Exhibit_E,_Construction_Plans,_26-B-28SR.pdf
PDF 10 MB Posted
- Solicitation number
- 26-B-28SR
- Issued by
- Volusia County, Florida
About this file
This file comprises construction plans and technical drawings prepared by TransSystems Corporation Consultants for the County of Volusia, Department of Public Works, for the Taylor Road Bridge Rehabilitation project (Bridge No. 794009) over Spruce Creek in Port Orange, Florida. The project involves the fabrication and installation of a crutch bent at intermediate Bent 2 to remove weight restrictions, along with scour countermeasures including pile installation (HP 14X102 steel H-piles with concrete encasement), a reinforced concrete pile cap, elastomeric bearings, and fabric-formed concrete revetment with filter point fabric and rock rubble. The work scope includes erosion control measures, stormwater pollution prevention, traffic maintenance, mobilization, maintenance of traffic control, and final as-built documentation. The project site is located at Bridge No. 794009, a 50-foot-long by 43-foot-wide structure with two 25-foot spans, and encompasses approximately 0.058 acres of soil disturbance limited to structural maintenance improvements and erosion protection.
The construction plans indicate design specifications conforming to the Florida Department of Transportation Standards (FDOT) dated July 2025, with structural analysis using LRFD methodology and HL-93 live loads. Environmental classification designates the substructure as moderately aggressive and superstructure as slightly aggressive based on soil testing and water quality analysis. Core boring data from location BB-01 extends to an 82-foot depth with NAVD88 vertical datum reference. The design includes a 100-year scour elevation of -0.8 feet with pile tips designed to achieve nominal bearing resistance of 100 tons per pile. Construction sequencing requires placement of erosion control devices prior to any work, with floating turbidity barriers mandated for water depths exceeding 3 feet during wet season operations. Contractor responsibilities include coordination with Florida Power & Light for overhead distribution lines located approximately 30 feet south of the bridge, compliance with Chapter 556 of the Florida Statutes for utility location, and restoration of all disturbed areas to their original condition upon project completion.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N
HAVE CHANGED DUE TO REPRODUCTION.
NOTE: THE SCALE OF THESE PLANS MAY
3:41:28 PM c:\transystems\pw_local\transyscorp-pw1\d1508499\KeySheet01.DGN11/4/2025
BEE LINE
EXPRESSWAY
F
LO
R
ID
A
STU
R N P
IK
E
PENSACOLA
FORT WALTON
BEACH
PANAMA
CITY
CHIPLEY
TALLAHASSEE
LAKE CITY 295
JACKSONVILLE
ST AUGUSTINE
GAINESVILLE
OCALA DAYTONA BEACH
DELAND
NEW PORT RICHEY
TAMPA
LAKELAND
MELBOURNE -
COCOA
ORLANDO
BARTOW
ST PETERSBURG
SARASOTA -
BRADENTON
FT PIERCE
FT MYERS
WEST
PALM
BEACH
FT LAUDERDALE
MIAMI
NAPLES
KEY WEST
STRUCTURE SHOP DRAWINGS
SHEET DESCRIPTIONSHEET NO.
ROAD AND BRIDGE DEPARTMENT
BRIDGE NO. 794009
VICINITY MAP
REVISIONS:
COUNTY OF VOLUSIA
PROJECT LOCATION
0 1 2
MILES
T17S
T16S
T17S
CONTRACT PLANS
INDEX OF PLANS
VOLUSIA COUNTY PROJECT MANAGER
STATEMENT OF WORK
CERTIFICATE OF AUTHORIZATION NO. 7503
VENDOR NO. 430839725
(954) 653-4700
FORT LAUDERDALE, FLORIDA 33309
3230 W. COMMERCIAL BLVD., SUITE 450
TRANSYSTEMS CORPORATION CONSULTANTS
PLANS PREPARED BY:
ROBERT FALK, P.E.
Public Works Department
PROJECT NO.
YEAR
FISCAL
NO.
SHEET
B-1
GOVERNING STANDARD SPECIFICATIONS:
RSQ NO.
(954) 653-4700
FORT LAUDERDALE, FLORIDA 33309
SUITE 450
3230 W. COMMERCIAL BLVD.
TRANSYSTEMS CORPORATION CONSULTANTS
NATALIE M. RODRIGUEZ, P.E. 70945
TO BE SUBMITTED TO:
T16S
R
E
R
E
R
E
R
E
20-SQ-119SR PC3691
BENT INSTALLATION AS SHOWN IN THE PLANS.
ABUTMENT/WINGWALLS AND BENT 2 CRUTCH
COUNTERMEASURES AT THE
OPERATIONS NECESSARY FOR SCOUR
AND MATERIALS AND PERFORMING ALL
FURNISHING ALL LABOR, EQUIPMENT, SUPPLIES,
THE WORK UNDER THIS CONTRACT INCLUDES
TAYLOR ROAD OVER SPRUCE CREEK
BRIDGE NO. 794009
TAYLOR ROAD BRIDGE REHABILITATION
VOLUSIA.
DECISION MAKING SHALL BE TAKEN TO MEAN THE COUNTY OF
REFERENCES TO FDOT OR ENGINEER RESPONSIBILITY FOR
HTTP://WWW.FDOT.GOV/PROGRAMMANAGEMENT/IMPLEMENTED/SPECBOOKS
CONSTRUCTION AT THE FOLLOWING WEBSITE:
STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE
FLORIDA DEPARTMENT OF TRANSPORTATION, JULY 2025
EXISTING PLANS
EXISTING CONDITION PHOTOS
REVETMENT DETAILS
REINFORCING BAR LIST
CRUTCH BENT CAP DETAILS
PEDESTAL DETAILS
BEARING DETAILS
CRUTCH BENT FRAMING PLAN AND SECTION
PILE DATA TABLE
CRUTCH BENT FOUNDATION LAYOUT
REPORT OF CORE BORINGS
CRUTCH BENT ELEVATION
STORMWATER POLLUTION PREVENTION PLAN
EROSION CONTROL PLAN
ELEVATION WITH WORK IDENTIFICATION
GENERAL PLAN WITH WORK IDENTIFICATION
GENERAL NOTES AND PAY ITEM NOTES (2 OF 2)
GENERAL NOTES AND PAY ITEM NOTES (1 OF 2)
SIGNATURE SHEET
KEY SHEET
BX-1 THRU BX-23
B-19
B-18
B-17
B-16
B-15
B-14
B-13
B-12
B-11
B-10
B-9
B-8
B-7
B-6
B-5
B-4
B-3
B-2
B-1
P
P P
S p r u c e C
A ir po rt R d.
Halifax Dr.
A ir po rt R d.
P
P
PORT ORANGE
Pop. 45,823
Area
Rest
Exit
Ta yl or R oa d
MANAGEMENT AREA
TOMOKA SOUTH WILDLIFE
St.
Charles
S am su la
D r.
AIRPORT
CREEK
SPRUCE
T om oka F arm s R oad
SIGNED AND SEALED BY:
THIS ITEM HAS BEEN DIGITALLY
NATALIE M. RODRIGUEZ, P.E. NO. 70945
FORT LAUDERDALE, FL 33309
3230 W. COMMERCIAL BLVD., SUITE 450
TRANSYSTEMS CORPORATION CONSULTANTS
WITH RULE 61G15-23.004, F.A.C
RESPONSIBLE FOR THE FOLLOWING SHEETS IN ACCORDANCE
THE ABOVE NAMED PROFESSIONAL ENGINEER SHALL BE
SIGNED AND SEALED BY:
THIS ITEM HAS BEEN DIGITALLY
WITH RULE 61G15-23.004, F.A.C
RESPONSIBLE FOR THE FOLLOWING SHEETS IN ACCORDANCE
THE ABOVE NAMED PROFESSIONAL ENGINEER SHALL BE
STATE OF
R E
E
NI
G
NE LANOI
S S
E
F O
R P
ESNECI
L
A
DIROL
F
Z E
U
GI
RDOR .M EIL
A
T A
N No 70945
STATE OF
R E
E
NI
G
NE LANOI
S S
E
F O
R P
ESNECI
L
A
DIROL
F
LL
IH .M NIVE
K
No 72949
ANY ELECTRONIC COPIES
SIGNATURES MUST BE VERIFIED ON
ON THE DATE ADJACENT TO THE SEAL
ANY ELECTRONIC COPIES
SIGNATURES MUST BE VERIFIED ON
ON THE DATE ADJACENT TO THE SEAL
KEVIN M. HILL, P.E. NO. 72949
SUNRISE, FL 33351
5389 N. NOB HILL ROAD
AREHNA ENGINEERING, INC.
B-2
SIGNATURE SHEET
DRAWN BY:
RJL
CHECKED BY:
NMR
DESIGNED BY:
JPD
CHECKED BY:
NMR
TRANSYSTEMS CORPORATION CONSULTANTS
3230 W. COMMERCIAL BLVD., SUITE 450
FORT LAUDERDALE, FLORIDA 33309
NATALIE M. RODRIGUEZ, P.E.
P.E. NO. 70945
DESCRIPTIONBYDATE
REVISIONS
DESCRIPTIONBYDATE
SHEET TITLE:
PROJECT NAME:
SIGNATURE SHEET
BRIDGE NO. 794009
REF. DWG. NO.
SHEET NO.
B-2
REPORT OF CORE BORINGS
SIGNATURE SHEET
SHEET DESCRIPTION
B-10
B-2
SHEET NO.
BRIDGE REHABILITATION
TAYLOR ROAD OVER SPRUCE CREEK
EXISTING CONDITION PHOTOS
REVETMENT DETAILS
REINFORCING BAR LIST
CRUTCH BENT CAP DETAILS
PEDESTAL DETAILS
BEARING DETAILS
CRUTCH BENT FRAMING PLAN AND SECTION
PILE DATA TABLE
CRUTCH BENT FOUNDATION LAYOUT
CRUTCH BENT ELEVATION
STORMWATER POLLUTION PREVENTION PLAN
EROSION CONTROL PLAN
ELEVATION WITH WORK IDENTIFICATION
GENERAL PLAN WITH WORK IDENTIFICATION
GENERAL NOTES AND PAY ITEMS (2 OF 2)
GENERAL NOTES AND PAY ITEMS (1 OF 2)
SIGNATURE SHEET
KEY SHEET
SHEET DESCRIPTION
B-19
B-18
B-17
B-16
B-15
B-14
B-13
B-12
B-11
B-9
B-8
B-7
B-6
B-5
B-4
B-3
B-2
B-1
SHEET NO.
Natalie M Rodriguez
2025.11.04 16:21:59-05'00'
Kevin M Hill
2025.11.04 16:14:23 -05'00'
T H
E
O F
F I
C I
A L
R
C O
I
S
E E
T
E C
T R
O N
C
G I
T A
L
Y
G N
A L
U
D
L E
G
A
C
BRIDGE NO. 794009
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
REVISIONS
DATE BY DESCRIPTION DATE BY DESCRIPTION
rllogan 11/3/2025 6:30:39 PM c:\transystems\pw_local\transyscorp-pw1\a-e_rllogan\d1508499\B1GeneralNotes01.dgn
P.E. NO. 70945
3230 W. COMMERCIAL BLVD., SUITE 450
TRANSYSTEMS CORPORATION CONSULTANTS
FORT LAUDERDALE, FLORIDA 33309
RJL
JPD
NMR
NATALIE M. RODRIGUEZ, P.E.
NMR
DESIGN SPECIFICATIONS
GOVERNING STANDARDS AND CONSTRUCTION SPECIFICATIONS
DESIGN BULLETINS, AS APPLICABLE.
FDOT DESIGN MANUAL DATED JANUARY 2025, AND SUBSEQUENT ROADWAY 3.
DESIGN SPECIFICATIONS, 10TH EDITION.
OFFICIALS (AASHTO) LOAD AND RESISTANCE FACTOR (LRFD) BRIDGE
AMERICAN ASSOCIATION OF STATE HIGHWAY AND TRANSPORTATION 2.
STRUCTURES DESIGN BULLETINS, AS APPLICABLE.
FDOT STRUCTURES MANUAL DATED JANUARY 2025, AND SUBSEQUENT 1.
VERTICAL DATUM
VERTICAL DATUM 1988 (NAVD 88).
ELEVATIONS SHOWN IN THE PLANS ARE BASED ON THE NORTH AMERICAN
ENVIRONMENTAL CLASSIFICATION
SUBSTRUCTURE: MODERATELY AGGRESSIVE
SUPERSTRUCTURE: SLIGHTLY AGGRESSIVE
DESIGN METHODOLOGY
OPERATIONAL IMPORTANCE FACTOR IS 1.0.2.
STRENGTH, SERVICE, EXTREME EVENT, AND FATIGUE LIMIT STATES.
LOAD AND RESISTANCE FACTOR DESIGN (LRFD) METHOD USING APPLICABLE 1.
STRUCTURAL ANALYSIS PROGRAM
FB-MULTIPIER VERSION 6.0.0
DESIGN LOADING
SEASONAL VARIATION: MEAN TEMPERATURE
TEMPERATURE RISE FROM MEAN
STEEL ONLYITEM
70 °F
50 °F
TEMPERATURE FALL FROM MEAN 40 °F
90 °FTEMPERATURE RANGE
COEFFICIENT OF THERMAL EXPANSION 0.0000065/°F
MATERIALS
OF THE SPECIFICATIONS SHALL AMENDED TO MEAN THE COUNTY OF VOLUSIA.
CONTRACT DOCUMENTS. THE DEFINITION OF THE DEPARTMENT IN ARTICLE 1-3
SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION, AS AMENDED BY
REVISED INDEX DRAWINGS AS APPENDED HEREIN, AND JULY 2025 STANDARD
FLORIDA DEPARTMENT OF TRANSPORTATION, FY 2025-26 STANDARD PLANS AND
PLAN DIMENSIONS AND GENERAL NOTES
STEEL FABRICATION
WELDING
BOLTED CONNECTIONS
PAINTING
GENERAL NOTES AND PAY ITEM NOTES (1 OF 2)
WEATHERING STEEL IS TO REMAIN UNCOATED.1.
VEGETATION.
CONTRACTOR SHALL USE CARE TO MINIMIZE DISTURBANCE TO SURROUNDING
INTERFERES WITH THE SCOUR COUNTERMEASURES INSTALLATION. THE
DEBRIS, VEGETATION, EXISTING SILT AND DIRT WHICH DIRECTLY
REMOVE AND DISPOSE OF OFF-SITE ANY EXISTING SUBMERGED OR SURFACE 5.
COMMENCING ANY CONSTRUCTION ACTIVITIES.
ACCOMPLISHING THE WORK TO THE ENGINEER FOR APPROVAL PRIOR TO
SUBMIT A DETAILED WORK PLAN OUTLINING METHODS AND PROCEDURES FOR 4.
AND FIT OF THEIR WORK.
CLAIMS. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR FABRICATION
FAILURE TO FIELD VERIFY DIMENSIONS WILL NOT BE JUSTIFICATION FOR 3.
NOTIFY THE ENGINEER OF ANY DISCREPANCIES.
ALL DIMENSIONS AND CONDITIONS REQUIRED TO PERFORM THE WORK AND
AS-BUILT CONDITIONS. CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING
AND LIMITED FIELD INVESTIGATIONS AND MAY NOT REPRESENT THE
DETAILED IN THE ORIGINAL CONSTRUCTION PLANS OF THE EXISTING BRIDGE
AND WATERLINE ELEVATIONS SHOWN ARE BASED ON THE INFORMATION AS
DIMENSION VERIFICATION: UNLESS OTHERWISE NOTED, THE DIMENSIONS 2.
HORIZONTALLY OR VERTICALLY UNLESS OTHERWISE NOTED.
ALL DIMENSIONS IN THESE PLANS ARE MEASURED IN FEET EITHER 1.
A. UNIFORM TEMPERATURE IN ACCORDANCE WITH SDG SECTION 2.7.1.
DESIGN TEMPERATURES:4.
SECTION 2.4. FOR VOLUSIA COUNTY, THE DESIGN WIND SPEED IS 150 MPH.
WIND LOADS ARE IN ACCORDANCE WITH AASHTO SECTION 3.8 AND SDG
WIND LOAD:3.
STRUCTURAL STEEL, 490 PCF
ASPHALT WEARING SURFACE, 140 PCF
REINFORCED CONCRETE, 150 PCF
DEAD LOADS:2.
HL-93 WITH DYNAMIC LOAD ALLOWANCE
LIVE LOADS:1.
A. BEARINGS
AASHTO/AWS D1.5 BRIDGE WELDING CODE:
MEMBERS IN ACCORDANCE WITH THE CURRENT EDITION OF THE
THE FOLLOWING MEMBERS ARE CLASSIFIED AS ANCILLARY 5.
EXPENSE.
BEARINGS DAMAGED BY FIELD WELDING AT THE CONTRACTOR'S
WHEN FIELD WELDING SOLE PLATES TO GIRDER FLANGES. REPLACE
D1.5 FOR NON-ANCILLARY ITEMS. AVOID DAMAGE TO BEARINGS
FIELD WELDING SHALL BE PER REQUIREMENTS OF AASHTO/AWS 4.
TO THE ENGINEER FOR APPROVAL.
ATTACHING ERECTION HARDWARE SHALL BE FORMALLY SUBMITTED
FIELD WELDING TO ANY STRUCTURAL STEEL FOR THE PURPOSE OF 3.
FOR FILLET WELDS SHALL BE FEXX = 70KSI.
FOR GRADE 50W BASE METAL. THE WELD FILLER METAL STRENGTH 2.
2025 EDITION OF THE AASHTO/AWS D1.5 BRIDGE WELDING CODE.
PERFORM NON-DESTRUCTIVE TESTING ON WELDS AS REQUIRED BY 1.
B-3
C. POLYVINYL CHLORIDE (PVC)
B. SCHEDULE 80
A. UV- RESISTANT
CLEAR DIMENSION IS NOTED TO FACE OF CONCRETE.
OF REINFORCING STEEL ARE TO CENTERLINE OF BAR EXCEPT WHERE
ALLOWABLE TOLERANCES. ALL DIMENSIONS PERTAINING THE LOCATION
AS “MINIMUM COVER”. SEE SPECIFICATIONS SECTION 415 FOR
INCLUDE PLACEMENT AND FABRICATION TOLERANCES UNLESS SHOWN
B. CONCRETE COVER DIMENSIONS SHOWN IN THE PLANS DO NOT
A. CAST-IN-PLACE SUBSTRUCTURE, 4 INCHES
OTHERWISE NOTED.
B. PROVIDE ¾ INCH CHAMFERS ON ALL EXPOSED EDGES, UNLESS
A. CLASS IV CONCRETE, 5500 PSI MIN. 28-DAY COMPRESSIVE STRENGTH.
5. DRAINAGE PIPE:
CONCRETE COVER:4.
CONCRETE:3.
GRADE 60 CARBON STEEL PER SPECIFICATIONS SECTION 931.
REINFORCING STEEL:2.
ACCORDANCE WITH STANDARD SPECIFICATIONS SECTION 962.
SUBJECT TO TENSILE STRESSES AND SHALL BE TESTED IN
THE BOTTOM FLANGE AND WEB OF THE CRUTCH BENT GIRDERS ARE
B. CHAPPY V-NOTCH:
ASTM A709 GRADE 50W UNLESS OTHERWISE NOTED.
A. STRUCTURAL STEEL:1.
NORMAL TO THE TOP FLANGE.
ALL ENDS OF GIRDERS AND INTERMEDIATE STIFFENERS SHALL BE 2.
SPECIFICATIONS SECTION 460.
SHOP ASSEMBLIES ARE REQUIRED IN ACCORDANCE WITH 1.
FAYING SURFACES.
460 AND 560 OF THE SPECIFICATIONS FOR PREPARATION OF
DESIGNED WITH A CLASS B SURFACE CONDITION. SEE SECTIONS
BOLTED CONNECTIONS IDENTIFIED AS SLIP-CRITICAL ARE 4.
OTHERWISE.
ALL BOLTED CONNECTIONS ARE SLIP-CRITICAL UNLESS NOTED 3.
ALL BOLT HOLES MUST HAVE A DIAMETER OF Ǝ”. 2.
UNLESS OTHERWISE NOTED.
ASTM F3125 GRADE A325, TYPE 3 FOR ALL BOLTED CONNECTIONS,
USE Ɔ" DIAMETER HIGH-STRENGTH BOLTS IN ACCORDANCE WITH 1.
BRIDGE REHABILITATION
TAYLOR ROAD OVER SPRUCE CREEK
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
C
BRIDGE NO. 794009
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
REVISIONS
kjallali 11/4/2025 2:38:32 PM c:\transystems\pw_local\transyscorp-pw1\d1508499\B1GeneralNotes01.dgn
TRANSYSTEMS CORPORATION CONSULTANTS
FORT LAUDERDALE, FLORIDA 33309
RJL
JPD
NMR
UTILITIES
PROVIDING ACCESS FOR COUNTY
ENVIRONMENTAL NOTES
CONSTRUCTION STAGING AND WORK AREAS
RESTORATION OF DISTURBED AREAS
SATISFACTION.
DISTURBED AREAS TO THEIR ORIGINAL CONDITION TO THE COUNTY’S
THE COUNTY. AFTER COMPLETING CONSTRUCTION ACTIVITIES, RESTORE ANY
ANTICIPATED STAGING AREAS AND SUBMIT A REPORT WITH PHOTOGRAPHS TO
BEFORE STARTING CONSTRUCTION, DOCUMENT THE CONDITION OF ALL
SITE INSPECTION
COMPENSATION.
ANY SUCH REQUIREMENTS WILL NOT ENTITLE THE CONTRACTOR TO ADDITIONAL
AND LABOR REQUIRED BY THE CONTRACT DOCUMENTS. FAILURE TO ACCOUNT FOR
SOLELY RESPONSIBLE FOR INCLUDING IN THEIR BID ALL ITEMS, MATERIALS,
NATURE OF THE WORK REQUIRED UNDER THIS CONTRACT. THE CONTRACTOR IS
CURRENT CONDITION OF THE SITE AND TO DETERMINE THE EXTENT AND
VISIT THE PROJECT SITE PRIOR TO SUBMITTING A BID TO ASSESS THE
FINAL AS-BUILT DRAWINGS
CONSTRUCTED.
PROVIDE FINAL AS-BUILT PLANS WHICH INDICATE HOW THE PROJECT WAS
SCOPE OF WORK
PAY ITEM NOTES
FINAL INSPECTION
WITH THE COUNTY.
TWO WEEKS PRIOR TO COMPLETION OF THE PROJECT, SCHEDULE INSPECTION
GENERAL NOTES AND PAY ITEM NOTES (2 OF 2)
POLLUTION AND EROSION CONTROL
EMAIL: CHRISTOPHER.BUONANNI@FPL.COM
OFFICE: (407) 328-1911
FPL DISTRIBUTION CHRIS BUONANNI
LINES.
WITHIN THE OSHA-PRESCRIBED MINIMUM APPROACH DISTANCES TO THE
CONSTRUCTION WILL NOT BRING PEOPLE, EQUIPMENT, OR MATERIALS
TO OBTAIN INFORMATION ON THE SERVICE OF THESE LINES. ENSURE
APPROXIMATELY 30 FEET SOUTH OF THE BRIDGE. COORDINATE WITH FPL
OVERHEAD DISTRIBUTION LINES ARE PRESENT WITHIN THE RIGHT OF WAY,
PRIOR TO START OF CONSTRUCTION.
CALL FLORIDA AS REQUIRED BY CHAPTER 556 OF THE FLORIDA STATUTES
FOR UTILITIES ON AND AROUND THE STRUCTURE, CONTACT SUNSHINE ONE
MAINTAIN AND REPAIR EROSION AND SEDIMENT CONTROL DEVICES. 7.
COMPLETED.
START OF ANY CONSTRUCTION AND MAINTAINED UNTIL CONSTRUCTION IS
SITE. ALL EROSION CONTROL DEVICES MUST BE IN PLACE PRIOR TO THE
REMOVE ONSITE SEDIMENT PRIOR TO DISCHARGE OF RUNOFF FROM THE
OFFSITE RUNOFF FROM DISCHARGING ACROSS DISTURBED AREAS, AND
BE MAINTAINED TO MINIMIZE THE AMOUNT OF SOIL DISTURBED, PREVENT
CONTRACT PLANS SHEETS. THE EROSION AND SEDIMENT CONTROLS SHALL
EROSION AND SEDIMENT CONTROL MEASURES ARE SHOWN ON THE 6.
THE CHANNEL IS LESS THAN 3 FEET (DRY SEASON).
BARRIER SHALL BE SUBSTITUTED FOR FTB WHEN THE WATER DEPTH IN
EQUAL OR GREATER THAN 3 FEET (WET SEASON). STAKED TURBIDITY
(FTB) SHALL ONLY BE USED WHEN THE WATER DEPTH IN THE CHANNEL IS
BASED ON THE CONSTRUCTION SEASON. FLOATING TURBIDITY BARRIER
ADJUST WATER POLLUTION ABATEMENT AND SEDIMENT CONTROL MEASURES
CHANNEL BOTTOM IS PRONE TO INUNDATION DURING THE WET SEASON. 5.
CONTROL UPON COMPLETION OF THE PROJECT.
REMOVE ALL TEMPORARY MATERIALS USED FOR POLLUTION AND EROSION 4.
COUNTY IMMEDIATELY.
YOU ENCOUNTER CONTAMINATED SOIL OR GROUNDWATER, CONTACT THE
ETC.) FROM SPILLING INTO SURFACE WATERS. IF A SPILL OCCURS OR IF
WILL PREVENT POTENTIAL POLLUTANTS (FUEL, LUBRICANTS, HERBICIDES,
SPECIFY THE MANAGEMENT PRACTICES AND CONTAINMENT METHODS THAT
REPORTING, AND RESPONSE, AS REQUIRED BY THE SPECIFICATIONS.
EQUIPMENT AND MATERIALS, TOXIC SUBSTANCE AND SPILL CONTAINMENT
SUBMIT EROSION CONTROL PLAN TO THE COUNTY, INCLUDING STAGING OF 3.
THE WATER BODY AT ALL TIMES.
IMPACTS. PREVENT ANY DISCHARGE OR MATERIALS FROM FALLING INTO
MAINTAIN WATER QUALITY STANDARDS AND PREVENT ANY OFF-SITE 2.
ACTIVITIES.
FOLLOWING THE SPECIFICATIONS, BEFORE STARTING ANY CONSTRUCTION
SUBMIT THE POLLUTION CONTROL PLAN TO THE COUNTY FOR APPROVAL, 1.
DO NOT OPERATE OVERWEIGHT CONSTRUCTION VEHICLES ON THE BRIDGE. 2.
BE STORED ON THE BRIDGE.
COUNTY. MATERIALS, CONSTRUCTION EQUIPMENT, AND DEBRIS SHALL NOT
PROPOSED STAGING OR STORAGE AREAS SHALL BE APPROVED BY THE 1.
OPERATIONS.
RESTORE ANY WORK OR STAGING AREAS DAMAGED BY CONSTRUCTION 4.
CONTROL NECESSARY TO PERFORM THE ABOVE TASKS.
COORDINATE WITH THE COUNTY AND PROVIDE TEMPORARY TRAFFIC 3.
CONCRETE REVETMENT AS SHOWN ON SHEETS B-18 THROUGH B-19.
DISPOSAL OF MATERIALS FOR INSTALLATION OF FABRIC FORMED
FURNISH ALL LABOR, MATERIALS AND EQUIPMENT, REMOVAL AND 2.
AS SHOWN ON SHEETS B-9 THROUGH B-17.
FABRICATE AND INSTALL CRUTCH BENT AT INTERMEDIATE BENT 2 1.
B-4
MATERIAL, WHICH REMAINS HIS PROPERTY.
FEDERAL PERMITS RELATED TO THE REMOVAL AND DISPOSAL OF
MUST OBTAIN, AT HIS OWN COST, ALL NECESSARY LOCAL, STATE, AND
WITH ALL LOCAL, STATE, AND FEDERAL REQUIREMENTS. THE CONTRACTOR
PROPERLY DISPOSE OF ALL COLLECTED WASTE MATERIALS IN ACCORDANCE 3.
SITE.
REMOVE AND DISPOSE ALL CONSTRUCTION MATERIALS FROM THE PROJECT 2.
COUNTY.
DEBRIS THAT FALLS IN WATER AT NO ADDITIONAL EXPENSE TO THE
MATERIALS FROM ENTERING THE WATERWAY. IMMEDIATELY REMOVE
TAKE ALL RESPONSIBLE PRECAUTIONS TO PREVENT UNAUTHORIZED 1.
CONCRETE ENCASEMENT.
TO FURNISH AND INSTALL THE CRUTCH BENT PILES. INCLUDING THE
THIS PAY ITEM INCLUDES ALL MATERIALS, LABOR AND INCIDENTALS NECESSARY
ITEM 455-35 STEEL PILING, HP 14X102
ANCHOR RODS SHALL BE INCLUDED, AS PER PLAN, FOR PAYMENT.
THE LAMINATED ELASTOMERIC BEARINGS, INCLUDING THE LOAD PLATES AND
ALL MATERIALS, LABOR AND INCIDENTALS NECESSARY TO FURNISH AND INSTALL
ITEM 400-147 COMPOSITE NEOPRENE PADS
ACTIVE WORK AREAS.
MOVEMENT OF VEHICLES, PEDESTRIANS, AND BICYCLES AROUND STAGING AND
THIS PAY ITEM INCLUDES ALL WORK REQUIRED TO PROVIDE FOR SAFE
ITEM 102-1 MAINTENANCE OF TRAFFIC
LOCAL, STATE, AND FEDERAL ENVIRONMENTAL SAFETY REGULATIONS.
DEBRIS CONTAINMENT DEVICES, AND EROSION CONTROL MEASURES. ADHERE TO
TESTING, INCLUDING BUT NOT LIMITED TO SCAFFOLDING PLATFORMS, BARGES,
REQUIRED TO PROVIDE SAFE ACCESS FOR INSPECTION AND MATERIALS
THIS PAY ITEM INCLUDES THE COST OF THE ITEMS, EQUIPMENT, ETC.,
ITEM 101-1 MOBILIZATION:
BID ITEMS.
INDIVIDUAL BID ITEMS SHALL BE INCLUDED IN THE CONTRACT UNIT PRICE FOR
PAYMENT FOR INCIDENTAL ITEMS NOT SPECIFICALLY COVERED IN THE
INSPECTION OF THE PROJECT.
PROVIDE SAFE ACCESS FOR COUNTY PERSONNEL AT ALL TIMES FOR THEIR
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
C
S H
L D
R
L A
N E
S H
L D
R
L A
N E
¡ TAYLOR RD.
R/W LINE
¡ BRIDGE
(T Y P
R/W LINE
BARRIER (TYP.)
TURBIDITY
(TYP.)
12'-0"
O U
T T
O
O U
T
HEADWALL AND APRON
CONCRETE PIPE WITH
EXISTING REINFORCED
(TYP.)
CROSS BEAM
NEW STEEL
CONCRETE PILE CAP
NEW REINFORCED
FORMED REVETMENT
NEW FILTER POINT FABRIC
APPROXIMATE LOCATION OF WETLANDS
APPROXIMATE LOCATION OF WETLANDS
APPROXIMATE LOCATION OF WETLANDS APPROXIMATE LOCATION OF WETLANDS
BRIDGE NO. 794009
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
REVISIONS
kjallali 11/4/2025 2:33:41 PM c:\transystems\pw_local\transyscorp-pw1\d1508499\B1Plan01.dgn
TRANSYSTEMS CORPORATION CONSULTANTS
FORT LAUDERDALE, FLORIDA 33309
RJL
JPD
NMR
O P
E
:1
S L
O P
E
:1
S L
O P
E
:1
S L
O P
E
:1
BEGIN APPROACH SLAB BEGIN BRIDGE END BRIDGE END APPROACH SLAB
PLAN
NOTES:
WORK IDENTIFICATION:
LEGEND:
EXISTING STRUCTURE
PROPOSED STRUCTURE
A
BB
FABRIC FORMED REVETMENT
LIMITS OF ROCK RUBBLE AND FILTER POINT
REVETMENT
LIMITS OF FILTER POINT FABRIC FORMED
GENERAL PLAN WITH
WORK INDENTIFICATION
CC
EXISTING OVERHEAD ELECTRICAL
BB-01
BORING LOCATION
SHEETS B-9 THRU B-17 FOR DETAILS.
NEW CRUTCH BENT AT BENT 2. SEE
SHEET B-18.
2. FOR SECTIONS A-A, B-B AND C-C REFER TO
DOWNSTREAM SIDES OF THE BRIDGE.
STREAMBED ELEVATIONS ON THE UPSTREAM AND
A UNIFORM TRANSITION BETWEEN THE NATURAL
FOLLOWING REVETMENT INSTALLATION TO PROVIDE
INSTALLATION AND REPLACE FILL AS NECESSARY
1. EXCAVATE AS NECESSARY FOR REVETMENT
DEBRIS IN CONFLICT WITH REVETMENT INSTALLATION.
REMOVE AREAS OF PALMS, HEAVY VEGETATION,
A
B-5
REVETMENT. SEE SHEET B-18 FOR DETAILS.
8" FILTER POINT FABRIC FORMED
DETAILS.
NEW ROCK RUBBLE. SEE SHEET B-18 FOR
FIELD OBSERVED WETLAND BOUNDARIES
ABUTMENT 1 ABUTMENT 3
BENT 2
INDICATES WORK IDENTIFICATION
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
C
SPAN 1
25'-0"
50'-0"±
EL. 9.5
HIGH WATER
WATER EL. 5.4
EXISTING
SPAN 2
25'-0"
42 3 2 43
(TYP.)
CROSS BEAM
NEW STEEL
CONCRETE PILE CAP
NEW REINFORCED
CHANNEL BOTTOM
APPROXIMATE
¡ NEW CRUTCH BENT
¡ BENT 2
(TYP.)
WITH ENCASEMENT
NEW STEEL H-PILE
BRIDGE NO. 794009
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
REVISIONS
kjallali 11/4/2025 2:34:05 PM c:\transystems\pw_local\transyscorp-pw1\d1508499\B1Plan01.dgn
TRANSYSTEMS CORPORATION CONSULTANTS
FORT LAUDERDALE, FLORIDA 33309
RJL
JPD
NMR
ELEVATION
NOTES:
LEGEND:
E N
D
B
E N
T
E N
D
B
E N
T
EXISTING STRUCTURE
PROPOSED STRUCTURE
FORMED REVETMENT
LIMITS OF FILTER POINT FABRIC
POINT FABRIC FORMED REVETMENT
LIMIIT OF ROCK RUBBLE AND FILTER
ELEVATION WITH
WORK IDENTIFICATION
DOWNSTREAM SIDES OF THE BRIDGE.
STREAMBED ELEVATIONS ON THE UPSTREAM AND
A UNIFORM TRANSITION BETWEEN THE NATURAL
FOLLOWING REVETMENT INSTALLATION TO PROVIDE
INSTALLATION AND REPLACE FILL AS NECESSARY
1. EXCAVATE AS NECESSARY FOR REVETMENT
WORK IDENTIFICATION:
SHEETS B-9 THRU B-17 FOR DETAILS.
NEW CRUTCH BENT AT BENT 2. SEE
DEBRIS IN CONFLICT WITH REVETMENT INSTALLATION.
REMOVE AREAS OF PALMS, HEAVY VEGETATION,
# INDICATES WORK IDENIFICATION
B-6
REVETMENT. SEE SHEET B-18 FOR DETAILS.
8" FILTER POINT FABRIC FORMED
DETAILS.
NEW ROCK RUBBLE. SEE SHEET B-18 FOR
BARRIER (78 FT)
FLOATING TURBIDITY
BARRIER (78 FT)
FLOATING TURBIDITY
B-7
N
T
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
C
BRIDGE NO. 794009
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
REVISIONS
DATE BY DESCRIPTION DATE BY DESCRIPTION
kjallali 11/4/2025 10:20:28 AM c:\transystems\pw_local\transyscorp-pw1\d1519572\AERIAL.dgn
P.E. NO. 70945
3230 W. COMMERCIAL BLVD., SUITE 450
TRANSYSTEMS CORPORATION CONSULTANTS
FORT LAUDERDALE, FLORIDA 33309
rjl
JPD
NMR
NATALIE M. RODRIGUEZ, P.E.
NMR
BRIDGE REHABILITATION
EROSION CONTROL PLAN
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
C
BRIDGE NO. 794009
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
REVISIONS
kjallali 11/4/2025 2:47:53 PM c:\transystems\pw_local\transyscorp-pw1\d1519572\B1GeneralNotes01.dgn
TRANSYSTEMS CORPORATION CONSULTANTS
FORT LAUDERDALE, FLORIDA 33309
RJL
JPD
NMR
STORMWATER POLLUTION PREVENTION PLAN
SITE DESCRIPTION:1.0
NATURE OF CONSTRUCTION ACTIVITY:1.A
SEQUENCE OF MAJOR SOIL DISTURBING ACTIVITIES:1.B
AREA ESTIMATES:1.C
0.058 ACRESTOTAL AREA TO BE DISTURBED:
0.058 ACRESTOTAL SITE AREA:
RUNOFF DATA:1.D
SITE MAP:1.E
EROSION AND SEDIMENT CONTROLS:2.A
STORMWATER MANAGEMENT:2.B
OTHER CONTROLS:2.C
WASTE DISPOSAL:2.C.1
OFF-SITE VEHICLE TRACKING & DUST CONTROL:2.C.2
SEPTIC SYSTEMS.
AND LOCAL REGULATIONS FOR WASTE DISPOSAL, AND SANITARY SEWER OR
DESCRIBE THE PROPOSED PROCEDURES TO COMPLY WITH APPLICABLE STATE
IN THE SECTION 104 EROSION CONTROL PLAN, THE CONTRACTOR SHALL
SANITARY SEWER, OR SEPTIC TANK REGULATIONS:
STATE AND LOCAL REGULATIONS FOR WASTE DISPOSAL,2.C.3
MAINTENANCE:3.0
BEFORE THE FLOATING TURBIDITY BARRIER IS EXPIRED.
* FLOATING TURBIDITY BARRIER - PROJECT IS ANTICIPATED TO BE COMPLETED
INSPECTIONS:4.0
PROVIDE ADDITIONAL MEASURES, AS APPROVED BY THE ENGINEER.
SEDIMENT, AND PREVENT DISCHARGING POLLUTANTS, THE CONTRACTOR SHALL
STRUCTURAL PRACTICES ARE NOT SUFFICIENT TO MINIMIZE EROSION, RETAIN
IF INSPECTIONS INDICATE THAT THE INSTALLED STABILIZATION AND
THAT INDICATE ITEMS ARE NOT IN GOOD WORKING ORDER.
THE CONTRACTOR SHALL INITIATE REPAIRS WITHIN 24 HOURS OF INSPECTION
* LOCATIONS WHERE VEHICLES ENTER OR EXIT THE SITE.
* FLOATING TURBIDITY BARRIER
STORMWATER POLLUTION PREVENTION PLAN.
INSPECT THAT CONTROLS INSTALLED IN THE FIELD AGREE WITH THE LATEST
CONDUCTED AT LEAST ONCE EVERY MONTH. THE CONTRACTOR SHALL ALSO
SITES HAVE BEEN PERMANENTLY STABILIZED, INSPECTIONS SHALL BE
INSTALL AND MAINTAIN RAIN GAUGES AND RECORD THE DAILY RAINFALL. WHERE
STORM THAT IS 0.50 INCHES OR GREATER. TO COMPLY, THE CONTRACTOR SHALL
EVERY SEVEN CALENDAR DAYS AND WITHIN 24 HOURS OF THE END OF A
QUALIFIED PERSONNEL SHALL INSPECT THE FOLLOWING ITEMS AT LEAST ONCE
NON-STORMWATER DISCHARGES:5.0
APPROVED STATE AND LOCAL PLANS AND PERMITS:2.C.6
IMPACT COORDINATOR.
CONTACTED, WHO WILL THEN NOTIFY THE VOLUSIA COUNTY CONTAMINATION
CEASE IN THAT AREA. VOLUSIA COUNTY PROJECT ENGINEER SHALL BE
IF CONTAMINATED SOIL OR GROUNDWATER IS ENCOUNTERED, OPERATIONS SHALL
DISCHARGES.
PROPOSED MEASURES TO PREVENT POLLUTION OF THESE NON-STORMWATER
FROM FIRE FIGHTING ACTIVITIES). THE CONTRACTOR SHALL DESCRIBE THE
IDENTIFY ALL ANTICIPATED NON-STORMWATER DISCHARGES (EXCEPT FLOWS
IN THE SECTION 104 EROSION CONTROL PLAN, THE CONTRACTOR SHALL
BRIDGE IS 50 FT. LONG BY 43 FT. WIDE.
CREEK. THE PROJECT IS LOCATED AT BRIDGE NO. 794009, THE EXISTING
OF A CRUTCH BENT AT BENT 2 AT THE TAYLOR ROAD BRIDGE OVER SPRUCE
COUNTERMEASURES ALONG THE ABUTMENT AND WINGWALLS AND INSTALLATION
THIS PROJECT LOCATED IN VOLUSIA COUNTY, INVOLVES INSTALLATION OF SCOUR
B-8
LIMITS.
STRUCTURAL MAINTENANCE IMPROVEMENT. SEE SHEET B-5 FOR
SOIL DISTURBANCE IS LIMITED TO EROSION PROTECTION AND
* AREAS OF SOIL DISTURBANCE:
N/A. WORK IS LIMITED TO STRUCTURAL MAINTENANCE IMPROVEMENTS.
* APPROXIMATE SLOPES:
N/A. WORK IS LIMITED TO STRUCTURAL MAINTENANCE IMPROVEMENTS.
* DRAINAGE PATTERNS:
THESE CONSTRUCTION PLANS:
FOR THE PLAN SHEETS REFERENCED ARE IDENTIFIED ON THE KEY SHEET OF
OF THE REQUIRED INFORMATION IS DESCRIBED BELOW. THE SHEET NUMBERS
THE CONSTRUCTION PLANS ARE BEING USED AS THE SITE MAPS. THE LOCATION
240910-1.
ST. JOHNS RIVER WATER MANAGEMENT DISTRICT (SJRWMD) GENERAL PERMIT
RUNOFF COEFFICENTS: N/A
*DISCHARGE POINTS TO SURFACE WATERS: N/A
* SURFACE WATERS: SPRUCE CREEK
WORK IS LIMITED TO STRUCTURAL MAINTENANCE IMPROVEMENTS.
* AREAS TO BE STABILIZED: N/A
SHEET.
CONTROL ITEMS ARE PROVIDED IN THE EROSION CONTROL PLAN
LOCATIONS AND QUANTITIES OF TEMPORARY EROSION AND SEDIMENT
* LOCATIONS OF TEMPORARY CONTROLS:
WORK IS LIMITED TO STRUCTURAL MAINTENANCE IMPROVEMENTS.
* AREAS TO NOT BE DISTURBED: N/A
RECEIVING WATERS: N/A1.F
THE SWPPP IN THE SECTION 104 EROSION CONTROL PLAN.
THE CONTRACTOR IS SOLELY RESPONSIBLE FOR DOCUMENTING THIS PORTION OF
FERTILIZERS AND PESTICIDES: N/A2.C.4
TOXIC SUBSTANCES:2.C.5
MIGRATION, STORAGE, AND DISPOSAL OF THESE SUBSTANCES.
JOB AND PROVIDE A PLAN ADDRESSING THE GENERATION, APPLICATION,
PROVIDE A LIST OF TOXIC SUBSTANCES THAT ARE LIKELY TO BE USED ON THE
IN THE SEDIMENT AND EROSION CONTROL PLAN, THE CONTRACTOR SHALL
CONTROL PLAN.
DOCUMENTING THIS PORTION OF THE SWPPP IN THE SECTION 104 EROSION
MINIMIZE LOSS OF LOAD INTO THE AIR. THE CONTRACTOR IS RESPONSIBLE FOR
CONSTRUCTION VEHICLES WILL BE REQUIRED TO COVER THEIR LOADS TO
INSTALL FLOATING TURBIDITY BARRIER PER THE EROSION CONTROL PLAN.
PORTION OF THE SWPPP IN THE SECTION 104 EROSION CONTROL PLAN.
PRACTICES. THE CONTRACTOR IS RESPONSIBLE FOR DOCUMENTING THIS
SEQUENCE OF CONSTRUCTION AND THE USE OF STABILIZATION STRUCTURAL
THE FOLLOWING DISCUSSION DEFINES GENERAL GUIDELINES FOR THE
PROJECT PLANS.
4. CRUTCH BENT CONSTRUCTION: CRUTCH BENT SHALL BE INSTALLED PER
SHALL BE INSTALLED PER PROJECT PLANS.
3. SCOUR COUNTERMEASURES CONSTRUCTION: ALL SCOUR COUNTERMEASURES
THE SCOUR COUNTERMEASURES.
2. CLEARING AND GRUBBING, EARTHWORK REQUIRED FOR INSTALLATION OF
1. PLACEMENT OF ALL EROSION CONTROL DEVICES.
CONSTRUCTION ACTIVITIES IN THE SECTION 104 EROSION CONTROL PLAN.
CONTRACTOR TO CONTRACTOR. THE CONTRACTOR IS RESPONSIBLE FOR ALL
SEQUENCE FOR THE ENTIRE PROJECT CAN VARY SIGNIFICANTLY FROM
THIS DOCUMENT, AND IS APPROVED BY THE ENGINEER. THE DETAILED
EXCEEDS THE EROSION AND SEDIMENT CONTROL PRACTICES DESCRIBED IN
THE CONTRACTOR CAN PROPOSE AN ALTERNATIVE THAT IS EQUAL TO OR
THE FOLLOWING SEQUENCE OF MAJOR ACTIVITIES SHALL BE FOLLOWED UNLESS
LEGEND:
TYPICAL SECTION - WEST ELEVATION
T
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
"4 11'-4
SHOULDER
8'-0"
LANE
12'-0"
LANE
12'-0"
SHOULDER
8'-0"
"4 11'-4
"4 15'-3"2
142'-8"4 15'-3
¡ BEARING
¡ HP 14X102 (TYP.)
¡ BEARING
EL. 7.38
EL. 10.38
NEW CRUTCH BENT
¡ TAYLOR RD. AND
"4 16'-1012 @ 2'-5" = 29'-0""4
16'-10
EL. 5.4
WATER
EXISTING
NEW HP 14X102 (TYP.)
NEW HP 14X102 (TYP.)
PILES (TYP.)
PRESTRESSED
EXISTING
PILE ENCASEMENT (TYP.)
(M I N
2'-3"2'-3""2 124'-4"2
124'-42'-3"2'-3"
(M I N
EL. -0.8
100-YEAR SCOUR
CHANNEL BOTTOM OR
LOWER OF EXISTING
EL. -0.8
100-YEAR SCOUR
CHANNEL BOTTOM OR
LOWER OF EXISTING
SHEET B-13)
(TYP.) (SEE
DIAPHRAGM
INTERMEDIATE
PILE CAP (TYP.)
NEW CONCRETE
BEARING (TYP.)
NEW ELASTOMERIC
NEW W36X247
(SEE NOTE 1) (TYP.)
PEDESTAL "B"
NEW CONCRETE
(SEE NOTE 1) (TYP.)
PEDESTAL "A"
NEW CONCRETE
CAP EL. 14.10
TOP OF EXIST.
CAP EL. 12.63
BOT. OF EXIST.
CAP EL. 13.04
BOT. OF EXIST.
CAP EL. 14.35
TOP OF EXIST.
CAP EL. 14.01
TOP OF EXIST.
CAP EL. 12.52
BOT. OF EXIST.
BRIDGE NO. 794009
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
REVISIONS
kjallali 11/4/2025 10:22:51 AM c:\transystems\pw_local\transyscorp-pw1\d1508499\B1IntBentDet01.dgn
TRANSYSTEMS CORPORATION CONSULTANTS
FORT LAUDERDALE, FLORIDA 33309
RJL
JPD
NMR
CRUTCH BENT ELEVATION
WATER LINE
EXISTING STRUCTURE
PROPOSED STRUCTURE
B-9
PILE ENCASEMENT NOTES:
TOP BEVEL PER MANUFACTURER'S RECOMMENDATIONS.
PILE CAP AND THE TOP OF THE ENCASEMENT TO ALLOW FOR
PROVIDE ADEQUATE OFFSET BETWEEN THE BOTTOM OF THE 2.
APPROVED EQUAL TO THE LIMITS SHOWN ON THE PLAN.
ENCASEMENT SYSTEM, SUCH AS DENSO SEASHIELD OR
ONCE PILES ARE IN PLACE, FURNISH AND INSTALL PILE 1.
NOTES:
SEE NOTE 3
SEE NOTE 3
SEE NOTE 3
SEE NOTE 3
SEE NOTE 3
SEE NOTE 3
DISCREPANCY FROM ELEVATIONS SHOWN.
ERECTING CRUTCH BENT. NOTIFY ENGINEER OF ANY
VERIFY EXISTING BENT CAP ELEVATIONS PRIOR TO 3.
SHEET B-16.
FOR REINFORCED CONCRETE PILE CAP DETAILS SEE 2.
FOR CONCRETE PEDESTAL DETAILS SEE SHEET B-15.1.
Bore #
Latitude
Longitude
Elevation
Vertical Datum
Date
Driller
Hammer
Rig
BB-01
29.0840121
-81.0650003
18'
NAVD88
5/13/2025
J. BARRIOS
Auto
D50
14" ASPHALT
4" LIMEROCK BASE
BROWN TO GRAY FINE SAND (SP)
GRAY FINE SAND WITH SOME SHELL FRAGMENTS (SP)
GRAY SLIGHTLY SILTY FINE SAND (SP-SM)
GRAY FINE SAND WITH SOME SHELL FRAGMENTS (SP)
GRAY SLIGHTLY SILTY FINE SAND WITH TRACE LIMESTONE FRAGMENTS (SP-SM)
GRAY TO LIGHT GRAY SLIGHTLY SILTY FINE SAND (SP-SM)
LIGHT GRAY FINE SILTY SAND (SM)
GRAY FINE SAND WITH LITTLE TO SOME LIMESTONE FRAGMENTS (SP)
LIGHT BROWN LIMESTONE
LIGHT BROWN TO GRAY FINE SAND (SP)
LIGHT BROWN FINE SAND WITH TRACE LIMESTONE FRAGMENTS (SP)
Boring Terminated at Elev. -82ft
Casing Length 100ft
50/3
50/2
GRAY TO BROWN FINE SAND (SP)
GRAY TO BROWN FINE SAND WITH SILT (SP-SM)
GRAY TO BROWN FINE SAND (SP)
GRAY FINE SAND (SP)
GRAY SILTY SAND (SM)
E L E
V A
T I O
N
(F
E E
T
N A
V D
-5
-10
-15
-20
-25
-30
-35
-40
-45
-50
-55
-60
-65
-70
-75
-80
-85
E L E
V A
T I O
N
(F
E E
T
N A
V D
-5
-10
-15
-20
-25
-30
-35
-40
-45
-50
-55
-60
-65
-70
-75
-80
-85
LIGHT BROWN FINE TO COARSE SAND WITH FEW LIMEROCK FRAGMENTS (SP)
LEGEND
SAND
UNIFIED SOIL CLASSIFICATION SYSTEM (ASTM D 2488)
GROUP SYMBOL AS DETERMINED BY VISUAL REVIEW
SP
NUMBERS TO THE LEFT OF BORINGS INDICATE
SPT VALUE FOR 12 INCHES OF PENETRATION
(UNLESS OTHERWISE NOTED).
N
AREHNA PROJECT NO. B-20-060.01
SAFETY HAMMER
MEDIUM DENSE
AUTOMATIC HAMMER
GRANULAR MATERIALS-
SPT N-VALUE
GREATER THAN 24
LESS THAN 3
(BLOWS/FT.)
SPT N-VALUE
(BLOWS/FT.)
GREATER THAN 40
3 to 8
16 to 30
8 to 15
LESS THAN 1
3 to 6
1 to 3
6 to 12
24 to 40
8 to 24
12 to 24
CONSISTENCY
FIRM
SOFT
VERY STIFF
STIFF
SILTS AND CLAYS
VERY SOFT
4 to 8
2 to 4
RELATIVE DENSITY
LOOSE
DENSE
VERY DENSE
(BLOWS/FT.)
SPT N-VALUE
(BLOWS/FT.)
30 to 50
10 to 30
4 to 10
SPT N-VALUE
LESS THAN 2
VERY LOOSE
HARD GREATER THAN 30
LESS THAN 4
GREATER THAN 50
APPROXIMATE SPT BORING LOCATION
SILTY SAND
ASPHALT
LIMESTONE
GROUNDWATER TABLE
NUMBER OF BLOWS FOR 4 INCHES OF PENETRATION50/4
CASING
GRAVEL
SHELLY SAND
GRAVELLY SAND
SLIGHTLY AGGRESSIVE
(RESISTIVITY = 4,600 OHM-CM)
STEEL: MODERATELY AGGRESSIVE
CONCRETE: SLIGHTLY AGGRESSIVE
SUPERSTRUCTURE
SUBSTRUCTURE
SUBSTRUCTURE
7.8
0 PPM
90 PPM
9,000 OHM-CM
pH
SULFATES
CHLORIDES
RESISTIVITY
ENVIRONMENTAL CLASSIFICATION:
TEST RESULTS: SOIL
7.5
20 PPM
55 PPM
4,600 OHM-CM
WATER
NATURAL MOISTURE CONTENT (%)
FINES PASSING THE #200 STANDARD SIEVE (%)
w%
-200
Feet
100200
N
TAYLOR RD
BB-01
-200 = 10 w% = 27
Sample @ 14' to 16'
-200 = 20 w% = 33
Sample @ 53.5' to 55'
-200 = 41 w% = 45
Sample @ 73.5' to 75'
T
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
C
BRIDGE NO. 794009
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
REVISIONS
kjallali 11/4/2025 2:53:10 PM c:\transystems\pw_local\transyscorp-pw1\d1508499\B1Boring01.dgn
REPORT OF CORE BORINGS
P.E. NO. 72949
5389 N. NOB HILL ROAD
AREHNA ENGINEERING, INC.
SUNRISE, FLORIDA 33351
DG
AT
KH
KEVIN M. HILL, P.E.
KH
B-10
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
C
3'-6""2 124'-4"2
124'-43'-6"
(TYP.)
90°0'0" SQ. PILE (TYP.)
EXISTING 14"
UTILITES
OVERHEAD
EXISTING
EXISTING BENT 2 CAP
15'-1"±
¡ CRUTCH BENT
¡ BENT 2
(BENT 2S)
¡ NEW HP 14X102 (TYP.)
� NEW CRUTCH BENT
¡ TAYLOR RD.
(BENT 2N)
¡ NEW HP 14X102 (TYP.)
BRIDGE NO. 794009
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
REVISIONS
rllogan 11/3/2025 6:46:17 PM c:\transystems\pw_local\transyscorp-pw1\a-e_rllogan\d1508499\B1FoundLay01.dgn
TRANSYSTEMS CORPORATION CONSULTANTS
FORT LAUDERDALE, FLORIDA 33309
RJL
JPD
NMR
PLAN
LEGENDNOTES:
UTILITIES.
INFORMATION ABOUT OVERHEAD
3. REFER TO GENERAL NOTES FOR
ALONG ¡ PILES.
2. PILE SPACINGS ARE DIMENSIONED
1. ALL PILES TO BE DRIVEN PLUMB.
CRUTCH BENT FOUNDATION LAYOUT
PROPOSED STRUCTURE
TEST PILE LOCATION
B-11
EXISTING STRUCTURE
EXISTING OVERHEAD ELECTRICAL
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
C
BRIDGE NO. 794009
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
REVISIONS
kjallali 11/4/2025 10:27:56 AM c:\transystems\pw_local\transyscorp-pw1\d1508499\PILE DATA TABLE.dgn
TRANSYSTEMS CORPORATION CONSULTANTS
FORT LAUDERDALE, FLORIDA 33309
RJL
JPD
NMR
PILE DATA TABLE
DESIGN CRITERIAINSTALLATION CRITERIA PILE CUT-OFF ELEVATIONS
NUMBER
BENT
or
PIER
(in.)
SIZE
PILE
(tons)
RESISTANCE
BEARING
NOMINAL
(ft.)
ELEVATION
TIP
MINIMUM
(ft.)
ELEVATION
JET
REQUIRED
(ft.)
ELEVATION
PREFORM
REQUIRED
(tons)
LOAD
DESIGN
FACTORED
(tons)
DRAG
DOWN
(tons)
RESISTANCE
SCOUR
TOTAL
(tons)
RESISTANCE
SCOUR
NET
(ft.)
ELEVATION
SCOUR
100-YEAR
PILE 1 PILE 2 PILE 3 PILE 4
FACTORED DESIGN LOAD + NET SCOUR RESISTANCE + DOWN DRAG
Ø
= NOMINAL BEARING RESISTANCE
(tons)
LOAD
UPLIFT
DESIGN
FACTORED
Ø
M P
R E
S S I O
N
TABLE DATE 01/01/16
(tons)
RESISTANCE
UPLIFT
NOMINAL
Ø
P
L I F
T
2N
2S
PILE DATA TABLE
50 60HP 14x102 100 N/A -23 N/A N/A N/A N/A -0.8 0.75 N/A 8.38
HP 14x102 100 N/A -23 50 N/A N/A 60 N/A N/A -0.8 0.75 N/A
12 12
12 12
100% DYNAMIC TESTING IS REQUIRED AT ALL NEW PILES.
WHICHEVER IS DEEPER.
BELOW THE 100-YEAR SCOUR ELEVATION OR REQUIRED JET ELEVATION,
THE CONTRACTOR SHOULD NOT ANTICIPATE BEING ALLOWED TO JET PILES
NO JETTING WILL BE ALLOWED WITHOUT THE APPROVAL OF THE ENGINEER.
FOR DETERMINATION OF THE REQUIRED DRIVING RESISTANCE.
DIFFER FROM THOSE SHOWN ON THE TABLE, THE ENGINEER SHALL BE RESPONSIBLE
UNTIL THE PILE DRIVING IS COMPLETED. IF JETTING OR PREFORMING ELEVATIONS
LOWERED TO THE ELEVATION AND CONTINUE TO OPERATE AT THIS ELEVATION
WHEN A REQUIRED JETTING ELEVATION IS SHOWN, THE JET SHALL BE
MINIMUM TIP ELEVATION IS REQUIRED FOR LATERAL STABILITY.
INSTALLATION ACTIVITIES.
VERIFY LOCATION OF ALL UTILITIES PRIOR TO ANY PILE
STORM EVENT.
100-YEAR SCOUR ELEVATION - ESTIMATED ELEVATION OF SCOUR DUE TO THE 100 YEAR
TO THE SCOUR ELEVATION.
REQUIRED PREFORMED OR JETTING ELEVATION
RESISTANCE PROVIDED BY THE SOIL FROM THE
NET SCOUR RESISTANCE - AN ESTIMATE OF THE ULTIMATE STATIC SIDE FRICTION
RESISTANCE PROVIDED BY THE SCOURABLE SOIL.
TOTAL SCOUR RESISTANCE - AN ESTIMATE OF THE ULTIMATE STATIC SIDE FRICTION
(SPECIFY ONLY WHEN DESIGN REQUIRES UPLIFT CAPACITY).
THE 100 YEAR SCOUR ELEVATION TO RESIST PULLOUT OF THE PILE
UPLIFT RESISTANCE - THE ULTIMATE SIDE FRICTION CAPACITY THAT MUST BE OBTAINED BELOW
PILE INSTALLATION NOTES
(ft.)
LENGTH
PILE
TEST
B-12
8.38
8.38
8.38
8.38
8.38
8.38
8.38
CRUTCH BENT FRAMING PLAN
B
SECTION A-A
SECTION B-B
(TYP.)
(TYP.)
(TYP.)
LEGEND:
GIRDER ELEVATION
BA
A
NOTES:
WELD TERMINATION DETAIL
(T Y P
MILL TO BEAR
(M I N
T
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
C
"2 126'-7"2
126'-7
53'-3"
90°0'0"
9" 9"
"4 11'-8"4
11'-8
1'-10"
"2 13'-4
C I P
T
O P
P I N
G
"2 13'-4
(T Y P
M I N
(T Y P
(TYP.)
1" MIN.
¡ TAYLOR RD.
T O
P
F
L A
N G
E
E X I S
T I N
G
C
H A
N N
E L
B
E A
M
END CROSS FRAME (TYP.)
¡ BENT 2
¡ BEARING ¡ BEARING
W36X247
STIFFENER (TYP.)
" x 7" BEARING 4
¡ BEARING¡ BEARING
"2 1L5X5X
BOLTS (TYP.)
" Ø A325 8
¡ W36X247 (TYP.)
" (TYP.)2
1L5X5X
¡ BENT 2
(TYP.)
STIFFENER
" x 7" 4
BEAM STEM (TYP.)
EXISTING CHANNEL
STIFFENER (TYP.)
" x 7" BEARING 4
BEARING (TYP.)
ELASTOMERIC
7'-6"
16'-0""2 110'-7"2
110'-716'-0"
16'-0""2 110'-7"2
110'-716'-0"
(TYP.)
INT DIAPHRAGM
BACK OF NEAR SIDE ANGLE
" FILL PLATE WELDED TO THE 4
(TYP.)
FROM GIRDERS
DRAINAGE AWAY
REDIRECT
PIPE TO
DECK DRAINAGE
TO BRIDGE
ADD EXTENSION
54'-9"
¡ NEW W36X247
(T Y P
(T Y P
(TYP.)
"2
(TYP.)
"4
(TYP.)
"4
WELD (TYP.)
"4
3"
3"
"8
BENT CAP
CRUTCH
CONCRETE
(TYP.)
ANCHOR ROD
TYP.
"8
TYP.
"8
(TYP.)
(SEE NOTE 2)
CONCRETE PEDESTAL
(TYP.)
PIPE (TO REMAIN)
DECK DRAINAGE
EXISTING BRIDGE
MC18x42.7 DIAPHRAGM
EXISTING 14" SQ. PILE
(TYP.)
¡ W36X247
(TYP.)
STRENGTH BOLTS
" DIAMETER HIGH 8
(TYP.)
" x 7" STIFFENER 4
BRIDGE NO. 794009
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
REVISIONS
kjallali 11/4/2025 10:33:43 AM c:\transystems\pw_local\transyscorp-pw1\d1508499\B1IntBentDet02.dgn
TRANSYSTEMS CORPORATION CONSULTANTS
FORT LAUDERDALE, FLORIDA 33309
RJL
JPD
NMR
CRUTCH BENT FRAMING PLAN AND SECTION
Ð
EXISTING STRUCTURE
PROPOSED STRUCTURE
B-13
Ð
Ð
FOR BEARING DETAILS, SEE SHEET B-14. 3.
SHEET B-15.
FOR CONCRETE PEDESTAL DETAILS SEE 2.
FABRICATION.
SHOP DRAWINGS ARE REQUIRED FOR STEEL 1.
PLAN VIEW
SECTION A-A
NOTES
"2 110"2
1102" ℄ BEARING ASS ℄ GIRDE
SOLE PLATE
7" 7"
1'-2"
(T Y P
M I N
COVER (TYP.)
" ELASTOMER4
1 "
3 ~ 10 GAGE STEEL PLATES
" ELASTOMER COVER4
LAYER (TYP.)
SECTION A-A
(T Y P
10"
SOLE PLATE
¡ BEARING
¡ GIRDER &
BEARING PAD
ELASTOMERIC
BEARING PAD
ELASTOMERIC
W36x247
SIDES ONLY
" (TYP.)4
5" 5"
1'-0"
A
A
B B
SECTION B-B
SOLE PLATE
W36x247
W36x247
9"
BEARING PAD
ELASTOMERIC
(T Y P
M I N
¡ ANCHOR ROD
¡ BEARING &
(TYP.)
STIFFENER
BEARING
BEARING STIFFENER
(TYP.)
℄ ANCHOR  ℄ ANCHOR ℄ BEAR
* NOTE: END 1 = BENT 2N, END 2 = BENT 2S
COVER (TYP.)
" ELASTOMER4
3 ~ 10 GAGE STEEL PLATES
" ELASTOMER COVER4
LAYER (TYP.)
10"
SECTION B-B
1'-2"
"8 51 "8
SLOTTED HOLE DETAIL
℄ ANCHOR ℄ BEARI ℄ ANCHOR
"4
ANCHOR ROD DETAIL
REMOVAL
NUT TO PREVENT
TORQUE LOCKING
BEARING PAD
ELASTOMERIC
SOLE PLATE
W36x247
HOLE WITH GROUT
4" Ø PREFORMED
GROUT TUBE
(TYP.)
(SEE DETAIL)
ANCHOR ROD
(TYP.)
(SEE DETAIL)
ANCHOR ROD
(TYP.)
TWO HEAVY HEX NUTS
SWEDGE ANCHOR ROD WITH
" Ø F1554 GRADE 55 4
(TYP.)
(SEE DETAIL THIS SHEET)
SLOTTED HOLE
¡ ANCHOR ROD
¡ BEARING &
TOP OF CRUTCH BENT CAP
(TYP.)
SIDES ONLY
TOP OF CRUTCH BENT CAP
TOP OF CRUTCH BENT CAP
(TYP.)
FACE PER SPECIFICATION
CAULK FRONT AND BACK
DETAIL "C"
9"
M I
"8 1"16
DETAIL "C"
DETAIL "C"
2"
G
A P
IN ACCORDANCE WITH SPECIFICATION SECTION 962-11.
D. ANCHOR RODS, NUTS, AND WASHERS SHALL BE HOT DIP GALVANIZED
C. WASHERS: F436
B. HEAVY HEX NUTS: A563 GRADE DH
A. ANCHOR RODS: ASTM F1554 GRADE 55
BEARING ANCHORAGE MATERIALS: 5.
VULCANIZATION DURING THE MOLDING PROCESS.
THE STEEL SOLE PLATE SHALL BE BONDED TO THE ELASTOMER BY 4.
DURING WELDING.
CRAYONS SHALL BE USED TO MONITOR THE STEEL TEMPERATURE
BE KEPT TO BELOW 250 DEGREES F (12O DEGREES C). TEMPERATURE
THE TEMPERATURE OF THE STEEL ADJACENT TO THE BEARING MUST 3.
GRADE 35, TYPE 1.
2. STEEL PLATES IN BEARING PADS SHALL CONFORM TO ASTM A1011
FROM FDOT STANDARD PLANS INDEX 400-510, EXCEPT AS NOTED.
PSI, AND CONFORM TO ALL THE REQUIREMENTS OF THE TYPE AA PAD
NEOPRENE BEARING PADS SHALL HAVE A SHEAR MODULUS (G) OF 150 1.
T
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
C
BRIDGE NO. 794009
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
REVISIONS
kjallali 11/4/2025 11:54:31 AM c:\transystems\pw_local\transyscorp-pw1\d1508499\B1BearingDet01.dgn
TRANSYSTEMS CORPORATION CONSULTANTS
FORT LAUDERDALE, FLORIDA 33309
RJL
JPD
NMR
BEARING DETAILS
B-14
LOCATION
L W
NO.
REQ'D
4NEW CRUTCH BENT
BEARING PAD DATA TABLE
PAD
TYPE
AA MODIFIED
BEAM
TYPE
W36x247 1 AND 2
BEAM BEARING PAD
DIMENSION
1'-2"10"
END *
(SHOWING BEARING PAD ONLY)
(SHOWING BEARING PAD ONLY)
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
C
1'-0"
¡ DOUBLE TEE STEM
(BELOW STEMS OF WIDENING DOUBLE TEE BEAMS)
¡ W36
3"6"3"
¡ W36
3"5"5"3"
1'-4"
¡ SHEAR STUDS (TYP.) ¡ SHEAR STUDS (TYP.)
(BELOW STEMS OF ORIGINAL CHANNEL BEAMS)
4P01 (TYP.)
4P02 (TYP.)
SPA. = 1'-0"
4~4P02 @ 4"
¡ W36
"2 11'-4
¡ W36
4P01
4P02
SPA. = 8"
3~4P01 @ 4"
1'-0"
TOP FLANGE
BOT. OF W36
TOP FLANGE
BOT. OF W36
4P03 (TYP.)
6"
5"5"
"2 11'-4 1'-4"
SPA. = 1'-0"
4~4P03 @ 4"
SPA. = 1'-0"
4~4P03 @ 4"
STUD (TYP.)
HEADED SHEAR
" 4
1" DIA. X 24
4P034P03
(TYP.)
2" COVER
(TYP.)
2" COVER
(S
D O
U B
L E
T
E E
(N
D O
U B
L E
T
E E
(S
D O
U B
L E
T
E E
(N
D O
U B
L E
T
E E
STUD (TYP.)
HEADED SHEAR
" DIA. X 4" 4
¡ JOINT OR ¡ STEM
PEDESTAL "A"
PEDESTAL "B"
8"
8"
BRIDGE NO. 794009
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
REVISIONS
kjallali 11/4/2025 3:19:21 PM c:\transystems\pw_local\transyscorp-pw1\d1508499\B1IntBentDet04.dgn
TRANSYSTEMS CORPORATION CONSULTANTS
FORT LAUDERDALE, FLORIDA 33309
RJL
JPD
NMR
PEDESTAL DETAILS
B-15
PEDESTAL "A" PLAN
B
A
A
SECTION C-C
SECTION A-A
SECTION B-B
SECTION D-D
B D D
C
C
PEDESTAL "B" PLAN
NOTES:
FIELD-MEASURED PEDESTAL HEIGHT IS LESS THAN 3 INCHES.
MAINTAIN CONCRETE COVER. NOTIFY THE ENGINEER IF THE
HEIGHTS MAY VARY. FIELD-CUT 4P03 LEGS AS NECESSARY TO
ASSUMES ZERO CAMBER IN THE W36 CROSS GIRDER. ACTUAL
PEDESTAL HEIGHTS ARE BASED ON AVAILABLE SURVEY DATA AND 4.
CHANNEL BEAMS AND DOUBLE TEE BEAMS.
PEDESTALS SHALL PROVIDE BEARING FOR EXISTING PRECAST 3.
THE TOP AND SIDES OF THE CONCRETE PEDESTALS.
CONCRETE COVER FOR REINFORCEMENT BARS SHALL BE 2 INCHES ON 2.
BEAM STEM PRIOR TO CASTING CONCRETE PEDESTALS.
SPECIFICATION SECTION 700-11 TO BOTTOM OF EXISTING PRECAST
ADHERE ORGANIC FELT BOND BREAKER IN ACCORDANCE WITH 1.
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
C
6'-6"
ANCHOR BOLT (TYP.)
¡ HP 14 (TYP.)
¡ ANCHOR BOLT
E M
B E
D
¡ HP 14 (TYP.)
BOLT (TYP.)
¡ ANCHOR ¡ ANCHOR BOLT
¡ BEARING &
¡ CAP,
(T Y P
5B02
5B02
8B03 (TYP.)
5B01 (TYP.)
5B01
(TYP.)
9B04
(TYP.)
9B05
9B05
@ 6" SPACING
9B06
(TYP.)
8B03
(TYP.)
2 ~ 9B07
5B02
(TYP.)
2 ~ 9B06
(TYP.)
2 ~ 9B05
(TYP.)
2 ~ 9B04
5 ~ 9B04
@ 6" SPA.
5 ~ 9B04
(TYP.)
9B07
9B07
B
M A
X
S P
A
M A
X
S P
A
B
9B06
@ 6" MAX. SPA.
6 ~ 9B06
(TYP.)
5B09
13 ~ 5B01 EVENLY SPACED
6'-6"
1'-6"1'-9"1'-9"1'-6"
6'-6"
3'-6"
4'-6"
14 ~ 5B02 EVENLY SPACED
PILE (TYP.)
WITH 5B02 AT
8B03 LAPPED
¡ W36X247
¡ W36X247
HP 14 (TYP.)
3'-3" 3'-3"
(TYP.)
5B09
7'-6"
E M
B E
D
¡ BENT 2
BRIDGE NO. 794009
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
REVISIONS
kjallali 11/4/2025 11:06:58 AM c:\transystems\pw_local\transyscorp-pw1\d1508499\B1IntBentDet03.dgn
TRANSYSTEMS CORPORATION CONSULTANTS
FORT LAUDERDALE, FLORIDA 33309
RJL
JPD
NMR
CRUTCH BENT CAP DETAILS
PILE CAP PLAN
SECTION A-A
SECTION B-B
A
B
B
TOP REINFORCEMENT BOTTOM REINFORCEMENT
B-16
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
C
BRIDGE NO. 794009
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
REVISIONS
kjallali 11/4/2025 11:26:12 AM c:\transystems\pw_local\transyscorp-pw1\d1508499\B1ReinfBar.dgn
TRANSYSTEMS CORPORATION CONSULTANTS
FORT LAUDERDALE, FLORIDA 33309
RJL
JPD
NMR
REINFORCING BAR LIST
LENGTH
FT INSIZE DES BARS
NO TYP
BAR
STY B C D E F H J K N
ANGNOA G FT IN FR FT IN FR FT IN FR FT IN FR FT IN FR FT IN FR FT IN FR FT IN FR
MARK \
5 B08 5-10 4 1 5-10
5 B09 6-10 4 1 6-10
5 B01 12- 4 13 5 2- 4 6-10 0- 5 0- 5
5 B02 9-10 14 11 5-10 2- 0 2- 0
8 B03 5- 1 8 11 2- 2 0-11 2- 0
9 B05 6- 2 4 11 3- 0 1- 7 1- 7
9 B07 6- 3 4 11 3- 1 1- 7 1- 7
B-17
9 B04 6-10 9 1 6-10
9 B06 5-10 10 1 5-10
LOCATION PILE CAP NO. REQUIRED = 2
END OF LIST
LOCATION CROSS GIRDER PEDESTALS NO. REQUIRED = 2
4 P03 2- 0 104 11 1- 0 0- 6 0- 6
4 P01 1- 0 12 1 1- 0
4 P02 0- 8 16 1 0- 8
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
C
(M I N
WINGWALL
FRONT FACE OF
FILTER FABRIC
GEOTEXTILE
(M I N
FILTER FABRIC
GEOTEXTILE
ABUTMENT/PILE
FRONT FACE OF
6" (TYP.)
6" (TYP.)
NATURAL SLOPE
FORMED REVETMENT
POINT FABRIC
ARMORFORM FILTER
13'-0"
FILTER FABRIC
GEOTEXTILE
8'-0"5'-0"11"
(M I N
HEADWALL AND APRON
EXISTING CONCRETE
13'-0"
BEDDING STONE
ELEVATION
STREAMBED
NATURAL
(M I N
ELEVATION
STREAMBED
NATURAL
(M I N
BEDDING STONE
BEDDING STONE
9'-0"4'-0"
4'-0" 9'-0"
FORMED REVETMENT
FILTER POINT FABRIC
ABUTMENT/PILE AND
GROUT VOID BETWEEN
5'-0" 5'-0"
(M
I N
(M
I N
(TYP.)
(DITCH LINING)
RIPRAP RUBBLE
(DITCH LINING)
RIPRAP RUBBLE
(M I N
(M
I N
5'-0"
FORMED REVETMENT
POINT FABRIC
ARMORFORM FILTER
(DITCH LINING)
RIPRAP RUBBLE
REVETMENT
FABRIC FORMED
FILTER POINT
ARMORFORM
FABRIC FORMED REVETMENT
WINGWALL AND FILTER
GROUT VOID BETWEEN
FABRIC FORMED REVETMENT
WINGWALL AND FILTER
GROUT VOID BETWEEN
BRIDGE NO. 794009
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
REVISIONS
kjallali 11/4/2025 3:03:52 PM c:\transystems\pw_local\transyscorp-pw1\d1508499\B1MiscDet01.dgn
TRANSYSTEMS CORPORATION CONSULTANTS
FORT LAUDERDALE, FLORIDA 33309
RJL
JPD
NMR
LEGEND:
EARTH
FORMED REVETMENT
FILTER POINT FABRIC
NEW
EXISTING
SECTION A-A SECTION B-B
NOTES:
REVETMENT DETAILS
SECTION C-C
BEDDING STONE
REFER TO SHEET B-5.
2. FOR LOCATIONS OF SECTIONS A-A, B-B AND C-C
BE REPLACED (FILLED) WITHIN THE SAME WORKDAY.
1. ALL MATERIAL DISPLACED FOR EXCAVATION SHALL
CONCRETE
RIPRAP RUBBLE (DITCH LINING)
STREAMBED MATERIAL
B-18
F I
C I
C O
E E
T
E C
T R
O N
G I
T A
L
G N
A L
D
L E
G
A
C
BRIDGE NO. 794009
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
REVISIONS
rllogan 11/3/2025 7:05:46 PM c:\transystems\pw_local\transyscorp-pw1\a-e_rllogan\d1508499\B1MiscDet02.dgn
TRANSYSTEMS CORPORATION CONSULTANTS
FORT LAUDERDALE, FLORIDA 33309
RJL
JPD
NMR
VEGETATION AT NORTHWEST WINGWALL VEGETATION AT NORTHEAST WINGWALL VEGETATION AT SOUTHEAST WINGWALL
VEGETATION AND DRAINAGE PIPE AT SOUTHWEST WINGWALL NORTH ELEVATION SOUTH ELEVATION
EXISTING CONDITION PHOTOS
B-19
File details come from the government source that posted it. Updated .