ECAT_BP2_DRAWING_SET_-_05_FUEL_STATION_Rev_1__26-11-13.pdf
PDF 3 MB Posted
- Solicitation number
- PD 26-27.004
- Issued by
- Escambia County, Florida
About this file
This is a drawing set for Bid Package #2 of the Escambia County Area Transit (ECAT) Facility Fuel Station, a construction project located at 2 Clarinda Lane in Pensacola, Florida. The drawing package includes structural, architectural, plumbing, electrical, and technology specifications for the fuel station canopies and associated equipment. The fuel station comprises two canopies (north and south) measuring 125 feet in length and 24 feet in width, designed to accommodate electronic fuel dispensers for diesel and unleaded gasoline, above-ground fuel tanks, and related infrastructure. The project is governed by the 8th Edition of the Florida Building Code as adopted by Escambia County, with design parameters including wind speeds of 156 mph (basic) and 121 mph (ASD), seismic design category D, and soil bearing capacity of 1.5 ksf. The drawing set was last revised on November 12, 2026, and includes detailed notes on deferred submittals, shop drawings, pre-engineered canopy requirements, concrete specifications, reinforcing steel standards, and post-installed anchor installation procedures. Key consulting firms include ADG (Architect of Record), RLG Consulting Engineers, KEDbluestone, and Hodgson Douglas Landscape Architects.
The structural design incorporates a prefabricated canopy system with delegated design responsibility assigned to the canopy manufacturer, requiring that all shop drawings be sealed by a registered professional engineer in Florida. Foundation design is based on Geotechnical Report #26-162 prepared by Larry M Jacobs & Associates, with continuous and isolated footing bearing capacities of 1.5 ksf and soil sliding resistance of 0.5 ksf. All concrete work must comply with ACI 318, with compressive strength of 4,000 psi for footings and all other concrete elements, and concrete protection for reinforcement of 3 inches for footings and 2 inches for walls. The electrical system includes a 45 kVA transformer (XFMR-LEF1), two branch circuit panelboards (HEF1 and LEF1), LED lighting fixtures, and emergency power-off systems meeting NEC Article 514 Class 1 Division 2 specifications for hazardous fuel station environments. Plumbing systems include double-wall polyethylene containment piping below grade and schedule 40 black steel piping above grade, sized for automotive fuel delivery at 125 psi working pressure. The technology scope encompasses security camera systems, access control, mass notification speakers, intercom systems, and data infrastructure, with coordination required between the electrical contractor and technology system providers.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGN DATA
1. THE DESIGN OF THE STRUCTURE AND PARTS THEREOF IS IN ACCORDANCE WITH THE 8TH EDITION OF FLORIDA BUILDING
CODE, AS AMENDED AND ADOPTED BY ESCAMBIA COUNTY.
2. ROOF LIVE LOADS:
AREA UNIFORM SPECIAL COMMENTS
ROOF, GENERAL
LIVE LOAD REDUCTION
20 psf -
ROOF, EQUIP LOADS SEE ROOF PLAN
3. SNOW LOADS: NOT APPLICABLE PER FBC
FACTORED COMPONENTS AND CLADDING WALL LOADS
POSITIVE PRESSURE (psf) NEGATIVE PRESSURE (psf)
AREA (SQ FT)
LESS THAN 10
GREATER THAN 500
INTERIOR & CORNER ZONE INTERIOR ZONE CORNER ZONE
47 -52
-46
-41
-38 -37
-44
-54
-47
CORNER ZONE IS A DISTANCE OF 3'-0" FROM WALL CORNERS
LINEAR INTERPOLATE FOR LOADS BETWEEN SPECIFIED AREAS
6. FLOOD DESIGN DATA:
THIS PROJECT IS NOT LOCATED WITHIN A FLOOD HAZARD AREA
7. SPECIAL LOADS:
VEHICULAR BARRIERS
AREA
AWNINGS & CANOPIES
UNIFORM
20 psf
6.0 ksf
CONCENTRATED
300 lbs.
IMPACT SECTION OF CODE
FBC 1607.9
FBC 1607.13.4
8. ROOF RAIN LOAD DATA:
RAIN INTENSITY (15-DURATION)
4.9 in/hr
FACTORED COMPONENTS AND CLADDING ROOF LOADS
POSITIVE PRESSURE (psf) NEGATIVE PRESSURE (psf)
AREA (SQ FT)
LESS THAN 10
GREATER THAN 500
PERIMETER ZONE, "B" IS A DISTANCE OF 17'-6" FROM EDGE OF BUILDING
CORNER ZONE, "C" IS A DISTANCE OF 6'-0" FROM EDGE OF BUILDING
ZONE 2 ZONE 3 ZONE 2
-119
-92
-83
-73
ZONE 3
-166
-111
-94
-73
LINEAR INTERPOLATE FOR LOADS BETWEEN SPECIFIED AREAS
3 3
B
C
ROOF WIND LOAD LAYOUT
YES, PER FBC 1607.14
RAIN INTENSITY (60-DURATION)
9.12 in/hr
4. WIND DESIGN DATA:
ASD WIND SPEED Vasd 121 mph
RISK CATEGORY
BASIC WIND SPEED (3 SECOND GUST)
WIND EXPOSURE
INTERNAL PRESSURE COEFFICIENT
COMPONENTS AND CLADDING
156 mph
+/- 0.00
PER ASCE 7-22
N/A
N/A
TORNADO SPEED, Vt
EFFECTIVE PLAN AREA
II
C
6. SEISMIC DESIGN DATA:
SEISMIC IMPORTANCE FACTOR, Ie
MAPPED SPECTRAL RESPONSE ACCEL.
RISK CATEGORY
SITE CLASS
SPECTRAL RESPONSE COEFFICIENTS
SEISMIC DESIGN CATEGORY
Ss =
BASIC SEISMIC-FORCE-RESISTING SYSTEM
DESIGN BASE SHEAR
SEISMIC RESPONSE COEFFICIENT, Cs
RESPONSE MODIFICATION FACTOR, R
ANALYSIS PROCEDURE USED
SDS =
S1 =
SD1 =
0.11 0.063
0.090.1
0.033xW
1.0
II
DEFAULT
B
STEEL SYSTEMS NOT SPECIFICALLY
DETAILED FOR SEISMIC RESISTANCE
0.033
3.0
EQUIVALENT LATERAL FORCE
1. PROJECT SPECIFICATIONS ARE A PART OF THE CONTRACT DOCUMENTS. CONTRACTOR SHALL REVIEW THE SPECIFICATIONS AND NOTIFY ARCHITECT OF DISCREPANCIES BEFORE PROCEEDING WITH WORK.
2. STRUCTURAL DRAWINGS ARE AN INTEGRAL COMPONENT TO THE CONTRACT DOCUMENTS. CONTRACTOR SHALL
REVIEW AND COORDINATE ACCORDINGLY.
A. PRIOR TO FABRICATION OR INSTALLATION OF STRUCTURAL MEMBERS, CONTRACTOR SHALL COMPARE
STRUCTURAL DIMENSIONS AND SECTIONS WITH ARCHITECTURAL DIMENSIONS AND SECTIONS.
DISCREPANCIES ARE TO BE REPORTED IN WRITING TO THE ARCHITECT.
B. PRINCIPAL OPENINGS ARE SHOWN ON THESE DRAWINGS. REFER TO ARCHITECTURAL, MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR OTHER OPENINGS NOT SHOWN.
C. REFER TO ARCHITECTURAL DRAWINGS FOR ELEVATIONS AND LOCATIONS OF SLAB DEPRESSIONS AND
CURBS NOT SHOWN. PROVIDE POSITIVE SLOPE TO ALL DRAINS.
D. CONTRACTOR SHALL COORDINATE PENETRATIONS, SLEEVES, CURBS, AND INSERTS REQUIRED FOR THE
CONTRACT DOCUMENTS.
E. CONTRACTOR SHALL VERIFY SIZE, WEIGHT, LOCATION, AND SUPPORT CONDITIONS OF MECHANICAL
EQUIPMENT SUPPORTED ON OR SUSPENDED FROM THE ROOF OR FLOORS.
F. CONTRACTOR SHALL COORDINATE CONSTRUCTION WITH ADJACENT STRUCTURES AND UTILITIES.
G. CONTRACTOR SHALL NOTIFY IN WRITING THE ARCHITECT & ENGINEER OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH WORK.
3. TEMPORARY SHORING AND BRACING DURING CONSTRUCTION
A. CONTRACTOR SHALL PROVIDE TEMPORARY BRACING OF COMPONENTS DURING CONSTRUCTION TO MEET
REGULATORY REQUIREMENTS FOR SAFETY.
B. CONTRACTOR SHALL PROVIDE TEMPORARY SHORING AND BRACING OF WALLS AND GRADE BEAMS DURING
CONSTRUCTION. SHORE WALLS AND GRADE BEAMS DURING THE BACKFILLING AND COMPACTION PROCESS.
C. CONTRACTOR SHALL PROVIDE NECESSARY TEMPORARY BRACING AND SHORING DURING CONSTRUCTION
UNTIL STRUCTURAL FRAMING AND DIAPHRAGMS ARE COMPLETED. TEMPORARY BRACING SHALL BE
DESIGNED UNDER THE SUPERVISION OF A LICENSED ENGINEER.
4. SELECTION OF CONSTRUCTION MEANS, METHODS, TECHNIQUES, AND PROCEDURES, AS WELL AS SAFETY PRECAUTIONS AND PROGRAMS, ARE SOLELY THE CONTRACTOR’S RESPONSIBILITIES. AS SUCH, CONSTRUCTION ENGINEERING AND DESIGN RESULTING FROM THESE SELECTIONS IS THE RESPONSIBILITY OF THE CONTRACTOR.
A. EXAMPLES INCLUDE, BUT ARE NOT LIMITED TO, ENGINEERING OF SHORING AND SCAFFOLDING SYSTEMS;
LOAD CHECKS AND STRUCTURAL MODIFICATIONS FOR STORAGE, STAGING, AND CONSTRUCTION
EQUIPMENT LOADING; MEANS OF EGRESS FOR HEAVY EQUIPMENT; CRANE SELECTION, LOCATION, SUPPORT
AND BRACING; TEMPORARY HOISTS, LIFTS AND PLATFORMS.
B. CONTRACTOR SHALL ENSURE THAT APPROPRIATE ENGINEERING IS PERFORMED BY A LICENSED ENGINEER FOR THE WORK, CONSULTED WITH ON FIELD MODIFICATIONS, SPECIFY APPROPRIATE LEVELS OF
INSPECTION OF THE WORK, AND TO REVIEW INSPECTION REPORTS.
C. CONSTRUCTION ENGINEERING FEES HAVE NOT BEEN INCLUDED IN THE BASE FEE TO THE
OWNER/ARCHITECT. IF REQUESTED, THE EOR MAY CONSIDER PERFORMING THESE SERVICES AS AN
ADDITIONAL SERVICE PAID BY THE CONTRACTOR.
5. PRE-CONSTRUCTION MEETINGS SHALL BE CONDUCTED TO DISCUSS SUBGRADE PREPARATION, FOUNDATION CONSTRUCTION, WALL BACKFILL, VOID FORM SYSTEMS, CONCRETE FORMING & PLACING, AND TESTING &
INSPECTION REQUIREMENTS.
6. CONTRACTOR SHALL COMPLY WITH REQUIREMENTS AS LISTED IN THE STATEMENT OF SPECIAL INSPECTIONS.
GENERAL NOTES
1. DEFERRED SUBMITTALS ARE PORTIONS OF THE OVERALL DESIGN WHICH ARE NOT SUBMITTED AT TIME OF PERMIT
APPLICATION AND ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL.
2. DEFERRED SUBMITTALS WILL BE REVIEWED FOR THE LIMITED PURPOSE OF CHECKING FOR CONFORMANCE WITH INFORMATION GIVEN IN THE CONTRACT DOCUMENTS. SUBMITTAL REVIEW WILL NOT BE CONDUCTED FOR THE PURPOSE OF DETERMINING THE ACCURACY AND COMPLETENESS OF OTHER DETAILED INFORMATION SUCH AS DIMENSIONS AND QUANTITIES, OR FOR SUBSTANTIATING INSTRUCTIONS FOR INSTALLATION OR SYSTEMS DESIGNED
BY THE CONTRACTOR WHICH REMAINS THE RESPONSIBILITY OF THE CONTRACTOR.
REVIEW SHALL NOT CONSTITUTE APPROVAL OF SAFETY PRECAUTIONS OR OF ANY CONSTRUCTION MEANS, METHODS, SEQUENCES OR PROCEDURES.
APPROVAL OF A SPECIFIC ITEM SHALL NOT INDICATE APPROVAL OF AN ASSEMBLY OF WHICH THE ITEM IS A
COMPONENT.
3. FOLLOWING DEFERRED SUBMITTALS ARE TO BE PROVIDED FOR REVIEW:
A. CONCRETE FORMWORK / RETENTION SYSTEMS
B. PRE-ENGINEERED CANOPIES
SUPPLIER’S ENGINEERS SHALL PROVIDE SIGNED AND SEALED CALCULATIONS WITH THE SUBMITTAL FOR REVIEW.
REVIEW WILL BE LIMITED TO CONFORMANCE WITH DESIGN AND PERFORMANCE CRITERIA SPECIFIED IN THE CONSTRUCTION DOCUMENTS AND THE INTERFACE BETWEEN THESE ITEMS/SYSTEMS AND THE BUILDING STRUCTURE. THE MANUFACTURER/SUPPLIER AND ITS SPECIALTY STRUCTURAL ENGINEER REMAIN RESPONSIBLE FOR THE DESIGN OF THE ITEM/SYSTEM WILL RETAIN ALL RIGHTS AND RESPONSIBILITIES FOR THE DESIGN OF THE
PRODUCT AND THE CONNECTIONS TO THE BUILDING STRUCTURE.
NO WORK ON STRUCTURAL ELEMENTS SUPPORTING OR RELATED TO THESE ITEMS IS TO PROCEED UNLESS THE REVIEW STAMP CLEARLY INDICATES "REVIEWED" OR "REVIEWED, SEE COMMENTS" BY THE ENGINEER.
4. FOLLOWING SHOP DRAWINGS ARE TO BE PROVIDED FOR APPROVAL:
A. CONCRETE MIXES
B. REINFORCING STEEL
SHOP DRAWINGS ARE TO BE DISTRIBUTED ONLY FROM RETURNED SUBMITTALS BEARING AN INITIALED REVIEW STAMP AND WORK ON THESE ITEMS SHALL NOT PROCEED UNLESS THE STAMP CLEARLY INDICATES THE DRAWINGS
ARE "APPROVED" OR "APPROVED AS NOTED."
5. CONCRETE IS A MATERIAL DESIGNED BY THE SUPPLIER TO MEET THE STRENGTH AND PERFORMANCE CRITERIA SPECIFIED IN THE CONTRACT DOCUMENTS. CONCRETE MIX DESIGNS SHALL BE IN CONFORMANCE WITH ACI 318.
SUBMIT MIX DESIGNS AND THE TESTING LAB REVIEW TO THE ARCHITECT/ENGINEER FOR REVIEW.
MANY VARIABLES, INCLUDING ENVIRONMENTAL CONDITIONS AFFECT THE QUALITY OF CONCRETE. THE CONTRACTOR IS RESPONSIBLE FOR CONTROLLING VARIABLES AND REQUESTING MIX MODIFICATIONS AND SHALL BE
SOLELY RESPONSIBLE FOR THE QUALITY OF CONCRETE DELIVERED AND PLACED ON THE SITE.
6. BEFORE SUBMISSION FOR REVIEW, GENERAL CONTRACTOR SHALL PRE-CHECK SUBMITTALS. SUBMITTALS MUST BEAR AN INITIALED REVIEW STAMP OF THE GENERAL CONTRACTOR. SUBMITTALS WITHOUT REVIEW STAMPS WILL
BE RETURNED WITHOUT REVIEW AND SHALL NOT BE CAUSE FOR CLAIMS OF DELAY.
7. SCHEDULE SUBMITTALS SUFFICIENTLY IN ADVANCE OF THE DATE REQUIRED TO ALLOW REASONABLE TIME FOR PROCESSING AND REVIEW BY THE DESIGN TEAM. THIS SHALL INCLUDE A MINIMUM OF TEN WORKING DAYS FOR ENGINEER'S PROCESSING AND REVIEW. INCLUDE TIME FOR CONTRACTOR’S RESUBMISSION AND SUBSEQUENT
REVIEW IF NECESSARY.
SHORTER REVIEW PERIODS WILL ONLY BE HONORED WITH PRIOR WRITTEN CONSENT. THESE ACCELERATED SERVICES, AND APPROPRIATE COMPENSATION, MUST BE NEGOTIATED WITH THE ENGINEER AND ARCHITECT IN
ADVANCE.
TEN DAY REVIEW PERIODS CAN NOT BE HONORED WHEN LARGE QUANTITIES OF SHOP DRAWINGS ARE SUBMITTED AT ONE TIME. WHEN THIS HAPPENS, THE CONTRACTOR SHALL SUBMIT AN ITEMIZED LIST INDICATING PRIORITIES AND
REASONABLE RETURN DATES.
REVIEW OF RESUBMITTALS WILL BE LIMITED TO ONLY EARLIER COMMENTS AND IS NOT AN EXTENSIVE REVIEW.
8. USE OF REPRODUCTIONS OF THESE CONTRACT DRAWINGS, INCLUDING THE USE OF ELECTRONIC FILES, BY ANY CONTRACTOR IN LIEU OF THE INDEPENDENT PREPARATION OF SHOP DRAWINGS, SIGNIFIES THEIR ACCEPTANCE OF ALL INFORMATION SHOWN HEREON AS CORRECT AND OBLIGATES HIMSELF TO ANY JOB EXPENSE, REAL OR IMPLIED, ARISING DUE TO ANY ERRORS THAT MAY OCCUR HEREON.
9. NOT USED
DEFERRED SUBMITTALS NOTES
1. FOUNDATION DESIGN AND SUBSURFACE INFORMATION IS BASED ON GEOTECHNICAL REPORT #26-162 PREPARED FOR THIS PROJECT BY LARRY M JACOBS & ASSOCIATES, INC AND DATED MAY 1, 2026 & EMAIL RESPONSE DATED
SEPTEMBER 1, 2026.
2. GEOTECHNICAL ENGINEER OF RECORD (GER) IS SOLELY RESPONSIBLE FOR ESTABLISHING FOUNDATION, SLAB-ON- GRADE AND PAVEMENT DESIGN CRITERIA, AND FOR THE CONSTRUCTION RECOMMENDATIONS FOR EXCAVATION, SUBGRADE PREPARATION, BACKFILLING AND COMPACTION.
3. GEOTECHNICAL INFORMATION INDICATED IN THE STRUCTURAL CONSTRUCTION DOCUMENTS IS INTENDED TO REPLICATE THE RECOMMENDATIONS STATED IN THE GEOTECHNICAL ENGINEERING REPORT. PRESENTATION OF THIS INFORMATION IN THE STRUCTURAL DOCUMENTS DOES NOT DEMONSTRATE, STATE OR IMPLY GEOTECHNICAL EXPERTISE BY THE STRUCTURAL ENGINEER. CONTRACTOR SHALL OBTAIN A COPY OF THE REPORT AND COMPLY
WITH THE RECOMMENDATIONS INDICATED THEREIN.
4. IF DISCREPANCIES BETWEEN THE REPORT AND CONSTRUCTION DOCUMENTS ARE DISCOVERED, THE REPORT SHALL GOVERN. ALL CLARIFICATIONS AND INTERPRETATIONS OF THE REPORT SHALL BE MADE BY THE GER AND
REPORTED TO THE ARCHITECT FOR COORDINATION WITH THE DESIGN TEAM.
GEOTECHNICAL INFORMATION
1. BEARING STRATA SHOWN ON THE DETAILS IS NATIVE SOILS. PREPARE FOUNDATION BEARING MATERIAL PER THE
GEOTECHNICAL ENGINEER'S RECOMMENDATIONS.
2. FOUNDATION ALLOWABLE DESIGN SOIL VALUES:
CONTINUOUS FOOTING BEARING - 1.5ksf * ISOLATED FOOTING BEARING - 1.5ksf *
SOIL SLIDING RESISTANCE (NATIVE SOIL) 0.5
* IF CONTINUOUS FOOTING OR ISOLATED FOOTING WIDTH EXCESS 3FT IN DIMENSION, THE SOIL BENEATH FOOTING
SHALL HAVE ADDITIONAL 2FT OF SOIL COMPACTION PER GEOTECHNICAL REPORT.
RETAINING WALL DESIGN VALUES
SOIL DENSITY Yd- 95PCF (VERY LOOSE SLIGHTLY SILTY SAND) AT REST Ka- 0.4xYd PASSIVE PRESSURE Kp- 2.5XYd
3. ALL FOOTING EXCAVATIONS SHALL BE CLEANED TO REMOVE ALL LOOSE SOIL MATERIAL AND OTHER DEBRIS AND
SHOULD NOT BE ALLOWED TO DESICCATE PRIOR TO PLACEMENT OF CONCRETE.
4. CONCRETE FOR FOUNDATIONS SHALL BE FORMED ON THE SIDES (EARTH FORMED FOUNDATIONS WILL NOT BE
ALLOWED). PROPERLY PLACE AND COMPACT FILL MATERIAL AROUND SIDES OF FOOTINGS.
5. ALL FOUNDATION EXCAVATIONS SHALL BE INSPECTED BY THE TESTING AGENCY.
SHALLOW FOUNDATION NOTES
1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH ACI 318- PER GOVERNING BUILDING CODE.
2. CONCRETE IN THE FOLLOWING AREAS SHALL HAVE SAND AND GRAVEL OR CRUSHED STONE AGGREGATES AND THE DESIGNATED COMPRESSIVE STRENGTH IN 28 DAYS UNLESS NOTED OTHERWISE. NORMAL WEIGHT AGGREGATES
SHALL CONFORM TO ASTM C33.
FOOTING -------------------------------------------------------------- f'c = 4,000 psi ALL OTHER CONCRETE ---------------------------------------- f'c = 4,000 psi
3. CONCRETE PROTECTION FOR REINFORCEMENT SHALL BE AS FOLLOWS:
REFER TO ACI 318 - SECTION 7.7 FOR CONDITIONS NOT NOTED.
FOOTINGS ------------------------------------------------ 3"
WALL ------------------------------------------------------- 2"
4. MAXIMUM NOMINAL COARSE AGGREGATE SIZE SHALL BE 1 1/2" MAX FOR PIERS AND 1" MAX TYPICAL UNLESS NOTED
OTHERWISE.
5. CONCRETE SLUMPS SHALL BE AS FOLLOWS:
CONCRETE CONTAINING HRWR------ 10" MAX
ALL OTHER CONCRETE ---------------- 5" MAX, 2" MIN
6. CONCRETE EXPOSED TO WEATHER SHALL BE AIR-ENTRAINED AS FOLLOWS:
3/4" NOMINAL AGGREGATE SIZE 4% TO 8%
1" NOMINAL AGGREGATE SIZE 3.5% TO 6.5%
1 1/2" NOMINAL AGGREGATE SIZE 3% TO 6%
7. ALL CAST IN PLACE WALLS AND CONTINUOUS FOOTINGS SHALL BE FORMED ON SIDES. ALL ELEMENTS OF THE FORMS, FORMWORK, BRACING AND SHORING SHALL CONSIST OF WOOD, METAL OR OTHER MANUFACTURED PRODUCTS AS SPECIFIED. EARTH MAY NOT BE USED AS A FORM, EITHER DIRECTLY OR INDIRECTLY. NEITHER
EARTH TRENCHES NOR EARTH TRENCHES LINED WITH ANOTHER MATERIAL ARE ACCEPTABLE.
8. THERE SHALL BE NO HORIZONTAL CONSTRUCTION JOINTS IN CONCRETE POURS. ALL CONSTRUCTION JOINTS SHALL BE MADE IN THE CENTER OF SPANS WITH VERTICAL BULK HEADS. THE LOCATION OF CONSTRUCTION JOINTS SHALL
BE APPROVED BY THE STRUCTURAL ENGINEER.
9. UNLESS OTHERWISE NOTED OR DETAILED, PROVIDE (2)#5, (1) EACH FACE AROUND UNFRAMED OPENINGS IN CONCRETE WALLS AND GRADE BEAMS. PLACE BARS PARALLEL TO SIDES OF OPENINGS AND EXTEND 24 INCHES
BEYOND CORNERS.
10. PROVIDE EQUIPMENT BASES AND SUPPORTS AS REQUIRED, COMPLYING WITH APPROVED MANUFACTURERS
CERTIFIED SHOP DRAWINGS AND DETAILS.
11. SIZE AND LOCATION OF BASES AND EMBEDDED ANCHORS FOR EQUIPMENT SHALL BE COORDINATED WITH
EQUIPMENT SUPPLIER AND ALL BE IN ACCORDANCE WITH APPROVED SHOP DRAWINGS.
12. NO ALUMINUM OF ANY TYPE SHALL BE ALLOWED IN THE CONCRETE WORK, UNLESS COATED AND APPROVED BY
THE ENGINEER OR RECORD.
CONCRETE NOTES
1. ALL REINFORCING STEEL SHALL BE NEW DEFORMED BILLET STEEL CONFORMING TO ASTM A615, GRADE 60.
2. DETAILING OF REINFORCEMENT SHALL BE IN ACCORDANCE WITH THE ACI DETAILING MANUAL.
3. REINFORCING BARS MAY BE SPLICED ONLY AS SHOWN ON THE DRAWINGS EXCEPT THAT REINFORCING DESIGNATED AS "CONTINUOUS" MAY BE CONTACT LAP SPLICED WITH TENSION LAP PER ACI 318 CHAPTER 25.
4. FOR CONTINUOUS FOOTING REINFORCING, PER FOOTINGS REINFORCEMENT LAP SPLICES SCHEDULED ON S110.
5. PROVIDE CORNERS BARS OF SAME SIZE AND QUANTITY AS CONTINUOUS TOP AND BOTTOM REINFORCING OF
GRADE BEAMS AT ALL GRADE BEAM CORNERS AND INTERSECTIONS.
REINFORCING STEEL NOTES
1. POST-INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED ON THE CONSTRUCTION DOCUMENTS. THE CONTRACTOR SHALL OBTAIN APPROVAL FROM THE ENGINEER-OF-RECORD PRIOR TO INSTALLING POST-INSTALLED ANCHORS IN PLACE OF MISSING OR MISPLACED CAST-IN-PLACE ANCHORS. CARE SHALL BE TAKEN IN PLACING POST-INSTALLED ANCHORS TO AVOID CONFLICTS WITH EXISTING REINFORCING OR POST-TENSIONING.
2. SUBSTITUTION REQUESTS, FOR PRODUCTS OTHER THAN THOSE SPECIFIED BELOW, SHALL BE SUBMITTED BY THE CONTRACTOR TO THE ENGINEER-OF-RECORD ALONG WITH CALCULATIONS THAT ARE PREPARED & SEALED BY A REGISTERED PROFESSIONAL ENGINEER. THE CALCULATIONS SHALL DEMONSTRATE THAT THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING EQUIVALENT PERFORMANCE VALUES (MINIMUM) OF THE SPECIFIED PRODUCT USING THE APPROPRIATE DESIGN PROCEDURE AND/OR STANDARD(S) AS REQUIRED BY THE BUILDING CODE.
3. POST-INSTALLED ANCHORS INCLUDE EXPANSION ANCHORS, UNDERCUT ANCHORS AND ADHESIVE ANCHORS.
ADHESIVE ANCHORS SHALL CONSIST OF A STRUCTURAL ADHESIVE AND STEEL INSERT. STEEL INSERTS SHALL BE EITHER ASTM F1554, GRADE 36 THREADED ROD OR ASTM A615, GRADE 60 REINFORCING STEEL UNLESS NOTED OTHERWISE ON THE DRAWINGS. PROVIDE, STORE AND INSTALL PRODUCTS IN STRICT CONFORMANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS.
4. EXPANSION ANCHORS FOR USE IN CRACKED AND UNCRACKED CONCRETE SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI 355.2 AND ICC-ES AC193. EXPANSION ANCHORS SHALL BE EITHER HILTI KWIK BOLT TZ ANCHORS OR SIMPSON STRONG-TIE STRONG-BOLT 2 ANCHORS, UNLESS NOTED OTHERWISE ON DRAWINGS. EXPANSION ANCHORS SHALL BE 3/4" DIAMETER WITH 4 3/4" EMBEDMENT UNLESS NOTED OTHERWISE
ON THE DRAWINGS.
5. EXPANSION ANCHORS FOR USE IN SOLID-GROUTED CONCRETE MASONRY SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC01. EXPANSION ANCHORS IN CMU SHALL BE EITHER HILTI KWIK
BOLT 3 ANCHORS OR SIMPSON STRONG-TIE WEDGE-ALL ANCHORS.
6. UNDERCUT ANCHORS FOR USE IN CRACKED AND UNCRACKED CONCRETE SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI 355.2 AND ICC-ES AC193. UNDERCUT ANCHORS SHALL BE EITHER HILTI HDA ANCHORS OR SIMPSON STRONG-TIE TORQ-CUT ANCHORS, UNLESS NOTED OTHERWISE ON DRAWINGS.
7. STRUCTURAL ADHESIVES FOR USE IN CRACKED AND UNCRACKED CONCRETE SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI 355.4 AND ICC-ES AC308. STRUCTURAL ADHESIVES SHALL BE HILTI HIT-RE 500-SD EPOXY, HILTI HIT-HY 200-A ADHESIVE, SIMPSON STRONG-TIE SET-XP ADHESIVE OR SIMPSON STRONG- TIE AT-XP ADHESIVE UNLESS NOTED OTHERWISE ON THE DRAWINGS. REFER TO DRAWINGS FOR SIZE AND EMBEDMENT REQUIREMENTS. ALL THREADED RODS USED IN EXTERIOR EXPOSURES SHALL BE GALVANIZED.
8. THE FOLLOWING PARAMETERS HAVE BEEN USED IN THE DESIGN OF ALL ADHESIVE ANCHORS UNLESS NOTED
OTHERWISE ON THE DRAWINGS:
A. MINIMUM AGE OF CONCRETE – 28 DAYS
B. CONCRETE TEMPERATURE RANGE FOR ANCHORS NOT EXPOSED TO THE ENVIRONMENT – MAXIMUM SHORT
TERM TEMPERATURE OF 104°F; MAXIMUM LONG TERM TEMPERATURE OF 75°F.
C. CONCRETE TEMPERATURE RANGE FOR ANCHORS EXPOSED TO THE ENVIRONMENT – MAXIMUM SHORT TERM
TEMPERATURE OF 150°F; MAXIMUM LONG TERM TEMPERATURE OF 110°F.
D. MOISTURE CONDITION OF CONCRETE AT THE TIME OF INSTALLATION – DRY CONCRETE
E. HOLE DRILLING AND PREPARATION – PER THE MANUFACTURER’S PRINTED INSTALLATION INSTRUCTIONS
9. ANCHOR CAPACITY IS DEPENDANT UPON THE SPACING BETWEEN ADJACENT ANCHORS AND THE PROXIMITY OF ANCHORS TO THE EDGE OF CONCRETE. INSTALL ANCHORS IN ACCORDANCE WITH THE SPACING AND EDGE
CLEARANCES INDICATED ON THE DRAWINGS.
10. PRIOR TO PLACEMENT, THE CONTRACTOR SHALL HAVE THE MANUFACTURER’S TECHNICAL REPRESENTATIVE VISIT THE SITE TO INSTRUCT THE CONSTRUCTION TEAM AND TESTING LAB ON PROPER STORAGE AND INSTALLATION TECHNIQUES. THE CONTRACTOR SHALL PROVIDE A LETTER FROM THE MANUFACTURER’S REPRESENTATIVE
STATING THAT SUCH A VISIT WAS CONDUCTED.
11. ALL EXPANSION ANCHORS SHALL BE INSPECTED BY AN INDEPENDENT TESTING LAB FOR THE FOLLOWING:
A. CORRECT LOCATION AND POSITION OF HOLE.
B. CORRECT HOLE DIAMETER
C. CORRECT EMBEDMENT DEPTH.
D. CORRECT BOLT TYPE AND FINISH.
E. CONDITION OF HOLE IN CONNECTION MATERIAL (NO BURNING OF HOLES ALLOWED).
F. SNUG TIGHT FIT.
12. ADHESIVE ANCHORS SHALL BE INSPECTED AND TESTED BY AN INDEPENDENT TESTING LAB AS FOLLOWS:
ALL ANCHORS SHALL BE INSPECTED FOR THE FOLLOWING:
A. CORRECT LOCATION AND POSITION OF HOLE.
B. CORRECT THREADED ROD OR REINFORCING BAR SIZE.
C. CORRECT THREADED ROD OR REINFORCING BAR TYPE AND FINISH.
D. CONDITION OF HOLE IN CONNECTION MATERIAL (NO BURNING OF HOLES ALLOWED).
E. SNUG TIGHT FIT.
F. CORRECT EMBEDMENT DEPTH.
G. HOLE PREPARATION (INCLUDING DRILL BIT TYPE WHERE CRITICAL TO MANUFACTURER) AND CLEANOUTS
PER MANUFACTURER'S RECOMMENDATIONS.
H. ADHESIVE TYPE, EXPIRATION DATE AND METHOD OF STORAGE.
I. ADHESIVE AND ANCHOR INSTALLATION PER MANUFACTURER’S RECOMMENDATIONS.
J. 10% OF EACH TYPE AND SIZE OF ANCHOR SHALL BE PROOF LOADED PER THE MANUFACTURER’S
RECOMMENDATIONS. IF 10% OF THE TESTED ANCHORS FAIL TO ACHIEVE THE SPECIFIED PROOF LOAD, ALL
ANCHORS OF THE SAME DIAMETER AND TYPE SHALL BE TESTED.
13. THE TESTING LAB SHALL PREPARE AN INSPECTION REPORT SPECIFICALLY INDICATING DEGREE OF CONFORMANCE
IN ALL CATEGORIES LISTED ABOVE.
POST-INSTALLED ANCHOR NOTES
1. ALL SUBGRADE SHALL BE PREPARED IN STRICT CONFORMANCE TO THE GEOTECHNICAL ENGINEER’S RECOMMENDATIONS. REFER TO THE GEOTECHNICAL REPORT, SUPPLEMENTARY LETTERS AND SPECIFICATIONS
FOR ADDITIONAL INFORMATION.
THE SUBGRADE SHALL BE IMPROVED TO REDUCE THE POTENTIAL FOR SUBGRADE MOVEMENT TO LESS THAN OF ONE INCH TOTAL SETTLEMENT & 1/2 INCH OF DIFFERENTIAL SETTLEMENT BY RE-COMPACTING IN-SITU SOIL AS
APPROVED BY GEOTECH ENGINEER.
THE FOLLOWING IS A SUMMARY OF THE INFORMATION CONTAINED IN THE GEOTECHNICAL ENGINEER’S
RECOMMENDATIONS:
A. THE BUILDING EXCAVATION AREA SHALL EXTEND BEYOND THE BUILDING LINE A MINIMUM OF 5 FEET IN GENERAL. AT ALL ENTRANCES AND AT AREAS WITH SIDEWALKS/PAVING DIRECTLY ADJACENT TO THE
BUILDING.
B. WITHIN THE BUILDING AREA, EXCAVATE AND REMOVE ALL FILL MATERIAL. REFER TO THE GEOTECHNICAL REPORT FOR APPROXIMATE DEPTHS OF FILL. THE TESTING LAB SHALL DETERMINE THROUGH FIELD
OBSERVATION AND TESTING THAT ALL UNACCEPTABLE FILLS HAVE BEEN REMOVED.
C. WITHIN THE BUILDING AREA, RE-COMPACT NATIVE SOIL OR IMPORTED FILL AS REQUIRED TO PROVIDE A COMPACTED MATERIAL BENEATH BUILDING AREA. FOOTING THAT HAVE A WIDTH GREATER THAN 3FT IN
WIDTH WILL REQUIRE ADDITIONAL 2FT OF SOIL COMPACTION BENEATH FOOTING.
D. SCARIFY EXPOSED NATIVE SOILS TO A DEPTH OF 12 INCHES FOR FOOTING LESS THAN 3FT IN WIDTH AND RECOMPACT TO A MINIMUM OF 95% OF MODIFIED PROCTOR (ASTM D1557) AT A MINIMUM OF +2 PERCENTAGE POINTS ABOVE THE OPTIMUM MOISTURE CONTENT FOR THE SOIL AS DIRECTED IN THE
GEOTECHNICAL REPORT.
K. SELECT FILL SHALL CONSIST OF A SLIGHTLY SILTY SAND OR SILTY/CLAYEY SAND. ALL SELECT FILL SHALL BE
APPROVED BY THE GEOTECHNICAL ENGINEER.
L. SPREAD THE SELECT FILL IN THIN LOOSE LIFTS NOT EXCEEDING 10 TO 12 INCHES THICK FOR SLIGHTLY SILTY SAND OR LIFTS NOT EXCEEDING 6 TO 8 INCHES THICK FOR SILTY/CLAYEY SAND AND UNIFORMLY COMPACT TO A MINIMUM OF 95% OF ASTM D1557 WITHIN +2 OR –2 PERCENTAGE POINTS OF THE OPTIMUM MOISTURE
CONTENT FOR THE SOIL AS RECOMMENDED IN THE GEOTECHNICAL REPORT.
M. PLACE FIRST LIFT OF SELECT FILL WET OF OPTIMUM TO PREVENT DRYING OF THE UNDERLYING SUBGRADE.
N. PROTECT FILL TO PREVENT DESICCATION PRIOR TO PLACING A SUBSEQUENT LIFT.
2. CONTACT THE GEOTECHNICAL ENGINEER FOR ANY QUESTIONS REGARDING INTERPRETATION OR CLARIFICATION OF
THE ABOVE INFORMATION.
3. FOUNDATION AND SUBGRADE PREPARATION SHALL BE MONITORED AND TESTED BY THE SOILS ENGINEER. REFER
TO SPECIFICATIONS FOR QUALITY CONTROL REQUIREMENTS.
SUBGRADE PREPARATION
1. SEE PREFABRICATED CANOPY MANUFACTURER'S DRAWINGS FOR FOUNDATIONS, BASE PLATES & A.B., COLUMN, ROOF METAL DECK, PURLINS, AND FRAMING.
2. THE GENERAL CONTRACTOR SHALL PROVIDE AND SET ANCHOR BOLTS AND EMBED PLATES AS PER
PREFABRICATED CANOPY MANUFACTURER'S DRAWINGS.
3. THE CONTRACTOR SHALL COMPARE STRUCTURAL DRAWINGS WITH PREFABRICATED CANOPY MANUFACTURER'S DRAWINGS AND REPORT ANY DISCREPANCY TO THE ENGINEER PRIOR TO FABRICATION OR INSTALLATION OF
STRUCTURAL MEMBERS.
4. PREMANUFACTURED CANOPY SHOP DRAWINGS (PLANS, DETAILS, CALCULATIONS) SHALL BEAR THE SEAL OF A
REGISTERED PROFESSIONAL ENGINEER, IN THE STATE OF THE PROJECT.
5. METAL BUILDING DESIGN LOADS SHALL BE AS FOLLOWS:
A. WIND: SEE GENERAL NOTES
LATERAL DEFLECTION LIMIT H/240
B. GRAVITY: ROOF LIVE LOAD: 20 psf REDUCIBLE PER CODE ROOF DEAD LOAD: STRUCTURE WEIGHT + 5 psf COLLATERAL +
MECHANICAL UNITS AS SHOWN.
DEFLECTION LIMITS: LL = L/360
TOTAL = L/240
PREMANUFACTURED CANOPY NOTES
Architect of Record:
ADG
800 SW ADAMS STREET, SUITE 101
PEORIA, IL 61602
R e vi si o n s
P - 309.672.6948
Discipline:Discipline:Discipline:
P - P - P -
Discipline:
P -
PROJECT NO.
DATE
DRAWN BY
STATUS
Discipline: Owner Consultant
QSC SERVICES, LLC
PMB #69
545 BRENT LN. PENSACOLA, FL
P - 309.231.8272
OWNER ID:
Design and Construction Administration Division
ESCAMBIA COUNTY, FL
100 E. BLOUNT ST. PENSACOLA, FL 32501
ESCAMBIA COUNTY AREA TRANSIT - FACILITY:
05 - FUEL STATION BUILDING
2 CLARINDA LN
PENSACOLA, FLORIDA, 32505 S001GENERAL NOTES
MEP COMPANY NAME
KEDbluestone, PEORIA, IL 61602
707 NE JEFFERSON AVE
RLG CONSULTING ENGINEERS
12001 N CENTRAL, EXPY #300
DALLAS, TX 75243
RLG CONSULTING ENGINEERS
12001 N CENTRAL, EXPY #300
DALLAS, TX 75243
214.739.8100 214.739.8100 515.259.5957
HODGSON DOUGLAS LANDSCAPE ARCHITECTS
12001 N CENTRAL EXPY, STE 1170
DALLAS, TX 75243
214.749.0333
BID PACKAGE #2 - NOT FOR CONSTRUCTION
10/22/2026
RLG
A D
D
.1
.1
ADD
ADD
NORTH CANOPY
SOUTH CANOPY
A
6'
6"
1' - 0" 1' - 0"
2' - 0"
6' - 6"
28' - 0"
6' - 6"
6'
6"
0"
0"
0"
41' - 0"
5'
0"
12' - 0" 12' - 0"
24' - 0"
11' - 0" 2' - 0" 11' - 0"
NORTH CANOPY
SOUTH CANOPY
BASE POINT COORDINATE:
N 538706' 44" E 1106715' 48"
BASE POINT COORDINATE:
N 538733' 35" E 1106679' 53"
128.65°
X300 1
X300
B
C
D
E
F
A
FR
O
M C
AN
O
PY
F
AC
E
TO
C
O
LU
M N
G
RI
D
LI
N E
6'
6"
FR
O M
C
AN
O
PY
F
AC
E
TO
C O
LU
M
N G
RI
D
LI
N
E 6'
6"
X300
EQ. EQ.
CANOPY WIDTH
24' - 0"
LE
N
GT
H
O F
TH
E
CA
N
O
PY
5'
0"
FROM CANOPY FACE TO COLUMN GRID LINE
6' - 6"
28' - 0"
FROM CANOPY FACE TO COLUMN GRID LINE
6' - 6"
CANOPY LENGTH
41' - 0"
EQ
EQ
CA
NOPY
W
ID
TH
0"
NORTH CANOPY
SOUTH CANOPY
GUTTERS AND DOWNSPOUTS ARE PROVIDED BY FUEL STATION CANOPY VENDOR.
CODE MINIMUM REQUIREMENTS ARE LISTED BELOW:
GUTTER: 3"X3"
DOWNSPOUT: 1.86 SQUARE INCHES
X300 1
X300
A
X300
NORTH CANOPY
SOUTH CANOPY
UL-2
UL-2
DS-1
DS-2
X300 1
X300
A
X300
1/8" = 1'-0"
3 REFLECTED CEILING PLAN
3D VIEW, ROOF AND EXTERIOR WALL ASSEMBLIES3D VIEW, ROOF AND EXTERIOR WALL ASSEMBLIES
Architect of Record:
ADG
800 SW ADAMS STREET, SUITE 101
PEORIA, IL 61602
Re vi sio ns
P - 309.672.6948
Discipline:Discipline:Discipline:
P - P - P -
Discipline:
P -
PROJECT NO.
DATE
DRAWN BY
STATUS
Discipline: Owner Consultant
QSC SERVICES, LLC
PMB #69
545 BRENT LN. PENSACOLA, FL
P - 309.231.8272
OWNER ID:
Design and Construction Administration Division
ESCAMBIA COUNTY, FL
100 E. BLOUNT ST. PENSACOLA, FL 32501
ESCAMBIA COUNTY AREA
TRANSIT - FACILITY:
05 - FUEL STATION CANOPIES
2 CLARINDA LN
PENSACOLA, FLORIDA, 32505
X001LAYOUT PLAN, 3D VIEWS AND WALL / ROOF
ASSEMBLIES
MEP COMPANY NAME
KEDbluestone, PEORIA, IL 61602
707 NE JEFFERSON AVE
RLG CONSULTING ENGINEERS
12001 N CENTRAL, EXPY #300
DALLAS, TX 75243
RLG CONSULTING ENGINEERS
12001 N CENTRAL, EXPY #300
DALLAS, TX 75243
214.739.8100 214.739.8100 515.259.5957
HODGSON DOUGLAS LANDSCAPE ARCHITECTS
12001 N. CENTRAL EXPRESSWAY, STE 1170
DALLAS, TX 75243
214.749.0333
BID PACKAGE #2 - NOT FOR CONSTRUCTION
11/12/2026
ADG
AD
D
/0 5/
1/8" = 1'-0"
1 LAYOUT PLAN
1/8" = 1'-0"
4 ROOF PLAN
1/8" = 1'-0"
2 EQUIPMENT PLAN
NOTE: DELEGATED DESIGN
CANOPY, FOUNDATIONS, ROOF DECK, FASCIA,
AND ROOF DRAINAGE SYSTEM INCLUDING
DOWNSPOUTS.
COORDINATE DOWNSPOUTS AT GRADE AND/OR
TIE-IN TO CIVIL UNDERGROUND STORM.
N N NN
EQUIPMENT SCHEDULEEQUIPMENT SCHEDULE
NO. DESCRIPTION FURNISHED BY INSTALLED BY Count
DS-1 ELECTRONIC FUEL DISPENSER - DIESEL SINGLE-SIDED CONTRACTOR CONTRACTOR 1
DS-2 ELECTRONIC FUEL DISPENSER - DIESEL DOUBLE-SIDED CONTRACTOR CONTRACTOR 1
UL-2 ELECTRONIC FUEL DISPENSER - UNLEADED DOUBLE-SIDED CONTRACTOR CONTRACTOR 2
PROVIDE UNDER SLAB AT VAPOR BARRIER
2'X2' LED FLAT PANEL
LIGHTING LEGEND
2'X2' LED FLAT PANEL W/ EMERGENCY
BATTERY
4" DIAMETER OPEN DOWNLIGHT
12,000 GAL ABOVE GROUND FUEL TANK - SEE CIVIL SITE SET FOR PROPOSED
FUEL TANK LOCATIONS
OWNER CONTRACTOR 3
ADD
ADD
PIPING APPLICATION SCHEDULE (PLUMBING)
SYSTEM LOCATION
DESIGN
WORKING
PRESSURE
(PSI)
MATERIAL JOINTS
USAGE SIZE
RANGE
NOTES
AUTOMOTIVE FUEL
BELOW GRADE 125
DOUBLE-WALL POLYETHYLENE
CONTAINMENT PIPING
DOUBLE-WALL FITTINGS ALL -
ABOVE GRADE 125 SCH 40 BLACK STEEL THREADED, AND/OR WELDED ALL -
B B
C C
D D
E E
F F
2" DIESEL FUEL PIPE
SERVING FUEL DISPENSER
2" DIESEL FUEL PIPE
SERVING FUEL DISPENSER
2" GASOLINE PIPE
SERVING FUEL DISPENSER
2" GASOLINE PIPE
SERVING FUEL DISPENSER
B B
C C
D D
E E
F F
2" DIESEL FUEL UP
2" DIESEL FUEL UP
D
IE
S E
L F
U E
L
G A
S O
L
IN
E
2" GASOLINE UP
2" GASOLINE UP
2" DIESEL FUEL
TO DIESEL FUEL TANKS, SEE SITE
PLAN FOR PIPE CONTINUATION
2" GASOLINE
TO GASOLINE FUEL TANK, SEE SITE
PLAN FOR PIPE CONTINUATION
KEY MAP
C03.01
C03.05
C03.03
C03.02
C03.04
5518 NW 88th Street Johnston, IA 50131 515-727-0700 www.KEDbluestone.com
KED
bluestone
Architect of Record:
ADG
800 SW ADAMS STREET, SUITE 101
PEORIA, IL 61602
R e vi si o n s
P - 309.672.6948
Discipline:Discipline:Discipline:
P - P - P -
Discipline:
P -
PROJECT NO.
DATE
DRAWN BY
STATUS
Discipline: Owner Consultant
QSC SERVICES, LLC
PMB #69
545 BRENT LN. PENSACOLA, FL
P - 309.231.8272
OWNER ID:
Design and Construction Administration Division
ESCAMBIA COUNTY, FL
100 E. BLOUNT ST. PENSACOLA, FL 32501
PROJECT NUMBER: 126-030
KEDbluestone RESERVES PROPRIETARY RIGHTS, INCLUDING
COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN
THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE
PROPERTY OF KEDbluestone AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
KEDbluestone. © 2026 KEDbluestone
ESCAMBIA COUNTY AREA TRANSIT - FACILITY:
05 - FUEL STATION CANOPIES
2 CLARINDA LN
PENSACOLA, FLORIDA, 32505 PF100PLUMBING FLOOR PLANS
KEDbluestone
707 NE JEFFERSON AVE,
PEORIA, IL 61602
RLG CONSULTING ENGINEERS
12001 N CENTRAL, EXPY #300
DALLAS, TX 75243
RLG CONSULTING ENGINEERS
12001 N CENTRAL, EXPY #300
DALLAS, TX 75243
214.739.8100 214.739.8100 515.259-5957
HODGSON DOUGLAS LANDSCAPE
12001 N. CENTRAL EXPRESSWAY, SUITE 1170
DALLAS, TX 75243
214.749.0333
BID PACKAGE 2 - NOT FOR CONSTRUCTION
10/22/2026
ADG
N
1/8" = 1'-0"
PLUMBING UNDERFLOOR PLAN
N
1/8" = 1'-0"
PLUMBING FLOOR PLAN
A D
D
/1
/2
J J
EPO
DPM
PP
T
CD CR
D#
I#
U#
PC
FAP
NEP
FAA
PIV
PS
TS
FS
SD
SD
B#
SD
DSD
RI
H
J
F
SD
A
S
S
A
S
S
AM
AR
HD
SD
ZAM
CO
VCC
DCD
F
H
S
ASD
FSD
1P 1 POLE (2P, 3P, 4P, ETC.)
A 6" ABOVE COUNTER OR BACKSPLASH
TO CENTERLINE OF DEVICE
A, AMP AMPERE
AC ABOVE COUNTER, AIR CONDITIONING UNIT
ACLG ABOVE CEILING
AF AMP FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFCI ARC FAULT CIRCUIT
INTERRUPTER
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
AMPL AMPLIFIER
ANNUN ANNUNCIATOR
APPROX APPROXIMATELY
AQ-STAT AQUASTAT
ARCH ARCHITECT, ARCHITECTURAL
AS AMP SWITCH
AT AMP TRIP
ATC AUTOMATIC TEMPERATURE CONTROLS
CONTRACTOR
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
B BLACK DEVICE COLOR WITH BLACK
UNBREAKABLE THERMOPLASTIC COVER
PLATE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BD BOARD
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
C CONDUIT
CAB CABINET
CAT CATALOG
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
CM CONSTRUCTION MANAGER
COMB COMBINATION
CMPR COMPRESSOR
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
CP CIRCULATING PUMP
CRT CATHODE-RAY TUBE
CT CURRENT TRANSFORMER
CTR CENTER
CU COPPER
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DO AUTOMATIC DOOR OPENER
DPR DAMPER
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
ECB ENCLOSED CIRCUIT BREAKER
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
ELU EMERGENCY LIGHTING UNIT
EM EMERGENCY
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EP ELECTRIC PNEUMATIC
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXH EXHAUST
EXP EXPLOSION PROOF
FA FIRE ALARM
FABP FIRE ALARM BOOSTER POWER
SUPPLY PANEL
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FPC FIRE PROTECTION CONTRACTOR
FU FUSE
FUDS FUSED SAFETY DISCONNECT SWITCH
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTOR
GND GROUND
GYP BD GYPSUM BOARD
HWC-# DOMESTIC WATER CIRCULATING PUMP
HOA HANDS-OFF-AUTOMATIC SWITCH
H INSTALL DEVICE HORIZONTALLY
HH HANDHOLE
HP HORSEPOWER
HPF HIGH POWER FACTOR
HT HEIGHT
HTG HEATING
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
IC INTERRUPTING CAPACITY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
I/W INTERLOCK WITH
J-BOX JUNCTION BOX
K.E.C. KITCHEN EQUIPMENT CONTRACTOR
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LT LIGHT
LTG LIGHTING
ELECTRICAL ABBREVIATIONS
LTNG LIGHTNING
LV LOW VOLTAGE
M INSTALL DEVICE IN MILLWORK
MAX MAXIMUM
MAG.S MAGNETIC STARTER
M/C MOMENTARY CONTACT
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDC MAIN DISTRIBUTION CENTER
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MMS MANUAL MOTOR STARTER
MOA MULTIOUTLET ASSEMBLY
MSP MOTOR STARTER PANELBOARD
MSBD MAIN SWITCHBOARD
N/A NOT APPLICABLE
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
N.O. NORMALLY OPEN
NPF NORMAL POWER FACTOR
NTS NOT TO SCALE
OC ON CENTER
OH OVERHEAD
OL OVERLOADS
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PC PLUMBING CONTRACTOR
PE PNEUMATIC ELECTRIC
PED PEDESTAL
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
PP POWER POLE
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
RAC RIGID ALUMINUM CONDUIT
RCPT RECEPTACLE
REQD REQUIRED
RM ROOM
RMC RIGID METALLIC CONDUIT
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SHT SHEET
SIM SIMILAR
SLD SINGLE-LINE DIAGRAM
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
SPP SINGLE-POINT POWER
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
S/S STOP/START PUSHBUTTONS
STA STATION
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TEL TELEPHONE
TERM TERMINAL
T TAMPER RESISTANT
TL TWIST LOCK
T-STAT THERMOSTAT
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TVTC TELEVISION TERMINAL CABINET
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UT UNDERGROUND TELEPHONE
UTIL UTILITY
UV ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VDT VIDEO DISPLAY TERMINAL
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WG WIRE GUARD
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
#" LOCATION-SPECIFIC MOUNTING
HEIGHT ABOVE FINISHED FLOOR
TO CENTERLINE OF DEVICE
∠ ANGLE
@ AT
▲ DELTA
' FEET
" INCHES
# NUMBER
Ø PHASE
C CENTER LINE
P PLATE
EQUIPMENT GROUNDING CONDUCTOR
PHASE CONDUCTOR (SHORT LINE)
NEUTRAL CONDUCTOR (LONG LINE)
EQUIPMENT/DEVICE HOME RUN KEY
1. BRANCH CIRCUIT WIRING SHALL BE #12AWG UNLESS NOTED OTHERWISE ON THE PLAN OR IN THE SCHEDULES.
2. AS A MINIMUM, USE 10 AWG CONDUCTOR FOR 20 AMPERE, 120 VOLT BRANCH CIRCUIT HOME RUNS LONGER
THAN 100 FEET AND 277 VOLT BRANCH CIRCUIT HOME RUNS LONGER THAN 200 FEET.
3. REFER TO SPECIFICATION SECTION 260519 FOR ADDITIONAL REQUIREMENTS.
GENERAL NOTES
LIGHTING CONTROL SYMBOLS
SYMBOL DESCRIPTION
WALL SWITCH
FIRE ALARM SYMBOLS
SYMBOL DESCRIPTION
CONTROL PANEL
NOTIFICATION APPLIANCE CIRCUIT
EXTENDER PANEL
REMOTE ANNUNCIATOR PANEL
POST INDICATOR VALVE AND TAMPER
SWITCH
AIR PRESSURE SWITCH
VALVE TAMPER SWITCH
WATER FLOW SWITCH
LINEAR BEAM SMOKE DETECTOR
DUCT SMOKE DETECTOR
DUCT SMOKE DETECTOR REMOTE
INDICATOR STATION
HEAT DETECTOR ADDRESSABLE
LINEAR HEAT DETECTION CABLE
ADDRESSABLE FIRE ALARM MANUAL
PULL STATION
SMOKE DETECTOR
AUDIO/VISUAL NOTIFICATION APPLIANCE,
CEILING MOUNTED
VISUAL NOTIFICATION APPLIANCE,
CEILING MOUNTED
SPEAKER NOTIFICATION APPLIANCE,
CEILING MOUNTED
SPEAKER/VISUAL NOTIFICATION APPLIANCE,
CEILING MOUNTED
HORN NOTIFICATION APPLIANCE, WALL
MOUNTED
AUDIO/VISUAL NOTIFICATION APPLIANCE,
WALL MOUNTED
SPEAKER NOTIFICATION APPLIANCE,
WALL MOUNTED
SPEAKER/VISUAL NOTIFICATION
APPLIANCE, WALL SWITCH
VISUAL NOTIFICATION APPLIANCE, WALL
MOUNTED
ADDRESSABLE MONITOR MODULE
ADDRESSABLE RELAY MODULE
HVAC ELEVATOR HOISTWAY DAMPER
HVAC SMOKE DAMPER
MAGNETIC DOOR HOLDER
ZONE ADAPTER MODULES
CEILING MOUNT SENSOR, DUAL
TECHNOLOGY
CEILING MOUNT SENSOR, INFRARED
TECHNOLOGY
CEILING MOUNT SENSOR, ULTRASONIC
TECHNOLOGY
GENERAL ELECTRICAL SYMBOLS
LINEAR BEAM SMOKE DETECTOR
BEAM SMOKE REFLECTOR
CO DETECTOR
ELECTRICAL CONNECTION
EMERGENCY STOP PUSH BUTTON
DIGITAL POWER METER
UTILITY TRANSFORMER
SWITCHBOARD
PANELBOARD
TRANSFORMER
DISCONNECT SWITCH
UTILITY POWER METER
VOICE COMMAND CENTER
DUCT CO DETECTOR
BELL
HIGH FIDELITY SPEAKER - CEILING MOUNT
AIR SAMPLING SMOKE DETECTOR
HIGH FIDELITY SPEAKER - WALL MOUNT
COMBINATION STARTER
ELECTRICAL EQUIPMENT
(DASHED LINES INDICATE CODE REQUIRED CLEARANCES)
BREAKER FUNCTION SCHEDULE
SYMBOL DESCRIPTION
A ARC FAULT INTERUPTER (AFCI)
AR ARC ENERGY REDUCTION MAINTENANCE SWITCH
E EXISTING BREAKER TO REMAIN
EM PROVIDE IDENTIFICATION PER NEC 700.12(I)(2)(4)
EN EXISTING BREAKER SERVING NEW CIRCUIT
G GROUND FAULT CIRCUIT INTERUPTER (GFCI) PROTECTION (5mA) GE GROUND FAULT CIRCUIT INTERUPTER FOR EQUIPMENT (30mA)
GF ADJUSTABLE GROUND FAULT PROTECTION FOR EQUIPMENT
HL HANDLE LOCK TO LOCK BREAKER IN CLOSED POSITION (RED FOR FIRE ALARM)
K# KEY INTERLOCK (# REPRESENTS GROUPED KEYING)
LSI LONG-TIME, SHORT-TIME, INSTANTANEOUS ADJUSTMENT
LSIG LONG-TIME, SHORT-TIME, INSTANTANEOUS ADJUSTMENT, AND GROUND FAULT ADJUSTMENT
LSIA LONG-TIME, SHORT-TIME, INSTANTANEOUS ADJUSTMENT, AND GROUND FAULT ALARM
N NEW BREAKER IN EXISTING PANEL
NE NEW BREAKER SERVING EXISTING CIRCUIT
SD DENOTE SERVICE DISCONNECT
ST SHUNT TRIP (120V OPERATED UNLESS NOTED OTHERWISE)
GENERAL PLAN SYMBOLS
NEW WORK BY THE EC (DARK SOLID LINE)
WORK BY OTHERS AND/OR EXISTING (LIGHT SOLID LINE)
DEMO WORK BY THE EC (DARK DASHED LINE)
NEW UNDERGROUND WORK BY THE EC (DARK DASHED LINE)
MATCHLINE
KEYED NOTE
LIGHTING CONTROL CALLOUT SYMBOL (DIAMOND)
1 ELECTRICAL EQUIPMENT SYMBOL (OCTAGON)
SECTION VIEW, TOP REPRESENTS DETAIL NUMBER, BOTTOM REPRESENTS SHEET NUMBER
ENLARGED VIEW, TOP REPRESENTS VIEW NUMBER, BOTTOM REPRESENTS SHEET NUMBER
POWER SYMBOLS
SYMBOL DESCRIPTION
DUPLEX / DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R
CORD REEL / CORD DROP
SIMPLEX RECEPTACLE, NEMA 5-20R
SPECIAL RECEPTACLE
RECESSED FLOOR BOX OR POKE-THRU
DUPLEX / DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, EMERGENCY POWER
MARK SCHEDULED EQUIPMENT (UNDERLINED)
MARK NONSCHEDULED EQUIPMENT
(E) MARK EXISTING EQUIPMENT - (E) PREFIX (HALFTONE)
(R) MARK EXISTING RELOCATED EQUIPMENT - (R) PREFIX
AUTOMATIC DOOR PUSH PAD
CEILING MOUNTED RECEPTACLE, NEMA 5-20R
LIGHTING SYMBOLS
SYMBOL DESCRIPTION
RECESSED MOUNTED (DIAGONAL SLASH)
RECESSED DOWNLIGHT (ARROW
INDICATES WALL WASH)
EMERGENCY LIGHT
POLE MOUNTED SITE FIXTURE
SURFACE OR PENDANT FIXTURE (DOTS)
WALL MOUNTED FIXTURE (STEM OR STEMS)
SURFACE MOUNTED
CRITICAL FIXTURE (FULL SHADED)
LIFE SAFETY (HALF SHADED)
SINGLE / DOUBLE FACED EXIT SIGN
EMERGENCY REMOTE HEAD (SINGLE/DOUBLE)
COMBINATION EXIT/EMERGENCY LIGHT
CYLINDRICAL FIXTURE (ARROW INDICATES
WALL WASH)
SURFACE MOUNT MULTI-OUTLET ASSEMBLY
FIRE SMOKE DAMPER
GROUND BAR
HAND HOLEHH-#
PHOTOCELL
HORSE POWER RATED SWITCH
H
BR
LHD
X
1. ALL INSTALLATIONS SHALL COMPLY WITH ALL APPLICABLE FEDERAL, STATE, AND LOCAL CODES INCLUDING, BUT NOT LIMITED TO, THE FLORIDA BUILDING CODES, AMERICANS WITH DISABILITIES ACT (ADA) ACCESSIBILITY GUIDELINES, AND THE INTERNATIONAL ENERGY CONSERVATION CODE (IECC). THE AUTHORITY HAVING JURISDICTION (AHJ) SHALL HAVE FINAL APPROVAL OF ALL INSTALLATIONS AND PRACTICES.
2. ALL MATERIALS FURNISHED SHALL BE NEW, FREE OF DEFECTS, AND LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) UNLESS NOTED
OTHERWISE.
3. INSTALLATION OF EQUIPMENT SHALL COMPLY WITH CURRENT STANDARDS AND SPECIFICATIONS APPROVED BY THE AHJ. INSTALL ALL CABLES AND WIRING IN CONDUIT OR RACEWAY UNLESS NOTED OTHERWISE. DO NOT SUPPORT CABLES OR WIRING FROM CEILING DEVICES, PIPING, DUCTWORK, OR CEILING
FRAMING. PROVIDE NEW WIRING FOR ALL BRANCH CIRCUITS AND FEEDERS.
4. FEEDERS SHOWN ON DRAWINGS ARE SCHEMATIC ONLY. CONDUIT RUNS SHALL NOT INCLUDE BENDS GREATER THAN 90 DEGREES. CONDUITS ABOVE
GRADE SHALL BE RUN PARALLEL OR PERPENDICULAR TO BUILDING LINES AND STRUCTURE.
5. CIRCUIT WIRING FOR THE EMERGENCY SYSTEM SHALL BE INSTALLED IN SEPARATE CONDUITS OR RACEWAYS AND SHALL REMAIN COMPLETELY
INDEPENDENT OF ALL OTHER WIRING AND EQUIPMENT PER NEC REQUIREMENTS.
6. ALL FEEDER AND BRANCH CIRCUITS TO PANELS, MOTORS, LIGHT FIXTURES, RECEPTACLES, AND GENERAL DISTRIBUTION EQUIPMENT SHALL INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR SIZED PER THE NEC. THE CONDUIT SYSTEM SHALL NOT BE USED AS AN EQUIPMENT GROUND.
7. REFER TO MECHANICAL AND PLUMBING EQUIPMENT SCHEDULES FOR EQUIPMENT CONNECTIONS, DISCONNECT REQUIREMENTS, AND CONTROLS. THE ELECTRICAL CONTRACTOR (EC) SHALL PROVIDE AND INSTALL ALL ITEMS INDICATED AS “BY EC” ON THE MECHANICAL AND PLUMBING SCHEDULES.
8. ALL WIRING AND FEEDER SIZES SHOWN ARE BASED ON COPPER CONDUCTORS UNLESS NOTED OTHERWISE. USE OF ALUMINUM FEEDER CONDUCTORS SHALL REQUIRE ENGINEER REVIEW OF FAULT CURRENT AND VOLTAGE DROP PRIOR TO INSTALLATION.
9. THE CONTRACTOR SHALL COORDINATE INSTALLATION OF ELECTRICAL SYSTEMS AND ALL EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS TO MAINTAIN
NEC-REQUIRED CLEARANCES, INCLUDING WORKING CLEARANCES AT ELECTRICAL DISTRIBUTION EQUIPMENT AND INSTALLATIONS ABOVE ACCESSIBLE
CEILINGS.
10. CONDUIT FOR POWER WIRING MAY BE INSTALLED BELOW FLOOR SLABS UNLESS NOTED OTHERWISE. RACEWAYS FOR LOW-VOLTAGE CABLING (CONTROLS, TELECOMMUNICATIONS, ETC.) SHALL NOT BE INSTALLED BELOW OR WITHIN FLOOR SLABS UNLESS SPECIFICALLY NOTED. WHERE LOW-VOLTAGE CABLING IS ROUTED BELOW OR WITHIN SLABS, CONTRACTOR SHALL VERIFY CABLING IS LISTED FOR SUCH USE.
11. ALL ELECTRICAL CONDUCTORS SHALL BE STRANDED COPPER WITH TYPE THHN/THWN INSULATION UNLESS NOTED OTHERWISE. MINIMUM WIRE SIZE SHALL
BE #12 AWG FOR GENERAL WIRING AND #10 AWG FOR HOMERUNS. REFER TO SPECIFICATIONS OR SHEET-SPECIFIC NOTES FOR ADDITIONAL INFORMATION.
12. ALL NEW CIRCUITS REQUIRING NEUTRAL CONDUCTORS SHALL HAVE DEDICATED NEUTRALS. SHARED NEUTRALS ARE NOT PERMITTED.
13. A GREEN EQUIPMENT GROUNDING CONDUCTOR SHALL BE PROVIDED TO ALL LOADS. THE CONDUCTOR SHALL BE SIZED PER THE NEC. ALL GROUNDING
CONDUCTORS SHALL BE INSTALLED IN CONDUIT.
14. ALL BUILDING WIRING SHALL BE INSTALLED IN CONDUIT TO ACHIEVE CIRCUITING AS SHOWN. MINIMUM BRANCH CONDUIT SIZE SHALL BE 3/4" UNLESS NOTED
OTHERWISE. SIZE CONDUCTORS PER NEC AMPACITY AND CONDUIT FILL REQUIREMENTS.
15. ALL HOME RUN CONDUITS FROM ELECTRICAL PANELBOARDS TO THE FIRST JUNCTION BOX SHALL BE A MINIMUM OF 1" CONDUIT AND SHALL TERMINATE IN A
4-11/16" SQUARE BY 2-1/8" DEEP (MINIMUM) JUNCTION BOX. JUNCTION BOX COVERS SHALL BE PAINTED AND CLEARLY MARKED WITH CIRCUIT NUMBERS.
EACH HOME RUN RACEWAY SHALL HAVE SPARE CAPACITY FOR ONE (1) ADDITIONAL CIRCUIT AND ITS DEDICATED NEUTRAL.
16. MC CABLING SHALL NOT BE USED UNLESS SPECIFICALLY NOTED OTHERWISE.
17. ALL CONDUITS SHALL BE CONCEALED IN WALLS, ABOVE CEILINGS, ETC., WHERE POSSIBLE.
18. ALL CONDUIT ROUTED EXPOSED IN FINISHED SPACES SHALL BE ROUTED PARALLEL OR PERPENDICULAR TO WALLS AND CEILINGS. EXPOSED CONDUIT
ROUTING SHALL BE REVIEWED WITH THE ARCHITECT AND ENGINEER PRIOR TO INSTALLATION.
19. COORDINATE THE EXACT LOCATION OF ALL DEVICES ABOVE OR BELOW COUNTERTOPS OR SIMILAR INSTALLATIONS WITH OTHER TRADES, ARCHITECTURAL
ELEVATIONS, AND APPROVED SUBMITTALS PRIOR TO ROUGH-IN. ARCHITECTURAL ELEVATIONS AND DETAILS TAKE PRECEDENCE OVER ELECTRICAL
DRAWINGS.
20. ALL CUTTING AND PATCHING REQUIRED FOR CONDUITS, DEVICES, OR OTHER ELECTRICAL EQUIPMENT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL
CONTRACTOR UNLESS NOTED OTHERWISE.
21. ALL PENETRATIONS THROUGH FIRE-RATED WALLS, FLOORS, AND CEILINGS SHALL BE SEALED WITH AN NRTL-APPROVED FIRESTOP SYSTEM EQUAL TO OR
EXCEEDING THE RATING OF THE PENETRATED ASSEMBLY.
22. COORDINATE LOCATIONS OF ALL ELECTRICAL ITEMS INCLUDING, BUT NOT LIMITED TO, LIGHTING FIXTURES, CEILING-MOUNTED DEVICES (OCCUPANCY
SENSORS, FIRE ALARM DEVICES, SPEAKERS, ETC.), SPRINKLER HEADS, AND HVAC DIFFUSERS/RETURNS. CENTER DEVICES IN CEILING TILES WHERE
POSSIBLE.
23. ALL CEILING DEVICES REQUIRING WIRE TERMINATIONS SHALL BE INSTALLED WITH MANUFACTURER-RECOMMENDED BACK BOXES AND SUPPORTS AS
REQUIRED BY THE NEC OR MANUFACTURER.
24. COORDINATE ALL MOUNTING OF ELECTRICAL MATERIALS, EQUIPMENT, AND DEVICES REQUIRED FOR EQUIPMENT SUPPLIED BY OTHERS. ELECTRICAL
INSTALLATIONS SHALL NOT INTERFERE WITH OPERATION OR ACCESS. ALL SUCH INSTALLATIONS SHALL BE REVIEWED AND APPROVED BY THE SUPPLYING
CONTRACTOR PRIOR TO ROUGH-IN.
25. BOXES LOCATED ON OPPOSITE SIDES OF FIRE-RATED WALLS SHALL BE OFFSET A MINIMUM OF 24" OR SHALL BE PROTECTED WITH A FIRE-RATED
MATERIAL EQUAL TO OR GREATER THAN THE WALL RATING.
26. BOXES LOCATED ON OPPOSITE SIDES OF NON-FIRE-RATED WALLS SHALL BE OFFSET A MINIMUM OF 6".
27. REMOVE AND REINSTALL CEILING TILES AS NECESSARY TO PERFORM REQUIRED ELECTRICAL WORK. REPLACE ALL DAMAGED CEILING TILES WITH NEW
TILES OF THE SAME MANUFACTURER AND MODEL.
28. PROVIDE FIELD TYPED PANELBOARD DIRECTORIES TO REFLECT AS-CONSTRUCTED CONDITIONS.
29. ALL REQUESTS FOR CHANGE PROPOSALS SHALL INCLUDE DETAILED BREAKDOWNS OF MATERIALS, LABOR, AND SUBCONTRACTOR COSTS. SUPPLIER
QUOTES SHALL BE PROVIDED ON SUPPLIER LETTERHEAD. LABOR UNITS FOR NEW MATERIAL INSTALLATIONS SHALL NOT EXCEED 75% OF NECA 1 “NORMAL
CONDITION” RATES WITHOUT SPECIFIC APPROVAL.
30. BID PACKAGE RESPONSIBILITY: EACH BID PACKAGE SHALL BE CONSIDERED INDEPENDENT AND COMPLETED. THE CONTRACTOR SHALL INCLUDE ALL LABOR, MATERIAL, EQUIPMENT, ACCESSORIES, COORDINATION, CONNECTIONS, EXCAVATION, BACKFILL, RESTORATION, TESTING AND OTHER WORK NECESSARY TO PROVIDE A COMPLETE AND OPERATIONAL INSTALLATION FOR THAT WORK INCLUDED WITHIN THAT BID PACKAGE. DO NOT ASSUME THAT WORK REQUIRED FOR A COMPLETE INSTALLATION WILL BE PROVIDED UNDER ANOTHER BID PACKAGE UNLESS SPECIFICALLY INDICATED.
5518 NW 88th Street Johnston, IA 50131 515-727-0700 www.KEDbluestone.com
KED
bluestone
Architect of Record:
ADG
800 SW ADAMS STREET, SUITE 101
PEORIA, IL 61602
R e vi si o n s
P - 309.672.6948
Discipline:Discipline:Discipline:
P - P - P -
Discipline:
P -
PROJECT NO.
DATE
DRAWN BY
STATUS
Discipline: Owner Consultant
QSC SERVICES, LLC
PMB #69
545 BRENT LN. PENSACOLA, FL
P - 309.231.8272
OWNER ID:
Design and Construction Administration Division
ESCAMBIA COUNTY, FL
100 E. BLOUNT ST. PENSACOLA, FL 32501
PROJECT NUMBER: 126-030
KEDbluestone RESERVES PROPRIETARY RIGHTS, INCLUDING
COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN
THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE
PROPERTY OF KEDbluestone AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
KEDbluestone. © 2026 KEDbluestone
ESCAMBIA COUNTY AREA TRANSIT - FACILITY:
05 - FUEL STATION CANOPIES
2 CLARINDA LN
PENSACOLA, FLORIDA, 32505 EF000ELECTRICAL COVER PAGE
KEDbluestone
707 NE JEFFERSON AVE,
PEORIA, IL 61602
RLG CONSULTING ENGINEERS
12001 N CENTRAL, EXPY #300
DALLAS, TX 75243
RLG CONSULTING ENGINEERS
12001 N CENTRAL, EXPY #300
DALLAS, TX 75243
214.739.8100 214.739.8100 515.259-5957
HODGSON DOUGLAS LANDSCAPE
12001 N. CENTRAL EXPRESSWAY, SUITE 1170
DALLAS, TX 75243
214.749.0333
BID PACKAGE 2 - NOT FOR CONSTRUCTION
10/22/2026
ADG
ELECTRICAL SHEET LIST
EF000 ELECTRICAL COVER PAGE
ES101 ELECTRICAL BID #2 SITE PLAN
ES102 ELECTRICAL SITE LIGHTING PLAN
ES103 ELECTRICAL SITE PHOTOMETRIC PLAN
ELF100 ELECTRICAL LIGHTING PLAN
EPF100 ELECTRICAL POWER PLAN
EPF300 ELECTRICAL ROOF PLAN
EF500 ELECTRICAL DETAILS
EF501 ELECTRICAL DETAILS
EF600 ELECTRICAL SCHEDULES
A D
D
/1
/2
B B
C C
D D
E E
F F
F7 F7
F7 F7
F7 F7
F7 F7
F7 F7
F7
F7
F7
F7
HEF1-2
'HEF1' 'LEF1'
1 1
12" x 12" NEMA 4X BOX WITH
SITE WINDOW. CONTAINS
PHOTOCELL, NLIGHT RELAY
AND 2-POLE DOUBLE THROW
OVERRIDE SWITCH FOR
CANOPY LIGHTING.
'XFMR-LEF1'
GDS-1
ELECTRICAL CONTRACTOR
TO ROUTE (2) 1" CONDUITS
TO FEED FARE PROCESSING
AND VESTIBULE LIGHTS AND
NLIGHT LIGHTING CONTROL
CABLING IN THE WASH
BUILDING FROM PANEL 'HEF1'.
(3) #10 IN 1" CONDUIT FROM HEF1-2
(3) #10 IN 1" CONDUIT FROM HEF1-7
HEF1-7
FUEL TANK BY OTHERS
FUEL TANK BY OTHERS
FUEL TANK BY OTHERS
45 kVA
NEMA 3R
KEY MAP
C03.01
C03.05
C03.03
C03.02
C03.04
5518 NW 88th Street Johnston, IA 50131 515-727-0700 www.KEDbluestone.com
KED
bluestone
Architect of Record:
ADG
800 SW ADAMS STREET, SUITE 101
PEORIA, IL 61602
R e vi si o n s
P - 309.672.6948
Discipline:Discipline:Discipline:
P - P - P -
Discipline:
P -
PROJECT NO.
DATE
DRAWN BY
STATUS
Discipline: Owner Consultant
QSC SERVICES, LLC
PMB #69
545 BRENT LN. PENSACOLA, FL
P - 309.231.8272
OWNER ID:
Design and Construction Administration Division
ESCAMBIA COUNTY, FL
100 E. BLOUNT ST. PENSACOLA, FL 32501
PROJECT NUMBER: 126-030
KEDbluestone RESERVES PROPRIETARY RIGHTS, INCLUDING
COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN
THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE
PROPERTY OF KEDbluestone AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
KEDbluestone. © 2026 KEDbluestone
ESCAMBIA COUNTY AREA TRANSIT - FACILITY:
05 - FUEL STATION CANOPIES
2 CLARINDA LN
PENSACOLA, FLORIDA, 32505 ELF100ELECTRICAL LIGHTING PLAN
KEDbluestone
707 NE JEFFERSON AVE,
PEORIA, IL 61602
RLG CONSULTING ENGINEERS
12001 N CENTRAL, EXPY #300
DALLAS, TX 75243
RLG CONSULTING ENGINEERS
12001 N CENTRAL, EXPY #300
DALLAS, TX 75243
214.739.8100 214.739.8100 515.259-5957
HODGSON DOUGLAS LANDSCAPE
12001 N. CENTRAL EXPRESSWAY, SUITE 1170
DALLAS, TX 75243
214.749.0333
BID PACKAGE 2 - NOT FOR CONSTRUCTION
10/22/2026
ADG
N
1/8" = 1'-0"
ELECTRICAL LIGHTING PLAN
KEYED NOTES:
1. PANEL SHALL BE LOCATED NEARBY
INDICATED LOCATION MOUNTED TO STRUT.
GENERAL NOTES:
1. ALL WIRING, RACEWAYS AND BOXES SHALL MEET NEC ARTICLE
514 CLASS 1 DIVISION 2 SPECIFICATIONS UNDER THE FUEL
CANOPY OR WITHIN 20' OF FUEL PUMPS.
2. ELECTRICAL CONTRACTOR TO COORDINATE FINAL SECURITY
CAMERA PLACEMENTS ON SITE LIGHTING POLE PRIOR TO
ORDERING LIGHT POLES. REFER TO TECHNOLOGY PLANS FOR
EXACT CAMERA PLACEMENT ON POLES.
A D
D
/1
/2
B B
C C
D D
E E
F F
UL-2 GAS
FUELING
PUMP
UL-2 GAS
FUELING
PUMP
DIESEL
FUELING
PUMP
DIESEL
FUELING
PUMP
DS-UL-2 GAS FUELING PUMP
30/1/4X
DS-UL-2 GAS FUELING PUMP
30/1/4X
DS-1-DIESEL FUELING PUMP
30/1/4X
DS-2-DIESEL FUELING PUMP
30/1/4X
'HEF1' 'LEF1'
GDS-1
T
1 1
FUEL
SHUT-OFF
FUEL TANK SHUT-OFF MOUNTED
TO TANK. FURNISH AND INSTALL
UNISTRUT RACKING AS REQUIRED
TO MOUNT EQUIPMENT
GAS
GAS
FUEL TANK
FUEL TANK
FUEL TANK
LEF1-5,7
LEF1-2,4
LEF1-8,10
MOUNT TO
STRUT
LEF1-21
CONCRETE SLAB
CONDUIT TO FEED
INTEGRAL FUEL
TANK PUMPS FROM
LEF1-(2,4),(5,7),(8,10)
ELECTRICAL CONTRACTOR
TO ROUTE CONDUIT TO
MAINTENANCE YARD TO
FEED GDS-1
ELECTRICAL CONTRACTOR
TO ROUTE CONDUIT TO
VAULT ROOM FOR LIGHTING
AND EQUIPMENT IN WASH
BUILDING FROM PANEL 'LEF1'
SEE DRAWING E600 FOR CIRCUITS
LEF1-16
LEF1-17
LEF1-11
LEF1-1
4 SETS OF
(3) #10 IN 1" CONDUIT
FROM LEF1-1,11,16,17
FUEL TANK BY OTHERS
FUEL TANK BY OTHERS
FUEL TANK BY OTHERS
LEF1-20
45 kVA
NEMA 3R
'XFMR-LEF1'
MGB-1
KEY MAP
C03.01
C03.05
C03.03
C03.02
C03.04
5518 NW 88th Street Johnston, IA 50131 515-727-0700 www.KEDbluestone.com
KED
bluestone
Architect of Record:
ADG
800 SW ADAMS STREET, SUITE 101
PEORIA, IL 61602
R e vi si o n s
P - 309.672.6948
Discipline:Discipline:Discipline:
P - P - P -
Discipline:
P -
PROJECT NO.
DATE
DRAWN BY
STATUS
Discipline: Owner Consultant
QSC SERVICES, LLC
PMB #69
545 BRENT LN. PENSACOLA, FL
P - 309.231.8272
OWNER ID:
Design and Construction Administration Division
ESCAMBIA COUNTY, FL
100 E. BLOUNT ST. PENSACOLA, FL 32501
PROJECT NUMBER: 126-030
KEDbluestone RESERVES PROPRIETARY RIGHTS, INCLUDING
COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN
THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE
PROPERTY OF KEDbluestone AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
KEDbluestone. © 2026 KEDbluestone
ESCAMBIA COUNTY AREA TRANSIT - FACILITY:
05 - FUEL STATION CANOPIES
2 CLARINDA LN
PENSACOLA, FLORIDA, 32505 EPF100ELECTRICAL POWER PLAN
KEDbluestone
70…