DIVISION 03 - CONCRETE
SECTION 03 39 00.00 10
CONCRETE CURING
11/10
PART 1 GENERAL
This specification covers concrete work primarily for drainage structures, equipment slabs, and driveways.
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN ASSOCIATION OF STATE HIGHWAY AND TRANSPORTATION OFFICIALS
(AASHTO)
AASHTO M 182 (2009) Standard Specification for Burlap Cloth Made from Jute or Kenaf and Cotton Mats
ASTM INTERNATIONAL (ASTM)
ASTM C 171 (2007) Standard Specification for Sheet Materials for Curing Concrete
ASTM C 309 (2007) Standard Specification for Liquid Membrane-Forming Compounds for Curing Concrete
U.S. ARMY CORPS OF ENGINEERS (USACE)
COE CRD-C 400 (1963) Requirements for Water for Use in Mixing or Curing Concrete
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-03 Product Data
Curing Materials; G Curing and Protection; G
SD-06 Test Reports
Testing and Inspection for CQC; G
1.3 DELIVERY, STORAGE, AND HANDLING
Materials shall be stored in such a manner as to avoid contamination and deterioration. Materials shall be capable of being accurately identified after bundles or containers are opened.
PART 2 PRODUCTS
2.1 CURING MATERIALS
2.1.1 Membrane-Forming Compound
Membrane-Forming curing compound shall conform to ASTM C 309, Type 1-D or 2, except that only a styrene acrylate or chlorinated rubber compound meeting Class B requirements shall be used for surfaces that are to be painted or are to receive bituminous roofing, or waterproofing, or floors that are to receive adhesive applications of resilient flooring. The curing compound selected shall be compatible with any subsequent paint, roofing, waterproofing, or flooring specified. Non-pigmented compound shall contain a fugitive dye, and shall have the reflective requirements in ASTM C 309 waived.
2.1.2 Burlap and Cotton Mat
Burlap and cotton mat used for curing shall conform to AASHTO M 182.
2.2 WATER
Water for curing shall be fresh, clean, potable, and free of injurious amounts of oil, acid, salt, or alkali, except that non-potable water may be used if it meets the requirements of COE CRD-C 400.
PART 3 EXECUTION
3.1 CURING AND PROTECTION
3.1.1 General
Concrete shall be cured by an approved method for the period of time given below:
Type III portland cement 3 days
Portland cement when accelerator is used to achieve high 3 days early strength, except when fly-ash
Type I portland cement 7 days
Type II portland cement 14 days
Portland cement blended with 25 percent of less fly-ash 14 days
Portland cement blended with more than 25 percent fly-ash 21 days
Immediately after placement, protect concrete from premature drying, extremes in temperatures, rapid temperature change and mechanical injury for the duration of the curing period. Concrete shall be protected from the damaging effects of rain for 12 hours and from flowing water for 14 days (7 days with Type III cement). No fire or excessive heat including welding shall be permitted near or in direct contact with concrete or concrete embedments at any time. Maintain air and forms in contact with concrete at a temperature above 50 degrees F for the first 3 days and at a temperature above 32 degrees F for the remainder of the specified curing period. Exhaust fumes from combustion heating units shall be vented to the outside of the enclosure, and heaters and ducts shall be placed and directed so as not to cause areas of overheating and drying of concrete surfaces or to create fire hazards. Materials and equipment needed for adequate curing and protection shall be available and at the site prior to placing concrete. No fire or excessive heat, including welding, shall be permitted near or in direct contact with the concrete at any time.
3.1.2 Moist Curing
Maintain concrete, to be moist-cured, continuously wet for the entire curing period, commencing immediately after finishing. If water or curing materials used stain or discolor concrete surfaces which are to be permanently exposed, the concrete surfaces shall be cleaned as approved. When wooden forms are left in place during curing, they shall be kept wet at all times. If steel forms are used in hot weather, non-supporting vertical forms shall be carefully broken loose from the concrete, soon after the concrete hardens, and curing water continuously applied into the void so as to continuously saturate the entire concrete surface. If the forms are removed before the end of the curing period, curing shall be carried out as on unformed surfaces, using suitable materials. Horizontal surfaces shall be cured by ponding, by continuous sprinkling, by continuously saturated burlap or cotton mats, or by continuously saturated plastic coated burlap. Burlap and mats shall be clean and free from any contamination and shall be completely saturated before being placed on the concrete. Provide an approved work system to ensure that moist curing is continuous 24 hours per day. Horizontal construction joints may be allowed to dry for 12 hours immediately prior to the placing of the following lift.
3.1.3 Membrane Forming Curing Compounds
3.1.3.1 Application Restrictions
Concrete may be cured with an approved membrane-forming curing compound in lieu of moist curing except that membrane curing will not be permitted on any surface to which a grout-cleaned finish is to be applied or other concrete is to be bonded, on any surface containing protruding steel reinforcement, on an abrasive aggregate finish. Membrane curing compound shall not be used on surfaces that are maintained at curing temperatures with free steam.
3.1.3.2 Pigmented Curing Compound
A pigmented curing compound meeting the requirements of the above paragraph may be used on surfaces that will not be exposed to view when the project is completed.
3.1.3.3 Non-pigmented Curing Compound
A non-pigmented curing compound containing a fugitive dye may be used on surfaces that will be exposed to view when the project is completed. Concrete cured with non-pigmented curing compound must be shaded from the sun for the first 3 days when the ambient temperature is 90 degrees F or higher.
3.1.3.4 Application
Apply the curing compound to formed surfaces immediately after the forms are removed and prior to any patching or other surface treatment except the cleaning of loose sand, mortar, and debris from the surface. The surfaces shall be thoroughly moistened with water, and the curing compound applied as soon as free water disappears. The curing compound shall be applied to unformed surfaces as soon as free water has disappeared and bleeding has stopped. The curing compound shall be applied in a two-coat continuous operation by approved motorized power-spraying equipment operating at a minimum pressure of 75 psi, at a uniform coverage of not more than 400 square feet per gallon for each coat, and the second coat shall be applied perpendicular to the first coat. Concrete surfaces that have been subjected to rainfall within 3 hours after curing compound has been applied shall be re-sprayed by the method and at the coverage specified. All concrete surfaces on which the curing compound has been applied shall be adequately protected for the duration of the entire curing period from pedestrian and vehicular traffic and from any other cause that will disrupt the continuity of the curing membrane.
3.1.4 Ponding or Immersion
Concrete shall be continually immersed throughout the curing period. Water shall not be more than 20 degrees F less than the temperature of the concrete.
3.1.5 Cold Weather Curing and Protection
When the daily ambient low temperature is less than 32 degrees F maintain the temperature of the concrete above 40 degrees F for the first seven days after placing. During the period of protection removal, control the air temperature adjacent to the concrete surfaces so that concrete near the surface will not be subjected to a temperature differential of more than 25 degrees F as determined by suitable temperature measuring devices furnished by the Contractor, as required, and installed adjacent to the concrete surface and 2 inches inside the surface of the concrete. Perform the installation of the thermometers as directed.
-- End of Section --