About this file
This is a set of architectural/engineering drawings and notes for the Fire House Generator replacement project at Fermi National Accelerator Laboratory. The document includes a foundation plan, floor plan, room finish schedule, door schedule, and detailed technical specifications for electrical and generator installations.
The drawings show specific requirements including a ground ring that must be 500 MCM copper and 30" deep with two ground rods and exothermic weld connections. There are notes regarding the removal of the current Automatic Transfer Switch (ATS) and rerouting of 480V power directly to a new ATS, with specifications for how the load side can enter the 120V transformer. The document includes photographs showing the desired connection point for the building regulator, existing electrical equipment configuration, and designated installation area for the generator annunciator panel and e-stop. Pad specifications indicate a thickness of 1'-10" with 12" of CA-7 Stone under concrete, though exact pad size is to be determined by equipment specifications.