ECAT_BP2_DRAWING_SET_-_05_FUEL_STATION_Rev_1__26-11-13.pdf

PDF 3 MB Posted

Attached to
CDBG-DR HS004 New Escambia County Area Transit (ECAT) Facility
Solicitation number
PD 26-27.004
Issued by
Escambia County, Florida

About this file

This is a drawing set for Bid Package #2 of the Escambia County Area Transit (ECAT) Facility Fuel Station, a construction project located at 2 Clarinda Lane in Pensacola, Florida. The drawing package includes structural, architectural, plumbing, electrical, and technology specifications for the fuel station canopies and associated equipment. The fuel station comprises two canopies (north and south) measuring 125 feet in length and 24 feet in width, designed to accommodate electronic fuel dispensers for diesel and unleaded gasoline, above-ground fuel tanks, and related infrastructure. The project is governed by the 8th Edition of the Florida Building Code as adopted by Escambia County, with design parameters including wind speeds of 156 mph (basic) and 121 mph (ASD), seismic design category D, and soil bearing capacity of 1.5 ksf. The drawing set was last revised on November 12, 2026, and includes detailed notes on deferred submittals, shop drawings, pre-engineered canopy requirements, concrete specifications, reinforcing steel standards, and post-installed anchor installation procedures. Key consulting firms include ADG (Architect of Record), RLG Consulting Engineers, KEDbluestone, and Hodgson Douglas Landscape Architects.

The structural design incorporates a prefabricated canopy system with delegated design responsibility assigned to the canopy manufacturer, requiring that all shop drawings be sealed by a registered professional engineer in Florida. Foundation design is based on Geotechnical Report #26-162 prepared by Larry M Jacobs & Associates, with continuous and isolated footing bearing capacities of 1.5 ksf and soil sliding resistance of 0.5 ksf. All concrete work must comply with ACI 318, with compressive strength of 4,000 psi for footings and all other concrete elements, and concrete protection for reinforcement of 3 inches for footings and 2 inches for walls. The electrical system includes a 45 kVA transformer (XFMR-LEF1), two branch circuit panelboards (HEF1 and LEF1), LED lighting fixtures, and emergency power-off systems meeting NEC Article 514 Class 1 Division 2 specifications for hazardous fuel station environments. Plumbing systems include double-wall polyethylene containment piping below grade and schedule 40 black steel piping above grade, sized for automotive fuel delivery at 125 psi working pressure. The technology scope encompasses security camera systems, access control, mass notification speakers, intercom systems, and data infrastructure, with coordination required between the electrical contractor and technology system providers.

View the file

Other files

File Type Posted
CDBG-DR_HS004_New_Escambia_County_Area_Transit_(ECAT)_Facility_(Addendum_#16_Revision).pdf PDF
ECAT_BP2_CONSTRUCTION_ADD-REV_1_WRITE-UP_Rev_1__26-11-13.pdf PDF
ECAT_BP2_PROJECT_MANUAL_Rev_1__26-11-13.pdf PDF
ECAT_BP2_DRAWING_SET_-_04_BUS_WASH_Rev_1__26-11-13.pdf PDF
ECAT_BP2_DRAWING_SET_-_03_TRANSFER_CENTER_Rev_1__26-11-13.pdf PDF
ECAT_BP2_DRAWING_SET_-_02_MAINTENANCE_BUILDING_Rev_1_26-11-13.pdf PDF
ECAT_BP2_DRAWING_SET_-_01_ADMINISTRATION_BUILDING_Rev_1_26-11-13.pdf PDF
ECAT_BP2_DRAWING_SET_-_00_SITE_SITE_Rev_1_26-11-13.pdf PDF
CDBG-DR_HS004_New_Escambia_County_Area_Transit_(ECAT)_Facility_(Addendum_#10_Revision).pdf PDF
CDBG-DR_HS004_New_Escambia_County_Area_Transit_(ECAT)_Facility_(Addendum_#9_Revision).pdf PDF
CDBG-DR_HS004_New_Escambia_County_Area_Transit_(ECAT)_Facility_(Addendum_#8_Revision).pdf PDF
CDBG-DR_HS004_New_Escambia_County_Area_Transit_(ECAT)_Facility.pdf PDF
ECAT_BP2_PROJECT_MANUAL_-_VOLUME_TWO.pdf PDF
ECAT_BP2_PROJECT_MANUAL_-_VOLUME_ONE.pdf PDF
ECAT_BP2_DRAWING_SET_-_05_FUEL_STATION.pdf PDF
ECAT_BP2_DRAWING_SET_-_04_BUS_WASH.pdf PDF
ECAT_BP2_DRAWING_SET_-_03_TRANSFER_CENTER.pdf PDF
ECAT_BP2_DRAWING_SET_-_02_MAINTENANCE_BUILDING.pdf PDF
ECAT_BP2_DRAWING_SET_-_01_ADMINISTRATION_BUILDING.pdf PDF
ECAT_BP2_DRAWING_SET_-_00_SITE.pdf PDF
FDOT_Liquidated-Damages-2026-2027.pdf PDF
Building_Construction_Wage_Determination_5.18.26.pdf PDF
Exhibit.FederalContractProvisions.HUD_10.22.26.pdf PDF
Escambia_County_Section_3_Business_Application_CDBG-DR.pdf PDF
Section-3-project-implementation-plan-template---forms-0-8.pdf PDF
Escambia_County_Section_3_Contract_Clause_CDBG-DR.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DESIGN DATA

1. THE DESIGN OF THE STRUCTURE AND PARTS THEREOF IS IN ACCORDANCE WITH THE 8TH EDITION OF FLORIDA BUILDING

CODE, AS AMENDED AND ADOPTED BY ESCAMBIA COUNTY.

2. ROOF LIVE LOADS:

AREA UNIFORM SPECIAL COMMENTS

ROOF, GENERAL

LIVE LOAD REDUCTION

20 psf -

ROOF, EQUIP LOADS SEE ROOF PLAN

3. SNOW LOADS: NOT APPLICABLE PER FBC

FACTORED COMPONENTS AND CLADDING WALL LOADS

POSITIVE PRESSURE (psf) NEGATIVE PRESSURE (psf)

AREA (SQ FT)

LESS THAN 10

GREATER THAN 500

INTERIOR & CORNER ZONE INTERIOR ZONE CORNER ZONE

47 -52

-46

-41

-38 -37

-44

-54

-47

CORNER ZONE IS A DISTANCE OF 3'-0" FROM WALL CORNERS

LINEAR INTERPOLATE FOR LOADS BETWEEN SPECIFIED AREAS

6. FLOOD DESIGN DATA:

THIS PROJECT IS NOT LOCATED WITHIN A FLOOD HAZARD AREA

7. SPECIAL LOADS:

VEHICULAR BARRIERS

AREA

AWNINGS & CANOPIES

UNIFORM

20 psf

6.0 ksf

CONCENTRATED

300 lbs.

IMPACT SECTION OF CODE

FBC 1607.9

FBC 1607.13.4

8. ROOF RAIN LOAD DATA:

RAIN INTENSITY (15-DURATION)

4.9 in/hr

FACTORED COMPONENTS AND CLADDING ROOF LOADS

POSITIVE PRESSURE (psf) NEGATIVE PRESSURE (psf)

AREA (SQ FT)

LESS THAN 10

GREATER THAN 500

PERIMETER ZONE, "B" IS A DISTANCE OF 17'-6" FROM EDGE OF BUILDING

CORNER ZONE, "C" IS A DISTANCE OF 6'-0" FROM EDGE OF BUILDING

ZONE 2 ZONE 3 ZONE 2

-119

-92

-83

-73

ZONE 3

-166

-111

-94

-73

LINEAR INTERPOLATE FOR LOADS BETWEEN SPECIFIED AREAS

3 3

B

C

ROOF WIND LOAD LAYOUT

YES, PER FBC 1607.14

RAIN INTENSITY (60-DURATION)

9.12 in/hr

4. WIND DESIGN DATA:

ASD WIND SPEED Vasd 121 mph

RISK CATEGORY

BASIC WIND SPEED (3 SECOND GUST)

WIND EXPOSURE

INTERNAL PRESSURE COEFFICIENT

COMPONENTS AND CLADDING

156 mph

+/- 0.00

PER ASCE 7-22

N/A

N/A

TORNADO SPEED, Vt

EFFECTIVE PLAN AREA

II

C

6. SEISMIC DESIGN DATA:

SEISMIC IMPORTANCE FACTOR, Ie

MAPPED SPECTRAL RESPONSE ACCEL.

RISK CATEGORY

SITE CLASS

SPECTRAL RESPONSE COEFFICIENTS

SEISMIC DESIGN CATEGORY

Ss =

BASIC SEISMIC-FORCE-RESISTING SYSTEM

DESIGN BASE SHEAR

SEISMIC RESPONSE COEFFICIENT, Cs

RESPONSE MODIFICATION FACTOR, R

ANALYSIS PROCEDURE USED

SDS =

S1 =

SD1 =

0.11 0.063

0.090.1

0.033xW

1.0

II

DEFAULT

B

STEEL SYSTEMS NOT SPECIFICALLY

DETAILED FOR SEISMIC RESISTANCE

0.033

3.0

EQUIVALENT LATERAL FORCE

1. PROJECT SPECIFICATIONS ARE A PART OF THE CONTRACT DOCUMENTS. CONTRACTOR SHALL REVIEW THE SPECIFICATIONS AND NOTIFY ARCHITECT OF DISCREPANCIES BEFORE PROCEEDING WITH WORK.

2. STRUCTURAL DRAWINGS ARE AN INTEGRAL COMPONENT TO THE CONTRACT DOCUMENTS. CONTRACTOR SHALL

REVIEW AND COORDINATE ACCORDINGLY.

A. PRIOR TO FABRICATION OR INSTALLATION OF STRUCTURAL MEMBERS, CONTRACTOR SHALL COMPARE

STRUCTURAL DIMENSIONS AND SECTIONS WITH ARCHITECTURAL DIMENSIONS AND SECTIONS.

DISCREPANCIES ARE TO BE REPORTED IN WRITING TO THE ARCHITECT.

B. PRINCIPAL OPENINGS ARE SHOWN ON THESE DRAWINGS. REFER TO ARCHITECTURAL, MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR OTHER OPENINGS NOT SHOWN.

C. REFER TO ARCHITECTURAL DRAWINGS FOR ELEVATIONS AND LOCATIONS OF SLAB DEPRESSIONS AND

CURBS NOT SHOWN. PROVIDE POSITIVE SLOPE TO ALL DRAINS.

D. CONTRACTOR SHALL COORDINATE PENETRATIONS, SLEEVES, CURBS, AND INSERTS REQUIRED FOR THE

CONTRACT DOCUMENTS.

E. CONTRACTOR SHALL VERIFY SIZE, WEIGHT, LOCATION, AND SUPPORT CONDITIONS OF MECHANICAL

EQUIPMENT SUPPORTED ON OR SUSPENDED FROM THE ROOF OR FLOORS.

F. CONTRACTOR SHALL COORDINATE CONSTRUCTION WITH ADJACENT STRUCTURES AND UTILITIES.

G. CONTRACTOR SHALL NOTIFY IN WRITING THE ARCHITECT & ENGINEER OF ANY DISCREPANCIES BEFORE

PROCEEDING WITH WORK.

3. TEMPORARY SHORING AND BRACING DURING CONSTRUCTION

A. CONTRACTOR SHALL PROVIDE TEMPORARY BRACING OF COMPONENTS DURING CONSTRUCTION TO MEET

REGULATORY REQUIREMENTS FOR SAFETY.

B. CONTRACTOR SHALL PROVIDE TEMPORARY SHORING AND BRACING OF WALLS AND GRADE BEAMS DURING

CONSTRUCTION. SHORE WALLS AND GRADE BEAMS DURING THE BACKFILLING AND COMPACTION PROCESS.

C. CONTRACTOR SHALL PROVIDE NECESSARY TEMPORARY BRACING AND SHORING DURING CONSTRUCTION

UNTIL STRUCTURAL FRAMING AND DIAPHRAGMS ARE COMPLETED. TEMPORARY BRACING SHALL BE

DESIGNED UNDER THE SUPERVISION OF A LICENSED ENGINEER.

4. SELECTION OF CONSTRUCTION MEANS, METHODS, TECHNIQUES, AND PROCEDURES, AS WELL AS SAFETY PRECAUTIONS AND PROGRAMS, ARE SOLELY THE CONTRACTOR’S RESPONSIBILITIES. AS SUCH, CONSTRUCTION ENGINEERING AND DESIGN RESULTING FROM THESE SELECTIONS IS THE RESPONSIBILITY OF THE CONTRACTOR.

A. EXAMPLES INCLUDE, BUT ARE NOT LIMITED TO, ENGINEERING OF SHORING AND SCAFFOLDING SYSTEMS;

LOAD CHECKS AND STRUCTURAL MODIFICATIONS FOR STORAGE, STAGING, AND CONSTRUCTION

EQUIPMENT LOADING; MEANS OF EGRESS FOR HEAVY EQUIPMENT; CRANE SELECTION, LOCATION, SUPPORT

AND BRACING; TEMPORARY HOISTS, LIFTS AND PLATFORMS.

B. CONTRACTOR SHALL ENSURE THAT APPROPRIATE ENGINEERING IS PERFORMED BY A LICENSED ENGINEER FOR THE WORK, CONSULTED WITH ON FIELD MODIFICATIONS, SPECIFY APPROPRIATE LEVELS OF

INSPECTION OF THE WORK, AND TO REVIEW INSPECTION REPORTS.

C. CONSTRUCTION ENGINEERING FEES HAVE NOT BEEN INCLUDED IN THE BASE FEE TO THE

OWNER/ARCHITECT. IF REQUESTED, THE EOR MAY CONSIDER PERFORMING THESE SERVICES AS AN

ADDITIONAL SERVICE PAID BY THE CONTRACTOR.

5. PRE-CONSTRUCTION MEETINGS SHALL BE CONDUCTED TO DISCUSS SUBGRADE PREPARATION, FOUNDATION CONSTRUCTION, WALL BACKFILL, VOID FORM SYSTEMS, CONCRETE FORMING & PLACING, AND TESTING &

INSPECTION REQUIREMENTS.

6. CONTRACTOR SHALL COMPLY WITH REQUIREMENTS AS LISTED IN THE STATEMENT OF SPECIAL INSPECTIONS.

GENERAL NOTES

1. DEFERRED SUBMITTALS ARE PORTIONS OF THE OVERALL DESIGN WHICH ARE NOT SUBMITTED AT TIME OF PERMIT

APPLICATION AND ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL.

2. DEFERRED SUBMITTALS WILL BE REVIEWED FOR THE LIMITED PURPOSE OF CHECKING FOR CONFORMANCE WITH INFORMATION GIVEN IN THE CONTRACT DOCUMENTS. SUBMITTAL REVIEW WILL NOT BE CONDUCTED FOR THE PURPOSE OF DETERMINING THE ACCURACY AND COMPLETENESS OF OTHER DETAILED INFORMATION SUCH AS DIMENSIONS AND QUANTITIES, OR FOR SUBSTANTIATING INSTRUCTIONS FOR INSTALLATION OR SYSTEMS DESIGNED

BY THE CONTRACTOR WHICH REMAINS THE RESPONSIBILITY OF THE CONTRACTOR.

REVIEW SHALL NOT CONSTITUTE APPROVAL OF SAFETY PRECAUTIONS OR OF ANY CONSTRUCTION MEANS, METHODS, SEQUENCES OR PROCEDURES.

APPROVAL OF A SPECIFIC ITEM SHALL NOT INDICATE APPROVAL OF AN ASSEMBLY OF WHICH THE ITEM IS A

COMPONENT.

3. FOLLOWING DEFERRED SUBMITTALS ARE TO BE PROVIDED FOR REVIEW:

A. CONCRETE FORMWORK / RETENTION SYSTEMS

B. PRE-ENGINEERED CANOPIES

SUPPLIER’S ENGINEERS SHALL PROVIDE SIGNED AND SEALED CALCULATIONS WITH THE SUBMITTAL FOR REVIEW.

REVIEW WILL BE LIMITED TO CONFORMANCE WITH DESIGN AND PERFORMANCE CRITERIA SPECIFIED IN THE CONSTRUCTION DOCUMENTS AND THE INTERFACE BETWEEN THESE ITEMS/SYSTEMS AND THE BUILDING STRUCTURE. THE MANUFACTURER/SUPPLIER AND ITS SPECIALTY STRUCTURAL ENGINEER REMAIN RESPONSIBLE FOR THE DESIGN OF THE ITEM/SYSTEM WILL RETAIN ALL RIGHTS AND RESPONSIBILITIES FOR THE DESIGN OF THE

PRODUCT AND THE CONNECTIONS TO THE BUILDING STRUCTURE.

NO WORK ON STRUCTURAL ELEMENTS SUPPORTING OR RELATED TO THESE ITEMS IS TO PROCEED UNLESS THE REVIEW STAMP CLEARLY INDICATES "REVIEWED" OR "REVIEWED, SEE COMMENTS" BY THE ENGINEER.

4. FOLLOWING SHOP DRAWINGS ARE TO BE PROVIDED FOR APPROVAL:

A. CONCRETE MIXES

B. REINFORCING STEEL

SHOP DRAWINGS ARE TO BE DISTRIBUTED ONLY FROM RETURNED SUBMITTALS BEARING AN INITIALED REVIEW STAMP AND WORK ON THESE ITEMS SHALL NOT PROCEED UNLESS THE STAMP CLEARLY INDICATES THE DRAWINGS

ARE "APPROVED" OR "APPROVED AS NOTED."

5. CONCRETE IS A MATERIAL DESIGNED BY THE SUPPLIER TO MEET THE STRENGTH AND PERFORMANCE CRITERIA SPECIFIED IN THE CONTRACT DOCUMENTS. CONCRETE MIX DESIGNS SHALL BE IN CONFORMANCE WITH ACI 318.

SUBMIT MIX DESIGNS AND THE TESTING LAB REVIEW TO THE ARCHITECT/ENGINEER FOR REVIEW.

MANY VARIABLES, INCLUDING ENVIRONMENTAL CONDITIONS AFFECT THE QUALITY OF CONCRETE. THE CONTRACTOR IS RESPONSIBLE FOR CONTROLLING VARIABLES AND REQUESTING MIX MODIFICATIONS AND SHALL BE

SOLELY RESPONSIBLE FOR THE QUALITY OF CONCRETE DELIVERED AND PLACED ON THE SITE.

6. BEFORE SUBMISSION FOR REVIEW, GENERAL CONTRACTOR SHALL PRE-CHECK SUBMITTALS. SUBMITTALS MUST BEAR AN INITIALED REVIEW STAMP OF THE GENERAL CONTRACTOR. SUBMITTALS WITHOUT REVIEW STAMPS WILL

BE RETURNED WITHOUT REVIEW AND SHALL NOT BE CAUSE FOR CLAIMS OF DELAY.

7. SCHEDULE SUBMITTALS SUFFICIENTLY IN ADVANCE OF THE DATE REQUIRED TO ALLOW REASONABLE TIME FOR PROCESSING AND REVIEW BY THE DESIGN TEAM. THIS SHALL INCLUDE A MINIMUM OF TEN WORKING DAYS FOR ENGINEER'S PROCESSING AND REVIEW. INCLUDE TIME FOR CONTRACTOR’S RESUBMISSION AND SUBSEQUENT

REVIEW IF NECESSARY.

SHORTER REVIEW PERIODS WILL ONLY BE HONORED WITH PRIOR WRITTEN CONSENT. THESE ACCELERATED SERVICES, AND APPROPRIATE COMPENSATION, MUST BE NEGOTIATED WITH THE ENGINEER AND ARCHITECT IN

ADVANCE.

TEN DAY REVIEW PERIODS CAN NOT BE HONORED WHEN LARGE QUANTITIES OF SHOP DRAWINGS ARE SUBMITTED AT ONE TIME. WHEN THIS HAPPENS, THE CONTRACTOR SHALL SUBMIT AN ITEMIZED LIST INDICATING PRIORITIES AND

REASONABLE RETURN DATES.

REVIEW OF RESUBMITTALS WILL BE LIMITED TO ONLY EARLIER COMMENTS AND IS NOT AN EXTENSIVE REVIEW.

8. USE OF REPRODUCTIONS OF THESE CONTRACT DRAWINGS, INCLUDING THE USE OF ELECTRONIC FILES, BY ANY CONTRACTOR IN LIEU OF THE INDEPENDENT PREPARATION OF SHOP DRAWINGS, SIGNIFIES THEIR ACCEPTANCE OF ALL INFORMATION SHOWN HEREON AS CORRECT AND OBLIGATES HIMSELF TO ANY JOB EXPENSE, REAL OR IMPLIED, ARISING DUE TO ANY ERRORS THAT MAY OCCUR HEREON.

9. NOT USED

DEFERRED SUBMITTALS NOTES

1. FOUNDATION DESIGN AND SUBSURFACE INFORMATION IS BASED ON GEOTECHNICAL REPORT #26-162 PREPARED FOR THIS PROJECT BY LARRY M JACOBS & ASSOCIATES, INC AND DATED MAY 1, 2026 & EMAIL RESPONSE DATED

SEPTEMBER 1, 2026.

2. GEOTECHNICAL ENGINEER OF RECORD (GER) IS SOLELY RESPONSIBLE FOR ESTABLISHING FOUNDATION, SLAB-ON- GRADE AND PAVEMENT DESIGN CRITERIA, AND FOR THE CONSTRUCTION RECOMMENDATIONS FOR EXCAVATION, SUBGRADE PREPARATION, BACKFILLING AND COMPACTION.

3. GEOTECHNICAL INFORMATION INDICATED IN THE STRUCTURAL CONSTRUCTION DOCUMENTS IS INTENDED TO REPLICATE THE RECOMMENDATIONS STATED IN THE GEOTECHNICAL ENGINEERING REPORT. PRESENTATION OF THIS INFORMATION IN THE STRUCTURAL DOCUMENTS DOES NOT DEMONSTRATE, STATE OR IMPLY GEOTECHNICAL EXPERTISE BY THE STRUCTURAL ENGINEER. CONTRACTOR SHALL OBTAIN A COPY OF THE REPORT AND COMPLY

WITH THE RECOMMENDATIONS INDICATED THEREIN.

4. IF DISCREPANCIES BETWEEN THE REPORT AND CONSTRUCTION DOCUMENTS ARE DISCOVERED, THE REPORT SHALL GOVERN. ALL CLARIFICATIONS AND INTERPRETATIONS OF THE REPORT SHALL BE MADE BY THE GER AND

REPORTED TO THE ARCHITECT FOR COORDINATION WITH THE DESIGN TEAM.

GEOTECHNICAL INFORMATION

1. BEARING STRATA SHOWN ON THE DETAILS IS NATIVE SOILS. PREPARE FOUNDATION BEARING MATERIAL PER THE

GEOTECHNICAL ENGINEER'S RECOMMENDATIONS.

2. FOUNDATION ALLOWABLE DESIGN SOIL VALUES:

CONTINUOUS FOOTING BEARING - 1.5ksf * ISOLATED FOOTING BEARING - 1.5ksf *

SOIL SLIDING RESISTANCE (NATIVE SOIL) 0.5

* IF CONTINUOUS FOOTING OR ISOLATED FOOTING WIDTH EXCESS 3FT IN DIMENSION, THE SOIL BENEATH FOOTING

SHALL HAVE ADDITIONAL 2FT OF SOIL COMPACTION PER GEOTECHNICAL REPORT.

RETAINING WALL DESIGN VALUES

SOIL DENSITY Yd- 95PCF (VERY LOOSE SLIGHTLY SILTY SAND) AT REST Ka- 0.4xYd PASSIVE PRESSURE Kp- 2.5XYd

3. ALL FOOTING EXCAVATIONS SHALL BE CLEANED TO REMOVE ALL LOOSE SOIL MATERIAL AND OTHER DEBRIS AND

SHOULD NOT BE ALLOWED TO DESICCATE PRIOR TO PLACEMENT OF CONCRETE.

4. CONCRETE FOR FOUNDATIONS SHALL BE FORMED ON THE SIDES (EARTH FORMED FOUNDATIONS WILL NOT BE

ALLOWED). PROPERLY PLACE AND COMPACT FILL MATERIAL AROUND SIDES OF FOOTINGS.

5. ALL FOUNDATION EXCAVATIONS SHALL BE INSPECTED BY THE TESTING AGENCY.

SHALLOW FOUNDATION NOTES

1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH ACI 318- PER GOVERNING BUILDING CODE.

2. CONCRETE IN THE FOLLOWING AREAS SHALL HAVE SAND AND GRAVEL OR CRUSHED STONE AGGREGATES AND THE DESIGNATED COMPRESSIVE STRENGTH IN 28 DAYS UNLESS NOTED OTHERWISE. NORMAL WEIGHT AGGREGATES

SHALL CONFORM TO ASTM C33.

FOOTING -------------------------------------------------------------- f'c = 4,000 psi ALL OTHER CONCRETE ---------------------------------------- f'c = 4,000 psi

3. CONCRETE PROTECTION FOR REINFORCEMENT SHALL BE AS FOLLOWS:

REFER TO ACI 318 - SECTION 7.7 FOR CONDITIONS NOT NOTED.

FOOTINGS ------------------------------------------------ 3"

WALL ------------------------------------------------------- 2"

4. MAXIMUM NOMINAL COARSE AGGREGATE SIZE SHALL BE 1 1/2" MAX FOR PIERS AND 1" MAX TYPICAL UNLESS NOTED

OTHERWISE.

5. CONCRETE SLUMPS SHALL BE AS FOLLOWS:

CONCRETE CONTAINING HRWR------ 10" MAX

ALL OTHER CONCRETE ---------------- 5" MAX, 2" MIN

6. CONCRETE EXPOSED TO WEATHER SHALL BE AIR-ENTRAINED AS FOLLOWS:

3/4" NOMINAL AGGREGATE SIZE 4% TO 8%

1" NOMINAL AGGREGATE SIZE 3.5% TO 6.5%

1 1/2" NOMINAL AGGREGATE SIZE 3% TO 6%

7. ALL CAST IN PLACE WALLS AND CONTINUOUS FOOTINGS SHALL BE FORMED ON SIDES. ALL ELEMENTS OF THE FORMS, FORMWORK, BRACING AND SHORING SHALL CONSIST OF WOOD, METAL OR OTHER MANUFACTURED PRODUCTS AS SPECIFIED. EARTH MAY NOT BE USED AS A FORM, EITHER DIRECTLY OR INDIRECTLY. NEITHER

EARTH TRENCHES NOR EARTH TRENCHES LINED WITH ANOTHER MATERIAL ARE ACCEPTABLE.

8. THERE SHALL BE NO HORIZONTAL CONSTRUCTION JOINTS IN CONCRETE POURS. ALL CONSTRUCTION JOINTS SHALL BE MADE IN THE CENTER OF SPANS WITH VERTICAL BULK HEADS. THE LOCATION OF CONSTRUCTION JOINTS SHALL

BE APPROVED BY THE STRUCTURAL ENGINEER.

9. UNLESS OTHERWISE NOTED OR DETAILED, PROVIDE (2)#5, (1) EACH FACE AROUND UNFRAMED OPENINGS IN CONCRETE WALLS AND GRADE BEAMS. PLACE BARS PARALLEL TO SIDES OF OPENINGS AND EXTEND 24 INCHES

BEYOND CORNERS.

10. PROVIDE EQUIPMENT BASES AND SUPPORTS AS REQUIRED, COMPLYING WITH APPROVED MANUFACTURERS

CERTIFIED SHOP DRAWINGS AND DETAILS.

11. SIZE AND LOCATION OF BASES AND EMBEDDED ANCHORS FOR EQUIPMENT SHALL BE COORDINATED WITH

EQUIPMENT SUPPLIER AND ALL BE IN ACCORDANCE WITH APPROVED SHOP DRAWINGS.

12. NO ALUMINUM OF ANY TYPE SHALL BE ALLOWED IN THE CONCRETE WORK, UNLESS COATED AND APPROVED BY

THE ENGINEER OR RECORD.

CONCRETE NOTES

1. ALL REINFORCING STEEL SHALL BE NEW DEFORMED BILLET STEEL CONFORMING TO ASTM A615, GRADE 60.

2. DETAILING OF REINFORCEMENT SHALL BE IN ACCORDANCE WITH THE ACI DETAILING MANUAL.

3. REINFORCING BARS MAY BE SPLICED ONLY AS SHOWN ON THE DRAWINGS EXCEPT THAT REINFORCING DESIGNATED AS "CONTINUOUS" MAY BE CONTACT LAP SPLICED WITH TENSION LAP PER ACI 318 CHAPTER 25.

4. FOR CONTINUOUS FOOTING REINFORCING, PER FOOTINGS REINFORCEMENT LAP SPLICES SCHEDULED ON S110.

5. PROVIDE CORNERS BARS OF SAME SIZE AND QUANTITY AS CONTINUOUS TOP AND BOTTOM REINFORCING OF

GRADE BEAMS AT ALL GRADE BEAM CORNERS AND INTERSECTIONS.

REINFORCING STEEL NOTES

1. POST-INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED ON THE CONSTRUCTION DOCUMENTS. THE CONTRACTOR SHALL OBTAIN APPROVAL FROM THE ENGINEER-OF-RECORD PRIOR TO INSTALLING POST-INSTALLED ANCHORS IN PLACE OF MISSING OR MISPLACED CAST-IN-PLACE ANCHORS. CARE SHALL BE TAKEN IN PLACING POST-INSTALLED ANCHORS TO AVOID CONFLICTS WITH EXISTING REINFORCING OR POST-TENSIONING.

2. SUBSTITUTION REQUESTS, FOR PRODUCTS OTHER THAN THOSE SPECIFIED BELOW, SHALL BE SUBMITTED BY THE CONTRACTOR TO THE ENGINEER-OF-RECORD ALONG WITH CALCULATIONS THAT ARE PREPARED & SEALED BY A REGISTERED PROFESSIONAL ENGINEER. THE CALCULATIONS SHALL DEMONSTRATE THAT THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING EQUIVALENT PERFORMANCE VALUES (MINIMUM) OF THE SPECIFIED PRODUCT USING THE APPROPRIATE DESIGN PROCEDURE AND/OR STANDARD(S) AS REQUIRED BY THE BUILDING CODE.

3. POST-INSTALLED ANCHORS INCLUDE EXPANSION ANCHORS, UNDERCUT ANCHORS AND ADHESIVE ANCHORS.

ADHESIVE ANCHORS SHALL CONSIST OF A STRUCTURAL ADHESIVE AND STEEL INSERT. STEEL INSERTS SHALL BE EITHER ASTM F1554, GRADE 36 THREADED ROD OR ASTM A615, GRADE 60 REINFORCING STEEL UNLESS NOTED OTHERWISE ON THE DRAWINGS. PROVIDE, STORE AND INSTALL PRODUCTS IN STRICT CONFORMANCE WITH THE

MANUFACTURER'S RECOMMENDATIONS.

4. EXPANSION ANCHORS FOR USE IN CRACKED AND UNCRACKED CONCRETE SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI 355.2 AND ICC-ES AC193. EXPANSION ANCHORS SHALL BE EITHER HILTI KWIK BOLT TZ ANCHORS OR SIMPSON STRONG-TIE STRONG-BOLT 2 ANCHORS, UNLESS NOTED OTHERWISE ON DRAWINGS. EXPANSION ANCHORS SHALL BE 3/4" DIAMETER WITH 4 3/4" EMBEDMENT UNLESS NOTED OTHERWISE

ON THE DRAWINGS.

5. EXPANSION ANCHORS FOR USE IN SOLID-GROUTED CONCRETE MASONRY SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC01. EXPANSION ANCHORS IN CMU SHALL BE EITHER HILTI KWIK

BOLT 3 ANCHORS OR SIMPSON STRONG-TIE WEDGE-ALL ANCHORS.

6. UNDERCUT ANCHORS FOR USE IN CRACKED AND UNCRACKED CONCRETE SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI 355.2 AND ICC-ES AC193. UNDERCUT ANCHORS SHALL BE EITHER HILTI HDA ANCHORS OR SIMPSON STRONG-TIE TORQ-CUT ANCHORS, UNLESS NOTED OTHERWISE ON DRAWINGS.

7. STRUCTURAL ADHESIVES FOR USE IN CRACKED AND UNCRACKED CONCRETE SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI 355.4 AND ICC-ES AC308. STRUCTURAL ADHESIVES SHALL BE HILTI HIT-RE 500-SD EPOXY, HILTI HIT-HY 200-A ADHESIVE, SIMPSON STRONG-TIE SET-XP ADHESIVE OR SIMPSON STRONG- TIE AT-XP ADHESIVE UNLESS NOTED OTHERWISE ON THE DRAWINGS. REFER TO DRAWINGS FOR SIZE AND EMBEDMENT REQUIREMENTS. ALL THREADED RODS USED IN EXTERIOR EXPOSURES SHALL BE GALVANIZED.

8. THE FOLLOWING PARAMETERS HAVE BEEN USED IN THE DESIGN OF ALL ADHESIVE ANCHORS UNLESS NOTED

OTHERWISE ON THE DRAWINGS:

A. MINIMUM AGE OF CONCRETE – 28 DAYS

B. CONCRETE TEMPERATURE RANGE FOR ANCHORS NOT EXPOSED TO THE ENVIRONMENT – MAXIMUM SHORT

TERM TEMPERATURE OF 104°F; MAXIMUM LONG TERM TEMPERATURE OF 75°F.

C. CONCRETE TEMPERATURE RANGE FOR ANCHORS EXPOSED TO THE ENVIRONMENT – MAXIMUM SHORT TERM

TEMPERATURE OF 150°F; MAXIMUM LONG TERM TEMPERATURE OF 110°F.

D. MOISTURE CONDITION OF CONCRETE AT THE TIME OF INSTALLATION – DRY CONCRETE

E. HOLE DRILLING AND PREPARATION – PER THE MANUFACTURER’S PRINTED INSTALLATION INSTRUCTIONS

9. ANCHOR CAPACITY IS DEPENDANT UPON THE SPACING BETWEEN ADJACENT ANCHORS AND THE PROXIMITY OF ANCHORS TO THE EDGE OF CONCRETE. INSTALL ANCHORS IN ACCORDANCE WITH THE SPACING AND EDGE

CLEARANCES INDICATED ON THE DRAWINGS.

10. PRIOR TO PLACEMENT, THE CONTRACTOR SHALL HAVE THE MANUFACTURER’S TECHNICAL REPRESENTATIVE VISIT THE SITE TO INSTRUCT THE CONSTRUCTION TEAM AND TESTING LAB ON PROPER STORAGE AND INSTALLATION TECHNIQUES. THE CONTRACTOR SHALL PROVIDE A LETTER FROM THE MANUFACTURER’S REPRESENTATIVE

STATING THAT SUCH A VISIT WAS CONDUCTED.

11. ALL EXPANSION ANCHORS SHALL BE INSPECTED BY AN INDEPENDENT TESTING LAB FOR THE FOLLOWING:

A. CORRECT LOCATION AND POSITION OF HOLE.

B. CORRECT HOLE DIAMETER

C. CORRECT EMBEDMENT DEPTH.

D. CORRECT BOLT TYPE AND FINISH.

E. CONDITION OF HOLE IN CONNECTION MATERIAL (NO BURNING OF HOLES ALLOWED).

F. SNUG TIGHT FIT.

12. ADHESIVE ANCHORS SHALL BE INSPECTED AND TESTED BY AN INDEPENDENT TESTING LAB AS FOLLOWS:

ALL ANCHORS SHALL BE INSPECTED FOR THE FOLLOWING:

A. CORRECT LOCATION AND POSITION OF HOLE.

B. CORRECT THREADED ROD OR REINFORCING BAR SIZE.

C. CORRECT THREADED ROD OR REINFORCING BAR TYPE AND FINISH.

D. CONDITION OF HOLE IN CONNECTION MATERIAL (NO BURNING OF HOLES ALLOWED).

E. SNUG TIGHT FIT.

F. CORRECT EMBEDMENT DEPTH.

G. HOLE PREPARATION (INCLUDING DRILL BIT TYPE WHERE CRITICAL TO MANUFACTURER) AND CLEANOUTS

PER MANUFACTURER'S RECOMMENDATIONS.

H. ADHESIVE TYPE, EXPIRATION DATE AND METHOD OF STORAGE.

I. ADHESIVE AND ANCHOR INSTALLATION PER MANUFACTURER’S RECOMMENDATIONS.

J. 10% OF EACH TYPE AND SIZE OF ANCHOR SHALL BE PROOF LOADED PER THE MANUFACTURER’S

RECOMMENDATIONS. IF 10% OF THE TESTED ANCHORS FAIL TO ACHIEVE THE SPECIFIED PROOF LOAD, ALL

ANCHORS OF THE SAME DIAMETER AND TYPE SHALL BE TESTED.

13. THE TESTING LAB SHALL PREPARE AN INSPECTION REPORT SPECIFICALLY INDICATING DEGREE OF CONFORMANCE

IN ALL CATEGORIES LISTED ABOVE.

POST-INSTALLED ANCHOR NOTES

1. ALL SUBGRADE SHALL BE PREPARED IN STRICT CONFORMANCE TO THE GEOTECHNICAL ENGINEER’S RECOMMENDATIONS. REFER TO THE GEOTECHNICAL REPORT, SUPPLEMENTARY LETTERS AND SPECIFICATIONS

FOR ADDITIONAL INFORMATION.

THE SUBGRADE SHALL BE IMPROVED TO REDUCE THE POTENTIAL FOR SUBGRADE MOVEMENT TO LESS THAN OF ONE INCH TOTAL SETTLEMENT & 1/2 INCH OF DIFFERENTIAL SETTLEMENT BY RE-COMPACTING IN-SITU SOIL AS

APPROVED BY GEOTECH ENGINEER.

THE FOLLOWING IS A SUMMARY OF THE INFORMATION CONTAINED IN THE GEOTECHNICAL ENGINEER’S

RECOMMENDATIONS:

A. THE BUILDING EXCAVATION AREA SHALL EXTEND BEYOND THE BUILDING LINE A MINIMUM OF 5 FEET IN GENERAL. AT ALL ENTRANCES AND AT AREAS WITH SIDEWALKS/PAVING DIRECTLY ADJACENT TO THE

BUILDING.

B. WITHIN THE BUILDING AREA, EXCAVATE AND REMOVE ALL FILL MATERIAL. REFER TO THE GEOTECHNICAL REPORT FOR APPROXIMATE DEPTHS OF FILL. THE TESTING LAB SHALL DETERMINE THROUGH FIELD

OBSERVATION AND TESTING THAT ALL UNACCEPTABLE FILLS HAVE BEEN REMOVED.

C. WITHIN THE BUILDING AREA, RE-COMPACT NATIVE SOIL OR IMPORTED FILL AS REQUIRED TO PROVIDE A COMPACTED MATERIAL BENEATH BUILDING AREA. FOOTING THAT HAVE A WIDTH GREATER THAN 3FT IN

WIDTH WILL REQUIRE ADDITIONAL 2FT OF SOIL COMPACTION BENEATH FOOTING.

D. SCARIFY EXPOSED NATIVE SOILS TO A DEPTH OF 12 INCHES FOR FOOTING LESS THAN 3FT IN WIDTH AND RECOMPACT TO A MINIMUM OF 95% OF MODIFIED PROCTOR (ASTM D1557) AT A MINIMUM OF +2 PERCENTAGE POINTS ABOVE THE OPTIMUM MOISTURE CONTENT FOR THE SOIL AS DIRECTED IN THE

GEOTECHNICAL REPORT.

K. SELECT FILL SHALL CONSIST OF A SLIGHTLY SILTY SAND OR SILTY/CLAYEY SAND. ALL SELECT FILL SHALL BE

APPROVED BY THE GEOTECHNICAL ENGINEER.

L. SPREAD THE SELECT FILL IN THIN LOOSE LIFTS NOT EXCEEDING 10 TO 12 INCHES THICK FOR SLIGHTLY SILTY SAND OR LIFTS NOT EXCEEDING 6 TO 8 INCHES THICK FOR SILTY/CLAYEY SAND AND UNIFORMLY COMPACT TO A MINIMUM OF 95% OF ASTM D1557 WITHIN +2 OR –2 PERCENTAGE POINTS OF THE OPTIMUM MOISTURE

CONTENT FOR THE SOIL AS RECOMMENDED IN THE GEOTECHNICAL REPORT.

M. PLACE FIRST LIFT OF SELECT FILL WET OF OPTIMUM TO PREVENT DRYING OF THE UNDERLYING SUBGRADE.

N. PROTECT FILL TO PREVENT DESICCATION PRIOR TO PLACING A SUBSEQUENT LIFT.

2. CONTACT THE GEOTECHNICAL ENGINEER FOR ANY QUESTIONS REGARDING INTERPRETATION OR CLARIFICATION OF

THE ABOVE INFORMATION.

3. FOUNDATION AND SUBGRADE PREPARATION SHALL BE MONITORED AND TESTED BY THE SOILS ENGINEER. REFER

TO SPECIFICATIONS FOR QUALITY CONTROL REQUIREMENTS.

SUBGRADE PREPARATION

1. SEE PREFABRICATED CANOPY MANUFACTURER'S DRAWINGS FOR FOUNDATIONS, BASE PLATES & A.B., COLUMN, ROOF METAL DECK, PURLINS, AND FRAMING.

2. THE GENERAL CONTRACTOR SHALL PROVIDE AND SET ANCHOR BOLTS AND EMBED PLATES AS PER

PREFABRICATED CANOPY MANUFACTURER'S DRAWINGS.

3. THE CONTRACTOR SHALL COMPARE STRUCTURAL DRAWINGS WITH PREFABRICATED CANOPY MANUFACTURER'S DRAWINGS AND REPORT ANY DISCREPANCY TO THE ENGINEER PRIOR TO FABRICATION OR INSTALLATION OF

STRUCTURAL MEMBERS.

4. PREMANUFACTURED CANOPY SHOP DRAWINGS (PLANS, DETAILS, CALCULATIONS) SHALL BEAR THE SEAL OF A

REGISTERED PROFESSIONAL ENGINEER, IN THE STATE OF THE PROJECT.

5. METAL BUILDING DESIGN LOADS SHALL BE AS FOLLOWS:

A. WIND: SEE GENERAL NOTES

LATERAL DEFLECTION LIMIT H/240

B. GRAVITY: ROOF LIVE LOAD: 20 psf REDUCIBLE PER CODE ROOF DEAD LOAD: STRUCTURE WEIGHT + 5 psf COLLATERAL +

MECHANICAL UNITS AS SHOWN.

DEFLECTION LIMITS: LL = L/360

TOTAL = L/240

PREMANUFACTURED CANOPY NOTES

Architect of Record:

ADG

800 SW ADAMS STREET, SUITE 101

PEORIA, IL 61602

R e vi si o n s

P - 309.672.6948

Discipline:Discipline:Discipline:

P - P - P -

Discipline:

P -

PROJECT NO.

DATE

DRAWN BY

STATUS

Discipline: Owner Consultant

QSC SERVICES, LLC

PMB #69

545 BRENT LN. PENSACOLA, FL

P - 309.231.8272

OWNER ID:

Design and Construction Administration Division

ESCAMBIA COUNTY, FL

100 E. BLOUNT ST. PENSACOLA, FL 32501

ESCAMBIA COUNTY AREA TRANSIT - FACILITY:

05 - FUEL STATION BUILDING

2 CLARINDA LN

PENSACOLA, FLORIDA, 32505 S001GENERAL NOTES

MEP COMPANY NAME

KEDbluestone, PEORIA, IL 61602

707 NE JEFFERSON AVE

RLG CONSULTING ENGINEERS

12001 N CENTRAL, EXPY #300

DALLAS, TX 75243

RLG CONSULTING ENGINEERS

12001 N CENTRAL, EXPY #300

DALLAS, TX 75243

214.739.8100 214.739.8100 515.259.5957

HODGSON DOUGLAS LANDSCAPE ARCHITECTS

12001 N CENTRAL EXPY, STE 1170

DALLAS, TX 75243

214.749.0333

BID PACKAGE #2 - NOT FOR CONSTRUCTION

10/22/2026

RLG

A D

D

.1

.1

ADD

ADD

NORTH CANOPY

SOUTH CANOPY

A

6'

6"

1' - 0" 1' - 0"

2' - 0"

6' - 6"

28' - 0"

6' - 6"

6'

6"

0"

0"

0"

41' - 0"

5'

0"

12' - 0" 12' - 0"

24' - 0"

11' - 0" 2' - 0" 11' - 0"

NORTH CANOPY

SOUTH CANOPY

BASE POINT COORDINATE:

N 538706' 44" E 1106715' 48"

BASE POINT COORDINATE:

N 538733' 35" E 1106679' 53"

128.65°

X300 1

X300

B

C

D

E

F

A

FR

O

M C

AN

O

PY

F

AC

E

TO

C

O

LU

M N

G

RI

D

LI

N E

6'

6"

FR

O M

C

AN

O

PY

F

AC

E

TO

C O

LU

M

N G

RI

D

LI

N

E 6'

6"

X300

EQ. EQ.

CANOPY WIDTH

24' - 0"

LE

N

GT

H

O F

TH

E

CA

N

O

PY

5'

0"

FROM CANOPY FACE TO COLUMN GRID LINE

6' - 6"

28' - 0"

FROM CANOPY FACE TO COLUMN GRID LINE

6' - 6"

CANOPY LENGTH

41' - 0"

EQ

EQ

CA

NOPY

W

ID

TH

0"

NORTH CANOPY

SOUTH CANOPY

GUTTERS AND DOWNSPOUTS ARE PROVIDED BY FUEL STATION CANOPY VENDOR.

CODE MINIMUM REQUIREMENTS ARE LISTED BELOW:

GUTTER: 3"X3"

DOWNSPOUT: 1.86 SQUARE INCHES

X300 1

X300

A

X300

NORTH CANOPY

SOUTH CANOPY

UL-2

UL-2

DS-1

DS-2

X300 1

X300

A

X300

1/8" = 1'-0"

3 REFLECTED CEILING PLAN

3D VIEW, ROOF AND EXTERIOR WALL ASSEMBLIES3D VIEW, ROOF AND EXTERIOR WALL ASSEMBLIES

Architect of Record:

ADG

800 SW ADAMS STREET, SUITE 101

PEORIA, IL 61602

Re vi sio ns

P - 309.672.6948

Discipline:Discipline:Discipline:

P - P - P -

Discipline:

P -

PROJECT NO.

DATE

DRAWN BY

STATUS

Discipline: Owner Consultant

QSC SERVICES, LLC

PMB #69

545 BRENT LN. PENSACOLA, FL

P - 309.231.8272

OWNER ID:

Design and Construction Administration Division

ESCAMBIA COUNTY, FL

100 E. BLOUNT ST. PENSACOLA, FL 32501

ESCAMBIA COUNTY AREA

TRANSIT - FACILITY:

05 - FUEL STATION CANOPIES

2 CLARINDA LN

PENSACOLA, FLORIDA, 32505

X001LAYOUT PLAN, 3D VIEWS AND WALL / ROOF

ASSEMBLIES

MEP COMPANY NAME

KEDbluestone, PEORIA, IL 61602

707 NE JEFFERSON AVE

RLG CONSULTING ENGINEERS

12001 N CENTRAL, EXPY #300

DALLAS, TX 75243

RLG CONSULTING ENGINEERS

12001 N CENTRAL, EXPY #300

DALLAS, TX 75243

214.739.8100 214.739.8100 515.259.5957

HODGSON DOUGLAS LANDSCAPE ARCHITECTS

12001 N. CENTRAL EXPRESSWAY, STE 1170

DALLAS, TX 75243

214.749.0333

BID PACKAGE #2 - NOT FOR CONSTRUCTION

11/12/2026

ADG

AD

D

/0 5/

1/8" = 1'-0"

1 LAYOUT PLAN

1/8" = 1'-0"

4 ROOF PLAN

1/8" = 1'-0"

2 EQUIPMENT PLAN

NOTE: DELEGATED DESIGN

CANOPY, FOUNDATIONS, ROOF DECK, FASCIA,

AND ROOF DRAINAGE SYSTEM INCLUDING

DOWNSPOUTS.

COORDINATE DOWNSPOUTS AT GRADE AND/OR

TIE-IN TO CIVIL UNDERGROUND STORM.

N N NN

EQUIPMENT SCHEDULEEQUIPMENT SCHEDULE

NO. DESCRIPTION FURNISHED BY INSTALLED BY Count

DS-1 ELECTRONIC FUEL DISPENSER - DIESEL SINGLE-SIDED CONTRACTOR CONTRACTOR 1

DS-2 ELECTRONIC FUEL DISPENSER - DIESEL DOUBLE-SIDED CONTRACTOR CONTRACTOR 1

UL-2 ELECTRONIC FUEL DISPENSER - UNLEADED DOUBLE-SIDED CONTRACTOR CONTRACTOR 2

PROVIDE UNDER SLAB AT VAPOR BARRIER

2'X2' LED FLAT PANEL

LIGHTING LEGEND

2'X2' LED FLAT PANEL W/ EMERGENCY

BATTERY

4" DIAMETER OPEN DOWNLIGHT

12,000 GAL ABOVE GROUND FUEL TANK - SEE CIVIL SITE SET FOR PROPOSED

FUEL TANK LOCATIONS

OWNER CONTRACTOR 3

ADD

ADD

PIPING APPLICATION SCHEDULE (PLUMBING)

SYSTEM LOCATION

DESIGN

WORKING

PRESSURE

(PSI)

MATERIAL JOINTS

USAGE SIZE

RANGE

NOTES

AUTOMOTIVE FUEL

BELOW GRADE 125

DOUBLE-WALL POLYETHYLENE

CONTAINMENT PIPING

DOUBLE-WALL FITTINGS ALL -

ABOVE GRADE 125 SCH 40 BLACK STEEL THREADED, AND/OR WELDED ALL -

B B

C C

D D

E E

F F

2" DIESEL FUEL PIPE

SERVING FUEL DISPENSER

2" DIESEL FUEL PIPE

SERVING FUEL DISPENSER

2" GASOLINE PIPE

SERVING FUEL DISPENSER

2" GASOLINE PIPE

SERVING FUEL DISPENSER

B B

C C

D D

E E

F F

2" DIESEL FUEL UP

2" DIESEL FUEL UP

D

IE

S E

L F

U E

L

G A

S O

L

IN

E

2" GASOLINE UP

2" GASOLINE UP

2" DIESEL FUEL

TO DIESEL FUEL TANKS, SEE SITE

PLAN FOR PIPE CONTINUATION

2" GASOLINE

TO GASOLINE FUEL TANK, SEE SITE

PLAN FOR PIPE CONTINUATION

KEY MAP

C03.01

C03.05

C03.03

C03.02

C03.04

5518 NW 88th Street Johnston, IA 50131 515-727-0700 www.KEDbluestone.com

KED

bluestone

Architect of Record:

ADG

800 SW ADAMS STREET, SUITE 101

PEORIA, IL 61602

R e vi si o n s

P - 309.672.6948

Discipline:Discipline:Discipline:

P - P - P -

Discipline:

P -

PROJECT NO.

DATE

DRAWN BY

STATUS

Discipline: Owner Consultant

QSC SERVICES, LLC

PMB #69

545 BRENT LN. PENSACOLA, FL

P - 309.231.8272

OWNER ID:

Design and Construction Administration Division

ESCAMBIA COUNTY, FL

100 E. BLOUNT ST. PENSACOLA, FL 32501

PROJECT NUMBER: 126-030

KEDbluestone RESERVES PROPRIETARY RIGHTS, INCLUDING

COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN

THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE

PROPERTY OF KEDbluestone AND SHALL NOT BE USED OR

REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

KEDbluestone. © 2026 KEDbluestone

ESCAMBIA COUNTY AREA TRANSIT - FACILITY:

05 - FUEL STATION CANOPIES

2 CLARINDA LN

PENSACOLA, FLORIDA, 32505 PF100PLUMBING FLOOR PLANS

KEDbluestone

707 NE JEFFERSON AVE,

PEORIA, IL 61602

RLG CONSULTING ENGINEERS

12001 N CENTRAL, EXPY #300

DALLAS, TX 75243

RLG CONSULTING ENGINEERS

12001 N CENTRAL, EXPY #300

DALLAS, TX 75243

214.739.8100 214.739.8100 515.259-5957

HODGSON DOUGLAS LANDSCAPE

12001 N. CENTRAL EXPRESSWAY, SUITE 1170

DALLAS, TX 75243

214.749.0333

BID PACKAGE 2 - NOT FOR CONSTRUCTION

10/22/2026

ADG

N

1/8" = 1'-0"

PLUMBING UNDERFLOOR PLAN

N

1/8" = 1'-0"

PLUMBING FLOOR PLAN

A D

D

/1

/2

J J

EPO

DPM

PP

T

CD CR

D#

I#

U#

PC

FAP

NEP

FAA

PIV

PS

TS

FS

SD

SD

B#

SD

DSD

RI

H

J

F

SD

A

S

S

A

S

S

AM

AR

HD

SD

ZAM

CO

VCC

DCD

F

H

S

ASD

FSD

1P 1 POLE (2P, 3P, 4P, ETC.)

A 6" ABOVE COUNTER OR BACKSPLASH

TO CENTERLINE OF DEVICE

A, AMP AMPERE

AC ABOVE COUNTER, AIR CONDITIONING UNIT

ACLG ABOVE CEILING

AF AMP FRAME

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFCI ARC FAULT CIRCUIT

INTERRUPTER

AHU AIR HANDLING UNIT

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

AMPL AMPLIFIER

ANNUN ANNUNCIATOR

APPROX APPROXIMATELY

AQ-STAT AQUASTAT

ARCH ARCHITECT, ARCHITECTURAL

AS AMP SWITCH

AT AMP TRIP

ATC AUTOMATIC TEMPERATURE CONTROLS

CONTRACTOR

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

B BLACK DEVICE COLOR WITH BLACK

UNBREAKABLE THERMOPLASTIC COVER

PLATE

BAS BUILDING AUTOMATION SYSTEM

BATT BATTERY

BD BOARD

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

C CONDUIT

CAB CABINET

CAT CATALOG

CATV CABLE TELEVISION

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CKT CIRCUIT

CLG CEILING

CM CONSTRUCTION MANAGER

COMB COMBINATION

CMPR COMPRESSOR

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

CP CIRCULATING PUMP

CRT CATHODE-RAY TUBE

CT CURRENT TRANSFORMER

CTR CENTER

CU COPPER

DEPT DEPARTMENT

DET DETAIL

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DO AUTOMATIC DOOR OPENER

DPR DAMPER

DS SAFETY DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

EC ELECTRICAL CONTRACTOR

ECB ENCLOSED CIRCUIT BREAKER

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

ELU EMERGENCY LIGHTING UNIT

EM EMERGENCY

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EP ELECTRIC PNEUMATIC

EPO EMERGENCY POWER OFF

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXIST EXISTING

EXH EXHAUST

EXP EXPLOSION PROOF

FA FIRE ALARM

FABP FIRE ALARM BOOSTER POWER

SUPPLY PANEL

FACP FIRE ALARM CONTROL PANEL

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FLUOR FLUORESCENT

FPC FIRE PROTECTION CONTRACTOR

FU FUSE

FUDS FUSED SAFETY DISCONNECT SWITCH

GA GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GFP GROUND FAULT PROTECTOR

GND GROUND

GYP BD GYPSUM BOARD

HWC-# DOMESTIC WATER CIRCULATING PUMP

HOA HANDS-OFF-AUTOMATIC SWITCH

H INSTALL DEVICE HORIZONTALLY

HH HANDHOLE

HP HORSEPOWER

HPF HIGH POWER FACTOR

HT HEIGHT

HTG HEATING

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND AIR

CONDITIONING

IC INTERRUPTING CAPACITY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

I/W INTERLOCK WITH

J-BOX JUNCTION BOX

K.E.C. KITCHEN EQUIPMENT CONTRACTOR

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LT LIGHT

LTG LIGHTING

ELECTRICAL ABBREVIATIONS

LTNG LIGHTNING

LV LOW VOLTAGE

M INSTALL DEVICE IN MILLWORK

MAX MAXIMUM

MAG.S MAGNETIC STARTER

M/C MOMENTARY CONTACT

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDC MAIN DISTRIBUTION CENTER

MDP MAIN DISTRIBUTION PANEL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MMS MANUAL MOTOR STARTER

MOA MULTIOUTLET ASSEMBLY

MSP MOTOR STARTER PANELBOARD

MSBD MAIN SWITCHBOARD

N/A NOT APPLICABLE

NFDS NON-FUSED SAFETY DISCONNECT

SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

N.O. NORMALLY OPEN

NPF NORMAL POWER FACTOR

NTS NOT TO SCALE

OC ON CENTER

OH OVERHEAD

OL OVERLOADS

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PC PLUMBING CONTRACTOR

PE PNEUMATIC ELECTRIC

PED PEDESTAL

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

PP POWER POLE

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QTY QUANTITY

RAC RIGID ALUMINUM CONDUIT

RCPT RECEPTACLE

REQD REQUIRED

RM ROOM

RMC RIGID METALLIC CONDUIT

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SHT SHEET

SIM SIMILAR

SLD SINGLE-LINE DIAGRAM

S/N SOLID NEUTRAL

SPEC SPECIFICATION

SPKR SPEAKER

SP SPARE

SPP SINGLE-POINT POWER

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

S/S STOP/START PUSHBUTTONS

STA STATION

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TEL TELEPHONE

TERM TERMINAL

T TAMPER RESISTANT

TL TWIST LOCK

T-STAT THERMOSTAT

TTC TELEPHONE TERMINAL CABINET

TV TELEVISION

TVTC TELEVISION TERMINAL CABINET

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UT UNDERGROUND TELEPHONE

UTIL UTILITY

UV ULTRAVIOLET

V VOLT

VA VOLT-AMPERES

VDT VIDEO DISPLAY TERMINAL

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WATT

W/ WITH

WG WIRE GUARD

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

#" LOCATION-SPECIFIC MOUNTING

HEIGHT ABOVE FINISHED FLOOR

TO CENTERLINE OF DEVICE

∠ ANGLE

@ AT

▲ DELTA

' FEET

" INCHES

# NUMBER

Ø PHASE

C CENTER LINE

P PLATE

EQUIPMENT GROUNDING CONDUCTOR

PHASE CONDUCTOR (SHORT LINE)

NEUTRAL CONDUCTOR (LONG LINE)

EQUIPMENT/DEVICE HOME RUN KEY

1. BRANCH CIRCUIT WIRING SHALL BE #12AWG UNLESS NOTED OTHERWISE ON THE PLAN OR IN THE SCHEDULES.

2. AS A MINIMUM, USE 10 AWG CONDUCTOR FOR 20 AMPERE, 120 VOLT BRANCH CIRCUIT HOME RUNS LONGER

THAN 100 FEET AND 277 VOLT BRANCH CIRCUIT HOME RUNS LONGER THAN 200 FEET.

3. REFER TO SPECIFICATION SECTION 260519 FOR ADDITIONAL REQUIREMENTS.

GENERAL NOTES

LIGHTING CONTROL SYMBOLS

SYMBOL DESCRIPTION

WALL SWITCH

FIRE ALARM SYMBOLS

SYMBOL DESCRIPTION

CONTROL PANEL

NOTIFICATION APPLIANCE CIRCUIT

EXTENDER PANEL

REMOTE ANNUNCIATOR PANEL

POST INDICATOR VALVE AND TAMPER

SWITCH

AIR PRESSURE SWITCH

VALVE TAMPER SWITCH

WATER FLOW SWITCH

LINEAR BEAM SMOKE DETECTOR

DUCT SMOKE DETECTOR

DUCT SMOKE DETECTOR REMOTE

INDICATOR STATION

HEAT DETECTOR ADDRESSABLE

LINEAR HEAT DETECTION CABLE

ADDRESSABLE FIRE ALARM MANUAL

PULL STATION

SMOKE DETECTOR

AUDIO/VISUAL NOTIFICATION APPLIANCE,

CEILING MOUNTED

VISUAL NOTIFICATION APPLIANCE,

CEILING MOUNTED

SPEAKER NOTIFICATION APPLIANCE,

CEILING MOUNTED

SPEAKER/VISUAL NOTIFICATION APPLIANCE,

CEILING MOUNTED

HORN NOTIFICATION APPLIANCE, WALL

MOUNTED

AUDIO/VISUAL NOTIFICATION APPLIANCE,

WALL MOUNTED

SPEAKER NOTIFICATION APPLIANCE,

WALL MOUNTED

SPEAKER/VISUAL NOTIFICATION

APPLIANCE, WALL SWITCH

VISUAL NOTIFICATION APPLIANCE, WALL

MOUNTED

ADDRESSABLE MONITOR MODULE

ADDRESSABLE RELAY MODULE

HVAC ELEVATOR HOISTWAY DAMPER

HVAC SMOKE DAMPER

MAGNETIC DOOR HOLDER

ZONE ADAPTER MODULES

CEILING MOUNT SENSOR, DUAL

TECHNOLOGY

CEILING MOUNT SENSOR, INFRARED

TECHNOLOGY

CEILING MOUNT SENSOR, ULTRASONIC

TECHNOLOGY

GENERAL ELECTRICAL SYMBOLS

LINEAR BEAM SMOKE DETECTOR

BEAM SMOKE REFLECTOR

CO DETECTOR

ELECTRICAL CONNECTION

EMERGENCY STOP PUSH BUTTON

DIGITAL POWER METER

UTILITY TRANSFORMER

SWITCHBOARD

PANELBOARD

TRANSFORMER

DISCONNECT SWITCH

UTILITY POWER METER

VOICE COMMAND CENTER

DUCT CO DETECTOR

BELL

HIGH FIDELITY SPEAKER - CEILING MOUNT

AIR SAMPLING SMOKE DETECTOR

HIGH FIDELITY SPEAKER - WALL MOUNT

COMBINATION STARTER

ELECTRICAL EQUIPMENT

(DASHED LINES INDICATE CODE REQUIRED CLEARANCES)

BREAKER FUNCTION SCHEDULE

SYMBOL DESCRIPTION

A ARC FAULT INTERUPTER (AFCI)

AR ARC ENERGY REDUCTION MAINTENANCE SWITCH

E EXISTING BREAKER TO REMAIN

EM PROVIDE IDENTIFICATION PER NEC 700.12(I)(2)(4)

EN EXISTING BREAKER SERVING NEW CIRCUIT

G GROUND FAULT CIRCUIT INTERUPTER (GFCI) PROTECTION (5mA) GE GROUND FAULT CIRCUIT INTERUPTER FOR EQUIPMENT (30mA)

GF ADJUSTABLE GROUND FAULT PROTECTION FOR EQUIPMENT

HL HANDLE LOCK TO LOCK BREAKER IN CLOSED POSITION (RED FOR FIRE ALARM)

K# KEY INTERLOCK (# REPRESENTS GROUPED KEYING)

LSI LONG-TIME, SHORT-TIME, INSTANTANEOUS ADJUSTMENT

LSIG LONG-TIME, SHORT-TIME, INSTANTANEOUS ADJUSTMENT, AND GROUND FAULT ADJUSTMENT

LSIA LONG-TIME, SHORT-TIME, INSTANTANEOUS ADJUSTMENT, AND GROUND FAULT ALARM

N NEW BREAKER IN EXISTING PANEL

NE NEW BREAKER SERVING EXISTING CIRCUIT

SD DENOTE SERVICE DISCONNECT

ST SHUNT TRIP (120V OPERATED UNLESS NOTED OTHERWISE)

GENERAL PLAN SYMBOLS

NEW WORK BY THE EC (DARK SOLID LINE)

WORK BY OTHERS AND/OR EXISTING (LIGHT SOLID LINE)

DEMO WORK BY THE EC (DARK DASHED LINE)

NEW UNDERGROUND WORK BY THE EC (DARK DASHED LINE)

MATCHLINE

KEYED NOTE

LIGHTING CONTROL CALLOUT SYMBOL (DIAMOND)

1 ELECTRICAL EQUIPMENT SYMBOL (OCTAGON)

SECTION VIEW, TOP REPRESENTS DETAIL NUMBER, BOTTOM REPRESENTS SHEET NUMBER

ENLARGED VIEW, TOP REPRESENTS VIEW NUMBER, BOTTOM REPRESENTS SHEET NUMBER

POWER SYMBOLS

SYMBOL DESCRIPTION

DUPLEX / DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R

CORD REEL / CORD DROP

SIMPLEX RECEPTACLE, NEMA 5-20R

SPECIAL RECEPTACLE

RECESSED FLOOR BOX OR POKE-THRU

DUPLEX / DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, EMERGENCY POWER

MARK SCHEDULED EQUIPMENT (UNDERLINED)

MARK NONSCHEDULED EQUIPMENT

(E) MARK EXISTING EQUIPMENT - (E) PREFIX (HALFTONE)

(R) MARK EXISTING RELOCATED EQUIPMENT - (R) PREFIX

AUTOMATIC DOOR PUSH PAD

CEILING MOUNTED RECEPTACLE, NEMA 5-20R

LIGHTING SYMBOLS

SYMBOL DESCRIPTION

RECESSED MOUNTED (DIAGONAL SLASH)

RECESSED DOWNLIGHT (ARROW

INDICATES WALL WASH)

EMERGENCY LIGHT

POLE MOUNTED SITE FIXTURE

SURFACE OR PENDANT FIXTURE (DOTS)

WALL MOUNTED FIXTURE (STEM OR STEMS)

SURFACE MOUNTED

CRITICAL FIXTURE (FULL SHADED)

LIFE SAFETY (HALF SHADED)

SINGLE / DOUBLE FACED EXIT SIGN

EMERGENCY REMOTE HEAD (SINGLE/DOUBLE)

COMBINATION EXIT/EMERGENCY LIGHT

CYLINDRICAL FIXTURE (ARROW INDICATES

WALL WASH)

SURFACE MOUNT MULTI-OUTLET ASSEMBLY

FIRE SMOKE DAMPER

GROUND BAR

HAND HOLEHH-#

PHOTOCELL

HORSE POWER RATED SWITCH

H

BR

LHD

X

1. ALL INSTALLATIONS SHALL COMPLY WITH ALL APPLICABLE FEDERAL, STATE, AND LOCAL CODES INCLUDING, BUT NOT LIMITED TO, THE FLORIDA BUILDING CODES, AMERICANS WITH DISABILITIES ACT (ADA) ACCESSIBILITY GUIDELINES, AND THE INTERNATIONAL ENERGY CONSERVATION CODE (IECC). THE AUTHORITY HAVING JURISDICTION (AHJ) SHALL HAVE FINAL APPROVAL OF ALL INSTALLATIONS AND PRACTICES.

2. ALL MATERIALS FURNISHED SHALL BE NEW, FREE OF DEFECTS, AND LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) UNLESS NOTED

OTHERWISE.

3. INSTALLATION OF EQUIPMENT SHALL COMPLY WITH CURRENT STANDARDS AND SPECIFICATIONS APPROVED BY THE AHJ. INSTALL ALL CABLES AND WIRING IN CONDUIT OR RACEWAY UNLESS NOTED OTHERWISE. DO NOT SUPPORT CABLES OR WIRING FROM CEILING DEVICES, PIPING, DUCTWORK, OR CEILING

FRAMING. PROVIDE NEW WIRING FOR ALL BRANCH CIRCUITS AND FEEDERS.

4. FEEDERS SHOWN ON DRAWINGS ARE SCHEMATIC ONLY. CONDUIT RUNS SHALL NOT INCLUDE BENDS GREATER THAN 90 DEGREES. CONDUITS ABOVE

GRADE SHALL BE RUN PARALLEL OR PERPENDICULAR TO BUILDING LINES AND STRUCTURE.

5. CIRCUIT WIRING FOR THE EMERGENCY SYSTEM SHALL BE INSTALLED IN SEPARATE CONDUITS OR RACEWAYS AND SHALL REMAIN COMPLETELY

INDEPENDENT OF ALL OTHER WIRING AND EQUIPMENT PER NEC REQUIREMENTS.

6. ALL FEEDER AND BRANCH CIRCUITS TO PANELS, MOTORS, LIGHT FIXTURES, RECEPTACLES, AND GENERAL DISTRIBUTION EQUIPMENT SHALL INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR SIZED PER THE NEC. THE CONDUIT SYSTEM SHALL NOT BE USED AS AN EQUIPMENT GROUND.

7. REFER TO MECHANICAL AND PLUMBING EQUIPMENT SCHEDULES FOR EQUIPMENT CONNECTIONS, DISCONNECT REQUIREMENTS, AND CONTROLS. THE ELECTRICAL CONTRACTOR (EC) SHALL PROVIDE AND INSTALL ALL ITEMS INDICATED AS “BY EC” ON THE MECHANICAL AND PLUMBING SCHEDULES.

8. ALL WIRING AND FEEDER SIZES SHOWN ARE BASED ON COPPER CONDUCTORS UNLESS NOTED OTHERWISE. USE OF ALUMINUM FEEDER CONDUCTORS SHALL REQUIRE ENGINEER REVIEW OF FAULT CURRENT AND VOLTAGE DROP PRIOR TO INSTALLATION.

9. THE CONTRACTOR SHALL COORDINATE INSTALLATION OF ELECTRICAL SYSTEMS AND ALL EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS TO MAINTAIN

NEC-REQUIRED CLEARANCES, INCLUDING WORKING CLEARANCES AT ELECTRICAL DISTRIBUTION EQUIPMENT AND INSTALLATIONS ABOVE ACCESSIBLE

CEILINGS.

10. CONDUIT FOR POWER WIRING MAY BE INSTALLED BELOW FLOOR SLABS UNLESS NOTED OTHERWISE. RACEWAYS FOR LOW-VOLTAGE CABLING (CONTROLS, TELECOMMUNICATIONS, ETC.) SHALL NOT BE INSTALLED BELOW OR WITHIN FLOOR SLABS UNLESS SPECIFICALLY NOTED. WHERE LOW-VOLTAGE CABLING IS ROUTED BELOW OR WITHIN SLABS, CONTRACTOR SHALL VERIFY CABLING IS LISTED FOR SUCH USE.

11. ALL ELECTRICAL CONDUCTORS SHALL BE STRANDED COPPER WITH TYPE THHN/THWN INSULATION UNLESS NOTED OTHERWISE. MINIMUM WIRE SIZE SHALL

BE #12 AWG FOR GENERAL WIRING AND #10 AWG FOR HOMERUNS. REFER TO SPECIFICATIONS OR SHEET-SPECIFIC NOTES FOR ADDITIONAL INFORMATION.

12. ALL NEW CIRCUITS REQUIRING NEUTRAL CONDUCTORS SHALL HAVE DEDICATED NEUTRALS. SHARED NEUTRALS ARE NOT PERMITTED.

13. A GREEN EQUIPMENT GROUNDING CONDUCTOR SHALL BE PROVIDED TO ALL LOADS. THE CONDUCTOR SHALL BE SIZED PER THE NEC. ALL GROUNDING

CONDUCTORS SHALL BE INSTALLED IN CONDUIT.

14. ALL BUILDING WIRING SHALL BE INSTALLED IN CONDUIT TO ACHIEVE CIRCUITING AS SHOWN. MINIMUM BRANCH CONDUIT SIZE SHALL BE 3/4" UNLESS NOTED

OTHERWISE. SIZE CONDUCTORS PER NEC AMPACITY AND CONDUIT FILL REQUIREMENTS.

15. ALL HOME RUN CONDUITS FROM ELECTRICAL PANELBOARDS TO THE FIRST JUNCTION BOX SHALL BE A MINIMUM OF 1" CONDUIT AND SHALL TERMINATE IN A

4-11/16" SQUARE BY 2-1/8" DEEP (MINIMUM) JUNCTION BOX. JUNCTION BOX COVERS SHALL BE PAINTED AND CLEARLY MARKED WITH CIRCUIT NUMBERS.

EACH HOME RUN RACEWAY SHALL HAVE SPARE CAPACITY FOR ONE (1) ADDITIONAL CIRCUIT AND ITS DEDICATED NEUTRAL.

16. MC CABLING SHALL NOT BE USED UNLESS SPECIFICALLY NOTED OTHERWISE.

17. ALL CONDUITS SHALL BE CONCEALED IN WALLS, ABOVE CEILINGS, ETC., WHERE POSSIBLE.

18. ALL CONDUIT ROUTED EXPOSED IN FINISHED SPACES SHALL BE ROUTED PARALLEL OR PERPENDICULAR TO WALLS AND CEILINGS. EXPOSED CONDUIT

ROUTING SHALL BE REVIEWED WITH THE ARCHITECT AND ENGINEER PRIOR TO INSTALLATION.

19. COORDINATE THE EXACT LOCATION OF ALL DEVICES ABOVE OR BELOW COUNTERTOPS OR SIMILAR INSTALLATIONS WITH OTHER TRADES, ARCHITECTURAL

ELEVATIONS, AND APPROVED SUBMITTALS PRIOR TO ROUGH-IN. ARCHITECTURAL ELEVATIONS AND DETAILS TAKE PRECEDENCE OVER ELECTRICAL

DRAWINGS.

20. ALL CUTTING AND PATCHING REQUIRED FOR CONDUITS, DEVICES, OR OTHER ELECTRICAL EQUIPMENT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL

CONTRACTOR UNLESS NOTED OTHERWISE.

21. ALL PENETRATIONS THROUGH FIRE-RATED WALLS, FLOORS, AND CEILINGS SHALL BE SEALED WITH AN NRTL-APPROVED FIRESTOP SYSTEM EQUAL TO OR

EXCEEDING THE RATING OF THE PENETRATED ASSEMBLY.

22. COORDINATE LOCATIONS OF ALL ELECTRICAL ITEMS INCLUDING, BUT NOT LIMITED TO, LIGHTING FIXTURES, CEILING-MOUNTED DEVICES (OCCUPANCY

SENSORS, FIRE ALARM DEVICES, SPEAKERS, ETC.), SPRINKLER HEADS, AND HVAC DIFFUSERS/RETURNS. CENTER DEVICES IN CEILING TILES WHERE

POSSIBLE.

23. ALL CEILING DEVICES REQUIRING WIRE TERMINATIONS SHALL BE INSTALLED WITH MANUFACTURER-RECOMMENDED BACK BOXES AND SUPPORTS AS

REQUIRED BY THE NEC OR MANUFACTURER.

24. COORDINATE ALL MOUNTING OF ELECTRICAL MATERIALS, EQUIPMENT, AND DEVICES REQUIRED FOR EQUIPMENT SUPPLIED BY OTHERS. ELECTRICAL

INSTALLATIONS SHALL NOT INTERFERE WITH OPERATION OR ACCESS. ALL SUCH INSTALLATIONS SHALL BE REVIEWED AND APPROVED BY THE SUPPLYING

CONTRACTOR PRIOR TO ROUGH-IN.

25. BOXES LOCATED ON OPPOSITE SIDES OF FIRE-RATED WALLS SHALL BE OFFSET A MINIMUM OF 24" OR SHALL BE PROTECTED WITH A FIRE-RATED

MATERIAL EQUAL TO OR GREATER THAN THE WALL RATING.

26. BOXES LOCATED ON OPPOSITE SIDES OF NON-FIRE-RATED WALLS SHALL BE OFFSET A MINIMUM OF 6".

27. REMOVE AND REINSTALL CEILING TILES AS NECESSARY TO PERFORM REQUIRED ELECTRICAL WORK. REPLACE ALL DAMAGED CEILING TILES WITH NEW

TILES OF THE SAME MANUFACTURER AND MODEL.

28. PROVIDE FIELD TYPED PANELBOARD DIRECTORIES TO REFLECT AS-CONSTRUCTED CONDITIONS.

29. ALL REQUESTS FOR CHANGE PROPOSALS SHALL INCLUDE DETAILED BREAKDOWNS OF MATERIALS, LABOR, AND SUBCONTRACTOR COSTS. SUPPLIER

QUOTES SHALL BE PROVIDED ON SUPPLIER LETTERHEAD. LABOR UNITS FOR NEW MATERIAL INSTALLATIONS SHALL NOT EXCEED 75% OF NECA 1 “NORMAL

CONDITION” RATES WITHOUT SPECIFIC APPROVAL.

30. BID PACKAGE RESPONSIBILITY: EACH BID PACKAGE SHALL BE CONSIDERED INDEPENDENT AND COMPLETED. THE CONTRACTOR SHALL INCLUDE ALL LABOR, MATERIAL, EQUIPMENT, ACCESSORIES, COORDINATION, CONNECTIONS, EXCAVATION, BACKFILL, RESTORATION, TESTING AND OTHER WORK NECESSARY TO PROVIDE A COMPLETE AND OPERATIONAL INSTALLATION FOR THAT WORK INCLUDED WITHIN THAT BID PACKAGE. DO NOT ASSUME THAT WORK REQUIRED FOR A COMPLETE INSTALLATION WILL BE PROVIDED UNDER ANOTHER BID PACKAGE UNLESS SPECIFICALLY INDICATED.

5518 NW 88th Street Johnston, IA 50131 515-727-0700 www.KEDbluestone.com

KED

bluestone

Architect of Record:

ADG

800 SW ADAMS STREET, SUITE 101

PEORIA, IL 61602

R e vi si o n s

P - 309.672.6948

Discipline:Discipline:Discipline:

P - P - P -

Discipline:

P -

PROJECT NO.

DATE

DRAWN BY

STATUS

Discipline: Owner Consultant

QSC SERVICES, LLC

PMB #69

545 BRENT LN. PENSACOLA, FL

P - 309.231.8272

OWNER ID:

Design and Construction Administration Division

ESCAMBIA COUNTY, FL

100 E. BLOUNT ST. PENSACOLA, FL 32501

PROJECT NUMBER: 126-030

KEDbluestone RESERVES PROPRIETARY RIGHTS, INCLUDING

COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN

THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE

PROPERTY OF KEDbluestone AND SHALL NOT BE USED OR

REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

KEDbluestone. © 2026 KEDbluestone

ESCAMBIA COUNTY AREA TRANSIT - FACILITY:

05 - FUEL STATION CANOPIES

2 CLARINDA LN

PENSACOLA, FLORIDA, 32505 EF000ELECTRICAL COVER PAGE

KEDbluestone

707 NE JEFFERSON AVE,

PEORIA, IL 61602

RLG CONSULTING ENGINEERS

12001 N CENTRAL, EXPY #300

DALLAS, TX 75243

RLG CONSULTING ENGINEERS

12001 N CENTRAL, EXPY #300

DALLAS, TX 75243

214.739.8100 214.739.8100 515.259-5957

HODGSON DOUGLAS LANDSCAPE

12001 N. CENTRAL EXPRESSWAY, SUITE 1170

DALLAS, TX 75243

214.749.0333

BID PACKAGE 2 - NOT FOR CONSTRUCTION

10/22/2026

ADG

ELECTRICAL SHEET LIST

EF000 ELECTRICAL COVER PAGE

ES101 ELECTRICAL BID #2 SITE PLAN

ES102 ELECTRICAL SITE LIGHTING PLAN

ES103 ELECTRICAL SITE PHOTOMETRIC PLAN

ELF100 ELECTRICAL LIGHTING PLAN

EPF100 ELECTRICAL POWER PLAN

EPF300 ELECTRICAL ROOF PLAN

EF500 ELECTRICAL DETAILS

EF501 ELECTRICAL DETAILS

EF600 ELECTRICAL SCHEDULES

A D

D

/1

/2

B B

C C

D D

E E

F F

F7 F7

F7 F7

F7 F7

F7 F7

F7 F7

F7

F7

F7

F7

HEF1-2

'HEF1' 'LEF1'

1 1

12" x 12" NEMA 4X BOX WITH

SITE WINDOW. CONTAINS

PHOTOCELL, NLIGHT RELAY

AND 2-POLE DOUBLE THROW

OVERRIDE SWITCH FOR

CANOPY LIGHTING.

'XFMR-LEF1'

GDS-1

ELECTRICAL CONTRACTOR

TO ROUTE (2) 1" CONDUITS

TO FEED FARE PROCESSING

AND VESTIBULE LIGHTS AND

NLIGHT LIGHTING CONTROL

CABLING IN THE WASH

BUILDING FROM PANEL 'HEF1'.

(3) #10 IN 1" CONDUIT FROM HEF1-2

(3) #10 IN 1" CONDUIT FROM HEF1-7

HEF1-7

FUEL TANK BY OTHERS

FUEL TANK BY OTHERS

FUEL TANK BY OTHERS

45 kVA

NEMA 3R

KEY MAP

C03.01

C03.05

C03.03

C03.02

C03.04

5518 NW 88th Street Johnston, IA 50131 515-727-0700 www.KEDbluestone.com

KED

bluestone

Architect of Record:

ADG

800 SW ADAMS STREET, SUITE 101

PEORIA, IL 61602

R e vi si o n s

P - 309.672.6948

Discipline:Discipline:Discipline:

P - P - P -

Discipline:

P -

PROJECT NO.

DATE

DRAWN BY

STATUS

Discipline: Owner Consultant

QSC SERVICES, LLC

PMB #69

545 BRENT LN. PENSACOLA, FL

P - 309.231.8272

OWNER ID:

Design and Construction Administration Division

ESCAMBIA COUNTY, FL

100 E. BLOUNT ST. PENSACOLA, FL 32501

PROJECT NUMBER: 126-030

KEDbluestone RESERVES PROPRIETARY RIGHTS, INCLUDING

COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN

THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE

PROPERTY OF KEDbluestone AND SHALL NOT BE USED OR

REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

KEDbluestone. © 2026 KEDbluestone

ESCAMBIA COUNTY AREA TRANSIT - FACILITY:

05 - FUEL STATION CANOPIES

2 CLARINDA LN

PENSACOLA, FLORIDA, 32505 ELF100ELECTRICAL LIGHTING PLAN

KEDbluestone

707 NE JEFFERSON AVE,

PEORIA, IL 61602

RLG CONSULTING ENGINEERS

12001 N CENTRAL, EXPY #300

DALLAS, TX 75243

RLG CONSULTING ENGINEERS

12001 N CENTRAL, EXPY #300

DALLAS, TX 75243

214.739.8100 214.739.8100 515.259-5957

HODGSON DOUGLAS LANDSCAPE

12001 N. CENTRAL EXPRESSWAY, SUITE 1170

DALLAS, TX 75243

214.749.0333

BID PACKAGE 2 - NOT FOR CONSTRUCTION

10/22/2026

ADG

N

1/8" = 1'-0"

ELECTRICAL LIGHTING PLAN

KEYED NOTES:

1. PANEL SHALL BE LOCATED NEARBY

INDICATED LOCATION MOUNTED TO STRUT.

GENERAL NOTES:

1. ALL WIRING, RACEWAYS AND BOXES SHALL MEET NEC ARTICLE

514 CLASS 1 DIVISION 2 SPECIFICATIONS UNDER THE FUEL

CANOPY OR WITHIN 20' OF FUEL PUMPS.

2. ELECTRICAL CONTRACTOR TO COORDINATE FINAL SECURITY

CAMERA PLACEMENTS ON SITE LIGHTING POLE PRIOR TO

ORDERING LIGHT POLES. REFER TO TECHNOLOGY PLANS FOR

EXACT CAMERA PLACEMENT ON POLES.

A D

D

/1

/2

B B

C C

D D

E E

F F

UL-2 GAS

FUELING

PUMP

UL-2 GAS

FUELING

PUMP

DIESEL

FUELING

PUMP

DIESEL

FUELING

PUMP

DS-UL-2 GAS FUELING PUMP

30/1/4X

DS-UL-2 GAS FUELING PUMP

30/1/4X

DS-1-DIESEL FUELING PUMP

30/1/4X

DS-2-DIESEL FUELING PUMP

30/1/4X

'HEF1' 'LEF1'

GDS-1

T

1 1

FUEL

SHUT-OFF

FUEL TANK SHUT-OFF MOUNTED

TO TANK. FURNISH AND INSTALL

UNISTRUT RACKING AS REQUIRED

TO MOUNT EQUIPMENT

GAS

GAS

FUEL TANK

FUEL TANK

FUEL TANK

LEF1-5,7

LEF1-2,4

LEF1-8,10

MOUNT TO

STRUT

LEF1-21

CONCRETE SLAB

CONDUIT TO FEED

INTEGRAL FUEL

TANK PUMPS FROM

LEF1-(2,4),(5,7),(8,10)

ELECTRICAL CONTRACTOR

TO ROUTE CONDUIT TO

MAINTENANCE YARD TO

FEED GDS-1

ELECTRICAL CONTRACTOR

TO ROUTE CONDUIT TO

VAULT ROOM FOR LIGHTING

AND EQUIPMENT IN WASH

BUILDING FROM PANEL 'LEF1'

SEE DRAWING E600 FOR CIRCUITS

LEF1-16

LEF1-17

LEF1-11

LEF1-1

4 SETS OF

(3) #10 IN 1" CONDUIT

FROM LEF1-1,11,16,17

FUEL TANK BY OTHERS

FUEL TANK BY OTHERS

FUEL TANK BY OTHERS

LEF1-20

45 kVA

NEMA 3R

'XFMR-LEF1'

MGB-1

KEY MAP

C03.01

C03.05

C03.03

C03.02

C03.04

5518 NW 88th Street Johnston, IA 50131 515-727-0700 www.KEDbluestone.com

KED

bluestone

Architect of Record:

ADG

800 SW ADAMS STREET, SUITE 101

PEORIA, IL 61602

R e vi si o n s

P - 309.672.6948

Discipline:Discipline:Discipline:

P - P - P -

Discipline:

P -

PROJECT NO.

DATE

DRAWN BY

STATUS

Discipline: Owner Consultant

QSC SERVICES, LLC

PMB #69

545 BRENT LN. PENSACOLA, FL

P - 309.231.8272

OWNER ID:

Design and Construction Administration Division

ESCAMBIA COUNTY, FL

100 E. BLOUNT ST. PENSACOLA, FL 32501

PROJECT NUMBER: 126-030

KEDbluestone RESERVES PROPRIETARY RIGHTS, INCLUDING

COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN

THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE

PROPERTY OF KEDbluestone AND SHALL NOT BE USED OR

REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

KEDbluestone. © 2026 KEDbluestone

ESCAMBIA COUNTY AREA TRANSIT - FACILITY:

05 - FUEL STATION CANOPIES

2 CLARINDA LN

PENSACOLA, FLORIDA, 32505 EPF100ELECTRICAL POWER PLAN