Attachment 8 - MAHG231017 - Original Window Spec Avery Manor (for reference).pdf

PDF 43 KB Posted

Attached to
Repair NPS Dorms Gutters and Windows
Solicitation number
FA301025R0027
Issued by

About this file

This document is a Technical Specification (Section 08520N) for Aluminum Windows for the FY 06 Student Dorm project at Keesler Air Force Base in Mississippi. The specification details requirements for aluminum windows, including mandatory compliance with American Architectural Manufacturers Association (AAMA) standards, specific performance criteria, and installation guidelines. Key technical requirements include windows with a thermal break to achieve a minimum Condensation Resistance Factor (CRF) of 56, forced entry resistance, and single hung and fixed window types designated as SH-HC50 and F-HC50.

The specification mandates specific manufacturing and installation standards, such as providing windows with insulating glass, anodized dark bronze finish, and screens for each operable sash. Installation requirements include precise positioning, proper sealing, and ensuring weathertight installation. The windows must meet antiterrorism standards (UFC 4-010-01), have AAMA certification, and include detailed submission requirements for shop drawings, product data, samples, and test reports. Contractors must provide structural calculations, comply with specified fabrication methods, and ensure windows are properly anchored and finished to meet the project's technical and aesthetic specifications.

View the file

Other files

File Type Posted
Attachment 11 - MAHG231017 - Addendum 2.pdf PDF
Solicitation Amendment FA301025R00270003 SF 30.pdf PDF
Solicitation Amendment - FA301025R00270003.pdf PDF
Solicitation Amendment - FA301025R00270002.pdf PDF
MAHG23-1017 - Additional QandA - 4Sept2025.pdf PDF
Attachment 10 - MAHG231017 - Addendum 1.pdf PDF
Solicitation Amendment FA301025R00270002 SF 30.pdf PDF
Solicitation Amendment - FA301025R00270001.pdf PDF
Attachment 9 - MAHG231017 - Original Joint Sealant Spec Avery Manor (for reference).pdf PDF
Solicitation Amendment FA301025R00270001 SF 30.pdf PDF
MAHG231017 - Questions and Answers - 26Aug2025.pdf PDF
Pre-Bid Site Visit 20Aug.pdf PDF
Attachment 3 -MAHG231017 Repair NPS Dorms Gutters and Windows Drawings.pdf PDF
Attachment 7 -Submittal Procedures.pdf PDF
Solicitation - FA301025R0027.pdf PDF
Attachment 5 -MAHG231017 Repair NPS Dorms Gutters and Windows MSS.xlsx XLSX spreadsheet
Attachment 6 -Wage Determination 11April2025.pdf PDF
Attachment 1 -MAHG231017 Repair NPS Dorms Gutters and Windows SOW.pdf PDF
Attachment 2 -MAHG231017 Repair NPS Dorms Gutters and Windows Specs.pdf PDF
Attachment 4 -MAHG231017 Repair NPS Dorms Gutters and Windows As-Builts.pdf PDF
Past Performance Reference List.pdf PDF
Past Performance Questionnaire.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FY 06 STUDENT DORM, KEESLER AFB, MS SOW8DORM

SECTION 08520N

ALUMINUM WINDOWS

02/04

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ALUMINUM ASSOCIATION (AA)

AA 45 (2003) Designation System for Aluminum Finishes

AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)

AAMA 101 (2002) Voluntary Specifications for Aluminum, Vinyl (PVC) and Wood Windows and Glass Doors

AAMA 1302 (1976) Voluntary Specifications for Forced-Entry Resistant Aluminum Prime Windows

AAMA 1503 (1998) Voluntary Test Method for Thermal Transmittance and Condensation Resistance of Windows, Doors and Glazed Wall Sections

AAMA 611 (1998) Voluntary Specification for Anodized Architectural Aluminum; includes 604.2, 606.1, 607.1 and 608.1 (which are no longer available as separate documents)

AAMA 902 (1999) Voluntary Specification for Sash Balances

1.2 CERTIFICATION

Each prime window unit shall bear the AAMA Label warranting that the product complies with AAMA 101. Certified test reports attesting that the prime window units meet the requirements of AAMA 101, including test size, will be acceptable in lieu of product labeling.

1.3 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for Contractor Quality Control approval. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.

The following shall be submitted in accordance with Section 01330 SUBMITTAL

PROCEDURES:

SD-02 Shop Drawings

SECTION 08520N Page 1

FA301025R0027

Attachment 8

Windows; G A/E

SD-03 Product Data

Windows; G A/E

Hardware; G A/E

Fasteners; G A/E

Screens; G A/E

Weatherstripping; G A/E

Accessories; G A/E

SD-04 Samples

Finish Sample G O/C

Window Sample G O/C

SD-05 Design Data

Structural calculations for deflection; G A/E

SD-06 Test Reports

Minimum condensation resistance factor

Resistance to forced entry

SD-10 Operation and Maintenance Data

Windows, Data Package 1; G O/C

Submit in accordance with Section 01781 OPERATION AND

MAINTENANCE DATA.

1.4 QUALITY ASSURANCE

1.4.1 Force Protection Standards

All windows shall meet the minimum standard of UFC 4-010-01, DOD Minimum Antiterrorism Standards for Buildings, latest edition.

1.4.2 Shop Drawing Requirements

Drawings shall indicate elevations of windows, full-size sections, thickness and gages of metal, fastenings, proposed method of anchoring, size and spacing of anchors, details of construction, method of glazing, details of operating hardware, mullion details, method and materials for weatherstripping, method of attaching screens, material and method of attaching subframes, stools, casings, sills, trim, installation details, and other related items.

SECTION 08520N Page 2

1.4.3 Sample Requirements

1.4.3.1 Finish Sample Requirements

Submit color chart of standard factory color coatings when factory-finish color coating is to be provided.

1.4.3.2 Window Sample Requirements

Submit one full-size window of each type proposed for use, complete with AAMA Label, glazing, hardware, anchors, and other accessories. Where screens or weatherstripping is required, fit sample windows with such items that are to be used. After approval, install each sample in work, clearly identified, and record its location.

1.4.4 Design Data Requirements

Submit calculations to substantiate compliance with deflection requirements. Calculations shall be provided by a Professional Engineer.

1.4.5 Test Report Requirements

Submit test reports for each type of window attesting that identical windows have been tested and meet the requirements specified herein for conformance to AAMA 101 including test size, minimum condensation resistance factor (CRF) , and resistance to forced entry.

1.5 DELIVERY AND STORAGE

Deliver windows to project site in an undamaged condition. Use care in handling and hoisting windows during transportation and at the jobsite.

Store windows and components out of contact with the ground, under a weathertight covering, so as to prevent bending, warping, or otherwise damaging the windows. Damaged windows shall be repaired to an "as new" condition as approved. If windows can not be repaired, provide a new unit.

1.6 PROTECTION

Protect finished surfaces during shipping and handling using the manufacturer's standard method, except that no coatings or lacquers shall be applied to surfaces to which calking and glazing compounds must adhere.

PART 2 PRODUCTS

2.1 WINDOWS

Prime windows shall comply with AAMA 101 and the requirements specified herein. In addition to compliance with AAMA 101, window framing members for each individual lite of glass shall not deflect to the extent that deflection perpendicular to the glass lite exceeds L/175 of the glass edge length when subjected to uniform loads at specified design pressures.

Structural calculations for deflection shall be provided to substantiate compliance with deflection requirements. Provide windows of types, performance classes, performance grades, combinations, and sizes indicated or specified. Design windows to accommodate hardware, glass, weatherstripping, screens, and accessories to be furnished. Each window shall be a complete factory assembled unit with or without glass installed.

Dimensions shown are minimum. Provide windows with insulating glass and

SECTION 08520N Page 3 thermal break necessary to achieve a minimum Condensation Resistance Factor (CRF) of 56 when tested in accordance with AAMA 1503.

2.1.1 Single Hung Windows (SH)

Type SH-HC50-Sash balances shall be tested and rated to conform with AAMA 902.

2.1.2 Fixed Windows (F)

Type F-HC50.

2.1.3 Forced Entry Resistant Windows

In addition to meeting the requirements of AAMA 101, windows designated for resistance to forced entry shall conform to the requirements of AAMA 1302.

2.1.4 Glass and Glazing

Materials are specified in Section 08800 GLAZING.

2.1.5 Calking and Sealing

Are specified in Section 07920 JOINT SEALANTS.

2.1.6 Weatherstripping

AAMA 101.

2.2 FABRICATION

Fabrication of window units shall comply with AAMA 101.

2.2 Provisions for Glazing

Design windows and rabbets suitable for glass thickness shown or specified.

Exterior glazing shall have a minimum frame bite of 3/8 inch for structurally glazed window systems and 1 inch for window systems that are not structurally glazed. Design sash for inside double glazing and for securing glass with glazing channels, or glazing compound.

2.3 Weatherstripping

Provide for ventilating sections of all windows to ensure a weather-tight seal meeting the infiltration requirements specified in AAMA 101. Provide easily replaceable factory-applied weatherstripping. Use molded vinyl, molded or molded-expanded neoprene or molded or expanded Ethylene Propylene Diene Terpolymer (EPDM) weatherstripping for compression contact surfaces.

Use treated woven pile or wool, or polypropylene or nylon pile bonded to nylon fabric and metal or plastic backing strip weatherstripping for sliding surfaces. Do no use neoprene or polyvinylchloride weatherstripping where they will be exposed to direct sunlight.

2.4 Fasteners

Use fasteners as standard with the window manufacturer for windows, trim, and accessories. Self-tapping sheet-metal screws are not acceptable for material more than 1/16 inch thick.

SECTION 08520N Page 4

2.5 Drips and Weep Holes

Provide continuous drips over heads of top ventilators. Where fixed windows adjoin ventilators, drips shall be continuous across tops of fixed windows. Provide drips and weep holes as required to return water to the outside.

2.6 Combination Windows

Windows used in combination shall be the same class and grade and shall be factory assembled. Where factory assembly of individual windows into larger units is limited by transportation considerations, prefabricate, match mark, transport, and field assemble.

2.7 Mullions and Transom Bars

Provide mullions between multiple window units which meet the design wind speed of 140 mph, or pressure of 45 psf, whichever is greater. Provide mullions with a structural thermal break. Secure mullions and transom bars to adjoining construction and window units in such a manner as to permit expansion and contraction and to form a weathertight joint. Provide mullion covers on the interior and exterior to completely close exposed joints and recesses between window units and to present a neat appearance.

2.8 Accessories

Provide windows complete with necessary hardware, fastenings, clips, fins, anchors, glazing beads, and other appurtenances necessary for complete installation and proper operation. Furnish extruded aluminum subframe receptors and subsill with each window unit.

2.8.1 Hardware

AAMA 101. The item, type, and functional characteristics shall be the manufacturer's standard for the particular window type. Provide hardware of suitable design and of sufficient strength to perform the function for which it is used. Equip all operating ventilators with a lock or latching device which can be secured from the inside.

2.8.2 Fasteners

Provide concealed anchors of the type recommended by the window manufacturer for the specific type of construction. Anchors and fasteners shall be compatible with the window and the adjoining construction. Provide a minimum of three anchors for each jamb located approximately 6 inches from each end and at midpoint. Frame connections to surrounding walls shall be designed to resist a combined ultimate loading of a tension force of 200 lbs. per inch and a shear force of 75 lbs. per inch.

2.9 Finishes

Exposed aluminum surfaces shall be factory finished with an anodic coating.

Color shall be dark bronze. All windows shall have the same finish.

2.9.1 Anodic Coating

Clean exposed aluminum surfaces and provide an anodized finish conforming to AA 45 and AAMA 611. Finish shall be:

SECTION 08520N Page 5

a. Architectural Class I ( 0.7 mil or thicker), designation AA-M10-C22-A42, integral color anodized.

2.10 Screens

AAMA 101. Provide one insect screen for each operable exterior sash or ventilator. Design screens to be rewirable, easily removable from inside the building, and to permit easy access to operating hardware.

a. Architectural Class I ( 0.7mil or thicker), designation AA-M10-C22-A42, integral color anodized.

PART 3 EXECUTION

3.1 INSTALLATION

3.1.1 Method of Installation

Install in accordance with the window manufacturer's printed instructions and details. Build in windows as the work progresses or install without forcing into prepared window openings. Set windows at proper elevation, location, and reveal; plumb, square, level, and in alignment; and brace, strut, and stay properly to prevent distortion and misalignment. Protect ventilators and operating parts against accumulation of dirt and building materials by keeping ventilators tightly closed and locked to frame. Bed screws or bolts in sill members, joints at mullions, contacts of windows with sills, built-in fins, and subframes in mastic sealant of a type recommended by the window manufacturer. Install windows in a manner that will prevent entrance of water and wind. Fasten insect screens securely in place.

3.1.2 Dissimilar Materials

Where aluminum surfaces are in contact with, or fastened to masonry, concrete, wood, or dissimilar metals, except stainless steel or zinc, the aluminum surface shall be protected from dissimilar materials as recommended in the Appendix to AAMA 101. Surfaces in contact with sealants after installation shall not be coated with any type of protective material.

3.1.3 Anchors and Fastenings

Make provision for securing units to each other, to masonry, and to other adjoining construction. Windows installed in masonry walls shall have head and jamb members designed to recess into masonry wall not less than 7/16 inch.

3.1.4 Adjustments After Installation

After installation of windows and completion of glazing and field painting, adjust all ventilators and hardware to operate smoothly and to provide weathertight sealing when ventilators are closed and locked. Lubricate hardware and operating parts as necessary. Adjust single hung windows to operate with maximum applied force of 25 pounds in either direction, not including breakaway friction force.

3.2 CLEANING

Clean interior and exterior surfaces of window units of mortar, plaster, paint spattering spots, and other foreign matter to present a neat

SECTION 08520N Page 6 appearance, to prevent fouling of weathering surfaces and weather-stripping, and to prevent interference with the operation of hardware. Replace all stained, discolored, or abraded windows that cannot be restored to their original condition with new windows.

-- End of Section --

SECTION 08520N Page 7

08520 - ALUMINUM WINDOWS
PART 1 GENERAL
1.1 REFERENCES
1.2 CERTIFICATION
1.3 SUBMITTALS
1.4 QUALITY ASSURANCE
1.4.1 Force Protection Standards
1.4.2 Shop Drawing Requirements
1.4.3 Sample Requirements
1.4.3.1 Finish Sample Requirements
1.4.3.2 Window Sample Requirements
1.4.4 Design Data Requirements
1.4.5 Test Report Requirements
1.5 DELIVERY AND STORAGE
1.6 PROTECTION
PART 2 PRODUCTS
2.1 WINDOWS
2.1.1 Single Hung Windows SH
2.1.2 Fixed Windows F
2.1.3 Forced Entry Resistant Windows
2.1.4 Glass and Glazing
2.1.5 Calking and Sealing
2.1.6 Weatherstripping
2.2 Provisions for Glazing
2.3 Weatherstripping
2.4 Fasteners
2.5 Drips and Weep Holes
2.6 Combination Windows
2.7 Mullions and Transom Bars
2.8 Accessories
2.8.1 Hardware
2.8.2 Fasteners
2.9 Finishes
2.9.1 Anodic Coating

2.10 Screens

PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Method of Installation
3.1.2 Dissimilar Materials
3.1.3 Anchors and Fastenings
3.1.4 Adjustments After Installation

3.2 CLEANING