PROJECT TITLE: F‐35 FUEL CELL MAINTENANCE FACILITY RENOVATION (Bldg 1344) LOCATION:
EIELSON AFB, ALASKA
PROJECT: FTQW 18‐0205
SOLICITATION QUESTIONS AND ANSWERS: Group 4
1. The answer to question 13 references "attached specification section 07 27 19 Self‐Adhering Air Barriers".
ANSWER: Please see the attached items.
2. The answer to question 16 references "Please see the attached specification section 06 10 00 Rough Carpentry".
ANSWER: Please see the attached items.
3. The answer to question 18 references "Please see the Revised A500 drawing attached."
ANSWER: Please see the attached items.
4. The answer to question 28 references "Specification 05 50 13 has been added for additional information on bar grating requirements."
ANSWER: Please see the attached items.
5. The answer to question 29 references "Please see attached detail 9a, 9b, & 9c/A810."
ANSWER: Please see the attached items.
F-35 FUEL CELL MAINTENANCE FACILITY RENOVATION FINAL
FTQW 18-0205
SECTION TABLE OF CONTENTS
DIVISION 05 - METALS
SECTION 05 50 13
MISCELLANEOUS METAL FABRICATIONS
05/17
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
PART 2 PRODUCTS
2.1 MATERIALS
2.1.1 Gratings
PART 3 EXECUTION
3.1 GENERAL INSTALLATION REQUIREMENTS
3.2 WORKMANSHIP
-- End of Section Table of Contents --
SECTION 05 50 13 Page 1
SECTION 05 50 13
MISCELLANEOUS METAL FABRICATIONS
05/17
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2015; Errata 1 2015; Errata 2 2016) Structural Welding Code - Steel
NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS (NAAMM)
NAAMM MBG 531 (2017) Metal Bar Grating Manual
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance with Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Floor Gratings; G
SD-03 Product Data
Floor Gratings; G
PART 2 PRODUCTS
2.1 MATERIALS
Provide exposed fastenings of compatible materials (avoid contact of dissimilar metals). Coordinate color and finish with the material to which fastenings are applied.
2.1.1 Gratings
a. Provide metal bar type grating in accordance with NAAMM MBG 531.
b. Anchor gratings to structural members with bolts, toggle bolts, or expansion shields and bolts.
c. Provide painted bar grating, one coat, black.
SECTION 05 50 13 Page 2
d. Provide unbanded edges.
PART 3 EXECUTION
3.1 GENERAL INSTALLATION REQUIREMENTS
Install items at locations indicated in accordance with manufacturer's instructions. Verify all field dimensions prior to fabrication. Include materials and parts necessary to complete each assembly, whether indicated or not. Miss-alignment and miss-sizing of holes for fasteners is cause for rejection. Conceal fastenings where practicable. Joints exposed to weather must be watertight.
3.2 WORKMANSHIP
Provide miscellaneous metalwork that is true and accurate in shape, size, and profile. Make angles and lines continuous and straight. Make curves consistent, smooth and unfaceted. Provide continuous welding along the entire area of contact except where tack welding is permitted. Do not tack weld exposed connections. Unless otherwise indicated and approved, provide a smooth finish on exposed surfaces. Provide countersuck rivets where exposed. Provide coped and mitered corner joints aligned flush and without gaps.
-- End of Section --
SECTION 05 50 13 Page 3
SECTION TABLE OF CONTENTS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
SECTION 06 10 00
ROUGH CARPENTRY
08/16
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 DELIVERY AND STORAGE
1.4 GRADING AND MARKING
1.4.1 Lumber
1.4.2 Plywood
1.4.3 Structural-Use and OSB Panels
1.4.4 Preservative-Treated Lumber and Plywood
1.5 SIZES AND SURFACING
1.6 MOISTURE CONTENT
1.7 PRESERVATIVE TREATMENT
1.8 CERTIFICATIONS
1.8.1 Certified Wood Grades
1.8.2 Indoor Air Quality Certifications
1.8.2.1 Adhesives and Sealants
PART 2 PRODUCTS
2.1 MATERIALS
2.1.1 Virgin Lumber
2.2 LUMBER
2.2.1 Framing Lumber
2.3 PLYWOOD, STRUCTURAL-USE, AND ORIENTED STRAND BOARD (OSB) PANELS
2.3.1 Wall Sheathing
2.3.1.1 Plywood
2.4 ROUGH HARDWARE
2.4.1 Bolts, Nuts, Studs, and Rivets
2.4.2 Lag Screws and Lag Bolts
2.4.3 Wood Screws
2.4.4 Nails
2.4.5 Buck Anchors
2.4.6 Metal Framing Anchors
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Wall Sheathing
3.1.1.1 Plywood, Structural-Use, and OSB Panel Wall Sheathing
3.2 MISCELLANEOUS
3.2.1 Wood Blocking
3.2.2 Wood Furring
3.2.3 Temporary Closures
SECTION 06 10 00 Page 1
SECTION 06 10 00 Page 2
SECTION 06 10 00
ROUGH CARPENTRY
08/16
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN FOREST FOUNDATION (AFF)
ATFS STANDARDS (2015) American Tree Farm System Standards of Sustainability 2015-2020
AMERICAN LUMBER STANDARDS COMMITTEE (ALSC)
ALSC PS 20 (2015) American Softwood Lumber Standard
AMERICAN WOOD COUNCIL (AWC)
AWC NDS (2015) National Design Specification (NDS) for Wood Construction
AWC WFCM (2012) Wood Frame Construction Manual for One- and Two-Family Dwellings
AMERICAN WOOD PROTECTION ASSOCIATION (AWPA)
AWPA BOOK (2015) AWPA Book of Standards
AWPA M2 (2016) Standard for the Inspection of Preservative Treated Wood Products for Industrial Use
AWPA M6 (2013) Brands Used on Preservative Treated Materials
AWPA P18 (2014) Nonpressure Preservatives
AWPA P49 (2015) Standard for Fire Retardant FR-1
AWPA P5 (2015) Standard for Waterborne Preservatives
AWPA T1 (2017) Use Category System: Processing and Treatment Standard
AWPA U1 (2017) Use Category System: User Specification for Treated Wood
APA - THE ENGINEERED WOOD ASSOCIATION (APA)
APA E30 (2016) Engineered Wood Construction Guide
SECTION 06 10 00 Page 3
APA E445 (2002) Performance Standards and Qualification Policy for Structural-Use Panels (APA PRP-108)
APA EWS R540 (2013) Builder Tips: Proper Storage and Handling of Glulam Beams
APA EWS T300 (2007) Technical Note: Glulam Connection Details
APA F405 (19) Product Guide: Performance Rated Panels
APA L870 (2010) Voluntary Product Standard, PS 1-09, Structural Plywood
APA S350 (2014) PS 2-10, Performance Standard for Wood-Based Structural-Use Panels
ASME INTERNATIONAL (ASME)
ASME B18.2.1 (2012; Errata 2013) Square and Hex Bolts and Screws (Inch Series)
ASME B18.2.2 (2015) Nuts for General Applications:
Machine Screw Nuts, Hex, Square, Hex Flange, and Coupling Nuts (Inch Series)
ASME B18.5.2.1M (2006; R 2011) Metric Round Head Short Square Neck Bolts
ASME B18.5.2.2M (1982; R 2010) Metric Round Head Square Neck Bolts
ASME B18.6.1 (2016) Wood Screws (Inch Series)
ASTM INTERNATIONAL (ASTM)
ASTM A153/A153M (2016) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A307 (2014; E 2017) Standard Specification for Carbon Steel Bolts, Studs, and Threaded Rod 60 000 PSI Tensile Strength
ASTM A653/A653M (2017) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM D3498 (2018; E 2018) Standard Specification for Adhesives for Field-Gluing Wood Structural Panels (Plywood or Oriented Stand Board) to Wood Based Floor System Framing
ASTM F1667 (2017) Standard Specification for Driven Fasteners: Nails
SECTION 06 10 00 Page 4
ASTM F547 (2017) Standard Terminology of Nails for Use with Wood and Wood-Base Materials
CSA GROUP (CSA)
CSA Z809-08 (R2013) Sustainable Forest Management
FOREST STEWARDSHIP COUNCIL (FSC)
FSC STD 01 001 (2015) Principles and Criteria for Forest Stewardship
GREEN SEAL (GS)
GS-36 (2013) Adhesives for Commercial Use
INTERNATIONAL CODE COUNCIL (ICC)
ICC IBC (2018) International Building Code
NATIONAL HARDWOOD LUMBER ASSOCIATION (NHLA)
NHLA Rules (2015) Rules for the Measurement & Inspection of Hardwood & Cypress
NORTHEASTERN LUMBER MANUFACTURERS ASSOCIATION (NELMA)
NELMA Grading Rules (2013) Standard Grading Rules for Northeastern Lumber
PROGRAMME FOR ENDORSEMENT OF FOREST CERTIFICATION (PEFC)
PEFC ST 2002:2013 (2015) PEFC International Standard Chain of Custody of Forest Based Products Requirements
REDWOOD INSPECTION SERVICE (RIS) OF THE CALIFORNIA REDWOOD
ASSOCIATION (CRA)
RIS Grade Use (1998) Redwood Lumber Grades and Uses
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule 1168 (2017) Adhesive and Sealant Applications
SOUTHERN CYPRESS MANUFACTURERS ASSOCIATION (SCMA)
SCMA Spec (1986; Supple. No. 1, Aug 1993) Standard Specifications for Grades of Southern Cypress
SOUTHERN PINE INSPECTION BUREAU (SPIB)
SPIB 1003 (2014) Standard Grading Rules for Southern Pine Lumber
SECTION 06 10 00 Page 5
SUSTAINABLE FOREST INITIATIVE (SFI)
SFI 2015-2019 (2015) Standards, Rules for Label Use, Procedures and Guidance
TRUSS PLATE INSTITUTE (TPI)
TPI 1 (2014) National Design Standard for Metal Plate Connected Wood Truss Construction, Including Commentary and Appendices
TPI HIB (1991) Commentary and Recommendations for Handling, Installing and Bracing Metal Plate Connected Wood Trusses
U.S. DEPARTMENT OF COMMERCE (DOC)
DOC/NIST PS56 (1973) Structural Glued Laminated Timber
DOC/NIST PS58 (1973) Basic Hardboard (ANSI A135.4)
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
CID A-A-1923 (Rev A; Notice 3) Shield, Expansion (Lag, Machine and Externally Threaded Wedge Bolt Anchors)
CID A-A-1924 (Rev A; Notice 3) Shield, Expansion (Self Drilling Tubular Expansion Shell Bolt Anchors
CID A-A-1925 (Rev A; Notice 3) Shield Expansion (Nail Anchors)
FS UU-B-790 (Rev A; Notice 2) Building Paper Vegetable Fiber: (Kraft, Waterproofed, Water Repellent and Fire Resistant)
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
40 CFR 770 Formaldehyde Standards for Composite Wood Products
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2013) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
WEST COAST LUMBER INSPECTION BUREAU (WCLIB)
WCLIB 17 (2015) Standard Grading Rules
WESTERN WOOD PRODUCTS ASSOCIATION (WWPA)
WWPA G-5 (2017) Western Lumber Grading Rules
SECTION 06 10 00 Page 6
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-03 Product Data
Structural-use and OSB Panels; G
Adhesives; G
SD-07 Certificates
Certificates of Grade; G
Preservative Treatment; G
Indoor Air Quality for Particleboard Underlayment; S
1.3 DELIVERY AND STORAGE
Deliver materials to the site in an undamaged condition. Store, protect, handle, and install prefabricated structural elements in accordance with manufacturer's instructions and as specified. Store materials off the ground to provide proper ventilation, with drainage to avoid standing water, and protection against ground moisture and dampness. Store materials with a moisture barrier at both the ground level and as a cover forming a well ventilated enclosure. Store wood I-beams and glue-laminated beams and joists on edge. Adhere to requirements for stacking, lifting, bracing, cutting, notching, and special fastening requirements. Do not use materials that have visible moisture or biological growth. Remove defective and damaged materials and provide new materials. Store separated reusable wood waste convenient to cutting station and area of work.
1.4 GRADING AND MARKING
1.4.1 Lumber
Mark each piece of framing and board lumber or each bundle of small pieces of lumber with the grade mark of a recognized association or independent inspection agency. Such association or agency must be certified by the Board of Review, American Lumber Standards Committee, to grade the species used. Surfaces that are to be exposed to view must not bear grademarks, stamps, or any type of identifying mark. Hammer marking will be permitted on timbers when all surfaces will be exposed to view.
1.4.2 Plywood
Mark each sheet with the mark of a recognized association or independent inspection agency that maintains continuing control over the quality of the plywood. The mark must identify the plywood by species group or span rating, exposure durability classification, grade, and compliance with APA L870. Surfaces that are to be exposed to view must not bear grademarks or other types of identifying marks.
SECTION 06 10 00 Page 7
1.4.3 Structural-Use and OSB Panels
Mark each panel with the mark of a recognized association or independent inspection agency that maintains continuing control over the quality of the panel. The mark must indicate end use, span rating, and exposure durability classification. Oriented Strand Board (OSB), APA F405.
1.4.4 Preservative-Treated Lumber and Plywood
The Contractor is responsible for the quality of treated wood products.
Each treated piece must be inspected in accordance with AWPA M2 and permanently marked or branded, by the producer, in accordance with AWPA M6.
The Contractor must provide Contracting Officer's Representative (COR) with the inspection report of an approved independent inspection agency that offered products comply with applicable AWPA Standards. The appropriate Quality Mark on each piece will be accepted, in lieu of inspection reports, as evidence of compliance with applicable AWPA treatment standards.
1.5 SIZES AND SURFACING
ALSC PS 20 for dressed sizes of yard and structural lumber. Lumber must be surfaced four sides. Size references, unless otherwise specified, are nominal sizes, and actual sizes must be within manufacturing tolerances allowed by the standard under which the product is produced. Other measurements are IP or SI standard.
1.6 MOISTURE CONTENT
Air-dry or kiln-dry lumber. Kiln-dry treated lumber after treatment.
Maximum moisture content of wood products must be as follows at the time of delivery to the job site:
a. Framing lumber and board, 19 percent maximum
d. Materials other than lumber; moisture content must be in accordance with standard under which the product is produced
1.7 PRESERVATIVE TREATMENT
a. 0.25 pcf intended for above ground use.
b. 0.40 pcf intended for ground contact and fresh water use. 0.60 pcf intended for Ammoniacal Copper Quaternary Compound (ACQ)-treated foundations. 0.80 to 1.00 pcf intended for ACQ-treated pilings. All wood must be air or kiln dried after treatment. Specific treatments must be verified by the report of an approved independent inspection agency, or the AWPA Quality Mark on each piece. Brush coat areas that are cut or drilled after treatment with either the same preservative used in the treatment or with a 2 percent copper naphthenate solution.
Plastic lumber must not be preservative treated. The following items must be preservative treated:
(1) Wood framing, woodwork, and plywood up to and including the subflooring at the first-floor level of structures having crawl spaces when the bottoms of such items are 24 inches or less from the earth underneath.
(2) Wood members that are in contact with water.
SECTION 06 10 00 Page 8
(3) Exterior wood steps, platforms, and railings; and all wood framing of open, roofed structures.
(4) Wood sills, soles, plates, furring, and sleepers that are less than 24 inches from the ground, furring and nailers that are set into or in contact with concrete or masonry.
(5) Nailers, edge strips, crickets, curbs, and cants for roof decks.
1.8 CERTIFICATIONS
1.8.1 Certified Wood Grades
Provide certificates of grade from the grading agency on graded but unmarked lumber or plywood attesting that materials meet the grade requirements specified herein.
1.8.2 Indoor Air Quality Certifications
Submit required indoor air quality certifications in one submittal package.
1.8.2.1 Adhesives and Sealants
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party programs that products meet the requirements of this Section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.
PART 2 PRODUCTS
2.1 MATERIALS
2.1.1 Virgin Lumber
Lumber fabricated from old growth timber is not permitted. Avoid companies who buy, sell, or use old growth timber in their operations, when possible.
2.2 LUMBER
2.2.1 Framing Lumber
Framing lumber such as studs, plates, caps, collar beams, cant strips, bucks, sleepers, nailing strips, and nailers and board lumber such as subflooring and wall and roof sheathing must be one of the species listed in the table below. Minimum grade of species must be as listed.
SECTION 06 10 00 Page 9
Table of Grades for Framing and Board Lumber
Grading Rules Species Framing Board Lumber
WWPA G-5 standard grading rules
Aspen, Douglas Fir-Larch, Douglas Fir South, Engelmann Spruce-Lodgepole Pine, Engelmann Spruce, Hem-Fir, Idaho White Pine, Lodgepole Pine, Mountain Hemlock, Mountain Hemlock-Hem-Fir, Ponderosa Pine-Sugar Pine, Ponderosa Pine-Lodgepole Pine, Subalpine Fir, White Woods, Western Woods, Western Cedars, Western Hemlock
All Species:
Standard Light Framing or No. 3 Structural Light Framing (Stud Grade for 2x4 nominal size, 10 feet and shorter)
All Species:
No. 3 Common
WCLIB 17 standard grading rules
Douglas Fir-Larch, Hem-Fir, Mountain Hemlock, Sitka Spruce, Western Cedars, Western Hemlock
All Species:
Standard Light Framing or No. 3 Structural Light Framing (Stud Grade for 2x4 nominal size, 10 feet and shorter)
All Species:
Standard
SECTION 06 10 00 Page 10
Table of Grades for Framing and Board Lumber
Grading Rules Species Framing Board Lumber
SPIB 1003 standard grading rules
Southern Pine All Species:
Standard Light Framing or No. 3 Structural Light Framing (Stud Grade for 2x4 nominal size, 10 feet and shorter)
No. 2 Boards
SCMA Spec standard specifications
Cypress No. 2 Common No. 2 Common
NELMA Grading Rules standard grading rules
Balsam Fir, Eastern Hemlock-Tamarack, Eastern Spruce, Eastern White Pine, Northern Pine, Northern Pine-Cedar
All Species:
Standard Light Framing or No. 3 Structural Light Framing (Stud Grade for 2x4 nominal size, 10 feet and shorter)
All Species:
No. 3 Common except Standard for Eastern White and Northern Pine
RIS Grade Use standard specifications
Redwood All Species:
Standard Light Framing or No. 3 Structural Light Framing (Stud Grade for 2x4 nominal size, 10 feet and shorter)
Construction Heart
SECTION 06 10 00 Page 11
Table of Grades for Framing and Board Lumber
Grading Rules Species Framing Board Lumber
NHLA Rules rules for the measurement and inspection of hardwood and cypress lumber
Cypress No. 2 Dimension No. 2 Common
2.3 PLYWOOD, STRUCTURAL-USE, AND ORIENTED STRAND BOARD (OSB) PANELS
APA L870, APA S350, APA E445, and APA F405 respectively.
2.3.1 Wall Sheathing
2.3.1.1 Plywood
C-D Grade, Exposure 1, and a minimum thickness of 1/2 inch, except where indicated to have greater thickness. Provide exterior grade material with phenol resin for interior and exterior applications.
2.4 ROUGH HARDWARE
Unless otherwise indicated or specified, rough hardware must be of the type and size necessary for the project requirements. Sizes, types, and spacing of fastenings of manufactured building materials UST be as recommended by the product manufacturer unless otherwise indicated or specified. Rough hardware exposed to the weather or embedded in or in contact with preservative treated wood, exterior masonry, or concrete walls or slabs must be hot-dip zinc-coated in accordance with ASTM A153/A153M. Nails and fastenings for fire-retardant treated lumber and woodwork exposed to the weather must be copper alloy or hot-dipped galvanized fasteners as recommended by the treated wood manufacturer.
2.4.1 Bolts, Nuts, Studs, and Rivets
ASME B18.2.1, ASME B18.5.2.1M, ASME B18.5.2.2M and ASME B18.2.2.
2.4.2 Lag Screws and Lag Bolts
ASME B18.2.1.
2.4.3 Wood Screws
ASME B18.6.1.
2.4.4 Nails
ASTM F547, size and type best suited for purpose. For sheathing and subflooring, length of nails must be sufficient to extend 1 inch into supports. In general, 8-penny or larger nails must be used for nailing through 1 inch thick lumber and for toe nailing 2 inch thick lumber;
SECTION 06 10 00 Page 12
16-penny or larger nails must be used for nailing through 2 inch thick lumber. Nails used with treated lumber and sheathing must be hot-dipped galvanized in accordance with ASTM A153/A153M. Nailing must be in accordance with the recommended nailing schedule contained in AWC WFCM.
Where detailed nailing requirements are not specified, nail size and spacing must be sufficient to develop an adequate strength for the connection. The connection's strength must be verified against the nail capacity tables in AWC NDS. Reasonable judgment backed by experience must ensure that the designed connection will not cause the wood to split. If a load situation exceeds a reasonable limit for nails, a specialized connector must be used.
2.4.5 Buck Anchors
Metal anchors, 1/4 by 6 inch long concrete screw. Anchorage of bucks must be as necessary to suit the conditions.
2.4.6 Metal Framing Anchors
Construct anchors to the configuration shown using hot dip zinc-coated steel conforming to ASTM A653/A653M, G90. Steel must be not lighter than 18 gage. Special nails supplied by the manufacturer must be used for all nailing.
PART 3 EXECUTION
3.1 INSTALLATION
Do not install building construction materials that show visual evidence of biological growth.
Conform to AWC WFCM unless otherwise indicated or specified. Select lumber sizes to minimize waste. Fit framing lumber and other rough carpentry, set accurately to the required lines and levels, and secure in place in a rigid manner. Do not splice framing members between bearing points. Set joists, rafters, and purlins with their crown edge up. Frame members for the passage of pipes, conduits, and ducts. Do not cut or bore structural members for the passage of ducts or pipes without approval. Reinforce all members damaged by such cutting or boring by means of specially formed and approved sheet metal or bar steel shapes, or remove and provide new, as approved. Provide as necessary for the proper completion of the work all framing members not indicated or specified. Spiking and nailing not indicated or specified otherwise must be in accordance with the Nailing Schedule contained in ICC IBC; perform bolting in an approved manner.
Spikes, nails, and bolts must be drawn up tight. Use slate or steel shims when leveling joists, beams, and girders on masonry or concrete. Do not use shimming on wood or metal bearings. When joists, beams, and girders are placed on masonry or concrete, a wood base plate must be positioned and leveled with grout. The joist, beam, or girder must then be placed on the plate. When joists, beams, and girders are set into masonry or concrete, a pocket must be formed into the wall. The joist, beam, or girder must then be placed into the pocket and leveled with a steel shim.
3.1.1 Wall Sheathing
3.1.1.1 Plywood, Structural-Use, and OSB Panel Wall Sheathing
Apply horizontally or vertically. Extend sheathing over and nail to sill and top plate. Abut sheathing edges over centerlines of supports. Allow
SECTION 06 10 00 Page 13
1/8 inch spacing between panels and 1/8 inch at windows and doors. If sheathing is applied horizontally, stagger vertical end joints. Nail panels with 6-penny nails spaced 6 inches o.c. along edges of the panel and 12 inches o.c. over intermediate supports. Keep nails 3/8 inches away from panel ledges. Provide 2 by 4 blocking for horizontal edges not otherwise supported.
3.2 MISCELLANEOUS
3.2.1 Wood Blocking
Provide proper sizes and shapes at proper locations for the installation and attachment of wood and other finish materials, fixtures, equipment, and items indicated or specified.
3.2.2 Wood Furring
Provide where shown and as necessary for facing materials specified. Except as shown otherwise, furring strips must be nominal one by 3, continuous, and spaced 16 inches o.c. Erect furring vertically or horizontally as necessary. Nail furring strips to masonry. Do not use wood plugs.
Provide furring strips around openings, behind bases, and at angles and corners. Furring must be plumb, rigid, and level and must be shimmed as necessary to provide a true, even plane with surfaces suitable to receive the finish required. Form furring for offsets and breaks in walls or ceilings on 1 by 4 wood strips spaced 16 inches o.c.
3.2.3 Temporary Closures
Provide with hinged doors and padlocks and install during construction at exterior doorways and other ground level openings that are not otherwise closed. Cover windows and other unprotected openings with polyethylene or other approved material, stretched on wood frames. Provide dustproof barrier partitions to isolate areas as directed.
SECTION 06 10 00 Page 14
SECTION TABLE OF CONTENTS
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
SECTION 07 27 19
SELF-ADHERING AIR BARRIERS
05/17
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 MISCELLANEOUS REQUIREMENTS
1.3.1 Product Data
1.4 DELIVERY, STORAGE, AND HANDLING
1.4.1 Delivery
1.4.2 Storage
1.5 ENVIRONMENTAL CONDITIONS
1.5.1 Temperature
1.5.2 Exposure to Weather and Ultraviolet Light
PART 2 PRODUCTS
2.1 SELF-ADHERING AIR BARRIER
2.1.1 Physical Properties
2.2 PRIMERS, ADHESIVES, AND MASTICS
PART 3 EXECUTION
3.1 EXAMINATION
3.2 PREPARATION
3.3 INSTALLATION
3.3.1 Installation of Self-adhering Air Barrier
3.4 PROTECTION AND CLEANING
3.4.1 Protection
3.4.1.1 Adjacent Surfaces
3.4.1.2 The Air Barrier Assembly
3.4.2 Cleaning
SECTION 07 27 19.01 Page 1
SECTION 07 27 19
SELF-ADHERING AIR BARRIERS
05/17
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AIR BARRIER ASSOCIATION OF AMERICA (ABAA)
ABAA Accreditation Accreditation
ABAA QAP Quality Assurance Program
ASTM INTERNATIONAL (ASTM)
ASTM D146/D146M (2004; E 2012; R 2012) Sampling and Testing Bitumen-Saturated Felts and Woven Fabrics for Roofing and Waterproofing
ASTM D1876 (2008; R 2015; E 2015) Standard Test Method for Peel Resistance of Adhesives (T-Peel Test)
ASTM D412 (2016) Standard Test Methods for Vulcanized Rubber and Thermoplastic Elastomers - Tension
ASTM D4263 (1983; R 2012) Indicating Moisture in Concrete by the Plastic Sheet Method
ASTM D4541 (2017) Standard Test Method for Pull-Off Strength of Coatings Using Portable Adhesion Testers
ASTM D570 (1998; E 2010; R 2010) Standard Test Method for Water Absorption of Plastics
ASTM D903 (1998; R 2017) Standard Test Method for Peel or Stripping Strength of Adhesive Bonds
ASTM E154/E154M (2008a; R 2013; E 2013) Water Vapor Retarders Used in Contact with Earth Under Concrete Slabs, on Walls, or as Ground Cover
ASTM E2178 (2013) Standard Test Method for Air Permeance of Building Materials
ASTM E2357 (2017) Standard Test Method for Determining Air Leakage of Air Barrier
SECTION 07 27 19.01 Page 2
Assemblies
ASTM E283 (2004; R 2012) Determining the Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen
ASTM E331 (2000; R 2016) Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference
ASTM E84 (2017) Standard Test Method for Surface Burning Characteristics of Building Materials
ASTM E96/E96M (2016) Standard Test Methods for Water Vapor Transmission of Materials
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 285 (2012) Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Non-Load-Bearing Wall Assemblies Containing Combustible Components
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval.Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-03 Product Data
Self-adhering Air Barrier; G
Primers, Adhesives, and Mastics; G
Safety Data Sheets; G
1.3 MISCELLANEOUS REQUIREMENTS
For self-adhering air barrier provide the following:
1.3.1 Product Data
Submit manufacturer's technical data indicating compliance with performance and environmental requirements, manufacturer's printed instructions for evaluating, preparing, and treating substrates, temperature and other limitations of installation conditions, safety requirements for installation, and Safety Data Sheets. Indicate flame and smoke spread ratings for all products.
SECTION 07 27 19.01 Page 3
1.4 DELIVERY, STORAGE, AND HANDLING
1.4.1 Delivery
Deliver and store materials in sufficient quantity to allow for uninterrupted flow of work. Inspect materials delivered to the site for damage and store out of weather. Deliver materials to the jobsite in their original unopened packages, clearly marked with the manufacturer's name, brand designation, description of contents, and shelf life of containerized materials. Store and handle to protect from damage.
1.4.2 Storage
Inspect materials delivered to the site for damage; unload and store out of weather in manufacturer's original packaging. Store only in dry locations, not subject to open flames or sparks, and easily accessible for inspection and handling. Protect stored materials from direct sunlight. Keep materials sealed and separated from absorptive materials, such as wood and insulation.
1.5 ENVIRONMENTAL CONDITIONS
1.5.1 Temperature
Install air barrier within the range of ambient and substrate temperatures as recommended in writing by the air barrier manufacturer. Verify that the surface to receive self-adhering air barrier is dry for a minimum of 48 hours prior to the installation of the barrier. Do not apply air barrier to damp or wet substrates. Do not apply during inclement weather or when ice, frost, surface moisture, or visible dampness is present on surfaces to be covered, or when precipitation is imminent.
1.5.2 Exposure to Weather and Ultraviolet Light
Protect air barrier products from direct exposure to rain, snow, sunlight, mist, and other extreme weather conditions. Replace, at no additional cost to the government, barrier products that have been exposed to ultraviolet (sun)light longer than allowed by manufacturer's written requirements.
PART 2 PRODUCTS
2.1 SELF-ADHERING AIR BARRIER
Provide minimum 0.040 inch thick self-adhering, vapor retarding, air barrier membrane consisting of a cross-laminated high density polyethylene (HDPE) film, fully coated with rubberized asphalt adhesive. Provide membrane in rolls of various widths interleaved with disposable silicone release paper. Self-adhering air barrier must exhibit no visible water leakage when tested in accordance with ASTM E331 and must perform as a liquid water drainage plane flashed to discharge to the exterior any incidental condensation or water penetration. Use regular or low temperature formulation depending on site conditions, within temperature ranges specified by manufacturer.
2.1.1 Physical Properties
a. Air Permeance (ASTM E2178): Less than 0.004 CFM per sf at 1.57 psf.
b. Air Leakage (ASTM E2357, ASTM E283): In accordance with Section
SECTION 07 27 19.01 Page 4
Section 07 05 23 PRESSURE TESTING AN AIR BARRIER SYSTEM FOR AIR
TIGHTNESS.
c. Tensile Strength (ASTM D412 die C modified): Not less than 400 psi.
d. Tensile Elongation (ASTM D412 die C modified): Not less than 200 percent.
e. Puncture Resistance (ASTM E154/E154M): Not less than 40 lbs.
f. Pliability (ASTM D146/D146M): Unaffected at minus 25 degrees F, 0.063 inch mandrel.
g. Lap Adhesion (ASTM D1876 modified): Not less than 4.0 lbs per inch.
h. Peel Adhesion (ASTM D903): Not less than 5.0 lbs per inch.
i. Water Vapor Permeance (Vapor Permeable Air Barrier) (ASTM E96/E96M, desiccant method B): greater than 10.0 perms.
j. Water Absorption (ASTM D570): Not to exceed 0.12 percent by weight.
k. Flame propagation of wall assemblies (NFPA 285): Pass
l. Surface Burning Characteristics (ASTM E84):
(1) Flame Spread Index Rating not higher than 75.
(2) Smoke Developed Index Rating not higher than 150.
2.2 PRIMERS, ADHESIVES, AND MASTICS
Provide primers, adhesives, mastics and other accessory materials as recommended in writing by the manufacturer of the self-adhering air barrier for adequate bonding to each type of substrate.
PART 3 EXECUTION
3.1 EXAMINATION
Before installing air barrier, examine substrates, areas, and conditions under which air barrier assemblies will be applied, with Installer present, for compliance with requirements. Ensure the following conditions are met:
a. Surfaces are sound, dry, even, and free of oil, grease, dirt, excess mortar or other contaminants.
b. Concrete surfaces are cured and dry, smooth without large voids, spalled areas or sharp protrusions.
c. Verify substrate is visibly dry and free of moisture. Test for capillary moisture by plastic sheet method in accordance with ASTM D4263 and take suitable measures until substrate passes moisture test.
d. Verify sealants used in sheathing are compatible with membrane proposed for use. Perform field peel adhesion test on materials to which sealants are adhered.
SECTION 07 27 19.01 Page 5
3.2 PREPARATION
Clean, prepare, and treat substrate in accordance with manufacturer's written instructions. Ensure clean, dust-free, and dry substrate for air barrier application.
a. Prime masonry and concrete substrates with conditioning primer.
b. Prime gypsum sheathing an adequate number of coats to achieve required bond, with adequate drying time between coats.
c. Prime wood, metal, and painted substrates with primer.
d. Prepare, treat, and seal vertical and horizontal surfaces at terminations and penetrations through air barrier and at protrusions.
3.3 INSTALLATION
3.3.1 Installation of Self-adhering Air Barrier
Install materials in accordance with manufacturer's recommendations and the following:
a. Apply primer at rate recommended by manufacturer prior to membrane installation. Allow primer to dry completely before membrane application. Apply as many coats as necessary for proper adhesion.
b. When membrane is properly positioned, press into place and roll membrane with roller immediately after placement.
c. Apply membrane sheets to shed water naturally without interception by a sheet edge, unless that edge is sealed with permanently flexible termination mastic.
d. Position subsequent sheets of membrane applied above so that membrane overlaps the membrane sheet below by a minimum of 2-1/2 inches, unless greater overlap is recommended by manufacturer. Roll into place with roller.
e. Make all side laps a minimum of 2-1/2 inches and all end laps a minimum of 5 inches, unless greater overlap is recommended by manufacturer.
Roll seams with roller.
f. Roll membrane to adhere to substrate. Cover corners and joints with two layers of reinforcement by first applying a 12 inch width of membrane centered along the axis. Flash drains and projections with a second ply of membrane for a distance of 6 inches from the drain or projection.
g. Seal around all penetrations through the air barrier resulting from pipes, vents, conduit, electrical fixtures, structural members, or other construction passing through it. Seal with termination mastic, extruded silicone sealant, membrane counterflashing or other sealing methods in accordance with manufacturer's written recommendations.
h. Continuously connect the air barrier between walls, roof, floor and below grade assemblies to form a continuous integrated air barrier system around the entire building enclosure. Extend the air barrier membrane into rough openings such as doors, windows, louvers, and other
SECTION 07 27 19.01 Page 6 exterior penetrations. Seal edges of barrier at junctures with rough openings.
i. At changes in substrate plane, provide transition material (e.g. bead of sealant, mastic, extruded silicone sealant, membrane counterflashing or other material recommended by manufacturer) under membrane to eliminate all sharp 90 degree inside corners and to make a smooth transition from one plane to another.
j. Provide mechanically fastened non-corrosive metal sheet to span gaps in substrate plane and to make a smooth transition from one plane to the other. Continuously support membrane with substrate.
k. At deflection and control joints, provide backup for the membrane to accommodate anticipated movement.
l. At expansion and seismic joints provide transition to the joint assemblies.
m. Apply a bead or trowel coat of mastic along membrane seams at reverse lapped seams, rough cuts, and as recommended by the manufacturer.
n. At end of each working day, seal top edge of membrane to substrate with termination mastic.
o. Do not allow materials to come in contact with chemically incompatible materials.
3.4 PROTECTION AND CLEANING
3.4.1 Protection
3.4.1.1 Adjacent Surfaces
Protect exposed adjacent surfaces that could be damaged by primers and adhesives associated with air barrier membrane. Provide protection during application and the remainder of construction in accordance with manufacturer's written instructions.
3.4.1.2 The Air Barrier Assembly
Protect finished portions of the air barrier assembly from damage during ongoing application and throughout the remainder of the construction period in accordance with manufacturer's written instructions. Coordinate timing of installation of materials that will cover the air barrier membrane to ensure the exposure period does not exceed that recommended by the air barrier manufacturer's written installation instructions. Remove and replace, at no additional cost to the government, membrane products that exceed the manufacturer's allowed exposure limits.
3.4.2 Cleaning
Clean spillage and soiling from adjacent construction using cleaning agents and procedures recommended by manufacturer of affected construction and as acceptable to the primary material manufacturer.
SECTION 07 27 19.01 Page 7
PROVIDE CONTINUOUS AIR TIGHT SEAL
AT WALL TERMINATION TO METAL DECK
AND ENTIRE WALL PERIMETER.
CONTINUOUS ACOUSTICAL SEALANT TO
ACCOMODATE STRUCTURAL DEFLECTION
METAL DECK PER STRUCTURAL
NOTCH SHEETROCK TO FIT METAL DECK
PROFILE WITH GAP SIZED TO
ACCOMODATE STRUCTURAL DEFLECTION.
WHERE METAL DECK FLUTES
ARE PARALLEL TO WALL
ASSEMBLY, SEE DETAIL
G A
P 1/
2" M
IN
FASTEN GYPSUM BOARD TO STUD.
FASTENERS TO TRACK PROHIBITED.
MAINTAIN 1/2" GAP BETWEEN TOP OF
GYPSUM AND STRUCTURE ABOVE
SEALANT
GYPSUM
J BEAD
PROVIDE DEFLECTION TRACK AT
NON BEARING STUD WALLS
EXTENDING TO STRUCTURE ABOVE
UNLESS NOTED OTHERWISE.
MAINTAIN 1/2” GAP BETWEEN
TOP OF STUD AND TRACK ABOVE
G A
P 1/
2" M
IN
INSTALL DEFLECTION TRACK PER
MANUFACTURERS RECOMMENDATIONS
SEE
ASSEMBLY
TYPE
1/ 2"
M
IN
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
F-35 FUEL CELL MAINTENANCE FACILITY RENOVATION
021702
AECC511
/2 2/
:2 2:
P
M
JB
FG
BIDDER QUESTION
10/22/18
3" = 1'-0"
INTERIOR FRAMING DETAIL - PARTITION
DEFLECTION ATTACHMENT
3" = 1'-0"
INTERIOR ACOUSTIC DETAIL - PARTITION
DEFLECTION ATTACHMENT - NOT PARALLEL
TO FLUTES
9A
A810
9B A810
FRICTION FIT FIBERGLASS BATT
INSULATION TO FILL CAVITY
WHERE METAL DECK FLUTES
ARE NOT PARALLEL TO WALL
ASSEMBLY, SEE DETAIL
CONTINUOUS ACOUSTICAL SEALANT
FILL CAVITY WITH CONTINUOUS
ACOUSTICAL SEALANT TO ACCOMODATE
STRUCTURAL DEFLECTION
PROVIDE CONTINUOUS AIR TIGHT SEAL
AT WALL TERMINATION TO METAL DECK
AND ENTIRE WALL PERIMETER.
20 GAGE METAL CLOSURE PLATE.
SPAN METAL DECK FLUTE COMPLETELY
TO PROVIDE CONTINUOUS SEAL
1" MIN, TYP
1" MIN
TYP
METAL DECK PER STRUCTURAL
PER
ASSEMBLY
TYPE
PER
ASSEMBLY
TYPE
FOR TYPICAL
ANNOTATION
SEE DETAIL
AS REQ'D FOR
AIR TIGHT SEAL
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
F-35 FUEL CELL MAINTENANCE FACILITY RENOVATION
021702
AECC511
/2 2/
:2 2:
P
M
Designer
Author
BIDDER QUESTION
10/22/18
9C
A810 3" = 1'-0"
INTERIOR ACOUSTIC DETAIL - PARTITION
DEFLECTION ATTACHMENT - PARALLEL TO
FLUTES
A - TYPICAL
1. ASSEMBLIES ARE DIAGRAMS ONLY, DO NOT SCALE.
2. ASSEMBLIES ARE INTENDED TO DESCRIBE MATERIALS AND
THEIR RELATIONSHIP WITHIN A GIVEN CEILING, FLOOR, ROOF,
OR WALL. PENETRATIONS, JOINTS, FINISHES, AND
INTERSECTIONS BETWEEN ASSEMBLIES ARE NOT SHOWN.
3. SEE A0 SHEETS FOR ARCHITECTURAL NOTES, SHEET
SEQUENCE, AND ASSEMBLY TAG LEGENDS.
4. SEE A2 SHEETS FOR FLOOR PLAN ASSEMBLY LOCATIONS.
5. SEE A4 SHEETS FOR SECTION ASSEMBLY LOCATIONS.
6. SEE A5 SHEETS FOR EXTERIOR DETAILS.
7. SEE A8 SHEETS FOR INTERIOR ASSEMBLIES, INTERIOR
ASSEMBLY NOTES, AND INTERIOR DETAILS.
B - FRAMING
1. PROVIDE 20 GAGE METAL STUDS UNLESS NOTED
OTHERWISE.
2. EXTEND CONTINUOUS STUDS FROM FLOOR TO STRUCTURE
ABOVE UNLESS NOTED OTHERWISE.
3. PROVIDE MANUFACTURERS STANDARD DEFLECTION TRACK
AT NON-BEARING STUD WALLS EXTENDING TO STRUCTURE.
4. SPACE STUDS AT 24" ON CENTER FOR TYPICAL WALLS
UNLESS NOTED OTHERWISE.
5. SPACE STUDS AT 16" ON CENTER FOR WALLS WITH CERAMIC
TILE, MOISTURE RESISTANT GYPSUM, OR ABUSE/IMPACT
RESISTANT GYPSUM UNLESS NOTED OTHERWISE.
6. PROVIDE BACKING AT ASSEMBLY MOUNTED ACCESSORIES,
EQUIPMENT, AND FIXTURES.
7. PROVIDE BACKING AT OWNER FURNISHED AND/OR OWNER
INSTALLED ASSEMBLY MOUNTED ACCESSORIES,
EQUIPMENT, AND FIXTURES.
C - SHEATHING
1. PROVIDE TYPE 'X' GYPSUM BOARD PER SPECIFICATIONS.
2. PROVIDE CONTINUOUS GYPSUM BOARD FROM FLOOR TO
STRUCTURE ABOVE UNLESS NOTED OTHERWISE.
3. PROVIDE GAP AT DEFLECTION TRACK PER MANUFACTURER
RECOMMENDATION. COORDINATE FIRE RATED AND SOUND
RATED CONDITIONS.
4. SEAL THROUGH WALL PENETRATIONS AT BOTH ABOVE
CEILING AND BELOW CEILING CONDITIONS.
5. PROVIDE CONTROL JOINTS IN GYPSUM BOARD AT 30'-0"
MAXIMUM SPACING OR PER UNITED STATES GYPSUM
ASSOCIATION.
D - EXTERIOR FINISHES
1. SEE MATERIAL SCHEDULE FOR FINISH INFORMATION
2. SEE ROOM SCHEDULE FOR INTERIOR FINISHES.
E - WATER RESISTANT ASSEMBLIES
1. PROVIDE MOISTURE RESISTANT GYPSUM BOARD WITHIN 4'-0"
OF PLUMBING FIXTURES.
2. PROVIDE MOISTURE RESISTANT GYPSUM BOARD IN JANITOR
ROOMS.
3. PROVIDE MOISTURE RESISTANT GYPSUM BOARD AT HEAD,
JAMB, AND SILL CONDITIONS OF EXTERIOR OPENINGS.
F - FIRE RATED ASSEMBLIES
1. SEE G1 SHEETS FOR CODE INFORMATION, CODE PLAN, AND
LOCATION OF FIRE RATED ASSEMBLIES.
2. ASSEMBLIES WITH GA FILE NUMBER SHALL BE
CONSTRUCTED IN ACCORDANCE WITH GYPSUM
ASSOCIATION GA-600-2015.
3. PROVIDE FIRE RESISTIVE RATED WOOD AND FIRE RESISTIVE
RATED PLYWOOD UNLESS NOTED OTHERWISE.
4. EXTEND CONTINUOUS FIRE RATED VERTICAL ASSEMBLIES
FROM TOP OF HORIZONTAL FIRE RATED ASSEMBLY BELOW
TO BOTTOM OF HORIZONTAL FIRE RATED ASSEMBLY ABOVE.
5. FIRE STOP PENETRATIONS THROUGH FIRE RATED
ASSEMBLIES.
G - WEATHER BARRIERS
1. BARRIER / RETARDER CONTINUITY IS CRITICAL FOR THE
PERFORMANCE AND DURABILITY OF THE ASSEMBLY.
2. FLASHING, SEALING, AND INSULATING TRANSITION SPACES
ARE CRITICAL COMPONENTS OF WATER, AIR, AND THERMAL
BARRIER CONTINUITY.
3. WATER RESISTIVE BARRIER COMPONENTS MUST BE
INSTALLED IN A SHINGLE FASHION (WEATHER LAPPED),
FROM FOOTING TO ROOF, WITH SUFFICIENT OVERLAP AND
NO EXPOSED CORNERS. AVOID TRAPPING MOISTURE IN
TIGHT SPACES OR CREATING FLAT HORIZONTAL AREAS THAT
CAN COLLECT WATER.
4. SOME PRODUCTS CAN SIMULTANEOUSLY ACT AS A WATER
RESISTIVE BARRIER, AIR BARRIER, AND/OR A VAPOR
RETARDER.
5. SUBSTITUTING ASSEMBLY COMPONENTS WITHOUT
ARCHITECTS APPROVAL CAN DRASTICALLY ALTER THE
DURABILITY AND ENERGY PERFORMANCE OF THE ASSEMBLY.
EXTERIOR ASSEMBLY NOTES
WX-8A EXTERIOR WALL EXISTING
COMPOSITE INSULATION VALUE
EXTERIOR
3" METAL
WALL PANEL
2X4 TREATED
WOOD BLOCKING
(2) LAYERS 3 1/2"
RIGID INSULATION
EXISTING 8" CMU
INTERIOR
VAPOR BARRIER
NEW 8" CMU AT INFILL.
CONSTRUCT PER S001
INTERIOREXTERIOR
EXISTING CMU
METAL FLASHING
2X4 TREATED WOOD
BLOCKING
ALUMINUM WINDOW
WINDOW BLIND, TYPICAL
CONTINUOUS SEALANT AND
BACKER ROD
EXISTING 3" METAL
WALL PANEL
3/4" TREATED PLYWOOD
FILL SHIM SPACE WITH SPRAY
FOAM
WX-8A
1/2" SOLID SURFACE TRIM
GROUT SOLID
2X TREATED WOOD
BLOCKING
1/4" X 6" FLAT PHILLIPS
TAPCON CONCRETE
SCREW @ 12" O.C.
(STAGGARED
INTERIOR
EXTERIOR
NEW ALUMINUM WINDOW
PRE-FINISHED METAL FLASHING;
SEAL TO EXTERIOR OF METAL
WALL PANEL AND EXTEND INTO
WINDOW OPENING TO TERMINATE
BEHIND WINDOW FRAME
2X4 TREATED WOOD BLOCKING
CONTINUOUS SEALANT
AND BACKER ROD
3/4" TREATED PLYWOOD
FILL SHIM SPACE WITH
SPRAY FOAM
TREATED BLOCKING TO
MATCH THICKNESS OF
ADJACENT METAL PANEL
WX-8A
1/2" SOLID SURFACE TRIM
1/4" X 6" FLAT PHILLIPS TAPCON
CONCRETE SCREW @ 12" O.C.
(STAGGARED
2X TREATED WOOD BLOCKING
INTERIOREXTERIOR
EXISTING CMU
METAL FLASHING
2x TREATED WOOD
BLOCKING CUT TO SLOPE
NEW ALUMINUM
WINDOW
CONTINUOUS SEALANT
AND BACKER ROD
3" METAL WALL PANEL
3/4" TREATED PLYWOOD
FILL SHIM SPACE WITH
SPRAY FOAM 3/16" TAPCON ANCHORS
AT 8" OC, MIN 1-1/2"
CONCRETE EMBED
CONTINUOUS SEALANT
SOLID SURFACE SILL
A500
WX-8A
GROUT SOLID
2X TREATED WOOD
BLOCKING
1/4" X 6" FLAT
PHILLIPS TAPCON
CONCRETE SCREW @
12" O.C. (STAGGARED
WX-8A
INTERIOREXTERIOR
WINDOW AS SPECIFIED
WINDOW BLIND, TYPICAL
1/2" SOLID SURFACE TRIM
CONTINUOUS SEALANT
FILL SHIM SPACE
WITH SPRAY FOAM
CONTINUOUS BACKER
ROD AND SEALANT
PRE-FINISHED METAL FLASHING
INTERIOR
EXTERIOR
WINDOW AS SPECIFIED
PRE-FINISHED METAL FLASHING; SEAL TO
EXTERIOR OF METAL WALL PANEL AND
EXTEND INTO WINDOW OPENING TO
TERMINATE BEHIND WINDOW FRAME
TREATED BLOCKING TO MATCH
THICKNESS OF ADJACENT METAL PANEL
CONTINUOUS SEALANT AND BACKER ROD
1/2" SOLID SURFACE TRIM
FILL SHIM SPACE WITH SPRAY FOAM
WX-8A
CONTINUOUS SEALANT
WX-8A
INTERIOREXTERIOR
WINDOW AS SPECIFIED
CONTINUOUS SEALANT
1/2" TREATED PLYWOOD
BULL NOSED SOLID
SURFACE WINDOW SILL
FILL SHIM SPACE WITH
SPRAY FOAM
CONTINUOUS BACKER
ROD AND SEALANT
PRE-FINISHED METAL
FLASHING
A500
1"
/2
FINISH PER MATERIAL SCHEDULE
INTERIOR
EXTERIOR
WX-8A
FINISH PER ROOM SCHEDULE
PRE-FINISHED METAL JOINT WITH
SEALANT BEAD. MATCH EXISTING
METAL PANEL COLOR.
2x TREATED WOOD BLOCKING
2x4 TREATED WOOD BLOCKING
CONTINUE AIR BARRIER ONTO
FACE OF EXISTING WOOD
FRAMING 3" MINIMUM
MATCH EXISTING WX-8A
INTERIOREXTERIOR
METAL FLASHING
2x TREATED WOOD
BLOCKING CUT TO SLOPE
NEW ALUMINUM WINDOW
CONTINUOUS SEALANT
AND BACKER ROD
3/4" TREATED
PLYWOOD
FILL SHIM SPACE WITH SPRAY FOAM 3/16" TAPCON ANCHORS
AT 8" OC, MIN 1-1/2"
CONCRETE EMBED
CONTINUOUS SEALANT
SOLID
SURFACE SILL
A500
MATCH
EXISTING
WX-8A
D ate
P roject N o.
A rchite cts E n g in e ers S urve yo rs
C o lle g e R oa d F a irb an ks A
K
907.452.1241 designalaska.com
21 M A
Y
F T
Q W
18-0205
A E
C C
S ht.
O f
354th C ivil E ngineer S quadron
E ielson A
F B
, A laska
P roject E ngineer
C hief E ngineer D raw n B y
D esigned B y R eference N o.
R ev D e scription
B y
D ate
10/22/2018 2:25:05 PM
JB
EX TER
IO
R D
ETA ILS - AS SEM
BL Y TYPE S
A
Q C
F / M
L M
F -35 FUEL C ELL M
AINT ENANCE F ACILITY RE NO
VATIO
N
3" = 1'-0"A500
1 EXTERIOR WINDOW DETAIL - HEAD AT NEW OPENING
3" = 1'-0"A500
2 EXTERIOR WINDOW DETAIL - JAMB AT NEW OPENING
3" = 1'-0"A500
3 EXTERIOR WINDOW DETAIL - SILL AT NEW OPENING
3" = 1'-0"A500
4 EXTERIOR WINDOW DETAIL - HEAD AT EXISTING OPENING
3" = 1'-0"A500
5 EXTERIOR WINDOW DETAIL - JAMB AT EXISTING OPENING
3" = 1'-0"A500
6 EXTERIOR WINDOW DETAIL - SILL AT EXISTING OPENING
6" = 1'-0"A500
7 INTERIOR CASEWORK DETAIL - SOLID SURFACE EDGE
AKAF AL
TS
TA E O
49 TH
S
JAMES D. BARTLETT
No. A10413
D E S I G N
A L
A S
K A
REG ISTERED PROFESSIONAL ARCHITE
CT10/22/18
3" = 1'-0"A500
8 EXTERIOR PLAN DETAIL - DOOR AND WINDOW INFILL
3" = 1'-0"A500
9 EXTERIOR WINDOW DETAIL - SILL AT DOOR INFILL
| 05 50 13 |
| MISCELLANEOUS METAL FABRICATIONS |
| 05 50 13 - MISCELLANEOUS METAL FABRICATIONS |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 SUBMITTALS |
| PART 2 PRODUCTS |
| 2.1 MATERIALS |
| 2.1.1 Gratings |
| PART 3 EXECUTION |
| 3.1 GENERAL INSTALLATION REQUIREMENTS |
| 3.2 WORKMANSHIP |
| 06 10 00 |
| ROUGH CARPENTRY |
| 06 10 00 - ROUGH CARPENTRY |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 SUBMITTALS |
| 1.3 DELIVERY AND STORAGE |
| 1.4 GRADING AND MARKING |
| 1.4.1 Lumber |
| 1.4.2 Plywood |
| 1.4.3 Structural-Use and OSB Panels |
| 1.4.4 Preservative-Treated Lumber and Plywood |
| 1.5 SIZES AND SURFACING |
| 1.6 MOISTURE CONTENT |
| 1.7 PRESERVATIVE TREATMENT |
| 1.8 CERTIFICATIONS |
| 1.8.1 Certified Wood Grades |
| 1.8.2 Indoor Air Quality Certifications |
| 1.8.2.1 Adhesives and Sealants |
| PART 2 PRODUCTS |
| 2.1 MATERIALS |
| 2.1.1 Virgin Lumber |
| 2.2 LUMBER |
| 2.2.1 Framing Lumber |
| 2.3 PLYWOOD, STRUCTURAL-USE, AND ORIENTED STRAND BOARD OSB PANELS |
| 2.3.1 Wall Sheathing |
| 2.3.1.1 Plywood |
| 2.4 ROUGH HARDWARE |
| 2.4.1 Bolts, Nuts, Studs, and Rivets |
| 2.4.2 Lag Screws and Lag Bolts |
| 2.4.3 Wood Screws |
| 2.4.4 Nails |
| 2.4.5 Buck Anchors |
| 2.4.6 Metal Framing Anchors |
| PART 3 EXECUTION |
| 3.1 INSTALLATION |
| 3.1.1 Wall Sheathing |
| 3.1.1.1 Plywood, Structural-Use, and OSB Panel Wall Sheathing |
| 3.2 MISCELLANEOUS |
| 3.2.1 Wood Blocking |
| 3.2.2 Wood Furring |
| 3.2.3 Temporary Closures |
| 07 27 19.01 |
| SELF-ADHERING AIR BARRIERS |
| 07 27 19.01 - SELF-ADHERING AIR BARRIERS |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 SUBMITTALS |
| 1.3 MISCELLANEOUS REQUIREMENTS |
| 1.3.1 Product Data |
| 1.4 DELIVERY, STORAGE, AND HANDLING |
| 1.4.1 Delivery |
| 1.4.2 Storage |
| 1.5 ENVIRONMENTAL CONDITIONS |
| 1.5.1 Temperature |
| 1.5.2 Exposure to Weather and Ultraviolet Light |
| PART 2 PRODUCTS |
| 2.1 SELF-ADHERING AIR BARRIER |
| 2.1.1 Physical Properties |
2.2 PRIMERS, ADHESIVES, AND MASTICS
| PART 3 EXECUTION |
| 3.1 EXAMINATION |
| 3.2 PREPARATION |
| 3.3 INSTALLATION |
| 3.3.1 Installation of Self-adhering Air Barrier |
| 3.4 PROTECTION AND CLEANING |
| 3.4.1 Protection |
| 3.4.1.1 Adjacent Surfaces |
| 3.4.1.2 The Air Barrier Assembly |
3.4.2 Cleaning
| BIDDER QUESTION_A500 and A810 DETAILS |
| Sheets |
| B001 - BIDDER QUESTION |
| B002 - BIDDER QUESTION |