Exhibit A.docx
DOCX document 15 KB Posted
- Attached to
- CHILLER AND VENTILATION MAINTENANCE
- Solicitation number
- ARFQ 0512 WSH2700000006 1
- Issued by
- Kanawha County, West Virginia
About this file
This is a Mandatory Exhibit A document outlining a bi-annual inspection and maintenance schedule for chiller and ventilation equipment maintenance services in West Virginia. The exhibit specifies detailed maintenance requirements for four categories of equipment: cooling towers, air-cooled chillers, water-cooled chillers, and exhaust fans. Cooling tower maintenance includes ten tasks ranging from cleaning the pan strainer and pan to checking water quality for biological contamination and inspecting fan blades. Air-cooled chiller maintenance requires three bi-annual tasks including condenser coil cleaning, fan blade inspection, and unit operation verification. Water-cooled chiller maintenance is the most extensive, encompassing eight tasks including water strainer cleaning, lubrication of control linkages and bearings, condenser tube inspection, oil sampling and analysis, compressor motor winding resistance measurement, and oil changes every 1,000 hours of operation per the Trane Oil Analysis Program. Exhaust fan maintenance requires four tasks including belt replacement, lubrication, fan inspection for cracks and vibrations, and operational verification.
The document does not contain information regarding pricing terms, set-asides, incumbent contractors, funding sources, response deadlines, contract award dates, or contract term and renewal options. This appears to be a performance specification document establishing the minimum maintenance standards and frequencies required of contractors performing chiller and ventilation maintenance services under the state and local contract opportunity.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| TCA.pdf | ||
| Exhibit B.xlsx | XLSX spreadsheet | |
| WV75 - Construction Bid Submission Review.pdf | ||
| WV36.pdf | ||
| WV43.pdf | ||
| RFQ Specifications.docx | DOCX document | |
| Exhibit C.xlsx | XLSX spreadsheet | |
| Bid Bond Form.pdf | ||
| Final_ARFQ_0512_WSH2700000006_1_WV_ARFQ_FORM.PDF | ||
| Bid Bond Instructions.pdf | ||
| BondPerform.pdf | ||
| Purchasing Affidavit.pdf | ||
| WV73 Drug Free Affidavit.pdf | ||
| BondLaborMat.pdf | ||
| WV72 Drug Free Coversheet.pdf | ||
| OSAFederalFundsContractClauseAddendum.pdf |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MANDATORY
Exhibit A Bi-Annual Inspection and Maintenance Schedule Cooling Tower Bi-Annual
1. Clean Pan Strainer
2. Clean and Flush Pan
3. Check and Adjust Float Valve
4. Check Vibration Switch
5. Check Water Distribution System for Proper Spray
6. Check Fan Blades for Cracks and Proper Balance
7. Lubricate all Bearings
8. Replace Belt (Spring) and Ensure Proper Tension / Operation
9. Clean Louvers and Fan Screens
10. Check Water Quality for Biological Contamination Air Cooled Chiller Bi-Annual
1. Clean Condenser Coils with coil cleaner and water
2. Inspect Fan Blades for Cracks, Vibration and Proper Operation
3. Check Unit for Proper Operation Compressor Amp Draw / Refrigerant Charge Water-Cooled Chiller Bi-Annual
1. Clean all water strainers in system
2. Lubricate the vane control linkage, bearings, and ball-joints
3. Lubricate the vane operator tang O-rings
4. Drain contents of rupture disk and purge discharge vent line drip leg
5. Inspect the condenser tubes for fouling and clean
6. Collect oil sample and submit to qualified lab for testing
7. Measure compressor motor windings resistance to ground
8. Change oil every 1000 hours of operation per Trane Oil Analysis Program Exhaust Fan Maintenance
1. Replace belt
2. Lube if possible
3. Inspect fan for cracks, vibrations and clean
4. Inspect proper operation of unit