Text version
CASS Station Hardware
Table of Contents
1. 106FX2-ST: Ethernet Switch pg 3- 4
2. 100 Series Installation Manual pg 5-24
3. 787-612 Power Supply Data pg 25-26
4. Circuit Breaker Data pg 27
5. Outlet Data pg 28
6. 700-CF3110ZL, Power Contactor pg 29-30
7. 800T-FX6A4, Mushroom Head, Push-Pull Pushbutton pg 31
8. 800T-48HB: Selector Switch pg 32-33
9. Power Stud Block pg 34-35
THE INDUSTRIAL NETWORK COMPANY
The N-TRON® 106FX2 is a low cost, unmanaged six port Industrial Ethernet Switch. It is housed in a hardened, metal, DIN-Rail enclosure, and is designed for use in industrial data acquisition, control, and Ethernet I/O applications.
PRODUCT FEATURES
• Compact Size, Small Footprint
• Unmanaged Operation
• Full IEEE 802.3 Compliance
• Four 10/100BaseTX RJ-45 Ports
• Two 100BaseFX Ports with ST or SC Connectors
• Extended Environmental Specifi cations
• -40ºC to 70ºC Operating Temperature
• >2M Hours MTBF
• RJ-45 Ports Support Full/Half Duplex Operation
• Auto Sensing Duplex, Speed, and MDIX (RJ-45)
• Up to 1.2 Gb/s Maximum Throughput
• Store-and-forward Technology
• LED Link/Activity Status Indication
• Redundant Power Inputs (10-30 VDC)
• Hardened Metal DIN-Rail Enclosure
PRODUCT OVERVIEW
The 106FX2 Industrial Network Switch is designed to solve the most demanding industrial communications requirements while providing high throughput and minimum downtime.
The 106FX2 provides four RJ-45 auto sensing 10/100BaseTX ports, plus two fi ber based Fast Ethernet uplink ports. All TX ports are full/half duplex capable, using leading-edge Ethernet switching technology.
The 106FX2 auto-negotiates the speed and flow control capabilities of the four TX port connections, and confi gures itself automatically. The two fi ber ports are 100BaseFX fi ber optic uplinks utilizing industry standard ST or SC duplex connectors.
Since the TX ports of the 106FX2 are auto sensing, there will be no need to make extensive wiring changes if upgrades are made to the host computers, plant systems, or Ethernet I/O modules. The switching fabric simply scales up or down automatically to match your specifi c network environment.
The 106FX2 supports up to 2,000 MAC addresses, thus enabling these products to support extremely sophisticated and complex network architectures.
The N-TRON 106FX2 is an ideal candidate for upgrading existing hubs and repeaters to increase bandwidth and determinism by virtually eliminating network collisions. The product also keeps the network affordable, while maintaining the plug & play simplicity of a unmanaged hub. The 106FX2 can simplify plant wiring by eliminating the need to bring data acquisition and control network connections back to a climate controlled environment.
The 106FX2 has extended operating environmental specifi cations to meet the harsh needs of the industrial environment. For cost savings and convenience the 106FX2 can be DIN-Rail mounted alongside Ethernet I/O or other industrial equipment. The unique compact size provides a small footprint, conserving space in the most critical dimension.
To increase reliability, the 106FX2 contains redundant power inputs. LEDs are provided to display the link status and activity of each port, as well as power on/ off status.
106FX2
THE INDUSTRIAL NETWORK COMPANY
Fiber Transceiver Characteristics Fiber Length 2km* 15km** 40km** 80km**
TX Power Min -19dBm -15dBm -5dBm -5dBm
RX Sensitivity Max -31dBm -31dBm -34dBm -34dBm
Wavelength 1310nm 1310nm 1310nm 1550nm
* Multimode Fiber Optic Cable ** Singlemode Fiber Optic Cable
Contact Information N-TRON Corp. N-TRON Asia N-TRON Europe GmbH 820 S. University Blvd., Suite 4E Unit 1209, Level 12 Alte Steinhauserstr 19 Mobile, AL 36609 USA Chong Hing Finance Center 6330 Cham / Zg Switzerland TEL: (251) 342-2164 288 Nanjing Road West TEL: +41 41 7406636 FAX: (251) 342-6353 200003 Shanghai FAX: +41 41 7406637 Website: www.N-TRON.com P.R. China Email: N-TRON_info@N-TRON.com TEL: +86-021-6133-7770
FAX: +86-021-6133-7999 REV 100426
® 2010 N-TRON, Corp. N-TRON and the N-TRON logo are trademarks of N-TRON, Corp. Product names mentioned herein are for identifi cation purposes only and may be trademarks and/or registered trademarks of their respective company. Specifi cations subject to change without notice. The responsibility for the use and application of N-TRON products rests with the end user. N-TRON makes no warranties as to the fi tness or suitability of any N-TRON product for any specifi c application. N-TRON Corporation shall not be liable for any damage resulting from the installation, use, or misuse of this product. Printed in USA.
BENEFITS
Industrial Network Switch
• Compact Size, Small Footprint
• Extended Environmental Specifi cations
• High Reliability/Availability
• Extended Environmental Specifi cations
• Hardened Metal DIN-Rail Enclosure
• High Performance
• High MTBF >2 Million Hours (measured)
Ease of Use
• Plug & Play Operation
• Four Auto Sensing 10/100BaseTX RJ-45 Ports
• RJ-45 Ports Auto Sense Duplex, Speed, and
Cable Type
• Compact DIN-Rail Package
Increased Performance
• Full Wire Speed Capable
• 100BaseFX Fiber Uplink
• Full Duplex Capable
• Eliminates Network Collisions
• Increases Network Determinism
Regulatory Approvals FCC Title 47 Part 15 Class A, ICES-003 Class A
CE: EN61000-6-2, EN61000-3-2,3; IEC61000-4-2,3,4,5,6,11
EN55011
UL/cUL: Hazardous Locations Class I, Div 2, Groups A, B, C, D or non-Hazardous Locations, ANSI/ISA 12.12.01-2000, T4A DNV Type Approved and ABS for Shipboard Applications
Designed to comply with:
IEEE 1613 for Electric Utility Substations NEMA TS1/TS2 for Traffi c Control Equipment
SPECIFICATIONS
Case Dimensions Height: 3.5" (8.9 cm) Width: 1.50" (3.8 cm) Depth: 3.6" (9.0 cm) Weight: 0.60 lbs. (0.27 kg) DIN-Rail: 35mm
Electrical Input Voltage: 10-30 VDC Input Current: 270mA@24V BTU/hr: 27@24VDC Inrush: 7.9Amp/0.7ms@24V
Environmental Operating Temperature: -40oC to 70oC Storage Temperature: -40oC to 85oC Operating Humidity: 10% to 95%
(Non Condensing) Operating Altitude: 0 to 10,000 ft.
Network Media 10BaseT: >Cat3 Cable 100BaseTX: >Cat5 Cable 100BaseFX:
Multimode: 50-62.5/125μm Singlemode: 7-10/125μm
Connectors 10/100BaseTX: Four (1) RJ-45 TX Ports 100BaseFX: One (1) ST or SC Duplex Port
Recommended Wiring Clearance Front: 4" (10.16 cm) Top: 1" (2.54 cm)
Ordering Information 106FX2-XX 100BaseFX multimode fi ber 106FXE2-XX-YY 100BaseFX singlemode fi ber NTPS-24-1.3 DIN-Rail Power Supply 24V@1.3 Amp 100-MDR-2 Metal Din Rail Option - Tall Enclosures Where "XX" is: ST for ST style fi ber connector, SC for SC style fi ber connector Where "YY" is: 15 for 15km max. fi ber segment length 40 for 40km max. fi ber segment length 80 for 80km max. fi ber segment length
* MDR option must be specifi ed with switch order - not fi eld upgradable
THE INDUSTRIAL NETWORK COMPANY
106FX2 with Standard DIN rail Mount
Optional 100-MDR-2 Metal DIN Rail Mount
® 2010 N-TRON, Corp. N-TRON and the N-TRON logo are trademarks of N-TRON, Corp. Specifi cations subject to change without notice. Printed in USA.
100 Series Media Converter &
Industrial Ethernet Switches
User Manual & Installation
Guide
Industrial Media Converter Installation Guide
102MC-XX
102MCE-XX-YY
104TX
105TX
105FX-XX
105FXE-XX-YY
106FX2
108TX
108TX-HV
Where: XX = ST or SC and YY = -15, -40, or -80
Copyright, © N-TRON Corp., 2008 820 S. University Blvd., Suite 4E Mobile, AL USA 36609
All rights reserved. Reproduction, adaptation, or translation without prior written permission from N-TRON Corp. is prohibited, except as allowed under copyright laws.
Ethernet is a registered trademark of Xerox Corporation. All other product names, company names, logos or other designations mentioned herein are trademarks of their respective owners.
The information contained in this document is subject to change without notice. N-TRON Corp. makes no warranty of any kind with regard to this material, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. In no event shall N-TRON Corp. be liable for any incidental, special, indirect or consequential damages whatsoever included but not limited to lost profits arising out of errors or omissions in this manual or the information contained herein.
Contact Information
N-TRON Corp.
820 South University Blvd.
Suite 4E Mobile, AL 36609
TEL: (251) 342-2164
FAX: (251) 342-6353
Website: www.n-tron.com Email: N-TRON_Support@n-tron.com
GENERAL SAFETY WARNINGS
WARNING: Do not operate the equipment in the presence of flammable gasses or fumes.
Operating electrical equipment in such an environment constitutes a definite safety hazard.
WARNING: If the equipment is used in the manner not specified by N-TRON Corp., the protection provided by the equipment may be impaired.
WARNING: Do not perform any services on the unit unless qualified to do so. Do not substitute unauthorized parts or make unauthorized modifications to the unit.
WARNING: Do not operate the unit with the end plates removed, as this could create a shock or fire hazard.
WARNING: Do not operate the equipment in a manner not specified by this manual.
ENVIRONMENTAL SAFETY WARNINGS
WARNING: Disconnect the power and allow to cool 5 minutes before touching.
ELECTRICAL SAFETY WARNINGS
WARNING: Disconnect the power cable before removing the end plates.
WARNING: Do not operate the unit with the end plates removed.
WARNING: Do not work on equipment or cables during periods of lightning activity.
WARNING: Do not perform any services on the unit unless qualified to do so.
WARNING: Observe proper DC Voltage polarity when installing power input cables. Reversing voltage polarity can cause permanent damage to the unit and void the warranty.
HAZARDOUS LOCATION INSTALLATION REQUIREMENTS
1. This equipment is suitable for use in Class I, Div 2, Groups A, B, C, and D, or unclassified or non-hazardous locations only.
2. WARNING: Explosion Hazard - Substitution of components may impair suitability for Class I, Division 2.
3. WARNING: Explosion hazard, do not disconnect while the circuit is live or unless the area is known to be non-hazardous.
4. WARNING: Explosion Hazard - Do not remove or replace the device unless power has been switched off or the area is known to be non-hazardous.
5. Use 60/75ºC rated Copper wire, (0.22Nm) 2 inch-lbs Tightening torque for field installed connectors.
6. WARNING: Install only in accordance with Local & National Codes of Authorities Having Jurisdiction.
7. Class I, Div 2 Installations require that power connections must be current limited at the power source with an in-line fuse rated at 0.5A.
8. Class I, Div 2 installations require that all devices connected to this product must be UL listed for the area in which it is installed.
9. Limited Operating Voltage: 12-30V for Class I, Div 2 installations.
100 Series Industrial Ethernet Switches
The 100 Series Unmanaged Industrial Ethernet Switches support high speed layer 2 switching between ports. This series of switches are housed in a ruggedized aluminum enclosure, and provide Category-5 compliant 10/100-BaseT connections for high performance network design, and hub/repeater upgrades.
All fiber products utilize the IEEE compliant SC or ST duplex connectors for fiber optic communications.
All 10/100Base-TX ports utilize the RJ45 shielded connectors.
The 102MC/MCE is a two port unmanaged media converter that converts 10/100BaseTX copper to 100BaseFX full duplex fiber.
The 104TX, 105TX, and 108TX are affordable and share a small footprint. Each switch is capable of auto negotiating 10/100 Mb and half/full duplex communications.
The 105FX/FXE has 4 ports similar to the 104TX, plus additional multimode fiber optic up-link port(s), capable of 2 Kilometers of 100 Mb communications for the FX models, and up to 80 Kilometers for the FXE models without the use of repeaters.
The 106FX2/FXE2 has 4 10/100BaseTX RJ-45 auto sensing ports and 2 100BaseFX ports with ST or SC connectors, capable of 2 Kilometers of 100 Mb communications for the FX models, and up to 80 Kilometers for the FXE models without the use of repeaters.
Key Features
• Full IEEE 802.3 & 100Base-FX Compliance
• Extended Environmental Specifications
• Support for Full/Half Duplex Operation
• LED Link/Activity Status Indication
• Autonegotiation, Autosensing Speed, Duplex, and Flow Control
• Up to 1.6 Gb/s Maximum Throughput
• Industry Standard 35mm DIN Rail Mounted Enclosure
108TX-HV Only
PACKAGE CONTENTS
Please make sure the package contains the following items:
1. 100 Series Media Converter or Ethernet Switch
2. Instruction Sheet
Contact your carrier if any items are damaged.
UNPACKING
Remove all the equipment from the packaging, and store the packaging in a safe place. File any damage claims with the carrier.
CLEANING
Clean only with a damp cloth.
INSTALLATION
Read the following warning before beginning the installation:
WARNING
Never install or work on electrical equipment or cabling during periods of lightning activity. Never connect or disconnect power when hazardous gasses are present.
LASER SAFETY (MCE and FXE models only -40 and -80)
CAUTION: CLASS 1 LASER PRODUCT. Do not stare into the laser!
DIN-Rail Mounting
Install the unit in a standard DIN rail. Recess the unit to allow at least 2” of horizontal clearance for CAT5e cable bend radius.
To install the unit to 35mm industrial DIN rail, place the top edge of the included mounting bracket on the back of the unit against the DIN rail at a 15° angle as shown. Rotate the bottom of the unit to the back (away from you) until it snaps into place.
To remove the unit from the 35mm industrial DIN rail, place a flat head screwdriver into the release clip found at the bottom of the unit, and apply downward force on the clip until it disengages from the bottom of the unit from the DIN rail. Rotate the bottom of the unit towards you and up at an approximate 15° upward angle to completely remove the unit.
Most N-Tron™ products are designed to be mounted on industry standard 35mm DIN rail.
However, DIN rail mounting may not be suitable for all applications. Our Universal Rack Mount Kit (P/N: URMK) may be used to mount the 100 Series enclosures to standard 19" racks as an option.
FRONT PANEL
From Top to Bottom:
SPD Speed LED LNK/ACT Link/Activity LED RJ45 Ports Auto sensing 10/100BaseT Connection
Green LED lights when Power is connected
NOTE: The top LED indicates Link/Activity (LNK/ACT), and the lower LED indicates Speed (SPD) status.
LED’s: The table below describes the operating modes:
LED Color Description
ON Power is Applied.
OFF Power is OFF.
LNK/ACT
ON Link established, no Activity on cable.
BLINKING Link established, Activity on cable OFF No link activity on cable.
SPD
ON LINK is 100Mbps.
OFF Link is 10Mbs.
APPLYING POWER (Top View)
Unscrew & Remove the DC Voltage Input Plug from the top header.
Install the DC Power Cables into the Plug (observing polarity on unit).
Plug the Voltage Input Plug back into the top header.
Tightening torque for the terminal block power plug is 0.22 Nm/0.162 Pound Foot.
All LED’s will flash ON Momentarily.
Verify the Power LED stays ON (GREEN).
Note: Either V1 or V2 can be connected to power for minimal operation. For redundant power operation, V1 and V2 plugs must be connected to separate DC Voltage sources. Use wire sizes of 16-28 gauge. The power cord should be limited to less than 10 meters in order to ensure optimum performance.
Recommended 24V DC Power Supplies, similar to:
100-240VAC: N-Tron NTPS-24-1.3, DC 24V/1.3
N-TRON SWITCH GROUNDING TECHNIQUES FOR 100 SERIES
The grounding philosophy of any control system is an integral part of the design. N-Tron switches are designed to be grounded, but the user has been given the flexibility to float the switch when required. The best noise immunity and emissions (i.e. CE) are obtained when the N-Tron switch chassis is connected to earth ground via a drain wire. Some N-Tron switches have metal din-rail brackets that can ground the switch if the din-rail is grounded. In some cases, N-Tron switches with metal brackets can be supplied with optional plastic brackets if isolation is required.
Users may run a drain wire & lug from the screw provided on the back face of the enclosure. In the event the provided grounding screw has been lost, care should be taken to limit the penetration of the outer skin by less than 1/4". Failure to do so may cause irreversible damage to the internal components of the switch.
Note: Ensure the power supply is grounded properly before applying power to the grounded switch. This may be verified by using a voltmeter to determine that there is no voltage difference between the power supply’s negative output terminal and the chassis grounding point of the switch.
As an alternative grounding method, both V- legs of the power input connector are connected to chassis internally on the PCB. Connecting a drain wire to earth ground from one of the V- terminal plugs as shown here will ground the switch and the chassis. The power leads from the power source should be limited to 3 meters or less in length.
If the use of shielded cables is required, it is generally recommended to only connect the shield at one end to prevent ground loops and interfere with low level signals (i.e. thermocouples, RTD, etc.).
Cat5e cables manufactured to EIA-568A or 568B specifications are required for use with N-Tron Switches.
In the event all Cat5e patch cable distances are small (i.e. All Ethernet devices are located the same local cabinet and/or referenced to the same earth ground), it is permissible to use fully shielded cables terminated to chassis ground at both ends in systems void of low level analog signals.
RJ45 CONNECTOR CRIMP SPECIFICATIONS
Please reference the illustration for your Cat5 cable specifications:
CONNECTING THE UNIT
For the 100BaseFX Fiber Optic port, remove the dust cap(s) from the fiber optic connector and connect the fiber optic cables. The TX port on the local unit should be connected to the RX port of the far end device, and the RX port should be connected to the TX port of the far end device.
For 10Base-T ports, plug a Category 3 (or greater) twisted pair cable into the RJ45 connector.
For 100Base-T ports, plug a Category 5 (or greater) twisted pair cable into the RJ45 connector.
Connect the other end to the far end station. Verify that the LNK LED’s are ON once the connection has been completed. To connect any other port to another Switch or Repeater, use a standard Cat5 straight through or crossover cable.
Warning: Creating a port to port connection on the same switch (i.e. loop) is an illegal operation and will create a broadcast storm which will crash the network!
TROUBLESHOOTING
1. Make sure the (Power LED) is ON.
2. Make sure you are supplying sufficient current for the version chosen. Note: The Inrush current will exceed the steady state current by ~ 2X.
3. Verify that Link LED’s are ON for both ports.
4. Verify cabling used between stations.
5. Verify that cabling is Category 3 or greater for 10Mbit Operation.
SUPPORT
Contact N-Tron Corporation at:
TEL: 251-342-2164
FAX: 251-342-6353
www.n-tron.com N-TRON_Support@n-tron.com
FCC STATEMENT
This product complies with Part 15 of the FCC-A Rules.
Operation is subject to the following conditions:
(1) This device may not cause harmful Interference
(2) This device must accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. Operation of this device in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
102MC/MCE - KEY SPECIFICATIONS
Physical Height: 2.87” (7.28cm) Width: 1.49” (3.78cm) Depth: 3.53” (8.96cm) Weight: 0.5 lbs. (0.22 kg) DIN Rail 35 mm
Electrical Input Voltage: 10-30 VDC (Regulated) Input Current: 140mA max. @ 24VDC (Steady State) Inrush Current: 8.5Amp/0.7 ms max. @ 24VDC Input Ripple: Less than 100 mV Input Wire Size: 16-28 AWG
Environmental Operating Temperature: -40°C to 80°C Storage Temperature: -40°C to 85°C Operating Humidity: 10% to 95% (Non Condensing) Operating Altitude: 0 to 10,000 ft.
Network Media 10BaseT: > Cat-3 Cable 100BaseT: > Cat-5 Cable 100BaseF: Multimode: 50-62.5/125µm Fiber
Singlemode: 7-10/125µm Fiber Fiber Transceiver Characteristics Fiber Length: 2km* 15km** 40km** 80km** TX Power Min -19dBm -15dBm -5dBm -5dBm RX Sensitivity Max: -31dBm -31dBm -34dBm -34dBm Wavelength: 1310nm 1310nm 1310nm 1550nm *=Multimode ** =Singlemode
Connectors 10/100BaseTX: RJ45 UTP Port 100BaseFX: SC or ST Duplex Port
Recommended Minimum Wiring Clearance:
Top: 1 " (2.54 cm) Front: 4 " (10.16 cm)
Warranty: Effective January 1, 2008, all N-TRON products carry a 3 year warranty from the date of purchase.
Regulatory Approvals: (Typical for Models 104TX, 105TX, 105FX, 106FX, 106FX2 & 108TX)
Safety: Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations, or Nonhazardous Locations only.
EMI: EN61000-6-4, EN55011 - Class A FCC Title 47, Part 15, Subpart B - Class A ICES-003 – Class A
EMS: EN61000-6-2
EN61000-4-2 (ESD)
EN61000-4-3 (RS)
EN61000-4-4 (EFT)
EN61000-4-5 (Surge) EN61000-4-6 (Conducted Disturbances)
GOST-R Certified.
104TX/105TX - KEY SPECIFICATIONS
Height: 2.87” (7.28cm) Width: 1.49” (3.78cm) Depth: 3.53” (8.96cm) Weight: 0.6 lbs. (0.27kg) DIN Rail 35 mm
Electrical Input Voltage: 10-30 VDC (Regulated) Input Current: 215 mA max. @ 24VDC (Steady State) Inrush Current: 7.8 Amp/0.7ms max. @ 24VDC Input Ripple: Less than 100 mV Input Wire Size: 16-28 AWG
Environmental Operating Temperature: -40°C to 80°C Storage Temperature: -40°C to 85°C Operating Humidity: 10% to 95% (Non Condensing) Operating Altitude: 0 to 10,000 ft.
Network Media 10BaseT: > Cat-3 Cable 100BaseT: > Cat-5 Cable
Connectors 10/100BaseT: RJ45 UTP Ports
Recommended Minimum Wiring Clearance:
Top: 1 " (2.54 cm) Front: 2 " (5.08 cm)
106FX/FX2 - KEY SPECIFICATIONS
Height: 3.83” (9.73cm) Width: 1.50” (3.81cm) Depth: 4.80” (12.2cm) Weight: 0.6 lbs. (0.27kg) DIN Rail 35 mm
Electrical Input Voltage: 10-30 VDC (Regulated) Input Current: 270 mA max. @ 24VDC (Steady State) Inrush Current: 8.0 Amp/0.7ms max. @ 24VDC
Environmental Operating Temperature: -40°C to 70°C Storage Temperature: -40°C to 85°C Operating Humidity: 10% to 95% (Non Condensing) Operating Altitude: 0 to 10,000 ft.
Network Media 10BaseT: > Cat-3 Cable 100BaseTX: > Cat-5 Cable 100BaseFX:
Multimode: 50-62.5/125µm Singlemode: 7-10/125µm
Connectors 10/100BaseTX Four (4) RJ-45 TX Ports 100BaseFX Two (2) ST or SC Duplex Ports
Recommended Minimum Wiring Clearance:
Top: 1 " (2.54 cm) Front: 4 " (10.16 cm)
108TX - KEY SPECIFICATIONS
Height: 3.5” (8.89cm) Width: 1.49” (3.78cm) Depth: 3.53” (8.96cm) Weight: 0.7 lbs. (0.31kg) DIN Rail 35 mm
Electrical Input Voltage: 10-30 VDC (Regulated) -HV option: 10-60 VDC (Regulated) Input Current: 250 mA max. @ 24VDC (Steady State) Inrush Current: 8.1 Amp/0.7ms max. @ 24VDC Input Ripple: Less than 100 mV Input Wire Size: 16-28 AWG
Environmental Operating Temperature: -40°C to 70°C Storage Temperature: -40°C to 85°C Operating Humidity: 10% to 95% (Non Condensing) Operating Altitude: 0 to 10,000 ft.
Network Media 10BaseT: > Cat-3 Cable 100BaseT: > Cat-5 Cable
Connectors 10/100BaseT: Eight (8) RJ45 UTP Ports
Recommended Minimum Wiring Clearance:
Top: 1 " (2.54 cm) Front: 2 " (5.08 cm)
105FX - KEY SPECIFICATIONS
Height: 3.83” (9.72cm) Width: 1.49” (3.78cm) Depth: 3.53” (8.96cm) Weight: 0.6 lbs. (0.27kg) DIN Rail 35 mm
Electrical Input Voltage: 10-30 VDC (Regulated) Input Current: 270mA max. @ 24VDC (Steady State) Inrush Current: 8.0Amp/0.7 ms max. @ 24VDC Input Ripple: Less than 100 mV Input Wire Size: 16-28 AWG
Environmental Operating Temperature: -40°C to 70°C Storage Temperature: -40°C to 85°C Operating Humidity: 10% to 95% (Non Condensing) Operating Altitude: 0 to 10,000 ft.
Network Media 10BaseT: > Cat-3 Cable 100BaseT: > Cat-5 Cable 100BaseFX:
Multimode: 50-62.5/125µm Fiber Singlemode: 7-10/125µm Fiber Fiber Transceiver Characteristics Fiber Length: 2km* 15km** 40km** 80km** TX Power Min -19dBm -15dBm -5dBm -5dBm RX Sensitivity Max: -31dBm -31dBm -34dBm -34dBm Wavelength: 1310nm 1310nm 1310nm 1550nm *=Multimode ** =Singlemode
Connectors 10/100BaseTX: RJ45 UTP Port 100BaseFX: SC or ST Duplex Port
Recommended Minimum Wiring Clearance:
Top: 1 " (2.54 cm) Front: 4 " (10.16 cm)
N-TRON Limited Warranty
N-TRON, Corp. warrants to the end user that this hardware product will be free from defects in workmanship and materials, under normal use and service, for the applicable warranty period from the date of purchase from N-TRON or its authorized reseller. If a product does not operate as warranted during the applicable warranty period, N-TRON shall, at its option and expense, repair the defective product or part, deliver to customer an equivalent product or part to replace the defective item, or refund to customer the purchase price paid for the defective product. All products that are replaced will become the property of N-TRON. Replacement products may be new or reconditioned. Any replaced or repaired product or part has a ninety (90) day warranty or the remainder of the initial warranty period, whichever is longer. N-TRON shall not be responsible for any custom software or firmware, configuration information, or memory data of customer contained in, stored on, or integrated with any products returned to N-TRON pursuant to any warranty.
OBTAINING WARRANTY SERVICE: Customer must contact N-TRON within the applicable warranty period to obtain warranty service authorization. Dated proof of purchase from N-TRON or its authorized reseller may be required. Products returned to N-TRON must be pre-authorized by N-TRON with a Return Material Authorization (RMA) number marked on the outside of the package, and sent prepaid and packaged appropriately for safe shipment. Responsibility for loss or damage does not transfer to N-TRON until the returned item is received by N-TRON. The repaired or replaced item will be shipped to the customer, at N-TRON’s expense, not later than thirty (30) days after N-TRON receives the product. N-TRON shall not be responsible for any software, firmware, information, or memory date of customer contained in, stored on, or integrated with any products returned to N-TRON for repair, whether under warranty or not.
ADVANCE REPLACEMENT OPTION: Upon registration, this product qualifies for advance replacement. A replacement product will be shipped within three (3) days after verification by N-TRON that the product is considered defective. The shipment of advance replacement products is subject to local legal requirements and may not be available in all locations. When an advance replacement is provided and customer fails to return the original product to N-TRON within fifteen (15) days after shipment of the replacement, N-TRON will charge customer for the replacement product, at list price.
WARRANTIES EXCLUSIVE: IF AN N-TRON PRODUCT DOES NOT OPERATE AS WARRANTED ABOVE, CUSTOMER'S SOLE REMEDY FOR BREACH OF THAT WARRANTY SHALL BE REPAIR, REPLACEMENT, OR REFUND OF THE PURCHASE PRICE PAID, AT N-TRON'S OPTION. TO THE FULL EXTENT ALLOWED BY LAW, THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND ARE IN LIEU OF ALL OTHER WARRANTIES, TERMS, OR CONDITIONS, EXPRESS OR IMPLIED, EITHER IN FACT OR BY OPERATION OF LAW, STATUTORY OR OTHERWISE, INCLUDING WARRANTIES, TERMS, OR CONDITIONS OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE, SATISFACTORY QUALITY, CORRESPONDENCE WITH DESCRIPTION, AND NON-INFRINGEMENT, ALL OF WHICH ARE EXPRESSLY DISCLAIMED.
N-TRON NEITHER ASSUMES NOR AUTHORIZES ANY OTHER PERSON TO ASSUME FOR IT ANY OTHER LIABILITY IN CONNECTION WITH THE SALE, INSTALLATION, MAINTENANCE OR USE OF ITS PRODUCTS. N-TRON SHALL NOT BE LIABLE UNDER THIS WARRANTY IF ITS TESTING AND EXAMINATION DISCLOSE THAT THE ALLEGED DEFECT OR MALFUNCTION IN THE PRODUCT DOES NOT EXIST OR WAS CAUSED BY CUSTOMER'S OR ANY THIRD PERSON'S MISUSE, NEGLECT, IMPROPER INSTALLATION OR TESTING, UNAUTHORIZED ATTEMPTS TO OPEN, REPAIR OR MODIFY THE PRODUCT, OR ANY OTHER CAUSE BEYOND THE RANGE OF THE INTENDED USE, OR BY ACCIDENT, FIRE, LIGHTNING, POWER CUTS OR OUTAGES, OTHER HAZARDS, OR ACTS OF GOD.
LIMITATION OF LIABILITY: TO THE FULL EXTENT ALLOWED BY LAW, N-TRON ALSO EXCLUDES FOR ITSELF AND ITS SUPPLIERS ANY LIABILITY, WHETHER BASED IN CONTRACT OR TORT (INCLUDING NEGLIGENCE), FOR INCIDENTAL, CONSEQUENTIAL, INDIRECT, SPECIAL, OR PUNITIVE DAMAGES OF ANY KIND, OR FOR LOSS OF REVENUE OR PROFITS, LOSS OF BUSINESS, LOSS OF INFORMATION OR DATA, OR OTHER FINANCIAL LOSS ARISING OUT OF OR IN CONNECTION WITH THE SALE, INSTALLATION, MAINTENANCE, USE, PERFORMANCE, FAILURE, OR INTERRUPTION OF ITS PRODUCTS, EVEN IF N-TRON OR ITS AUTHORIZED RESELLER HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES, AND LIMITS ITS LIABILITY TO REPAIR, REPLACEMENT, OR REFUND OF THE PURCHASE PRICE PAID, AT N-TRON'S OPTION. THIS DISCLAIMER OF LIABILITY FOR DAMAGES WILL NOT BE AFFECTED IF ANY REMEDY
PROVIDED HEREIN SHALL FAIL OF ITS ESSENTIAL PURPOSE.
DISCLAIMER: Some countries, states, or provinces do not allow the exclusion or limitation of implied warranties or the limitation of incidental or consequential damages for certain products supplied to consumers or the limitation of liability for personal injury, so the above limitations and exclusions may be limited in their application to you. When the implied warranties are not allowed to be excluded in their entirety, they will be limited to the duration of the applicable written warranty. This warranty gives you specific legal rights which may vary depending on local law.
GOVERNING LAW: This Limited Warranty shall be governed by the laws of the State of Alabama, U.S.A.
Power Supply Unit 1/2 Primary switched-mode, DC 24 V / 2.5 A D a t a s h e e t
WAGO Kontakttechnik GmbH Postfach 2880 � D-32385 Minden Tel.: 05 71 / 8 87-0 E-Mail: info@wago.com Hansastr. 27 � D-32423 Minden Fax.: 05 71 / 8 87-169 Web: http://www.wago.com
Subject to design changes
08.11.2004 / d561200e.doc
DC +
DC +
DC -
DC -
L
N
Description Item-No. Pack.-unit pcs
Input AC/DC 230 V ; Output DC 24 V / 2.5 A 787-612 1
Power supply unit with a broad input voltage range for assembly onto DIN 35 rail.
Characteristics:
• U/I characteristic.
• Short circuit proof.
• Open circuit proof.
• Use of switching regulator controller technology ensures compact design.
• High efficiency.
• Overload-proof (short time).
• Cutoff in case of thermal overload.
Technical Data Input Nominal voltage UI nom AC/DC* 230 V Voltage range AC 90-264 V
DC* 130-300 V
* Use of DC requires external protection
Frequency 50-60 Hz Input current Ii 0.6 Atyp. at AC 230 V Inrush current <10 AP Discharge current 940 µAtyp.
Output hold-up time >20 ms at AC 230 V Overvoltage protection Varistor at primary circuit Output Nominal voltage UO nom DC 24 V Voltage range DC 22-28.8 V adjustable Output current Io 2.5 A at DC 24 V Residual ripple <100 mVpp up to 20 MHz Adjustment accuracy max. 1.5 % Overvoltage protection max. DC 40 V Current limitation from approx.1.1 x Ia (see output characteristic) Efficiency 81 %typ.
Safety extra low voltage SELV General data Test voltage 4.2 kV Degree of protection IP 20 Protection class prepared for class I equipment Cooling system natural convection cooling when horizontally mounted Design encapsulated, for use in switchgear cabinets Parallel connection of power supply units permissible Operation indicator LED green (24 V o.k.)
Ambient operating temperature 0 °C...+60 °C Storage temperature -25 °C...+85 °C
Power Supply Unit 2/2 Primary switched-mode, DC 24 V / 2.5 A D a t a s h e e t
WAGO Kontakttechnik GmbH Postfach 2880 � D-32385 Minden Tel.: 05 71 / 8 87-0 E-Mail: info@wago.com Hansastr. 27 � D-32423 Minden Fax.: 05 71 / 8 87-169 Web: http://www.wago.com
Subject to design changes
08.11.2004 / d561200e.doc
Output characteristic Mounting system To be snapped onto DIN rail (EN 50022) Wire connection Terminal blocks with CAGE CLAMP®
(WAGO series 231) 0.08-2.5 mm2 / AWG 28-12**
** AWG12: THHN, THWN
Stripped length 8-9 mm / 0.33 in Weight 690 g Dimensions (WxHxD) (56 x 144***x 110) mm
(2.2 x 5.67***x 4.33) in *** from upper edge of DIN35 rail
Standards / prescriptions Safety EN 60950 Emission of interference EN 50081-1 Immunity to interference EN 61000-6-2
WAGO Corporation N120 W19129 Freistadt Road, Germantown, WI 53022 1-800 DIN Rail www.wago.com
DIN Rail Mount Pluggable Circuit Breaker
End Plate, Orange, 2 mm thick Adjacent jumper, Gray Alternate jumper, Gray Test Plug Adapter for 4 mmØ test plug End Clamp DIN Rail 35 mm x 7.5 mm, slotted, 2 M long
Accessories
Description Part # Package Qty
2-conductor circuit breaker terminal block, gray with 24 V indicator, tripped circuit with 110 V indicator, tripped circuit Plug-in circuit breaker with push button reset
0.25 A AC 250 V DC 65 V
0.5 A AC 250 V DC 65 V
1.0 A AC 250 V DC 65 V
2.0 A AC 250 V DC 65 V
3.0 A AC 250 V DC 65 V
4.0 A AC 250 V DC 65 V
5.0 A AC 250 V DC 65 V
6.0 A AC 250 V DC 65 V
8.0 A AC 250 V DC 65 V
10.0 A AC 250 V DC 65 V
Plug-in circuit breaker with on-off switch -switching duty rated
0.25 A AC 250 V DC 65 V
0.5 A AC 250 V DC 65 V
1.0 A AC 250 V DC 65 V
2.0 A AC 250 V DC 65 V
3.0 A AC 250 V DC 65 V
4.0 A AC 250 V DC 65 V
5.0 A AC 250 V DC 65 V
6.0 A AC 250 V DC 65 V
8.0 A AC 250 V DC 65 V
10.0 A AC 250 V DC 65 V
Consult factory for additional circuit breaker currents.
282-6696 25 282-6698/281-4413 25 Consult ffactory
5511001111113355 1 5511001111113366 1 5511001111113377 1 5511001111113388 1 5511001111113399 1 5511001111114400 1 5511001177667733 1 5511001111114411 1 5511001111114422 1 5511001111114433 1
5511001122449944 1 5511001122449955 1 5511001122449966 1 5511001122449977 1 5511001122449988 1 5511001122449999 1 5511001122550000 1 5511001122550011 1 5511001122550022 1 5511001122550033 1
Technical DData Voltage rating AC 250 V; DC 65 V Current ratings 0.1...10 A Typical life 3,000 operations at 1xlN (low resistive)
500 operations at 2xlN (inductive) Ambient temp. -20...+60° C (T60) -4...+140° F Insulation co-ordination Rated impulse Pollution (IEC 60664 and 60664A) withstand voltage degree
2.5kV 2 reinforced insulation in operating area Dielectric strength (IEC 60664 and 60664A) Test voltage operating area AC 3,000 V installation area AC 1,500 V
Insulation resistance >100 MΩ (DC 500 V) Interrupting capacity lcn 0.1...5 A 6 x lN
6...10 A 8 x lN Interrupting capacity AC 250 V; 2,000 A
(UL 1077) DC 65 V; 200 A
Degree of protection operating area IP 40 (IEC 60529/DIN 40050) terminal area IP 00 Vibration 5 g (57-500 Hz)±0.38mm (10- 57 Hz) to IEC 60068-2-6, Test Fc, 10 frequency cycles/axis
Shock 25 g (11 ms) to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5% salt mist, to IEC 60068-2-11, test Ka
Humidity 240 hours at 95% RH to IEC 60068-2-3, test Ca
Mass approx. 15 g
0.02 – 6 mm2 AWG 24 – 10 400 V/6 kV/3 * 600 V*, 30 A * 25/30 A *
Terminal block width 8 mm . 0.315 in l 12 – 13 mm / 0.49 in
* Current / Voltage limited to circuit breaker specification
Miniature thermal circuit breaker for protection of power distribution systems, automation systems, and process control applications.
Terminal block uses CAGE CLAMP®
Connection technology to reduce wiring time and provide a connection that is corrosion resistant, temperature cycling resistant and maintenance free.
282-333 100 282-402 100 282-409 100 282-170 50 249-116 100 210-112 10
85 mm/3.35 in.
m m
/3 .3 in
WAGO Utility Outlet 120 V/15 A Duplex Outlet Data sheet
Description
120 V / 15 A Duplex Outlet 51017543 1
Subject to design changes
Technical Data
Rated voltage Rated Current Rated AWG Wire Strip Length Mounting
Width Height Length Length w/connector
DIN rail Slotted 35 x 7.5 mm (2M)
End Stop Screwdriver
120 V UL / CSA Pending
15 A UL / CSA Pending
28 -12 UL / CSA Pending
9 - 10 mm / 0.35 in.
35 mm DIN rail
60 mm / 2.36 in.
68 mm / 2.68 in.
109 mm / 5.09 in.
210-113 10
249-116 100
210-620 1
W Application:
The WAGO UTLITY OUTLET is a convenient power source - in the control cabinet, for connecting laptops, solder irons, test equipment, lighting, etc.
Features:
• Ground pin located on the top to prevent loose metal objects (wire strands or screwdriver) from inadvertantly shorting the hot and neutral pins together.
• CAGE CLAMP connection for error / maintenance free connection - no torque specs.
• Color coded (and labeled) marking tags for easy and safe installation.
• Built-in test point for troubleshooting.
• Compact design takes up less space.
• 35 mm DIN rail mount provides easy installation.
60 mm / 2.36” m m
.0 8”
Dimensions
Accessories
Item Number Pack Unit (pcs)
WAGO Corporation N120 W19129 Freistadt Road; P.O. Box 1015; Germantown, WI 53022 1-800 DIN Rail (346-7245) Fax: (262) 255-3232 info.us@wago.com www.wago.com
Industrial Relays
9-148 Visit our website: www.ab.com/catalogs
Overview, Continued
Bulletin. No. 700-M/MB 700-CF 700S-CF 700-P 700S-P 700-R
Mechanically Linked contacts✶
Y† Y Y Y‡ Y‡ N
Double-break contacts Y Y Y Y Y —
Switch millions of operations at >1 A Y Y Y Y Y Y
Low-energy switching Y Y Y Y Y Y
Marine certification— vibration applications
Y Y Y Y Y Y
Relay Differences
Number of circuits to switch (number of poles)
4…8 4…10 (AC)
4…8 (DC) 8 2…12 2…12 2…8
Current ratings at
120V AC 10 A 10 A 10 A 10…35 A 10 A 5 A
Pneumatic timer option N Y N Y N Y
Electronic timer option Y Y Y Y N Y
Latch option N Y N Y N Y
Built-in surge suppression for 24V DC coil option
Y Y Y N N Y§
Convertible and replaceable contacts
N N N Y N Y
Switch 20…35 A on 6…12 poles N N N Y N N
DIN Rail Mounting Y Y Y N N N
Finger-Safe Terminals Y Y Y N N N
Poles permanently attached N N Y Y Y Y
✶ If a N.O. contact welds, the N.C. contacts will remain open and if a N.C. contact welds, the N.O. contacts will remain open.
† Yes for main poles only.
‡ Bulletins 700-P and 700S-P meet the component requirements for relays of ANSI B11.19 section 5.5.1 (Control Reliability).
§ Y for AC coil.
Bulletin 700-CF
Industrial Relays
9-149Visit our website: www.ab.com/catalogs
Overview/Product Selection
Bulletin 700-CF � IEC Industrial Relays (Finger Safe Design) � Positively-Guided/Mechanically-Linked Contacts per IEC 947-5-1
Annex L on Main and Auxiliary Contacts � Gold Plated, Bifurcated Version for Low Level Switching Applications � Master Control Relay Version rated 15 A (AC-15) � Solid-State and Pneumatic Timing Modules � 4…10 Poles � 12…600V Coils
Standards Compliance and Certifications
� IEC 60947-5-1
� UL 508
� CSA C22.2 No. 14
Προδυχτ Σελεχτιον
4-Pole AC Coil Voltage
⊗ AC Coil Voltage Code The Cat. No. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the Cat. No. Example: Cat. No. 700- CF220⊗ becomes Cat. No. 700-CF220D for 120V, 60 Hz
4-Pole DC Coil Voltage
⊗ DC Coil Voltage Code✶
The Cat. No. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the Cat. No. Example: Cat. No. 700- CF220⊗ becomes Cat. No. 700-CF220ZJ for 24V DC
AC-12 AC-15
Connection Diagrams
Contacts
Standard Contacts Cat. No.
Gold Plated Bifurcated Contacts Cat. No.
Master Contacts Cat. No.
�th [A] �th [A]
40 °C 60 °C 24/48V 120V 240V 400V 500V 600V 690V N.O. N.C.
20 20 10 10 10 6 2.5 1 1
2 2 700-CF220⊗ 700-CFB220⊗ 700-CFM220⊗
3 1 700-CF310⊗ 700-CFB310⊗ 700-CFM310⊗
4 0 700-CF400⊗ 700-CFB400⊗ 700-CFM400⊗
0 4 700-CF040⊗ 700-CFB040⊗ —
Voltage 12 24 32 36 42 48 100
110 110 120 127 200
220 208
230 230
240 240 277 347 380
400 400
415 440 480 500 550 600
50 Hz R K V W X Y KP — D P S KG L — — F — VA T — — — N — G B — M C —
60 Hz Q J — V — X — KP — D — — KG H L — — — A T I E — — — N B — — C
50/60 Hz — KJ — — — KY KP — KD — — KG KL — — KL KF — KA — — — — KN — KB — — — —
AC-12 AC-15
Connection Diagrams
Contacts
Standard Contacts Cat. No.
Gold Plated Bifurcated Contacts Cat. No.
Master Contacts Cat. No.
�th [A] �th [A]
40 °C 60 °C 24/48V 120V 240V 400V 500V 600V 690V N.O. N.C.
20 20 10 10 10 6 2.5 1 1
2 2 700-CF220⊗ 700-CFB220⊗ 700-CFM200⊗
3 1 700-CF310⊗ 700-CFB310⊗ 700-CFM310⊗
4 0 700-CF400⊗ 700-CFB400⊗ 700-CFM400⊗
Voltage 9 12 24 36 48 60 64 72 80 110 115 125 220 230 250
Standard ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT
With diode suppressor — — DJ — — — — — — — — — — — —
✶ When ordering DJ coil with built-in surge suppression, the DJ is not polarity sensitive. Drop out time: 14…20 ms.
Table of Contents
Product Selection . . . this page Accessories . . . . . . . . . 9-151 Specification . . . . . . . . 9-156 Approximate Dimensions . . . . . . . . . 9-159
Accessories — page 10-79 Legend Plates — page 10-91
Bulletin 800T/800H
30.5 mm Push Buttons
10-66 Visit our website: www.ab.com/catalogs
Push-Pull Operators
2-Position Push-Pull and Push-Pull/Twist Release Units, Non-Illuminated Note: A jumbo or large legend plate is recommended, if space allows.
2-Position Push-Pull Cat. No. 800T-FX6D4
2-Position Push-Pull/Twist Cat. No. 800T-FXT6D4
2-Position Push-Pull/Twist Cat. No. 800H-FRXT6D4
Approximate Dimensions — page 10-97
800 T – FX 1 A1
a b c d e d Color Cap
Code Color Blank No Cap§
1 Green 2 Black 3 Orange 4 Gray 5 White 6 Red 7 Blue 9 Yellow e Contact Block(s)
Code
Operator Position
Description
Out In Blank — — No Contacts on operator
Standard D1 O X 1 N.O.
D2 X O 1 N.C.
D4 X O 1 N.C.L.B.
A O X
X O
1 N.O. - 1 N.C.
A1 O X
X O
1 N.O. - 1 N.C.L.B.
A5 X X
O O
2 N.C.L.B.
a Protection Rating
Code Description T Metal, Type 4/13 H Plastic, Type 4/4X/13 b Finger-Safe Guards
Code Description Blank No Guards
C Guards on Terminals c Head Type‡
800T Type 4/13 Description
800H Type
4/4X/13 Code Code
FX Mushroom Head (Push-Pull) —
FXJ
Jumbo Mushroom Head
(Push-Pull)
FXT Push-Pull/Twist to Release FRXT
FXJT
Jumbo Head Push-Pull w/Twist to
Release
FRXJT
‡ Devices with N.C.L.B. contacts meet EN-418 and IEC 60947-5-5 standards for emergency stop applications.
§ Not valid with head Type J or JT.
e (cont’d) Contact Block(s)
Code
Operator Position
Description
Out In Blank — — No Contacts
PenTUFF (Low Voltage) D1V O X 1 N.O.
D2V X O 1 N.C.
D4V X O 1 N.C.L.B.
AV
O X
X O
1 N.O. - 1 N.C.
Class 1, Div. 2/Zone 2 Logic Reed
D1R O X 1 N.O.
D2R X O 1 N.C.
AR
O X
X O
1 N.O. - 1 N.C.
Sealed Switch D1P O X 1 N.O.
D2P X O 1 N.C.
AP
O X
X O
1 N.O.
1 N.C.
Stackable Sealed Switch D1Y O X 1 N.O.
D2Y X O 1 N.C.
AY
O X
X O
1 N.O. - 1 N.C.
Note: X = Closed/O = Open
Contact Type
Operator Position
Button Color
Type 4/13 Type 4/4X/13
Push-Pull‡ Push-Pull/
Twist Release‡ Push-Pull/
Twist Release‡
Maintained Maintained
Cat. No. Cat. No. Cat. No.Out In
N.C.L.B. X O
Red
800T-FX6D4 800T-FXT6D4 800H-FRXT6D4
N.O. - N.C.L.B.✶ O X
X
O 800T-FX6A1 800T-FXT6A1 800H-FRXT6A1
N.C.L.B. - N.C.L.B.✶
X X
O
O 800T-FX6A5 800T-FXT6A5 800H-FRXT6A5
Note: X = Closed/O = Open ✶ Normally closed late break contact. When button is pushed from the OUT to IN position, the mechanical detent action of the operator occurs before electrical contacts change state. When the button is pulled from the IN in the OUT position, the electrical contacts change state before the mechanical detent occurs.
800T-H48B
2-Position Cylinder Lock Operator
Note: X = Closed/O = Open ¬ Target tables are reversed from those shown.
T Keys removable from maintained positions only.
800 T –H31 A a b c d e
¬ Target tables are reversed from those shown.
T Keys removable from maintained positions only.
§ Contact target tables same as those listed for standard and PenTUFF contact blocks.
§ Device supplied with 2 keys. Replacement key part no. for standard D018 key is X-181170. See Replacement Keys for Cylinder Lock 2-, 3-, and 4-Position Selector Switches (800T only) for additional replacement key numbers.
Pow er B locks
Power Stud Blocks
1320122 Adder
1321122 CH 1
1322122 CH 2
200 Thermoplastic 1/4-20 X 9/16 1 1/4-20 X 9/16 1
1323122 CH 3
1320422 Adder
1321422 CH 1
1322422 CH 2
200 Thermoplastic M6 x 15 1 M6 x 15 1
1323422 CH 3
1421123 1 1422123 2 200 Phenolic 1/4-20 Screw 1 1/4-20 Screw 1 1423123 3 1421122 1 1422122 2 200 Phenolic 1/4-20 X 9/16 1 1/4-20 X 9/16 1 1423122 3 1431563 1 1432563 2 230 Phenolic 3/8-16 X1 3/16 1 3/8-16 X1 3/16 1 1433563 3 1431561 1 1432561 2 230 Phenolic 3/8-16 X1 3/16 1 1/4-20 X1 3/16 1 1433561 3 1441122 1 1442122 2 260 Phenolic 3/8-16 X1 7/16 1 1/4-20 X 9/16 2 1443122 3 1441553 1 1442553 2 230 Phenolic 3/8-16 X1 7/16 1 3/8-16 X1 7/16 1 1443553 3 1451573 1 1452573 2 360 Phenolic 3/8 - 16 X1 7/16 1 3/8 - 16 X1 7/16 2 1453573 3 1451583 1 1452583 2 360 Phenolic 3/8-16 X1 7/16 1 1/4 - 20 X1 7/16 2 1453583 3
1331563 CH 1
1332563 CH 2 310 Thermoplastic 3/8-16 X 1 3/16 1 3/8-16 X 1 3/16 1
1333563 CH 3
1331564 CH 1
1332564 CH 2 310 Thermoplastic M10 x 30 1 M10 x 30 1
1333564 CH 3
1451606 1 1452606 2 410 Phenolic 1/2-13 x 1 7/16 1 1/2-13 x 1 7/16 1 1453606 3 1441614 1 1442614 2 840 Phenolic 3/8-16 X 1 1 3/8-16 X 1 1 1443614 3
Specifications:
• Connector, High Conductive Copper, Tin Plated
• Stud, Brass, Tin Plated, Metric (M) Studs, Steel
• Suitable for Compression Wire Lugs
• UL Recognized File No. XCFR2.E62806
• CSA Certified File No. LR19766
• For detailed SCCR information, please visit www.marathonsp.com
600 Volts
CH = Available with hinge cover attached (See page 54 for available covers) See pages 56-59 for dimensional information
Catalog # Hinge
Poles Amps Material Connector Line Wire Openings Connector Load Wire Openings
Cover Configuration Range Per Pole Configuration Range Per Pole
Po w er B lo ck s
Power Terminal Block Dimensions
143 Series
142 Series
1 POLE 2 POLE 3 POLE
1 POLE 2 POLE 3 POLE
144 Series
1 POLE 2 POLE 3 POLE
.31 [7.9]
4.75 [120.6]
4.13 [104.8]
1.88 [47.8]
1.88 [47.8]
1.50 [38.2]
.015 [.38]
1.14 [29.0]
1.88 [47.8]
1.12 [28.3]
6.05 [153.6]
4.17 [105.9]
2.29 [58.1]
.52 [13.1]
2.90 [73.7]
.20/[5.2] DIA. THRU
.41/[10.3] C'BORE
x .18/[4.6] DP.