Wago:
Programmable Fieldbus Controller
& Hardware
Table of Contents
4. 750-841: Programmable Bus Coupler pg 3-4
5. 750-423: Module, 2-Channel Input pg 5
6. 750-513: Module, 2-Channel Output pg 6
7. 750-600: Module, End pg 7
24V 0V
01 02
0-
LINK
MS
NS
I/O
ETHERNET
C
D B
A
TxD/RxD
USR
ETHERNET TCP/IP
Programmable Fieldbus Controller; 10/100 Mbit/s; digital and analog signals
Fieldbus connection
RJ 45
Configuration and programming interface
Power jumper contacts
Status voltage supply -Power jumper contacts
-System Data contacts
Supply 24 V 0 V
Supply via power jumper contacts 24 V
0 V
750-841
This fieldbus controller allows the connection of the WAGO%SYSTEM as a slave to the ETHERNET.
The fieldbus controller is capable of supporting all I/O modules. The controller automatically configures itself, creating a local process image which may include analog, digital or specialty modules. Analog and specialty modules data is sent via words or bytes, digital data is packed into words or bytes.
This fieldbus controller is suitable for data rates of 10 Mbit /s and 100 Mbit /s. It is programmable according to IEC 61131-3 using 512 KB program memory, 128 KB data memory and 24 KB retentive memory. This 32-bit based CPU is capable of multitasking and has a battery backed real-time clock.
The controller offers many different application protocols which can be used for data acquisition or control (MODBUS, ETHERNET /IP) or for system managing and diagnostics (HTTP, BootP, DHCP, DNS, SNTP, FTP, SNMP and SMTP).
The WAGO ETHERNET controller has additional functionalities, which allow controlled access to the control and configuration data. Protection against unauthorized access is made possible with full TCP /IP functionality. When the security option is switched on, only predefined clients can communicate with the WAGO ETHERNET controller. The IP-filter is configured by means of web pages in the ETHERNET controller.
System DataItem Pack.-unit No. pcs
Programmable 100MBit ETHERNET fieldbus controller 750-841 1
Description
Max. no. of nodes limited by ETHERNET specification Transmission medium Twisted Pair S-UTP 100 Ω cat. 5 Buscoupler connection RJ 45 Max. length of fieldbus segment 100 m between hub station and 750-841 max. length of network limited by ETHERNET specification
Baud rate 10 /100 Mbits /s Protocols MODBUS /TCP (UDP), ETHERNET /IP, HTTP, BootP, DHCP, DNS, SNTP, FTP, SNMP, SMTP Programming WAGO-I/O-PRO CAA
IEC 61131-3 IL, LD, FBD, ST, FC
Subject to design changes
NEW 2004
WAGO Kontakttechnik GmbH Postfach 2880 • D-32385 Minden Tel.: +49(0)5 71 /8 87-0 E-Mail: info@wago.com Hansastr. 27 • D-32423 Minden Fax.: +49(0)5 71 /8 87-169 www.wago.com17.09.2004
DC
DC
24 V
10 nF
24 V
10 nF
0 V
24 V /0 V
24 V
0 V
0 V
750-841
Subject to design changes
Max. no. of I/O modules 64 with bus extension 255 per node Digital signals max. 2040 (inputs and outputs) Analog signals max. 1020 (inputs and outputs) Config. possibility via PC Program memory 512 Kbytes Data memory 128 Kbytes Non-volatile memory 24 Kbytes (retentive) Voltage supply DC 24 V (-15 % ... +20 %) Input current max. 500 mA at 24 V Efficiency of the power supply 87 % Internal current consumption 300 mA at 5 V Total current for I/O modules 1700 mA at 5 V Isolation 500 V system /supply Voltage via power jumper contacts DC 24 V (-15 % ... +20 %) Current via power jumper contacts max. DC 10 A
Technical Data
WAGO-I/O-PRO CAA 759-333 1
Miniature WSB Quick marking system plain 248-501 5 with marking see General Catalogue W4 Volume 3 pages 1.174 ... 1.175
General Specifications
Operating temperature 0 °C ... +55 °C Wire connection CAGE CLAMP® 0.08 mm2 ... 2.5 mm2; AWG 28 ... 14
8 ... 9 mm /0.33 in stripped length Dimensions (mm) W x H x L 51 x 65* x 100
* from upper edge of DIN 35 rail Weight ca 180 g Storage temperature -25 °C ... +85 °C Relative air humidity 95 % no condensation Vibration and acc. to IEC 60068-2-6 shock resistance acc. to IEC 60068-2-27 Degree of protection IP 20 EMC 1 -Immunity to interference acc. to EN 61000-6-2 (1999) EMC 1 -Emission of interference acc. to EN 50081-2 (1994)
Approvals
Accessories r see General Catalogue W4 Volume 3 Conformity marking 1
Item Pack.-unit No. pcs
EL
EC
TR
O
N
IC
S
ELECTRONICS
I/O modules
FI
EL
D B
U S
IN
TE
RF
A
C E
FI
EL
D B
U S
IN
TE
RF
A
C E
750-423 / 753-423
Subject to design changes WAGO Kontakttechnik GmbH & Co. KG Postfach 2880 •D-32385 Minden Tel.: +49(0)571/887-0 E-Mail: info@wago.com
25.04.2007 Hansastr. 27 •D-32423 Minden Fax: +49(0)571/887-169 www.wago.com
4-Channel Digital Input Module AC / DC 24 V 2- to 3-conductor connection; with power jumper contacts
Fig. Series 750 / Technical data see page 30 / Delivery without Mini WSB marker Series 750 / 753 marking see pages 20 ... 21 / 22 ... 23
DI 2
Data contacts
24 V
DI 4
DI 1
DI 3
0 V
Power jumper contacts
DI 3
DI 1
Status
DI 4
DI 2
Status
13 14
15 16
13 14
C
D B
A
750-423
DI 2 DI 1
DI 3
DI
DI 4
0 V
24 V 24 V
0 V 270pF 270pF
Status
750-423
The digital input module receives control signals from digital field devices (sensors, etc.).
Each input module has a noise-rejection filter with a time constant.
An optocoupler is used for electrical isolation between the bus and the field side.
Attention:
An additional supply module must be added for operation with AC 24 V!
Description Item no. Pack.
unit
4DI 24V AC/DC, 50ms, power contacts 750-423 1 4DI 24V AC/DC, 50ms, power contacts (without connector)
753-423 1
Accessories Item no. Pack.
unit
Connectors Connectors Series 753 753-110 25 Coding elements 753-150 100
Miniature WSB Quick marking system plain 248-501 5 with marking see pages 214 ... 215
Approvals
Series 750 and 753 r UL 508 Conformity marking 1
Series 750 4 EN 50021 II 3 GD EEx nA II T4 4 r UL 1604 Class I Div2 ABCD T4A
Technical Data
No. of inputs 4 Current consumpton (internal) 10 mA Voltage via power jumper contacts DC 24 V (-15 % ... +20 %) Signal voltage (0) DC -3 V ... +5 V; AC 0 V .. 5V Signal voltage (1) DC 11 V ... 30 V; AV 10 V .. 27 V Input filter 50 ms Input current typ. DC 7.5 mA; AC 9.5 mA Isolation 500 V system / supply Internal bit width 4 bits Wire connection CAGE CLAMP®
Cross sections 0.08 mm² ... 2.5 mm² / AWG 28 ... 14 Stripped length series 750 / 753 8 ... 9 mm / 0.33 in
9 ... 10 mm / 0.37 in Width 12 mm Weight approx. 50 g EMC 1-Immunity to interference acc. to EN 50082-2 (1996) EMC 1-Emission of interference acc. to EN 50081-1 (1993)
750-513 / 753-513
Subject to design changes WAGO Kontakttechnik GmbH & Co. KG Postfach 2880 •D-32385 Minden Tel.: +49(0)571/887-0 E-Mail: info@wago.com
10.09.2008 Hansastr. 27 •D-32423 Minden Fax: +49(0)571/887-169 www.wago.com
2-Channel Relay Output Module AC 230 V, DC 30 V isolated outputs; 2 make contacts
Fig. Series 750 / Technical data see page 28 / Delivery without Mini WSB marker Series 750 / 753 marking see pages 16 ... 17 / 18 ... 19
DO 2
Data contacts relay 2 relay 1 Status
DO 1
Status
Power jumper contact
L 2 L 1
N
14 24
K1 K2
C
D B
A
13 23
750-513
L
Status
DO 24
750-513
The connected load is switched via the digital output (relay contacts) from the control system.
The internal system voltage is used to trigger the relay.
The NO contacts are electrically isolated.
The switched status of the relay is shown by a LED.
Actuators with a ground (earth) wire may be directly connected to the module.
Description Item no. Pack.
unit
2DO 230V AC 2.0A/ Relay 2NO/ Potential Free
750-513 101)
2DO 230V AC 2.0A/ Relay 2NO/ Potential Free / without power jumper
750-513/000-001 1
2DO 230V AC 2.0A/ Relay 2NO/ Potential Free (without connector)
753-513 101)
1) Also available individually
Accessories Item no. Pack.
unit
753 Series connector 753-110 25 Coding elements 753-150 100
Miniature WSB quick marking system, plain 248-501 5 with marking see pages 256 ... 257
Approvals
Series 750 and 753 Conformity marking 1 r UL 508 4 r ANSI/ISA 12.12.01 Class I, Div. 2, Grp. ABCD, T4
Series 750 4 EN 60079-15 I M2 / II 3 GD Ex nC IIC T4 Marine applications see "Approvals Overview" in section 1
Technical Data
No. of outputs 2 make contacts Current consumption max. (internal) 100 mA Switching voltage (max.) AC 250 V / DC 30 V Switching power 500 VA / 60 W (resistive load) cos � max. =0.4; L/R max = 7 ms Switching current (min.) 10 mA / 5 V DC Switching current (max.) AC / DC 2 A Switching rate (max.) 30 / min (at nominal load) Pull-in time (max.) 10 ms Bounce time (typ.) 1.2 ms Drop-out time (max.) 10 ms Contact material Silver alloy Mechanical life 2 x 107 switching operations Electrical life 3 x 105 switching operations
(AC 2 A / 250 V) or (DC 2 A / 30 V) Isolation 1.5 kV eff. (field/system)*;
* 2.5 kV rated surge voltage;
Overvoltage category III
Internal bit width 2 bits Wire connection CAGE CLAMP®
Cross sections 0.08 mm² ... 2.5 mm² / AWG 28 ... 14 Stripped lengths (750 / 753 Series) 8 ... 9 mm / 0.33 in
9 ... 10 mm / 0.37 in Width 12 mm Weight 53.5 g EMC 1-Immunity to interference acc. to EN 50082-2 (1996) EMC 1-Emission of interference acc. to EN 50081-1 (1993) EMC marine applications - Immunity to interference acc. to Germanischer Lloyd (2003) EMC marine applications - Emission of interference acc. to Germanischer Lloyd (2003)
C
D B
A
750-600 rand marine applications see pages 1.10 ... 1.13
4 II 3 G EEx nA II T4, Class I Div2 ABCD T4A Conformity marking 1
Subject to design changes
General specifications
Item-No. Pack.-unit pcsDescription
Operating temperature 0 °C ... +55 °C Wire connection CAGE CLAMP® 0.08mm2 ... 2.5mm2; AWG 28 ... 14
8 ... 9mm/0.33 in stripped length Dimensions (mm) W x H x L 12 x 64* x 100
* from upper edge of 35 DIN rail Weight ca 35g Storage temperature -25 °C ... +85 °C Relative air humidity 95% no condensation Vibration and acc. to IEC 60068-2-6 shock resistance acc. to IEC 60068-2-27 Degree of protection IP 20 EMC 1 -Immunity to interference acc. to EN 50082-2 (1996) EMC 1 -Emission of interference acc. to EN 50081-1 (1993) EMC marine applications -Immunity to interf. acc. to Germanischer Lloyd (1997) EMC marine applications -Emission of interf. acc. to Germanischer Lloyd (1997)
Approvals
Accessories Item-No. Pack.-unit pcs
Delivery without miniature WSB
Miniature WSB quick marking system plain 248-501 5 with marking see pages 1.174 ... 1.175
After the fieldbus node is assembled with the correct buscoupler and selected I/O modules, the end module is snapped onto the assembly.
It completes the internal data circuit and ensures correct data flow.
One is required for each buscoupler.
End Module
End Module 750-600 10 1)
1) Also available individually
750-600
WAGO Kontakttechnik GmbH Postfach 2880 • D-32385 Minden Tel.: +49(0)5 71 /8 87-0 E-Mail: info@wago.com Hansastr. 27 • D-32423 Minden Fax.: +49(0)5 71 /8 87-169 www.wago.com21.01.2004