Jan 2004) Exterior Oil Wood Primer
MPI 71 (Jan 2004) Polyurethane, Moisture Cured, Clear, Flat
MPI 72 (Jan 2004) Polyurethane, Two Component, Pigmented, Gloss
MPI 77 (Jan 2004) Epoxy Gloss
MPI 79 (Jan 2004) Alkyd Anti-Corrosive Metal Primer
MPI 8 (Jan 2004) Exterior Alkyd, Flat, MPI Gloss Level I
MPI 9 (Jan 2004) Exterior Alkyd, Gloss, MPI Gloss Level 6
MPI 90 (Jan 2004) Interior Wood Stain, Semi-Transparent
MPI 94 (Jan 2004) Exterior Alkyd, Semi-Gloss, MPI Gloss Level 5
MPI 95 (Jan 2004) Quick Drying Primer for Aluminum
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SP-01 (2000) Environmentally Preferable Product Specification for Architectural and Anti-Corrosive Paints
THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)
SSPC Guide 6 (2004) Guide for Containing Debris Generated During Paint Removal Operations
SSPC Guide 7 (2004; E 2004) Guide for the Disposal of Lead-Contaminated Surface Preparation Debris
SSPC PA 1 (2000; E 2004) Shop, Field, and Maintenance Painting
SSPC PA Guide 3 (1982; E 1995) A Guide to Safety in Paint Application
SSPC Paint 18 (1982; E 2004) Paint Specification No. 18 Chlorinated Rubber Intermediate Coat Paint
SSPC QP 1 (1998; E 2004) Standard Procedure for Evaluating Painting Contractors (Field Application to Complex Industrial Structures)
SSPC SP 1 (1982; E 2004) Solvent Cleaning
SSPC SP 10 (2007) Near-White Blast Cleaning
SSPC SP 12 (2002) Surface Preparation and Cleaning of Metals by Water-jetting Prior to Recoating
SSPC SP 2 (1982; E 2004) Hand Tool Cleaning
SSPC SP 3 (2004; E 2004) Power Tool Cleaning
SSPC SP 6 (2007) Commercial Blast Cleaning
SSPC SP 7 (2007) Brush-Off Blast Cleaning
SSPC VIS 1 (2002; E 2004) Guide and Reference Photographs for Steel Surfaces Prepared by Dry Abrasive Blast Cleaning
SSPC VIS 3 (2004) Visual Standard for Power-and Hand-Tool Cleaned Steel
SSPC VIS 4 (1998; E 2000; E 2004) Guide and Reference Photographs for Steel Surfaces Prepared by Water-jetting
U.S. ARMY CORPS OF ENGINEERS (USACE)
EM 385-1-1 (2008) Safety and Health Requirements Manual
U.S. DEPARTMENT OF DEFENSE (DOD)
MIL-PRF-680 (Rev B) Degreasing Solvent
MIL-STD-101 (Rev B) Color Code for Pipelines & for Compressed Gas Cylinders
U.S. ENVIRONMENTAL PROTECTION AGENCY (EPA)
EPA Method 24 (2000) Determination of Volatile Matter Content, Water Content, Density, Volume Solids, and Weight Solids of Surface Coatings
U.S. FEDERAL AVIATION ADMINISTRATION (FAA)
FAA AC 70/7460-1 (Rev K) Obstruction Marking and Lighting
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
FED-STD-313 (Rev D; Am 1) Material Safety Data, Transportation Data and Disposal Data for Hazardous Materials Furnished to Government Activities
FED-STD-595 (Rev B; Am 1) Colors Used in Government Procurement
U.S. GREEN BUILDING COUNCIL (USGBC)
LEED (2002; R 2005) Leadership in Energy and Environmental Design(tm) Green Building Rating System for New Construction (LEED-NC)
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.1000 Air Contaminants
29 CFR 1910.1001 Asbestos
29 CFR 1910.1025 Lead
29 CFR 1926.62 Lead
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. The following shall be submitted in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
List" which lists paint by brand, label, product name and product code as of the date of contract award, will be used to determine compliance with the submittal requirements of this specification. The Contractor may choose to use a subsequent MPI "Approved Product List", however, only one list may be used for the entire contract and each coating system is to be from a single manufacturer. All coats on a particular substrate must be from a single manufacturer. No variation from the MPI Approved Products List is acceptable. Samples of specified materials may be taken and tested for compliance with specification requirements.
In keeping with the intent of Executive Order 13101, "Greening the Government through Waste Prevention, Recycling, and Federal Acquisition", products certified by SCS as meeting SCS SP-01 shall be given preferential consideration over registered products. Products that are registered shall be given preferential consideration over products not carrying any EPP designation.
SD-02 Shop Drawings
| Piping identification, G, 902 CES/CEP |
| Submit color stencil codes, G, 902 CES/CEP |
SD-03 Product Data
| Local/Regional Materials; (LEED), G, 902 CES/CEP |
| Submit documentation indicating distance between manufacturing facility and the project site. Indicate distance of raw material origin from the project site. Indicate relative dollar value of local/regional materials to total dollar value of products included in project. |
| Environmental Data, G, 902 CES/CEP |
| Materials; (LEED), G, 902 CES/CEP |
| Submit documentation indicating percentage of post-industrial and post-consumer recycled content per unit of product. Indicate relative dollar value of recycled content products to total dollar value of products included in project. |
| Coating; G, 902 CES/CEP |
| Manufacturer's Technical Data Sheets; (LEED), G, 902 CES/CEP |
| Indicate VOC content. |
| Sealant, G, 902 CES/CEP |
SD-04 Samples
| Color; G, 902 CES/CEP |
| Submit manufacturer's samples of paint colors. Cross reference color samples to color scheme as indicated. |
| Textured Wall Coating System; G, 902 CES/CEP |
| Sample Textured Wall Coating System Mock-Up; G, 902 CES/CEP |
SD-07 Certificates
| Applicator's qualifications, G, 902 CES/CEP |
| Qualification Testing laboratory for coatings; G, 902 CES/CEP |
SD-08 Manufacturer's Instructions
| Application instructions, G, 902 CES/CEP |
| Mixing, G, 902 CES/CEP |
| Detailed mixing instructions, minimum and maximum application temperature and humidity, potlife, and curing and drying times between coats. |
| Manufacturer's Material Safety Data Sheets, G, 902 CES/CEP |
| Submit manufacturer's Material Safety Data Sheets for coatings, solvents, and other potentially hazardous materials, as defined in FED-STD-313. |
SD-09 Reports
| Test Reports: Submit a test report as cited in ASTM D2244, Standard Test Method for Calculation of Color Differences From Instrumentally Measured Color Coordinates, Para 10, Report. For color matching: |
| a. Use the 3” X 5” color chip from FED-STD 595 C as the standard color to be matched. |
| b. Use CIE Illuminant D65 as the source of illumination under which the color is to be matched. |
| c. Use ASTM D2244 as the method by which the color is to be matched. Delta E or DE value shall not exceed 0.88. |
| d. Use the CIELAB scale as the color scale defined by ASTM D2244. |
SD-10 Operation and Maintenance Data
| Coatings; G, 902 CES/CEP |
| Preprinted cleaning and maintenance instructions for all coating systems shall be provided. |
SD-11 Closeout Submittals
| Local/Regional Materials; (LEED), G, 902 CES/CEP |
| LEED documentation relative to local/regional materials credit in accordance with LEED Reference Guide. Include in LEED Documentation Notebook. |
| Materials; (LEED), G, 902 CES/CEP |
| LEED documentation relative to recycled content credit in accordance with LEED Reference Guide. Include in LEED Documentation Notebook. |
| LEED documentation relative to low emitting materials credit in accordance with LEED Reference Guide. Include in LEED Documentation Notebook. |
1.3 APPLICATOR'S QUALIFICATIONS
1.3.1 Contractor Qualification
Submit the name, address, telephone number, FAX number, and e-mail address of the contractor that will be performing all surface preparation and coating application. Submit evidence that key personnel have successfully performed surface preparation and application of coatings on a minimum of three similar projects within the past three years. List information by individual and include the following:
a. Name of individual and proposed position for this work.
b. Information about each previous assignment including:
Position or responsibility Employer (if other than the Contractor) Name of facility owner Mailing address, telephone number, and telex number (if non-US) of facility owner Name of individual in facility owner's organization who can be contacted as a reference Location, size and description of structure Dates work was carried out Description of work carried out on structure
1.3.2 SSPC QP 1 Certification
All contractors and subcontractors that perform surface preparation or coating application shall be certified by the Society for Protective Coatings (formerly Steel Structures Painting Council) (SSPC) to the requirements of SSPC QP 1 prior to contract award, and shall remain certified while accomplishing any surface preparation or coating application. The painting contractors and painting subcontractors must remain so certified for the duration of the project. If a contractor's or subcontractor's certification expires, the firm will not be allowed to perform any work until the certification is reissued. Requests for extension of time for any delay to the completion of the project due to an inactive certification will not be considered and liquidated damages will apply. Notify the Contracting Officer of any change in contractor certification status.
1.4 QUALITY ASSURANCE
1.4.1 Field Samples and Tests
The Contracting Officer may choose up to two coatings that have been delivered to the site to be tested at no cost to the Government. Take samples of each chosen product as specified in the paragraph "Sampling Procedures." Test each chosen product as specified in the paragraph "Testing Procedure." Products which do not conform, shall be removed from the job site and replaced with new products that conform to the referenced specification. Testing of replacement products that failed initial testing shall be at no cost to the Government. Another required testing is Batch Quality Conformance Testing to prove conformance of the manufacturer's paint to the specified MPI standard. This testing is accomplished before the materials are delivered to the job site. Provide testing for all paint products. Test paint products as specified in the paragraph "Testing Procedure".
1.4.1.1 Sampling Procedure
The Contracting Officer will select paint at random from the products that have been delivered to the job site for sample testing. The Contractor shall provide one quart samples of the selected paint materials. The samples shall be taken in the presence of the Contracting Officer, and labeled, identifying each sample. Provide labels in accordance with the paragraph "Packaging, Labeling, and Storage" of this specification.
1.4.1.2 Testing Procedure
Provide Batch Quality Conformance Testing for specified products, as defined by and performed by MPI. As an alternative to Batch Quality Conformance Testing, the Contractor may provide Qualification Testing for specified products above to the appropriate MPI product specification, using the third-party laboratory approved under the paragraph "Qualification Testing" laboratory for coatings. The qualification testing lab report shall include the backup data and summary of the test results. The summary shall list all of the reference specification requirements and the result of each test. The summary shall clearly indicate whether the tested paint meets each test requirement. Note that Qualification Testing may take 4 to 6 weeks to perform, due to the extent of testing required.
Submit name, address, telephone number, FAX number, and e-mail address of the independent third party laboratory selected to perform testing of coating samples for compliance with specification requirements. Submit documentation that laboratory is regularly engaged in testing of paint samples for conformance with specifications, and that employees performing testing are qualified. If the Contractor chooses MPI to perform the Batch Quality Conformance testing, the above submittal information is not required, only a letter is required from the Contractor stating that MPI will perform the testing.
1.4.2 Textured Wall Coating System
Three complete samples of each indicated type, pattern, and color of textured wall coating system applied to a panel of the same material as that on which the coating system will be applied in the work. Samples of wall coating systems shall be minimum 125 x 175 mm (5 x 7 inches) and of sufficient size to show pattern repeat and texture.
1.4.3 Sample Textured Wall Coating System Mock-Up
After coating samples are approved, and prior to starting installation, a minimum 2430 mm x 2430 mm (8 foot x 8 foot) mock-up shall be provided for each substrate and for each color and type of textured wall coating, using the actual substrate materials. Once approved the mock-up samples shall be used as a standard of workmanship for installation within the facility. At least 48 hours prior to mock-up installation, the Contractor shall submit written notification to the Contracting Officer's Representative.
1.5 REGULATORY REQUIREMENTS
1.5.1 Environmental Protection
In addition to requirements specified elsewhere for environmental protection, provide coating materials that conform to the restrictions of the local Air Pollution Control District and regional jurisdiction. Notify Contracting Officer of any paint specified herein which fails to conform.
1.5.2 Lead Content
Do not use coatings having a lead content over 0.06 percent by weight of nonvolatile content.
1.5.3 Chromate Content
Do not use coatings containing zinc-chromate or strontium-chromate.
1.5.4 Asbestos Content
Materials shall not contain asbestos.
1.5.5 Mercury Content
Materials shall not contain mercury or mercury compounds.
1.5.6 Silica
Abrasive blast media shall not contain free crystalline silica.
1.5.7 Human Carcinogens
Materials shall not contain ACGIH 0100Doc and ACGIH 0100Doc confirmed human carcinogens (A1) or suspected human carcinogens (A2).
1.6 PACKAGING, LABELING, AND STORAGE
Paints shall be in sealed containers that legibly show the contract specification number, designation name, formula or specification number, batch number, color, quantity, date of manufacture, manufacturer's formulation number, manufacturer's directions including any warnings and special precautions, and name and address of manufacturer. Pigmented paints shall be furnished in containers not larger than 5 gallons. Paints and thinners shall be stored in accordance with the manufacturer's written directions, and as a minimum, stored off the ground, under cover, with sufficient ventilation to prevent the buildup of flammable vapors, and at temperatures between 40 to 95 degrees F. Do not store paint, polyurethane, varnish, or wood stain products with materials that have a high capacity to adsorb VOC emissions. Do not store paint, polyurethane, varnish, or wood stain products in occupied spaces.
1.7 SAFETY AND HEALTH
Apply coating materials using safety methods and equipment in accordance with the following:
Work shall comply with applicable Federal, State, and local laws and regulations, and with the ACCIDENT PREVENTION PLAN, including the Activity Hazard Analysis as specified in Section 01 35 26 GOVERNMENT SAFETY REQUIREMENTS and in Appendix A of EM 38 -1-1. The Activity Hazard Analysis shall include analyses of the potential impact of painting operations on painting personnel and on others involved in and adjacent to the work zone.
1.7.1 Safety Methods Used During Coating Application Comply with the requirements of SSPC‑PA Guide 3.
1.7.2 Toxic Materials
To protect personnel from overexposure to toxic materials, conform to the most stringent guidance of:
a. The applicable manufacturer's Material Safety Data Sheets (MSDS) or local regulation.
b. 29 CFR 1910.1000.
c. ACGIH 0100Doc, threshold limit values.
d. The appropriate OSHA standard in 29 CFR 1910.1025 and 29 CFR 1926.62 for surface preparation on painted surfaces containing lead. Removal and disposal of coatings which contain lead is specified in Section 02 83 00 LEAD-BASED PAINT (LBP) ABATEMENT AND DISPOSAL. Additional guidance is given in SSPC Guide 6 and SSPC Guide 7. . Contractor shall coordinate paint preparation activities with this specification section.
e. The appropriate OSHA standards in 29 CFR 1910.1001 for surface preparation of painted surfaces containing asbestos. Removal and disposal of coatings which contain asbestos materials is specified in Section 02 82 00 ASBESTOS ABATEMENT AND DISPOSAL. Refer to drawings for list of hazardous materials located on this project. Contractor shall coordinate paint preparation activities with this specification section.
1.8 ENVIRONMENTAL CONDITIONS
Comply, at minimum, with manufacturer recommendations for space ventilation during and after installation. Isolate area of application from rest of building when applying high-emission paints or coatings.
1.8.1 Coatings: Do not apply coating when air or substrate conditions are:
a. Less than 5 degrees F above dew point;
b. Below 50 degrees F or over 95 degrees F, unless specifically pre-approved by the Contracting Officer and the product manufacturer. Under no circumstances shall application conditions exceed manufacturer recommendations.
1.8.2 Post-Application
Vacate space for as long as possible after application. Wait a minimum of 48 hours before occupying freshly painted rooms. Maintain one of the following ventilation conditions during the curing period, or for 72 hours after application:
a. Supply 100 percent outside air 24 hours a day.
b. Supply airflow at a rate of 6 air changes per hour, when outside temperatures are between 55 degrees F and 85 degrees F and humidity is between 30 percent and 60 percent.
c. Supply airflow at a rate of 1.5 air changes per hour, when outside air conditions are not within the range stipulated above.
1.9 SUSTAINABLE DESIGN REQUIREMENTS
1.9.1 Local/Regional Materials
Use materials or products extracted, harvested, or recovered, as well as manufactured, within a 500 mile radius from the project site, if available from a minimum of three sources. See Section 01 33 29 LEED(tm) DOCUMENTATION for cumulative total local material requirements. Paint and coating materials may be locally available.
1.9.2 Environmental Data
Submit Table 1 of ASTM E 2129.
1.10 SCHEDULING
Allow paint, polyurethane, varnish, and wood stain installations to cure prior to the installation of materials that adsorb VOCs.
1.11 COLOR SELECTION
Color Coding For Shore-To-Ship Utility Connections: Paint hose connection fittings and shut-off valves the designated color. In addition to color coding provide 2 inch high stenciled letters using black stencil paint, clearly designating service for each connection.
Color Coding for Shore-to-Ship Utility Connections
Service Color FED-STD-595 No.
Potable Water* Blue 15044
Water Provided for Fire Protection** Red 11105
Chilled Water Striped Blue/White 15044/17886
Oily Waste Water Striped Yellow/Black 13538/17038
Sewer Gold 17043
Steam White 17886
High Pressure Air Gray 16081
Low Pressure Air Tan 10324
Fuel Yellow 13655
* This includes connections serving domestic functions.
** This includes non-potable salt water or, at some locations, fresh water connections provided for fire protection (may also include flushing and cooling requirements). Note: This does not include waterfront fire hydrants.
Colors of finish coats shall be as indicated or specified. Where not indicated or specified, colors shall be selected by the Contracting Officer. Manufacturers' names and color identification are used for the purpose of color identification only. Named products are acceptable for use only if they conform to specified requirements. Products of other manufacturers are acceptable if the colors approximate colors indicated and the product conforms to specified requirements. Tint each coat progressively darker to enable confirmation of the number of coats. Color, texture, and pattern of wall coating systems shall be as indicated in accordance with Section 09 06 90 COLOR SCHEDULE.
1.12 LOCATION AND SURFACE TYPE TO BE PAINTED
1.12.1 Painting Included
Where a space or surface is indicated to be painted, include the following unless indicated otherwise.
a. Surfaces behind portable objects and surface mounted articles readily detachable by removal of fasteners, such as screws and bolts.
b. New factory finished surfaces that require identification or color coding and factory finished surfaces that are damaged during performance of the work.
c. Existing coated surfaces that are damaged during performance of the work.
1.12.1.1 Exterior Painting
Includes new surfaces, existing coated surfaces, and existing uncoated surfaces, of the buildings and appurtenances. Also included are existing coated surfaces made bare by cleaning operations.
1.12.1.2 Interior Painting
Includes new surfaces, existing uncoated surfaces, and existing coated surfaces of the buildings and appurtenances as indicated and existing coated surfaces made bare by cleaning operations. Where a space or surface is indicated to be painted, include the following items, unless indicated otherwise.
a. Exposed columns, girders, beams, joists, and metal deck; and
b. Other contiguous surfaces.
1.12.2 Painting Excluded
Do not paint the following unless indicated otherwise.
a. Surfaces concealed and made inaccessible by panelboards, fixed ductwork, machinery, and equipment fixed in place.
b. Surfaces in concealed spaces. Concealed spaces are defined as enclosed spaces above suspended ceilings, furred spaces, attic spaces, crawl spaces, elevator shafts and chases.
c. Steel to be embedded in concrete.
d. Copper, stainless steel, aluminum, brass, and lead except existing coated surfaces.
e. Hardware, fittings, and other factory finished items.
1.12.3 Mechanical and Electrical Painting
Includes field coating of interior and exterior new and existing surfaces.
a. Where a space or surface is indicated to be painted, include the following items unless indicated otherwise.
(1) Exposed piping, conduit, and ductwork;
(2) Supports, hangers, air grilles, and registers;
(3) Miscellaneous metalwork and insulation coverings.
b. Do not paint the following, unless indicated otherwise:
(1) New zinc-coated, aluminum, and copper surfaces under insulation
(2) New aluminum jacket on piping
(3) New interior ferrous piping under insulation.
1.12.3.1 Fire Extinguishing Sprinkler Systems
Clean, pre-treat, prime, and paint new fire extinguishing sprinkler systems including valves, piping, conduit, hangers, supports, miscellaneous metalwork, and accessories. Apply coatings to clean, dry surfaces, using clean brushes. Clean the surfaces to remove dust, dirt, rust, and loose mill scale. Immediately after cleaning, provide the metal surfaces with one coat primer per schedules. Shield sprinkler heads with protective covering while painting is in progress. Upon completion of painting, remove protective covering from sprinkler heads. Remove sprinkler heads which have been painted and replace with new sprinkler heads. Provide primed surfaces with the following:
a. Piping in Unfinished Areas: Provide primed surfaces with one coat of red alkyd gloss enamel applied to a minimum dry film thickness of 1.0 mil in attic spaces, spaces above suspended ceilings, crawl spaces, pipe chases, mechanical equipment room, and spaces where walls or ceiling are not painted or not constructed of a prefinished material. In lieu of red enamel finish coat, provide piping with 2 inch wide red enamel bands or self-adhering red plastic bands spaced at maximum of 20 foot intervals.
b. Piping in Finished Areas: Provide primed surfaces with two coats of paint to match adjacent surfaces, except provide valves and operating accessories with one coat of red alkyd gloss enamel applied to a minimum dry film thickness of 1.0 mil. Provide piping with 2 inch wide red enamel bands or self-adhering red plastic bands spaced at maximum of 20 foot intervals throughout the piping systems.
1.12.4 Exterior Painting of Site Work Items
Field coat the following items: New Surfaces Existing Surfaces
a. [_____] [_____]
b. [_____] [_____]
c. [_____] [_____]]
1.12.5 MISCELLANEOUS PAINTING
Lettering Building, Room Number(s) Lettering shall be provided as scheduled on the drawings, shall be block Gothic type, and shall be black enamel or water-type decalcomania, finished with a protective coating of spar varnish. Samples shall be approved before application.
1.12.6 Definitions and Abbreviations
1.12.6.1 Qualification Testing
Qualification testing is the performance of all test requirements listed in the product specification. This testing is accomplished by MPI to qualify each product for the MPI Approved Product List, and may also be accomplished by Contractor's third party testing lab if an alternative to Batch Quality Conformance Testing by MPI is desired.
1.12.6.2 Batch Quality Conformance Testing
Batch quality conformance testing determines that the product provided is the same as the product qualified to the appropriate product specification. This testing shall only be accomplished by MPI testing lab.
1.12.6.3 Coating
A film or thin layer applied to a base material called a substrate. A coating may be a metal, alloy, paint, or solid/liquid suspensions on various substrates (metals, plastics, wood, paper, leather, cloth, etc.). They may be applied by electrolysis, vapor deposition, vacuum, or mechanical means such as brushing, spraying, calendaring, and roller coating. A coating may be applied for aesthetic or protective purposes or both. The term "coating" as used herein includes emulsions, enamels, stains, varnishes, sealers, epoxies, and other coatings, whether used as primer, intermediate, or finish coat. The terms paint and coating are used interchangeably.
1.12.6.4 DFT or dft
Dry film thickness, the film thickness of the fully cured, dry paint or coating.
1.12.6.5 DSD
Degree of Surface Degradation, the MPI system of defining degree of surface degradation. Five (5) levels are generically defined under the Assessment sections in the MPI Maintenance Repainting Manual.
1.12.6.6 EPP
Environmentally Preferred Products, a standard for determining environmental prefer ability in support of Executive Order 13101.
1.12.6.7 EXT
MPI short term designation for an exterior coating system.
1.12.6.8 INT
MPI short term designation for an interior coating system.
1.12.6.9 micron / microns The metric measurement for 0.001 mm or one/one-thousandth of a millimeter.
1.12.6.10 mil / mils The English measurement for 0.001 in or one/one-thousandth of an inch, equal to 25.4 microns or 0.0254 mm.
1.12.6.11 mm The metric measurement for millimeter, 0.001 meter or one/one-thousandth of a meter.
1.12.6.12 MPI Gloss Levels
MPI system of defining gloss. Seven (7) gloss levels (G1 to G7) are generically defined under the Evaluation sections of the MPI Manuals. Traditionally, Flat refers to G1/G2, Eggshell refers to G3, Semigloss refers to G5, and Gloss refers to G6.
Gloss levels are defined by MPI as follows:
Gloss Level Description Units @ 60 degrees Units @ 85 degrees
G1 Matte or Flat 0 to 5 10 max G2 Velvet 0 to 10 10 to 35 G3 Eggshell 10 to 25 10 to 35 G4 Satin 20 to 35 35 min G5 Semi-Gloss 35 to 70
G6 Gloss 70 to 85
G7 High Gloss
Gloss is tested in accordance with ASTM D 523. Historically, the Government has used Flat (G1 / G2), Eggshell (G3), Semi-Gloss (G5), and Gloss (G6).
1.12.6.13 MPI System Number
The MPI coating system number in each Division found in either the MPI Architectural Painting Specification Manual or the Maintenance Repainting Manual and defined as an exterior (EXT/REX) or interior system (INT/RIN). The Division number follows the CSI Master Format.
1.12.6.14 Paint
See Coating definition.
1.12.6.15 REX
MPI short term designation for an exterior coating system used in repainting projects or over existing coating systems.
1.12.6.16 RIN
MPI short term designation for an interior coating system used in repainting projects or over existing coating systems.
PART 2 - PRODUCTS
2.1 MATERIALS
Conform to the coating specifications and standards referenced in PART 3. Submit manufacturer's technical data sheets for specified coatings and solvents. [Minimum [20] [50] [_____] percent post-consumer recycled content for the following light-colored paints and primers: [_____]. Minimum [50] [90] [99] [_____] percent post-consumer recycled content for the following dark-colored paints and primers: [_____]. [All] [The following] consolidated latex paints shall contain a minimum of [100] [_____] percent post-consumer recycled content[: [_____]].] Comply with applicable regulations regarding toxic and hazardous materials.
PART 3 - EXECUTION
3.1 PROTECTION OF AREAS AND SPACES NOT TO BE PAINTED
Prior to surface preparation and coating applications, remove, mask, or otherwise protect, hardware, hardware accessories, machined surfaces, radiator covers, plates, lighting fixtures, public and private property, and other such items not to be coated that are in contact with surfaces to be coated. Following completion of painting, workmen skilled in the trades involved shall reinstall removed items. Restore surfaces contaminated by coating materials, to original condition and repair damaged items.
3.2 REPUTTYING AND REGLAZING
Remove cracked, loose, and defective putty or glazing compound on glazed sash and provide new putty or glazing compound. Where defective putty or glazing compound constitutes 30 percent or more of the putty at any one light, remove the glass and putty or glazing compound and reset the glass. Remove putty or glazing compound without damaging sash or glass. Clean rabbets to bare wood or metal and prime prior to reglazing. Putty for wood sash shall be a linseed oil putty. Glazing compound for metal sash shall conform to ASTM C 669. Patch surfaces to provide smooth transition between existing and new surfaces. Finish putty or glazing compound to a neat and true bead. Allow glazing compound time to cure, in accordance with manufacturer's recommendation, prior to coating application. Allow putty to set one week prior to coating application.
3.3 RESEALING OF EXISTING EXTERIOR JOINTS
3.3.1 Surface Condition
Surfaces shall be clean, dry to the touch, and free from frost and moisture; remove grease, oil, wax, lacquer, paint, defective backstop, or other foreign matter that would prevent or impair adhesion. Where adequate grooves have not been provided, clean out to a depth of 1/2 inch and grind to a minimum width of 1/4 inch without damage to adjoining work. Grinding shall not be required on metal surfaces.
3.3.2 Backstops
In joints more than 1/2 inch deep, install glass fiber roving or neoprene, butyl, polyurethane, or polyethylene foams free of oil or other staining elements as recommended by sealant manufacturer. Backstop material shall be compatible with sealant. Do not use oakum and other types of absorptive materials as backstops.
3.3.3 Primer and Bond Breaker
Install the type recommended by the sealant manufacturer.
3.3.4 Ambient Temperature
Between 38 degrees F and 95 degrees F when applying sealant.
3.3.5 Exterior Sealant
For joints in vertical surfaces, provide ASTM C 920, Type S or M, Grade NS, Class 25, Use NT. For joints in horizontal surfaces, provide ASTM C 920, Type S or M, Grade P, Class 25, Use T. Color(s) shall be selected by the Contracting Officer. Apply the sealant in accordance with the manufacturer's printed instructions. Force sealant into joints with sufficient pressure to fill the joints solidly. Sealant shall be uniformly smooth and free of wrinkles.
3.3.6 Cleaning
Immediately remove fresh sealant from adjacent areas using a solvent recommended by the sealant manufacturer. Upon completion of sealant application, remove remaining smears and stains and leave the work in a clean condition. Allow sealant time to cure, in accordance with manufacturer's recommendations, prior to coating.
3.4 SURFACE PREPARATION
Remove dirt, splinters, loose particles, grease, oil, disintegrated coatings, and other foreign matter and substances deleterious to coating performance as specified for each substrate before application of paint or surface treatments. Oil and grease shall be removed prior to mechanical cleaning. Cleaning shall be programmed so that dust and other contaminants will not fall on wet, newly painted surfaces. Exposed ferrous metals such as nail heads on or in contact with surfaces to be painted with water-thinned paints, shall be spot-primed with a suitable corrosion-inhibitive primer capable of preventing flash rusting and compatible with the coating specified for the adjacent areas.
3.4.1 Additional Requirements for Preparation of Surfaces With Existing Coatings Before application of coatings, perform the following on surfaces covered by soundly-adhered coatings, defined as those which cannot be removed with a putty knife:
a. Test existing finishes for lead before sanding, scraping, or removing. If lead is present, refer to paragraph Toxic Materials.
b. Wipe previously painted surfaces to receive solvent-based coatings, except stucco and similarly rough surfaces clean with a clean, dry cloth saturated with mineral spirits, ASTM D 235. Allow surface to dry. Wiping shall immediately precede the application of the first coat of any coating, unless specified otherwise.
c. Sand existing glossy surfaces to be painted to reduce gloss. Brush, and wipe clean with a damp cloth to remove dust.
d. The requirements specified are minimum requirements. Comply also with the application instructions of the paint manufacturer.
e. Previously painted surfaces [specified to be repainted] damaged during construction shall be thoroughly cleaned of all grease, dirt, dust or other foreign matter.
f. Blistering, cracking, flaking and peeling or other deteriorated coatings shall be removed.
g. Chalk shall be removed so that when tested in accordance with ASTM D 4214, the chalk resistance rating is no less than 8.
h. Slick surfaces shall be roughened. Damaged areas such as, but not limited to, nail holes, cracks, chips, and spalls shall be repaired with suitable material to match adjacent undamaged areas.
i. Edges of chipped paint shall be feather edged and sanded smooth.
j. Rusty metal surfaces shall be cleaned as per SSPC requirements. Solvent, mechanical, or chemical cleaning methods shall be used to provide surfaces suitable for painting.
k. New, proposed coatings shall be compatible with existing coatings.
3.4.2 Existing Coated Surfaces with Minor Defects
Sand, spackle, and treat minor defects to render them smooth. Minor defects are defined as scratches, nicks, cracks, gouges, spalls, alligatoring, chalking, and irregularities due to partial peeling of previous coatings. Remove chalking by sanding or blasting so that when tested in accordance with ASTM D 4214, the chalk rating is not less than 8.
3.4.3 Removal of Existing Coatings
Remove existing coatings from the following surfaces:
a. Surfaces containing large areas of minor defects;
b. Surfaces containing more than 20 percent peeling area; and
c. Surfaces designated by the Contracting Officer, such as surfaces where rust shows through existing coatings.
3.4.4 Substrate Repair
a. Repair substrate surface damaged during coating removal;
b. Sand edges of adjacent soundly-adhered existing coatings so they are tapered as smooth as practical to areas involved with coating removal; and
c. Clean and prime the substrate as specified.
3.5 PREPARATION OF METAL SURFACES
3.5.1 Existing and New Ferrous Surfaces
a. Ferrous Surfaces including Shop-coated Surfaces and Small Areas That Contain Rust, Mill Scale and Other Foreign Substances: Solvent clean or detergent wash in accordance with SSPC SP 1 to remove oil and grease. here shop coat is missing or damaged, clean according to SSPC SP 2, SSPC SP 3, SSPC SP 6, or SSPC SP 10. Brush-off blast remaining surface in accordance with SSPC SP 7; Water jetting to SSPC SP 12 WJ-4 may be used to remove loose coating and other loose materials. Use inhibitor as recommended by coating manufacturer to prevent premature rusting. Shop-coated ferrous surfaces shall be protected from corrosion by treating and touching up corroded areas immediately upon detection.
b. Surfaces With More Than 20 Percent Rust, Mill Scale, and Other Foreign Substances: Clean entire surface in accordance with SSPC SP 6/SSPC SP 12 WJ-3 or SSPC SP 10/SSPC SP 12 WJ-2.
c. Metal Floor Surfaces to Receive Nonslip Coating: Clean in accordance with SSPC SP 10 or SSPC SP 12 WJ-2.
3.5.2 Final Ferrous Surface Condition:
For tool cleaned surfaces, the requirements are stated in SSPC SP 2 and SSPC SP 3. As a visual reference, cleaned surfaces shall be similar to photographs in SSPC VIS 3.
For abrasive blast cleaned surfaces, the requirements are stated in SSPC SP 7, SSPC SP 6, and SSPC SP 10. As a visual reference, cleaned surfaces shall be similar to photographs in SSPC VIS 1.
For water-jet cleaned surfaces, the requirements are stated in SSPC SP 12. As a visual reference, cleaned surfaces shall be similar to photographs in SSPC VIS 4.
3.5.3 Galvanized Surfaces
a. New or Existing Galvanized Surfaces With Only Dirt and Zinc Oxidation Products: Clean with solvent, steam, or non-alkaline detergent solution in accordance with SSPC SP 1. If the galvanized metal has been passivated or stabilized, the coating shall be completely removed by brush-off abrasive blast. New galvanized steel to be coated shall not be "passivated" or "stabilized" If the absence of hexavalent stain inhibitors is not documented, test as described in ASTM D 2092, Appendix X2, and remove by one of the methods described therein.
b. Galvanized with Slight Coating Deterioration or with Little or No Rusting: Water jetting to SSPC SP 12 WJ3 to remove loose coating from surfaces with less than 20 percent coating deterioration and no blistering, peeling, or cracking. Use inhibitor as recommended by the coating manufacturer to prevent rusting.
c. Galvanized With Severe Deteriorated Coating or Severe Rusting:
Water jet to SSPC SP 12 WJ3 degree of cleanliness. Spot abrasive blast rusted areas as described for steel in SSPC SP 6, and waterjet to SSPC SP 12, WJ3 to remove existing coating.
3.5.4 Non-Ferrous Metallic Surfaces
Aluminum and aluminum-alloy, lead, copper, and other nonferrous metal surfaces.
a. Surface Cleaning: Solvent clean in accordance with SSPC SP 1 and wash with mild non-alkaline detergent to remove dirt and water soluble contaminants.
3.5.5 Terne-Coated Metal Surfaces
Solvent clean surfaces with mineral spirits, ASTM D 235. Wipe dry with clean, dry cloths.
3.5.6 Existing Surfaces with a Bituminous or Mastic-Type Coating Remove chalk, mildew, and other loose material by washing with a solution of 1/2 cup trisodium phosphate, 1/4 cup household detergent, one quart 5 percent sodium hypochlorite solution and 3 quarts of warm water.
3.6 PREPARATION OF CONCRETE AND CEMENTITIOUS SURFACE
3.6.1 Concrete and Masonry
a. Curing: Concrete, stucco and masonry surfaces shall be allowed to cure at least 30 days before painting, except concrete slab on grade, which shall be allowed to cure 90 days before painting.
b. Surface Cleaning: Remove the following deleterious substances.
(1) Dirt, Chalking, Grease, and Oil: Wash new and existing uncoated surfaces with a solution composed of 1/2 cup trisodium phosphate, 1/4 cup household detergent, and 4 quarts of warm water. Then rinse thoroughly with fresh water. Wash existing coated surfaces with a suitable detergent and rinse thoroughly. For large areas, water blasting may be used.
(2) Fungus and Mold: Wash new, existing coated, and existing uncoated surfaces with a solution composed of 1/2 cup trisodium phosphate, 1/4 cup household detergent, 1 quart 5 percent sodium hypochlorite solution and 3 quarts of warm water. Rinse thoroughly with fresh water.
(3) Paint and Loose Particles: Remove by wire brushing.
(4) Efflorescence: Remove by scraping or wire brushing followed by washing with a 5 to 10 percent by weight aqueous solution of hydrochloric (muriatic) acid. Do not allow acid to remain on the surface for more than five minutes before rinsing with fresh water. Do not acid clean more than 4 square feet of surface, per workman, at one time.
(5) Removal of Existing Coatings: For surfaces to receive textured coating MPI 42, remove existing coatings including soundly adhered coatings if recommended by textured coating manufacturer.
c. Cosmetic Repair of Minor Defects: Repair or fill mortar joints and minor defects, including but not limited to spalls, in accordance with manufacturer's recommendations and prior to coating application.
d. Allowable Moisture Content: Latex coatings may be applied to damp surfaces, but not to surfaces with droplets of water. Do not apply epoxies to damp vertical surfaces as determined by ASTM D 4263 or horizontal surfaces that exceed 3 lbs of moisture per 1000 square feet in 24 hours as determined by ASTM F 1869. In all cases follow manufacturer’s recommendations. Allow surfaces to cure a minimum of 30 days before painting.
3.6.2 Gypsum Board, Plaster, and Stucco
a. Surface Cleaning: Plaster and stucco shall be clean and free from loose matter; gypsum board shall be dry. Remove loose dirt and dust by brushing with a soft brush, rubbing with a dry cloth, or vacuum-cleaning prior to application of the first coat material. A damp cloth or sponge may be used if paint will be water-based.
b. Repair of Minor Defects: Prior to painting, repair joints, cracks, holes, surface irregularities, and other minor defects with patching plaster or spackling compound and sand smooth.
c. Allowable Moisture Content: Latex coatings may be applied to damp surfaces, but not surfaces with droplets of water. Do not apply epoxies to damp surfaces as determined by ASTM D 4263. New plaster to be coated shall have a maximum moisture content of 8 percent, when measured in accordance with ASTM D 4444, Method A, unless otherwise authorized. In addition to moisture content requirements, allow new plaster to age a minimum of 30 days before preparation for painting.
3.6.3 Existing Asbestos Cement Surfaces
Remove oily stains by solvent cleaning with mineral spirits, MIL-PRF-680 ASTM D 235. Remove loose dirt, dust, and other deleterious substances by brushing with a soft brush or rubbing with a dry cloth prior to application of the first coat material. Do not wire brush or clean using other abrasive methods. Surfaces shall be dry and clean prior to application of the coating.
3.7 PREPARATION OF WOOD AND PLYWOOD SURFACES
3.7.1 New, Existing Uncoated, and Existing Coated Plywood and Wood Surfaces, Except Floors:
a. Wood surfaces shall be cleaned of foreign matter. Surface Cleaning: Surfaces shall be free from dust and other deleterious substances and in a condition approved by the Contracting Officer prior to receiving paint or other finish. Do not use water to clean uncoated wood. Scrape to remove loose coatings. Lightly sand to roughen the entire area of previously enamel-coated wood surfaces.
b. Removal of Fungus and Mold: Wash existing coated surfaces with a solution composed of 3 ounces (2/3 cup) trisodium phosphate, 1 ounce (1/3 cup) household detergent, 1 quart 5 percent sodium hypochlorite solution and 3 quarts of warm water. Rinse thoroughly with fresh water.
c. Moisture content of the wood shall not exceed 12 percent as measured by a moisture meter in accordance with ASTM D 4444, Method A, unless otherwise authorized.
d. Wood surfaces adjacent to surfaces to receive water-thinned paints shall be primed and/or touched up before applying water-thinned paints.
e. Cracks and Nailheads: Set and putty stop nailheads and putty cracks after the prime coat has dried.
f. Cosmetic Repair of Minor Defects:
(1) Knots and Resinous Wood and Fire, Smoke, Water, and Color Marker Stained Existing Coated Surface: Prior to application of coating, cover knots and stains with two or more coats of 3-pound-cut shellac varnish, plasticized with 5 ounces of castor oil per gallon. Scrape away existing coatings from knotty areas, and sand before treating. Prime before applying any putty over shellacked area.
(2) Open Joints and Other Openings: Fill with whiting putty, linseed oil putty. Sand smooth after putty has dried.
(3) Checking: Where checking of the wood is present, sand the surface, wipe and apply a coat of pigmented orange shellac. Allow to dry before paint is applied.
g. Prime Coat For New Exterior Surfaces: Prime coat wood doors, windows, frames, and trim before wood becomes dirty, warped, or weathered.
3.7.2 Wood Floor Surfaces, Natural Finish
a. Initial Surface Cleaning: As specified in paragraph entitled "Surface Preparation."
b. Existing Loose Boards and Shoe Molding: Before sanding, re-nail loose boards. Countersink nails and fill with approved wood filler. Remove shoe molding before sanding and reinstall after completing other work. At Contractor's option, new shoe molding may be provided in lieu of reinstalling old. New wood molding shall be same size, wood species, and finish as the existing.
c. Sanding and Scraping: Sanding of wood floors is specified in Section 09 64 29 WOOD STRIP FLOORING, 09 64 23 WOOD PARQUET FLOORING, 09 64 66 WOOD ATHLETIC FLOORING, 09 64 00 PORTABLE (DEMOUNTABLE) WOOD FLOORING.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .