This document is a Section 07920 technical specification for Joint Sealants for the FY 06 Student Dorm project at Keesler Air Force Base in Mississippi. The specification details requirements for sealant materials, application methods, and surface preparation, with specific guidelines for different surfaces and joint types. Key technical requirements include using ASTM-standard sealants compatible with various materials like metal, glass, concrete, masonry, and wood, with precise instructions on joint width-to-depth ratios, primer application, and installation techniques.
The specification mandates sealant selection based on specific locations and surface types, with color-matching requirements for different applications such as interior joints between walls, partitions, tiles, and exterior surfaces like window frames and masonry walls. Environmental conditions are strictly defined, with sealant application permitted only when ambient temperatures are between 40 and 90 degrees Fahrenheit. Contractors must submit detailed product data, including manufacturer's descriptive information, Material Safety Data Sheets, and compliance certificates, and follow meticulous surface preparation and cleaning protocols to ensure proper sealant adhesion and performance.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FY 06 STUDENT DORM, KEESLER AFB, MS SOW8DORM
SECTION 07920
JOINT SEALANTS
10/03
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM C 834 (2000e1) Latex Sealants
ASTM C 920 (2002) Elastomeric Joint Sealants
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.
The following shall be submitted in accordance with Section 01330 SUBMITTAL
PROCEDURES:
SD-03 Product Data
Sealants G; A/E
Primers G; A/E
Bond breakers G; A/E
Backstops G; A/E
Manufacturer's descriptive data including storage requirements, shelf life, curing time, instructions for mixing and application, primer data (if required), recommended cleaning solvants and colors. A copy of the Material Safety Data Sheet shall be provided for each solvent, primer or sealant material.
SD-07 Certificates
Sealant
Certificates of compliance stating that the materials conform to the specified requirements.
1.3 ENVIRONMENTAL CONDITIONS
The ambient temperature shall be within the limits of 40 and 90 degrees F when sealant is applied.
SECTION 07920 Page 1
FA301025R0027
Attachment 9
1.4 DELIVERY AND STORAGE
Deliver materials to the job site in unopened manufacturers' external shipping containers, with brand names, date of manufacture, color, and material designation clearly marked thereon. Elastomeric sealant containers shall be labeled to identify type, class, grade, and use.
Carefully handle and store materials to prevent inclusion of foreign materials or subjection to sustained temperatures exceeding 90 degrees F or less than 0 degrees F.
PART 2 PRODUCTS
2.1 SEALANTS
Provide sealant that has been tested and found suitable for the substrates to which it will be applied.
2.1.1 Grout Sealant for Floor Tile
All grout joints of ceramic floor tile, unglazed quarry tile and porcelain paver tile shall be sealed with an elastomeric joint sealer to match the color of the grout. Sealer shall be Aqua Mix sealers, choice 15 gold by Aqua Mix Inc., 1-800-366-8677, or equivalent.
2.1.2 Interior Sealant
ASTM C 834, Type S or M, Grade NS, Class 12.5, Use NT. Locations and colors of sealant shall be as follows:
LOCATION COLOR
a. Small voids between walls or partitions and Match existing adjacent lockers, casework, shelving, surface color door frames, built-in or surface-mounted equipment and fixtures, and similar items.
b. Perimeter of frames at doors, windows, Match existing and access panels which adjoin exposed surface color interior concrete and masonry surfaces.
c. Joints of interior masonry walls and Match mortar partitions which adjoin columns, pilasters, concrete walls, and exterior walls unless otherwise detailed.
d. Joints between edge members for acoustical white tile and adjoining vertical surfaces.
e. Interior locations, not otherwise indicated Match adjacent or specified, where small voids exist between surface color materials specified to be painted.
f. Joints between bathtubs and ceramic tile; Match grout joints between shower receptors and ceramic tile; joints formed where nonplaner tile surfaces meet.
g. Joints formed between tile floors and tile Match grout base cove; joints between tile and dissimilar
SECTION 07920 Page 2
LOCATION COLOR
materials; joints occuring where substrates change.
h. Behind escutcheon plates at valve pipe Match grout penetrations and showerheads in showers.
2.1.3 Exterior Sealant
For joints in vertical surfaces, provide ASTM C 920, Type S or M, Grade NS, Class 25, Use NT. For joints in horizontal surfaces, provide ASTM C 920, Type S or M, Grade P, Class 25, Use T. Location(s) and color(s) of sealant shall be as follows:
LOCATION COLOR
a. Joints and recesses formed where frames Match adjacent and subsills of windows, doors, louvers, surface color and vents adjoin masonry, concrete, or of frame metal frames. Use sealant at both exterior and interior surfaces of exterior wall penetrations.
b. Joints between new and existing exterior Match existing masonry walls. surface color
c. Masonry joints where shelf angles occur. Match mortar
d. Expansion and control joints. Match mortar
e. Interior face of expansion joints in Match mortar exterior concrete or masonry walls where metal expansion joint covers are not required.
f. Voids where items pass through exterior Match mortar walls.
g. Metal reglets, where flashing is inserted Match mortar into masonry joints, and where flashing is penetrated by coping dowels.
h. Metal-to-metal joints where sealant is Match adjacent indicated or specified. color
i. Joints between ends of gravel stops, fascias, Match adjacent copings, and adjacent walls. color
2.1.4 Floor Joint Sealant
ASTM C 920, Type S or M, Grade P, Class 25, Use T. Location(s) and color(s) of sealant shall be as follows:
LOCATION COLOR
a. Seats of metal thresholds for
SECTION 07920 Page 3
LOCATION COLOR
exterior doors. Gray
b. Control and expansion joints in floors, Match adjacent slabs, ceramic tile, and walkways. surface color
2.2 PRIMERS
Provide a nonstaining, quick-drying type and consistency recommended by the sealant manufacturer for the particular application.
2.3 BOND BREAKERS
Provide the type and consistency recommended by the sealant manufacturer to prevent adhesion of the sealant to backing or to bottom of the joint.
2.4 BACKSTOPS
Provide glass fiber roving or neoprene, butyl, polyurethane, or polyethylene foams free from oil or other staining elements as recommended by sealant manufacturer. Backing shall be 25 to 33 percent oversize for closed cell and 40 to 50 percent oversize for open cell material, unless otherwise indicated. Backstop material shall be compatible with sealant.
Do not use oakum and other types of absorptive materials as backstops.
2.5 CLEANING SOLVENTS
Provide type(s) recommended by the sealant manufacturer except for aluminum and bronze surfaces that will be in contact with sealant.
PART 3 EXECUTION
3.1 SURFACE PREPARATION
Surfaces shall be clean, dry to the touch, and free from dirt frost, moisture, grease, oil, wax, lacquer, paint, or other foreign matter that would tend to destroy or impair adhesion. Oil and grease shall be removed with solvent and surfaces shall be wiped dry with clean cloths. When resealing an existing joint, remove existing calk or sealant prior to applying new sealant. For surface types not listed below, the sealant manufacturer shall be contacted for specific recommendations.
3.1.1 Steel Surfaces
Remove loose mill scale by sandblasting or, if sandblasting is impractical or would damage finish work, scraping and wire brushing. Remove protective coatings by sandblasting or using a residue-free solvent.
3.1.2 Aluminum or Bronze Surfaces
Remove temporary protective coatings from surfaces that will be in contact with sealant. When masking tape is used as a protective coating, remove tape and any residual adhesive just prior to sealant application. For removing protective coatings and final cleaning, use nonstaining solvents recommended by the manufacturer of the item(s) containing aluminum or bronze surfaces.
SECTION 07920 Page 4
3.1.3 Concrete and Masonry Surfaces
Where surfaces have been treated with curing compounds, oil, or other such materials, the materials shall be removed by sandblasting or wire brushing.
Laitance, efflorescence and loose mortar shall be removed from the joint cavity.
3.1.4 Wood Surfaces
Wood surfaces to be in contact with sealants shall be free of splinters and sawdust or other loose particles.
3.2 SEALANT PREPARATION
Do not add liquids, solvents, or powders to the sealant. Mix multicomponent elastomeric sealants in accordance with manufacturer's instructions.
3.3 APPLICATION
3.3.1 Joint Width-To-Depth Ratios
a. Acceptable Ratios:
JOINT WIDTH JOINT DEPTH
Minimum Maximum
For metal, glass, or other nonporous surfaces:
1/4 inch (minimum) 1/4 inch 1/4 inch over 1/4 inch 1/2 of Equal to width width
For wood, concrete, masonry:
1/4 inch (minimum) 1/4 inch 1/4 inch Over 1/4 inch to 1/2 inch 1/4 inch Equal to width
Over 1/2 inch to 2 inches 1/2 inch 5/8 inch Over 2 inches (As recommended by sealant manufacturer)
b. Unacceptable Ratios: Where joints of acceptable width-to-depth ratios have not been provided, clean out joints to acceptable depths and grind or cut to acceptable widths without damage to the adjoining work. Grinding shall not be required on metal surfaces.
3.3.2 Masking Tape
Masking tape may be placed on the finish surface on one or both sides of a joint cavity to protect adjacent finish surfaces from primer or sealant smears. Masking tape shall be removed within 10 minutes after joint has been filled and tooled.
3.3.3 Backstops
Install backstops dry and free of tears or holes. Tightly pack the back or
SECTION 07920 Page 5 bottom of joint cavities with backstop material to provide a joint of the depth specified. Install backstops in the following locations:
a. Where indicated.
b. Where backstop is not indicated but joint cavities exceed the acceptable maximum depths specified in paragraph entitled, "Joint Width-to-Depth Ratios."
3.3.4 Primer
Immediately prior to application of the sealant, clean out loose particles from joints. Where recommended by sealant manufacturer, apply primer to joints in concrete masonry units, wood, and other porous surfaces in accordance with sealant manufacturer's instructions. Do not apply primer to exposed finish surfaces.
3.3.5 Bond Breaker
Provide bond breakers to the back or bottom of joint cavities, as recommended by the sealant manufacturer for each type of joint and sealant used, to prevent sealant from adhering to these surfaces. Carefully apply the bond breaker to avoid contamination of adjoining surfaces or breaking bond with surfaces other than those covered by the bond breaker.
3.3.6 Sealants
Provide a sealant compatible with the material(s) to which it is applied.
Do not use a sealant that has exceeded shelf life or has jelled and can not be discharged in a continuous flow from the gun. Apply the sealant in accordance with the manufacturer's instructions with a gun having a nozzle that fits the joint width. Force sealant into joints to fill the joints solidly without air pockets. Tool sealant after application to ensure adhesion. Sealant shall be uniformly smooth and free of wrinkles. Upon completion of sealant application, roughen partially filled or unfilled joints, apply sealant, and tool smooth as specified. Sealer shall be applied over the sealant when and as specified by the sealant manufacturer.
3.4 PROTECTION AND CLEANING
3.4.1 Protection
Protect areas adjacent to joints from sealant smears. Masking tape may be used for this purpose if removed 5 to 10 minutes after the joint is filled.
3.4.2 Final Cleaning
Upon completion of sealant application, remove remaining smears and stains and leave the work in a clean and neat condition.
a. Masonry and Other Porous Surfaces: Immediately scrape off fresh sealant that has been smeared on masonry and rub clean with a solvent as recommended by the sealant manufacturer. Allow excess sealant to cure for 24 hour then remove by wire brushing or sanding.
b. Metal and Other Non-Porous Surfaces: Remove excess sealant with a solvent-moistened cloth.
SECTION 07920 Page 6
-- End of Section --
SECTION 07920 Page 7
| 07920 - JOINT SEALANTS |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 SUBMITTALS |
| 1.3 ENVIRONMENTAL CONDITIONS |
| 1.4 DELIVERY AND STORAGE |
| PART 2 PRODUCTS |
| 2.1 SEALANTS |
| 2.1.1 Grout Sealant for Floor Tile |
| 2.1.2 Interior Sealant |
| 2.1.3 Exterior Sealant |
| 2.1.4 Floor Joint Sealant |
| 2.2 PRIMERS |
| 2.3 BOND BREAKERS |
| 2.4 BACKSTOPS |
| 2.5 CLEANING SOLVENTS |
| PART 3 EXECUTION |
| 3.1 SURFACE PREPARATION |
| 3.1.1 Steel Surfaces |
| 3.1.2 Aluminum or Bronze Surfaces |
| 3.1.3 Concrete and Masonry Surfaces |
| 3.1.4 Wood Surfaces |
| 3.2 SEALANT PREPARATION |
| 3.3 APPLICATION |
| 3.3.1 Joint Width-To-Depth Ratios |
| 3.3.2 Masking Tape |
| 3.3.3 Backstops |
| 3.3.4 Primer |
| 3.3.5 Bond Breaker |
| 3.3.6 Sealants |
| 3.4 PROTECTION AND CLEANING |
| 3.4.1 Protection |
| 3.4.2 Final Cleaning |