This document is a technical specification for a repair project at Keesler Air Force Base in Biloxi, Mississippi, consisting of three detailed sections covering aluminum gutters and downspouts, joint sealants, and aluminum windows. The project (FA301025R0027) involves replacing damaged window assemblies, installing new gutters, and applying joint sealants across NPS dormitory buildings.

The specifications provide comprehensive technical requirements for each component. For gutters, the document specifies aluminum sheet materials (ASTM B 209, Alloy 3105-H24) with 0.040-inch thickness, minimum 8-inch gutters, and a 20-year manufacturer's warranty. Window requirements include specific performance tests for air infiltration, water resistance, and thermal transmittance, with windows constructed from 6063-T5 alloy aluminum, featuring a polyurethane thermal barrier and insulating glass. The joint sealants are primarily non-elastomeric, acrylic latex-based, intended for interior sealing around doors and gypsum board. The project emphasizes matching existing windows and maintaining high-quality installation standards with skilled tradespeople.

View the file

Other files

File Type Posted
Solicitation Amendment FA301025R00270003 SF 30.pdf PDF
Attachment 11 - MAHG231017 - Addendum 2.pdf PDF
Solicitation Amendment - FA301025R00270003.pdf PDF
Solicitation Amendment FA301025R00270002 SF 30.pdf PDF
Solicitation Amendment - FA301025R00270002.pdf PDF
MAHG23-1017 - Additional QandA - 4Sept2025.pdf PDF
Attachment 10 - MAHG231017 - Addendum 1.pdf PDF
Attachment 9 - MAHG231017 - Original Joint Sealant Spec Avery Manor (for reference).pdf PDF
Solicitation Amendment - FA301025R00270001.pdf PDF
Solicitation Amendment FA301025R00270001 SF 30.pdf PDF
MAHG231017 - Questions and Answers - 26Aug2025.pdf PDF
Attachment 8 - MAHG231017 - Original Window Spec Avery Manor (for reference).pdf PDF
Pre-Bid Site Visit 20Aug.pdf PDF
Attachment 5 -MAHG231017 Repair NPS Dorms Gutters and Windows MSS.xlsx XLSX spreadsheet
Past Performance Questionnaire.pdf PDF
Attachment 1 -MAHG231017 Repair NPS Dorms Gutters and Windows SOW.pdf PDF
Attachment 3 -MAHG231017 Repair NPS Dorms Gutters and Windows Drawings.pdf PDF
Attachment 4 -MAHG231017 Repair NPS Dorms Gutters and Windows As-Builts.pdf PDF
Past Performance Reference List.pdf PDF
Attachment 7 -Submittal Procedures.pdf PDF
Attachment 6 -Wage Determination 11April2025.pdf PDF
Solicitation - FA301025R0027.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

20 April 2025 Attachment 2

FA301025R0027

PROJECT:

REPAIR NPS DORMS GUTTERS AND WINDOWS

PROJECT NUMBER:

MAHG231017

KEESLER AIR FORCE BASE

BILOXI, MISSISSIPPI

Keesler AFB 508 L Street

Keesler AFB, MS 39534

INDEX

SECTION DESCRIPTION

07 71 23 Aluminum Gutter and Downspouts

07 92 00 Joint Sealants

08 51 13 Aluminum Windows

SECTION 07 71 23

ALUMINUM GUTTER AND DOWNSPOUTS

1.0 GENERAL

1.1 SECTION INCLUDES:

1.1.1 Gutters and Downspouts

1.2 RELATED SECTIONS

1.2.1 Section 07 92 00: Joint Sealants

1.3 REFERENCES

1.3.1 ASTM B 209 - Standard Specification for Aluminum and Aluminum- Alloy Sheet and Plate.

1.3.2 SMACNA - Architectural Sheet Metal Manual.

1.4 DESIGN/PERFORMANCE REQUIREMENTS

1.4.1 Conform to applicable code for size and method of rainwater discharge.

Manufacturer shall size gutters and downspouts according to current rain data for Keesler AFB, Biloxi, MS

1.4.2 American Architectural Manufacturers Association (AAMA) Specification

1405.1 "Specification for Aluminum Rain carrying Systems."

1.5 SUBMITTALS

1.5.1 Submit under provisions of the Statement of Work.

1.5.2 Product Data: Manufacturer's catalog data, detail sheets, and specifications.

1.5.3 Calculations for sizing the gutters and downspouts based on rain data for

Keesler AFB, Biloxi, MS.

1.5.4 Shop Drawings: Prepared specifically for this project; showing dimensions of metal gutters and accessories, fastening details and connections and interface with other products.

1.5.5 Selection Samples: For each finish product specified, two complete sets of color chips representing manufacturer's full range of available colors and patterns.

1.5.6 Verification Samples: For each finish product specified, two samples, minimum size 6 inches (150 mm) square, representing actual product, color, and patterns.

1.5.7 Manufacturer's Certificates: Certify products meet or exceed specified requirements.

1.5.8 Manufacturer’s warranties.

1.6 QUALITY ASSURANCE

1.6.1 Manufacturer Qualifications:

1.6.2 Installer Qualifications: Certified and approved installer of the sheet metal roofing manufacturer Englert, Inc.

1.6.3 Perform Work in accordance with SMACNA Manual.

1.7 DELIVERY, STORAGE, AND HANDLING

1.7.1 Store products in manufacturer's unopened packaging until ready for installation.

1.7.2 Store products to prevent twisting, bending, and abrasion, and to provide ventilation. Slope stored materials to drain.

1.7.3 During storage, prevent contact with materials capable of causing discoloration, staining, or other damage.

1.8 PROJECT CONDITIONS

1.8.1 Coordinate installation with installation of adjacent roofing, siding and related materials.

1.9 WARRANTY

1.9.1 Provide the Manufacturer's Limited 20-Year, pro-rated and non-transferable Warranty covering labor materials.

1.10 COORDINATION

1.10.1 Coordinate Work with other operations and installation of floor finish materials to avoid damage to installed underlayment and membrane materials.

2.0 PRODUCTS

2.1 MANUFACTURERS

2.1.1 Acceptable Manufacturer: Englert, Inc., which is located at: 1200 Amboy Ave.; Perth Amboy, NJ 08861; Toll Free Tel: 800- 364-5378; Tel: 732- 826-8614; Fax: 732-826-8865; Email: request info; Web:

www.englertinc.com.

2.1.2 Or approved equal

2.2 COMPONENTS

2.2.1 Gutters: Aluminum sheet, ASTM B 209, Alloy 3105-H24. Minimum tensile strength 26,000 psi, minimum yield strength 25,000 psi or equivalent. Continuous and seamless sheet aluminum, roll formed.

2.2.1.1 Thickness: 0.040 inch

2.2.1.2 Size: Minimum 8”. Gutters shall be sized by manufacturer based on rainfall data for Keesler AFB, Biloxi, MS.

2.2.2 Downspouts: Aluminum sheet, ASTM B 209, Alloy 3105-H24. Minimum tensile strength 26,000 psi, minimum yield strength 25,000 psi or equivalent.

2.2.2.1 Thickness: 0.040 inch

2.2.2.2 Size: Minimum 6”. Downspouts shall be sized by manufacturer based on rainfall data for Keesler AFB, Biloxi, MS.

2.2.3 Endcaps: Aluminum sheet, ASTM B 209, Alloy 3105-H24

2.2.3.1 Thickness: 0.040 inch.

2.2.4 Inside and Outside Mitres: Aluminum sheet, ASTM B 209, Alloy 3105-

H24

2.2.4.1 Thickness 0.040 inch.

2.2.5 Gutter Hangers and Anchors: Aluminum sheet, ASTM B 209, Alloy 3105- H24

2.2.5.1 Thickness 0.063 inch (1.60 mm). Provide types required to suit project requirements.

2.2.6 Downspout Anchors: Aluminum. Provide types required to suit project requirements.

2.2.7 Elbows: Aluminum sheet, ASTM B 209, Alloy 3105-H24. Minimum tensile strength 26,000 psi, minimum yield strength 25,000 psi or equivalent.

2.2.7.1 Thickness: 0.050 inch.

2.2.7.2 Size: To match downspouts.

2.2.8 Aluminum Finish - (Color by Contracting Officer) Two-coat system applied in a continuous baked-on process in a single operation, comprising of an acid-based primer and baked-on high performance linear polyester topcoat on exposed surfaces. Concealed surfaces finished with a polyester gold backer or wash coat.

2.2.9 Sealant: Provide as specified in Section 07 90 00.

2.2.10 Fasteners: Same material and finish as gutters and downspouts.

2.3 FABRICATION

2.3.1 Continuously form seamless gutters to the profiles and sizes specified.

2.3.2 Form downspouts of profiles and sizes specified.

2.3.3 Hem exposed edges of metal.

3.0 EXECUTION

3.1 EXAMINATION

3.1.1 Do not begin installation until substrates have been properly prepared.

3.1.2 Verify governing dimensions at building.

3.1.3 Verify surfaces are ready to receive gutters and downspouts.

3.1.4 If substrate preparation is the responsibility of another installer, notify

Architect of unsatisfactory preparation before proceeding.

3.2 PREPARATION

3.2.1 Clean surfaces thoroughly prior to installation.

3.2.2 Clean and repair if necessary, any adjoining work on which this work is in any way dependent for its proper installation.

3.2.3 Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions.

3.3 INSTALLATION

3.3.1 Install in accordance with manufacturer's instructions.

3.3.2 Install gutters using appropriate hangers to allow normal expansion and contraction.

3.3.3 Install gutter hangers using two 1-1/4 inch (32 mm) screw shank nails with

EDPM grommets and fastened into solid lumber.

3.3.4 All gutters shall be in continuous length for each elevation (run). No end laps are allowed.

3.3.5 Exercise care in placing aluminum in contact with other dissimilar metals or materials that are not compatible with aluminum.

3.3.6 Providing adequate insulation/separation wherever necessary, such as by painting or otherwise protecting when they are in contact with aluminum or when drainage from them passes over aluminum surfaces.

3.3.7 Install sealants where indicated to clean dry surfaces only without skips or voids.

3.4 PROTECTION

3.4.1 Protect installed products until completion of project.

3.4.2 Touch-up, repair or replace damaged products before Final Completion.

END OF SECTION

SECTION 07 92 00

JOINT SEALANTS

1.0 GENERAL

1.1 SUMMARY

1.1.1 The extent of each form and type of joint sealer is indicated on drawings and by provisions of this section.

1.1.2 The applications for joint sealers as work of this section include the following:

1.1.2.1 Wall joints at floors.

1.1.2.2 At locations where dissimilar metals and/or materials come together.

1.1.2.3 Other locations indicated.

1.2 SUBMITTALS

1.2.1 Submit according to the requirements stated in the SOW.

1.2.2 Product Literature

1.2.2.1 Submit product data sheets and the manufacturer's installation instructions. If two or more different sealants are to be in physical contact with each other, obtain from each manufacturer confirmation that its product is compatible with the proposed and adjacent products, including any other products which may be used by other sub-contractors. Include primer literature with the submittal document unless the manufacturer's sealant submittal specifically eliminates the need for a primer.

1.2.2.2 If a stain type primer is required for the sealant selected, such information shall be specifically included on submittal documents calling attention to the need for such staining type primer and noting the planned precautions to prevent exposed stain residue.

1.2.2.3 Include Safety Data Sheets for sealants.

1.2.3 Color Samples: Submit manufacturer's standard color chart. Submit cured samples of each chosen color for verification of actual color to be installed. Multiple cured samples may be required for selection. Color by

CO.

1.3 DELIVERY, STORAGE AND HANDLING

1.3.1 Deliver in manufacturer's original unopened container, clearly identifying each product specified, relating it to the product literature submitted.

1.3.2 Store in accordance with manufacturer's recommendation, with proper precautions concerning shelf life, temperature, humidity, and similar storage factors to ensure the fitness of the material when installed.

2.0 PRODUCTS

2.1 MATERIALS

2.1.1 General Sealer Performance Requirements

2.1.1.1 Provide colors indicated or, if not otherwise indicated, as selected by Contracting Officer from manufacturer's standard colors. Select materials for compatibility with joint surfaces and other indicated exposures, and except as otherwise indicated, select modulus of elasticity and hardness or grade recommended by manufacturer for each application indicated.

2.1.2 Type 1: Non-Elastomeric Sealants (Caulking)

2.1.2.1 Single component siliconized acrylic latex caulking compound:

ASTM C834, gun grade; flexible, paintable, non-staining, non-bleeding, acrylic emulsion.

2.1.2.2 Use: Interior sealing around doors and gypsum board.

2.1.2.3 Acceptable Manufacturers/Products, or Approved Equal:

2.1.2.3.1 GE Silicones RCS 20

2.1.2.3.2 Bostik, Chem-Calk 600

2.1.2.3.3 DAP, Inc., DAP ALEX PLUS Acrylic-latex Caulk Plus

Silicone

2.1.2.3.4 Pecora, AC-20 + Silicone

2.1.2.3.5 Sonneborn, Sonolac

2.1.2.3.6 Tremco, Tremflex 834 Acrylic Latex Caulk

2.2 ACCESSORIES

2.2.1 Primer: Non-staining type, recommended by sealant manufacturer to suit application.

2.2.2 Joint Primer/Sealer: Provide type of joint primer/sealer recommended by sealant manufacturer for joint surfaces to be primed or sealed.

2.2.3 Sealant Backer Rod: Compressible rod stock of open or closed cell polyethylene or polyurethane as recommended by sealant manufacturer for compatibility with sealant.

2.2.4 Bond Breaker Tape: An acceptable polyethylene or similar type bond breaker tape used to prevent three-sided adhesion in locations where backer rod cannot be used.

3.0 EXECUTION

3.1 EXAMINATION

3.1.1 Inspect substrate surface to assure that no bond breaker materials contaminate the surface to which the sealant is to adhere and to ensure that unsound substrates are repaired. Installation of sealant shall be evidence of acceptance of the substrate.

3.1.2 Verify joint dimensions prior to installation of the sealant to ensure that all dimensions are within tolerance established in the manufacturer's literature. Unacceptable variations shall be called to the Contracting Officers attention for resolution prior to installing any material.

3.2 PREPARATION

3.2.1 Clean joint surfaces immediately before installation of sealant or caulking compound. Remove dirt, insecure coatings, moisture and other substances which could interfere with bond of sealant or caulking compound. Etch concrete and masonry joint surfaces as recommended by sealant manufacturer.

3.2.2 Prime or seal joint surfaces where indicated, and where not indicated if recommended by sealant manufacturer, prior to installation of any backer rod or bond breaker tape. Do not allow primer/sealer to spill or migrate onto adjoining surfaces.

3.3 INSTALLATION

3.3.1 General: Comply with manufacturer's printed instructions, except where more stringent requirements are shown or specified, and except where manufacturer's technical representative directs otherwise.

3.3.2 Set joint filler units full depth of joint or position in joint to coordinate with other work, including installation of backer rods and sealants. Do not leave voids or gaps between ends of joint filler units.

3.3.3 Install sealant backer rod for liquid elastomeric sealants, except where shown to be omitted or recommended to be omitted by sealant manufacturer for application indicated in which case a bond breaker tape shall be used to prevent 3-sided adhesion. Apply backer rod using blunt or rounded tools which will ensure a uniform depth without puncturing the material. Use a rod oversized a minimum of 33% for closed cell and 50% for open cell, unless otherwise required by the manufacturer.

3.3.4 Employ only proven installation techniques, which will ensure that sealants are deposited in uniform, continuous ribbons without gaps or air pockets, with complete "wetting" of joint bond surfaces equally on opposite sides. Except as otherwise indicated, fill sealant rabbet to a slightly concave surface, slightly below adjoining surfaces, with a smooth, even finish.

3.3.5 Install sealant to depths as shown or, if not shown, as recommended by sealant manufacturer but within the following general limitations, measured at center (thin) section of bead.

3.3.5.1 For joints sealed with non-elastomeric sealants, fill joints to a depth in range of 75% to 125% of joint width.

3.3.6 Spillage: Do not allow sealants or compounds to overflow or spill onto adjoining surfaces or to migrate into voids of adjoining surfaces. Clean adjoining surfaces by whatever means may be necessary to eliminate evidence of spillage.

3.3.7 Curing: Cure sealants and caulking compounds in compliance with manufacturer's instructions and recommendations to obtain high early bond strength, internal cohesive strength and surface durability.

SECTION 08 51 13

ALUMINUM WINDOWS

1.0 GENERAL

1.1 WORK INCLUDED

1.1.1 Provide window assemblies and screens to replace damaged window assemblies and screens as per the drawings. Match existing windows as required.

1.2 TESTING AND PERFORMANCE REQUIREMENTS

1.2.1 Test Units

1.2.1.1 Air, water, and structural test unit shall conform to requirements set forth in ANSI/AAMA/NWWDA 101 I.S. 2-97 and AAMA 910- 93 or CSA A440. 2. Thermal test unit sizes shall be 47- 1/4" x 59" (1200 x 1500) for Series 8000 and 8100, 59"x 47-1/4" (1500 x 1200) for Series 8200. Unit shall consist of a single hung, fixed or horizontal sliding window.

1.3 Test Procedures and Performances

1.3.1 Windows shall conform to all AAMA/ANSI/NWWDA-101 I.S. 2-97 and

AAMA 910-93 or CSA A440 requirements for the window type referenced in 1.01.B. In addition, the following specific performance requirements shall be met.

1.3.2 Air Infiltration Test - With ventilators closed and locked, test unit in accordance with ASTM E 283-91 at a static air pressure difference of 6.24 psf. Air infiltration shall not exceed .30 cfm per foot of crack.

1.3.3 Water Resistance Test - With ventilators closed and locked, test unit in accordance with ASTM E 331-96/ASTM E 547 at a static air pressure difference of 12 psf. There shall be no uncontrolled water leakage.

1.3.4 Uniform Load Deflection Test - With ventilators closed and locked, test unit in accordance with ASTM E 330-97 at a static air pressure difference of 90 PSF positive and negative pressure. No member shall deflect over L/175 of its span.

1.3.5 Condensation Resistance Test (CRF) - With ventilators closed and locked, test unit in accordance with AAMA 1503. Condensation Resistance Factor (CRF) shall not be less than 49 for Series 8100 and 8200. Not less than 50 for Series 8000.

1.3.6 Thermal Transmittance Test (Conductive U-Value) - With ventilators closed and locked, test unit in accordance with NFRC 100 and AAMA 1503. Conductive thermal transmittance(U-Value) for Series 8000 and 8200 Windows shall have a range between 0.35 to 0.56 BTU/hr/ft2/ºF and Series 8100 Windows shall have a range between 0.33 to 0.56 bTU/hr/ft2/ºF.

1.3.7 AAMA CW60 Rating Testing Procedures - AAMA/WDMA/CSA

101/I.S.2/ A440-8 - Laboratory Performance Testing. AAMA 503-08 - Newly Installed Fenestration Products. AAMA 511-08 - Installed Fenestration Products After 6 Months.

1.4 QUALITY ASSURANCE

1.4.1 Provide test reports from AAMA accredited laboratories certifying the performance as specified in 1.05 or 11.15 of CSA A440.

1.4.2 Test reports shall be accompanied by the window manufacturer's letter of certification, stating the tested window meets or exceeds the referenced criteria for the appropriate AAMA/NWWDA 101/I.S.2-97 and AAMA 910-93 or CSA A440 window type.

1.5 SUBMITTALS

1.5.1 Contractor shall submit shop drawings, finish samples, test reports, and warranties as required in the Statement of Work.

1.6 WARRANTIES

1.6.1 Total Window System

1.6.1.1 The responsible contractor shall assume full responsibility and warrant for one year the satisfactory performance of the total window installation which includes that of the windows, hardware, glass (including insulating units), glazing, anchorage and setting system, sealing, flashing, etc., as it relates to air, water, and structural adequacy as called for in the specifications and approved shop drawings.

2.0 PRODUCTS

2.1 MATERIALS

2.1.1 Aluminum

2.1.1.1 Extruded aluminum shall be 6063-T5 alloy and tempered.

2.1.2 Thermal Barrier

2.1.2.1 Barrier material shall be poured in-place two-part polyurethane. To ensure that composite strength remains unaltered during thermal cycling, a mechanical bond between the aluminum and the thermal filling shall be created by mechanically abrading the extrusion thermal cavity prior to filling with the polyurethane polymer. A non- structural thermal barrier is unacceptable.

2.1.2.2 Specified hardware shall not bridge the thermal barrier.

2.1.3 Glass

2.1.3.1 Insulating glass shall consisting of ¼” exterior, ½” air spacer, and ¼” interior.

2.2 FABRICATION

2.2.1 General

2.2.1.1 All primary aluminum frame, extrusions or vent extrusions shall have a minimum wall thickness of .062 (1.57)

2.2.1.2 Depth of frame 4-1/2" (114.3) for 1" (25) glazing.

2.2.2 Frame

2.2.2.1 Frame components shall be mechanically fastened.

2.2.3 Ventilator

2.2.3.1 All vent extrusions shall be notched.

2.2.4 Screens

2.2.4.1 Screen frames shall have springs locking the screen in place.

2.2.4.2 Screen mesh shall be fiberglass.

2.2.5 Glazing

2.2.5.1 All units shall be either shop or field glazed.

2.2.6 Finish All exposed framing surfaces shall be free of scratches and other serious blemishes. Aluminum extrusions shall be given a caustic etch followed by an anodic oxide treatment to obtain Dark Bronze anodic coating. A Fluoropolymer paint coating conforming with the requirements of AAMA 2605. Color shall be CO.

3.0 EXECUTION

3.1 INSPECTION

3.1.1 Job Conditions

3.1.1.1 Verify that openings are dimensionally within allowable tolerances, plumb, level, clean, provide a solid anchoring surface, and are in accordance with approved shop drawings.

3.2 INSTALLATION

3.2.1 Use only skilled tradesmen with work done in accordance with approved shop drawings and specifications.

3.2.2 Adequately anchor to maintain positions permanently when subjected to normal thermal movement, specified building movement, and specified wind loads.

3.2.3 Adjust windows for proper operation after installation.

3.2.4 Furnish and apply sealants to provide a weather tight installation at all joints and intersections and at opening perimeters.

3.3 PROTECTION AND CLEANING

3.3.1 After completion of window installation, windows shall be inspected, adjusted, put into working order and left clean, free of labels, dirt, etc.

Protection from this point shall be the responsibility of the general contractor.