ECAT_BP2_DRAWING_SET_-_04_BUS_WASH_Rev_1__26-11-13.pdf
PDF 12 MB Posted
- Solicitation number
- PD 26-27.004
- Issued by
- Escambia County, Florida
About this file
This file comprises structural design drawings and construction documents for the Bus Wash facility, one of five structures comprising the New Escambia County Area Transit (ECAT) Facility in Pensacola, Florida. The drawings, prepared by RLG Consulting Engineers and dated October 22, 2026 (Addendum 01 dated November 12, 2026), provide comprehensive structural, architectural, mechanical, plumbing, and electrical design details for a bus wash building located at 10 Clarinda Lane. The facility consists of a wash bay (101), equipment room (102), ADA restroom (103), fare processing area (104), fare entrance (105), and vacuum room (106), with auxiliary structures including dumpster enclosures. The building is approximately 93 feet 4 inches by 63 feet 4 inches in plan dimension with precast concrete plank roof systems and masonry wall construction. The design incorporates the Interclean XJ404 FF bus wash system, with detailed specifications for foundation design, concrete placement, reinforcing steel, masonry construction, HVAC systems, plumbing connections, and electrical distribution. The drawings reference compliance with the 8th Edition Florida Building Code, ACI 318 concrete standards, and ASCE 7-22 wind design criteria, with wind speeds of 156 mph basic and seismic design category B. Bid documents indicate a non-mandatory pre-bid meeting on October 29, 2026, with bids due November 23, 2026 at 10:00 a.m.; substantial completion is specified within 180 to 335 consecutive calendar days from Notice to Proceed, plus 30 days for final completion.
The project budget and funding details are referenced in the related solicitation as part of a CDBG-DR (HUD Community Development Block Grant-Disaster Recovery) funded initiative. Bidders may bid individual lots or complete package options, with pricing structured as a base bid with deductive alternates and unit prices for specific elements. All work is subject to Davis-Bacon wage requirements. Successful bidders must hold a current Florida General Contractor (CGC) or Underground Utility and Excavation Contractor (CUC) license, provide performance and payment bonds, submit a Quality Control Plan, and maintain insurance coverage of $2,000,000 combined general liability. Federal compliance requirements include suspension and debarment verification, domestic preference, recovered materials procurement, MBE/WBE affirmative steps, E-Verify, and environmental provisions for Eastern Indigo Snakes and Tricolored Bats. Liquidated damages follow the Florida Department of Transportation schedule. The apparent lowest responsive and responsible bidder must submit a detailed Schedule of Values within three business days of bid opening for Florida Department of Commerce review before award authorization.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGN DATA
1. THE DESIGN OF THE STRUCTURE AND PARTS THEREOF IS IN ACCORDANCE WITH THE 8TH EDITION OF FLORIDA BUILDING
CODE, AS AMENDED AND ADOPTED BY ESCAMBIA COUNTY .
2. FLOOR LIVE LOADS.
AREA UNIFORM CONCENTRATED
OFFICES
IMPACT LIVE LOAD REDUCTION
50 psf 2.0 -kips
OFFICE CORRIDORS 1ST FLOOR 2.0 -kips
- kipsASSEMBLY AREAS -
STORAGE HEAVY - kips
STORAGE LIGHT -
kips -
100 psf
100 psf
250 psf
125 psf
3. ROOF LIVE LOADS:
AREA UNIFORM SPECIAL COMMENTS
ROOF, GENERAL
LIVE LOAD REDUCTION
20 psf -
ROOF, EQUIP LOADS SEE ROOF PLAN
4. SNOW LOADS: NOT APPLICABLE PER FBC
5. WIND DESIGN DATA:
ASD WIND SPEED Vasd 121 mph
RISK CATEGORY
BASIC WIND SPEED (3 SECOND GUST)
WIND EXPOSURE
INTERNAL PRESSURE COEFFICIENT
COMPONENTS AND CLADDING
156 mph
+/- 0.55
PER ASCE 7-22
FACTORED COMPONENTS AND CLADDING WALL LOADS
POSITIVE PRESSURE (psf) NEGATIVE PRESSURE (psf)
AREA (SQ FT)
LESS THAN 10
GREATER THAN 500
INTERIOR AND CORNER ZONE INTERIOR ZONE CORNER ZONE
-57
-52
-47
-44 -44
-51
-60
-71
CORNER ZONE IS A DISTANCE OF 3'-0" FROM WALL CORNERS
LINEAR INTERPOLATE FOR LOADS BETWEEN SPECIFIED AREAS
7. FLOOD DESIGN DATA:
THIS PROJECT IS NOT LOCATED WITHIN A FLOOD HAZARD AREA
8. SPECIAL LOADS:
VEHICULAR BARRIERS
AREA
AWNINGS & CANOPIES
UNIFORM
20 psf
6.0 ksf
CONCENTRATED
300 lbs.
IMPACT SECTION OF CODE
FBC 1607.9
FBC 1607.13.4
FACTORED COMPONENTS AND CLADDING ROOF LOADS
POSITIVE PRESSURE (psf) NEGATIVE PRESSURE (psf)
AREA (SQ FT)
LESS THAN 10
GREATER THAN 500
PERIMETER ZONE, "B" IS A DISTANCE OF 12'-0" FROM EDGE OF BUILDING
CORNER ZONE, "C" IS A DISTANCE OF 4'-0" FROM EDGE OF BUILDING
ALL ZONES 2 & 3 ZONE 2
-119
-93
-86
-76
ZONE 3
-162
-111
-96
-76
LINEAR INTERPOLATE FOR LOADS BETWEEN SPECIFIED AREAS
3 3
B
B
C
ROOF WIND LOAD LAYOUT
YES, PER FBC 1607.13.1
YES, PER FBC 1607.13.1
YES, PER FBC 1607.13.1
YES, PER FBC 1607.13.1.2
YES, PER FBC 1607.13.1.2
YES, PER FBC 1607.14
N/A
N/A
TORNADO SPEED, Vt
EFFECTIVE PLAN AREA
II
C
9. ROOF RAIN LOAD DATA:
RAIN INTENSITY (15-DURATION)
4.9 in/hrRAIN INTENSITY (60-DURATION)
9.12 in/hr
6. SEISMIC DESIGN DATA:
SEISMIC IMPORTANCE FACTOR, Ie
MAPPED SPECTRAL RESPONSE ACCEL.
RISK CATEGORY
SITE CLASS
SPECTRAL RESPONSE COEFFICIENTS
SEISMIC DESIGN CATEGORY
Ss =
BASIC SEISMIC-FORCE-RESISTING SYSTEM
DESIGN BASE SHEAR
SEISMIC RESPONSE COEFFICIENT, Cs
RESPONSE MODIFICATION FACTOR, R
ANALYSIS PROCEDURE USED
SDS =
S1 =
SD1 =
0.11 0.063
0.090.1
0.07xW
1.0
II
DEFAULT
B
ORDINARY PLAN MASONRY SHEAR
WALL
0.07
1.5
EQUIVALENT LATERAL FORCE
1. PROJECT SPECIFICATIONS ARE A PART OF THE CONTRACT DOCUMENTS. CONTRACTOR SHALL REVIEW THE SPECIFICATIONS AND NOTIFY ARCHITECT OF DISCREPANCIES BEFORE PROCEEDING WITH WORK.
2. STRUCTURAL DRAWINGS ARE AN INTEGRAL COMPONENT TO THE CONTRACT DOCUMENTS. CONTRACTOR SHALL
REVIEW AND COORDINATE ACCORDINGLY.
A. PRIOR TO FABRICATION OR INSTALLATION OF STRUCTURAL MEMBERS, CONTRACTOR SHALL COMPARE
STRUCTURAL DIMENSIONS AND SECTIONS WITH ARCHITECTURAL DIMENSIONS AND SECTIONS.
DISCREPANCIES ARE TO BE REPORTED IN WRITING TO THE ARCHITECT.
B. PRINCIPAL OPENINGS ARE SHOWN ON THESE DRAWINGS. REFER TO ARCHITECTURAL, MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR OTHER OPENINGS NOT SHOWN.
C. REFER TO ARCHITECTURAL DRAWINGS FOR ELEVATIONS AND LOCATIONS OF SLAB DEPRESSIONS AND
CURBS NOT SHOWN. PROVIDE POSITIVE SLOPE TO ALL DRAINS.
D. CONTRACTOR SHALL COORDINATE PENETRATIONS, SLEEVES, CURBS, AND INSERTS REQUIRED FOR THE
CONTRACT DOCUMENTS.
E. CONTRACTOR SHALL VERIFY SIZE, WEIGHT, LOCATION, AND SUPPORT CONDITIONS OF MECHANICAL
EQUIPMENT SUPPORTED ON OR SUSPENDED FROM THE ROOF OR FLOORS.
F. CONTRACTOR SHALL COORDINATE CONSTRUCTION WITH ADJACENT STRUCTURES AND UTILITIES.
G. CONTRACTOR SHALL NOTIFY IN WRITING THE ARCHITECT & ENGINEER OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH WORK.
3. TEMPORARY SHORING AND BRACING DURING CONSTRUCTION
A. CONTRACTOR SHALL PROVIDE TEMPORARY BRACING OF COMPONENTS DURING CONSTRUCTION TO MEET
REGULATORY REQUIREMENTS FOR SAFETY.
B. CONTRACTOR SHALL PROVIDE TEMPORARY SHORING AND BRACING OF WALLS AND GRADE BEAMS DURING
CONSTRUCTION. SHORE WALLS AND GRADE BEAMS DURING THE BACKFILLING AND COMPACTION PROCESS.
C. CONTRACTOR SHALL PROVIDE NECESSARY TEMPORARY BRACING AND SHORING DURING CONSTRUCTION
UNTIL STRUCTURAL FRAMING AND DIAPHRAGMS ARE COMPLETED. TEMPORARY BRACING SHALL BE
DESIGNED UNDER THE SUPERVISION OF A LICENSED ENGINEER.
4. SELECTION OF CONSTRUCTION MEANS, METHODS, TECHNIQUES, AND PROCEDURES, AS WELL AS SAFETY PRECAUTIONS AND PROGRAMS, ARE SOLELY THE CONTRACTOR’S RESPONSIBILITIES. AS SUCH, CONSTRUCTION ENGINEERING AND DESIGN RESULTING FROM THESE SELECTIONS IS THE RESPONSIBILITY OF THE CONTRACTOR.
A. EXAMPLES INCLUDE, BUT ARE NOT LIMITED TO, ENGINEERING OF SHORING AND SCAFFOLDING SYSTEMS;
LOAD CHECKS AND STRUCTURAL MODIFICATIONS FOR STORAGE, STAGING, AND CONSTRUCTION
EQUIPMENT LOADING; MEANS OF EGRESS FOR HEAVY EQUIPMENT; CRANE SELECTION, LOCATION, SUPPORT
AND BRACING; TEMPORARY HOISTS, LIFTS AND PLATFORMS.
B. CONTRACTOR SHALL ENSURE THAT APPROPRIATE ENGINEERING IS PERFORMED BY A LICENSED ENGINEER FOR THE WORK, CONSULTED WITH ON FIELD MODIFICATIONS, SPECIFY APPROPRIATE LEVELS OF
INSPECTION OF THE WORK, AND TO REVIEW INSPECTION REPORTS.
C. CONSTRUCTION ENGINEERING FEES HAVE NOT BEEN INCLUDED IN THE BASE FEE TO THE
OWNER/ARCHITECT. IF REQUESTED, THE EOR MAY CONSIDER PERFORMING THESE SERVICES AS AN
ADDITIONAL SERVICE PAID BY THE CONTRACTOR.
5. PRE-CONSTRUCTION MEETINGS SHALL BE CONDUCTED TO DISCUSS SUBGRADE PREPARATION, FOUNDATION CONSTRUCTION, WALL BACKFILL, VOID FORM SYSTEMS, CONCRETE FORMING & PLACING, AND TESTING &
INSPECTION REQUIREMENTS.
6. CONTRACTOR SHALL COMPLY WITH REQUIREMENTS AS LISTED IN THE STATEMENT OF SPECIAL INSPECTIONS.
GENERAL NOTES
1. DEFERRED SUBMITTALS ARE PORTIONS OF THE OVERALL DESIGN WHICH ARE NOT SUBMITTED AT TIME OF PERMIT
APPLICATION AND ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL.
2. DEFERRED SUBMITTALS WILL BE REVIEWED FOR THE LIMITED PURPOSE OF CHECKING FOR CONFORMANCE WITH INFORMATION GIVEN IN THE CONTRACT DOCUMENTS. SUBMITTAL REVIEW WILL NOT BE CONDUCTED FOR THE PURPOSE OF DETERMINING THE ACCURACY AND COMPLETENESS OF OTHER DETAILED INFORMATION SUCH AS DIMENSIONS AND QUANTITIES, OR FOR SUBSTANTIATING INSTRUCTIONS FOR INSTALLATION OR SYSTEMS DESIGNED
BY THE CONTRACTOR WHICH REMAINS THE RESPONSIBILITY OF THE CONTRACTOR.
REVIEW SHALL NOT CONSTITUTE APPROVAL OF SAFETY PRECAUTIONS OR OF ANY CONSTRUCTION MEANS, METHODS, SEQUENCES OR PROCEDURES.
APPROVAL OF A SPECIFIC ITEM SHALL NOT INDICATE APPROVAL OF AN ASSEMBLY OF WHICH THE ITEM IS A
COMPONENT.
3. FOLLOWING DEFERRED SUBMITTALS ARE TO BE PROVIDED FOR REVIEW:
A. CONCRETE FORMWORK / RETENTION SYSTEMS
B. PRECAST CONCRETE PLANKS (SIGNED AND SEALED CALCULATIONS AND DRAWINGS)
SUPPLIER’S ENGINEERS SHALL PROVIDE SIGNED AND SEALED CALCULATIONS WITH THE SUBMITTAL FOR REVIEW.
REVIEW WILL BE LIMITED TO CONFORMANCE WITH DESIGN AND PERFORMANCE CRITERIA SPECIFIED IN THE CONSTRUCTION DOCUMENTS AND THE INTERFACE BETWEEN THESE ITEMS/SYSTEMS AND THE BUILDING STRUCTURE. THE MANUFACTURER/SUPPLIER AND ITS SPECIALTY STRUCTURAL ENGINEER REMAIN RESPONSIBLE FOR THE DESIGN OF THE ITEM/SYSTEM WILL RETAIN ALL RIGHTS AND RESPONSIBILITIES FOR THE DESIGN OF THE
PRODUCT AND THE CONNECTIONS TO THE BUILDING STRUCTURE.
NO WORK ON STRUCTURAL ELEMENTS SUPPORTING OR RELATED TO THESE ITEMS IS TO PROCEED UNLESS THE REVIEW STAMP CLEARLY INDICATES "REVIEWED" OR "REVIEWED, SEE COMMENTS" BY THE ENGINEER.
4. FOLLOWING SHOP DRAWINGS ARE TO BE PROVIDED FOR APPROVAL:
A. CONCRETE MIXES
B. REINFORCING STEEL
C. MASONRY WALL REINFORCING
SHOP DRAWINGS ARE TO BE DISTRIBUTED ONLY FROM RETURNED SUBMITTALS BEARING AN INITIALED REVIEW STAMP AND WORK ON THESE ITEMS SHALL NOT PROCEED UNLESS THE STAMP CLEARLY INDICATES THE DRAWINGS
ARE "APPROVED" OR "APPROVED AS NOTED."
5. CONCRETE IS A MATERIAL DESIGNED BY THE SUPPLIER TO MEET THE STRENGTH AND PERFORMANCE CRITERIA SPECIFIED IN THE CONTRACT DOCUMENTS. CONCRETE MIX DESIGNS SHALL BE IN CONFORMANCE WITH ACI 318.
SUBMIT MIX DESIGNS AND THE TESTING LAB REVIEW TO THE ARCHITECT/ENGINEER FOR REVIEW.
MANY VARIABLES, INCLUDING ENVIRONMENTAL CONDITIONS AFFECT THE QUALITY OF CONCRETE. THE CONTRACTOR IS RESPONSIBLE FOR CONTROLLING VARIABLES AND REQUESTING MIX MODIFICATIONS AND SHALL BE
SOLELY RESPONSIBLE FOR THE QUALITY OF CONCRETE DELIVERED AND PLACED ON THE SITE.
6. BEFORE SUBMISSION FOR REVIEW, GENERAL CONTRACTOR SHALL PRE-CHECK SUBMITTALS. SUBMITTALS MUST BEAR AN INITIALED REVIEW STAMP OF THE GENERAL CONTRACTOR. SUBMITTALS WITHOUT REVIEW STAMPS WILL
BE RETURNED WITHOUT REVIEW AND SHALL NOT BE CAUSE FOR CLAIMS OF DELAY.
7. SCHEDULE SUBMITTALS SUFFICIENTLY IN ADVANCE OF THE DATE REQUIRED TO ALLOW REASONABLE TIME FOR PROCESSING AND REVIEW BY THE DESIGN TEAM. THIS SHALL INCLUDE A MINIMUM OF TEN WORKING DAYS FOR ENGINEER'S PROCESSING AND REVIEW. INCLUDE TIME FOR CONTRACTOR’S RESUBMISSION AND SUBSEQUENT
REVIEW IF NECESSARY.
SHORTER REVIEW PERIODS WILL ONLY BE HONORED WITH PRIOR WRITTEN CONSENT. THESE ACCELERATED SERVICES, AND APPROPRIATE COMPENSATION, MUST BE NEGOTIATED WITH THE ENGINEER AND ARCHITECT IN
ADVANCE.
TEN DAY REVIEW PERIODS CAN NOT BE HONORED WHEN LARGE QUANTITIES OF SHOP DRAWINGS ARE SUBMITTED AT ONE TIME. WHEN THIS HAPPENS, THE CONTRACTOR SHALL SUBMIT AN ITEMIZED LIST INDICATING PRIORITIES AND
REASONABLE RETURN DATES.
REVIEW OF RESUBMITTALS WILL BE LIMITED TO ONLY EARLIER COMMENTS AND IS NOT AN EXTENSIVE REVIEW.
8. USE OF REPRODUCTIONS OF THESE CONTRACT DRAWINGS, INCLUDING THE USE OF ELECTRONIC FILES, BY ANY CONTRACTOR IN LIEU OF THE INDEPENDENT PREPARATION OF SHOP DRAWINGS, SIGNIFIES THEIR ACCEPTANCE OF ALL INFORMATION SHOWN HEREON AS CORRECT AND OBLIGATES HIMSELF TO ANY JOB EXPENSE, REAL OR IMPLIED, ARISING DUE TO ANY ERRORS THAT MAY OCCUR HEREON.
9. NOT USED
DEFERRED SUBMITTALS NOTES
1. FOUNDATION DESIGN AND SUBSURFACE INFORMATION IS BASED ON GEOTECHNICAL REPORT #26-162 PREPARED FOR THIS PROJECT BY LARRY M JACOBS & ASSOCIATES, INC AND DATED MAY 1, 2026 & EMAIL RESPONSE DATED
SEPTEMBER 1, 2026.
2. GEOTECHNICAL ENGINEER OF RECORD (GER) IS SOLELY RESPONSIBLE FOR ESTABLISHING FOUNDATION, SLAB-ON- GRADE AND PAVEMENT DESIGN CRITERIA, AND FOR THE CONSTRUCTION RECOMMENDATIONS FOR EXCAVATION, SUBGRADE PREPARATION, BACKFILLING AND COMPACTION.
3. GEOTECHNICAL INFORMATION INDICATED IN THE STRUCTURAL CONSTRUCTION DOCUMENTS IS INTENDED TO REPLICATE THE RECOMMENDATIONS STATED IN THE GEOTECHNICAL ENGINEERING REPORT. PRESENTATION OF THIS INFORMATION IN THE STRUCTURAL DOCUMENTS DOES NOT DEMONSTRATE, STATE OR IMPLY GEOTECHNICAL EXPERTISE BY THE STRUCTURAL ENGINEER. CONTRACTOR SHALL OBTAIN A COPY OF THE REPORT AND COMPLY
WITH THE RECOMMENDATIONS INDICATED THEREIN.
4. IF DISCREPANCIES BETWEEN THE REPORT AND CONSTRUCTION DOCUMENTS ARE DISCOVERED, THE REPORT SHALL GOVERN. ALL CLARIFICATIONS AND INTERPRETATIONS OF THE REPORT SHALL BE MADE BY THE GER AND
REPORTED TO THE ARCHITECT FOR COORDINATION WITH THE DESIGN TEAM.
GEOTECHNICAL INFORMATION
1. BEARING STRATA SHOWN ON THE DETAILS IS COMPACTED NATIVE SOIL. PREPARE FOUNDATION BEARING MATERIAL
PER THE GEOTECHNICAL ENGINEER'S RECOMMENDATIONS.
2. FOUNDATION ALLOWABLE DESIGN SOIL VALUES:
CONTINUOUS FOOTING BEARING - 1.5ksf * ISOLATED FOOTING BEARING - 1.5ksf *
SOIL SLIDING RESISTANCE (NATIVE SOIL) 0.5
* IF CONTINUOUS FOOTING OR ISOLATED FOOTING WIDTH EXCESS 3FT IN DIMENSION, THE SOIL BENEATH FOOTING
SHALL HAVE ADDITIONAL 2FT OF SOIL COMPACTION PER GEOTECHNICAL REPORT.
RETAINING WALL DESIGN VALUES
SOIL DENSITY Yd- 95PCF (VERY LOOSE SLIGHTLY SILTY SAND) AT REST Ka- 0.4xYd PASSIVE PRESSURE Kp- 2.5XYd
3. ALL FOOTING EXCAVATIONS SHALL BE CLEANED TO REMOVE ALL LOOSE SOIL MATERIAL AND OTHER DEBRIS AND
SHOULD NOT BE ALLOWED TO DESICCATE PRIOR TO PLACEMENT OF CONCRETE.
4. CONCRETE FOR FOUNDATIONS SHALL BE FORMED ON THE SIDES (EARTH FORMED FOUNDATIONS WILL NOT BE
ALLOWED). PROPERLY PLACE AND COMPACT FILL MATERIAL AROUND SIDES OF FOOTINGS.
5. ALL FOUNDATION EXCAVATIONS SHALL BE INSPECTED BY THE TESTING AGENCY.
SHALLOW FOUNDATION NOTES
1. FLOOR SLAB SHALL BE 8" THICK CONCRETE SLAB OVER A 15 MIL VAPOR RETARDER, OVER SUBGRADE PREPARED PER THE GEOTECHNICAL ENGINEER'S RECOMMENDATIONS. TAPE ALL SEAMS, PENETRATIONS AND TEARS IN
THE VAPOR RETARDER WITH A COMPATIBLE WATERPROOF TAPE.
2. REINFORCE SLAB WITH #4 @ 12" CTRS. EACH WAY PLACED AND SUPPORTED ON CHAIRS OR CONCRETE BRIQUETS, AT SLAB MID DEPTH.
3. PROVIDE ONE OF THE FOLLOWING JOINTS ON THE CENTERLINE OF ALL COLUMNS, AND @ 15' O.C. MAXIMUM.
A. CONSTRUCTION JOINTS WHERE DETAILED ON DRAWINGS.
B. SAW CUT CONTROL JOINTS ELSEWHERE 2" DEEP OR ONE QUARTER OF THE SLAB DEPTH DEEP, WHICHEVER IS GREATER.
4. CUT SAW CUT JOINTS WITHIN 8 HOURS OF POURING CONCRETE.
5. CONCRETE FINISHES AND SPRAY ON CURRING / SEALING COMPOUNDS SHALL BE COORDINATED WITH
ARCHITECTURAL FLOORING FINISHES FOR COMPATIBILITY.
SLAB-ON-GRADE NOTES
1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH ACI 318- PER GOVERNING BUILDING CODE.
2. CONCRETE IN THE FOLLOWING AREAS SHALL HAVE SAND AND GRAVEL OR CRUSHED STONE AGGREGATES AND THE DESIGNATED COMPRESSIVE STRENGTH IN 28 DAYS UNLESS NOTED OTHERWISE. NORMAL WEIGHT AGGREGATES
SHALL CONFORM TO ASTM C33.
FOOTING AND SLABS ON GRADE --------------------------- f'c = 4,000 psi ALL OTHER CONCRETE ---------------------------------------- f'c = 4,000 psi
3. CONCRETE PROTECTION FOR REINFORCEMENT SHALL BE AS FOLLOWS:
REFER TO ACI 318 - SECTION 7.7 FOR CONDITIONS NOT NOTED.
FOOTINGS ---------------------------------------- 3"
SLABS-ON-GRADE ----------------------------- CENTERED
4. MAXIMUM NOMINAL COARSE AGGREGATE SIZE SHALL BE 1 1/2" MAX FOR PIERS AND 1" MAX TYPICAL UNLESS NOTED
OTHERWISE.
5. CONCRETE SLUMPS SHALL BE AS FOLLOWS:
CONCRETE CONTAINING HRWR------ 10" MAX
ALL OTHER CONCRETE ---------------- 5" MAX, 2" MIN
6. CONCRETE EXPOSED TO WEATHER SHALL BE AIR-ENTRAINED AS FOLLOWS:
3/4" NOMINAL AGGREGATE SIZE 4% TO 8%
1" NOMINAL AGGREGATE SIZE 3.5% TO 6.5%
1 1/2" NOMINAL AGGREGATE SIZE 3% TO 6%
7. ALL FOUNDATIONS AND CAST IN PLACE WALLS SHALL BE FORMED ON SIDES. ALL ELEMENTS OF THE FORMS, FORMWORK, BRACING AND SHORING SHALL CONSIST OF WOOD, METAL OR OTHER MANUFACTURED PRODUCTS AS SPECIFIED. EARTH MAY NOT BE USED AS A FORM, EITHER DIRECTLY OR INDIRECTLY. NEITHER EARTH TRENCHES
NOR EARTH TRENCHES LINED WITH ANOTHER MATERIAL ARE ACCEPTABLE.
8. THERE SHALL BE NO HORIZONTAL CONSTRUCTION JOINTS IN CONCRETE POURS. ALL CONSTRUCTION JOINTS SHALL BE MADE IN THE CENTER OF SPANS WITH VERTICAL BULK HEADS. THE LOCATION OF CONSTRUCTION JOINTS SHALL
BE APPROVED BY THE STRUCTURAL ENGINEER.
9. ALL CONSTRUCTION JOINTS SHOWN ON THE DRAWINGS SHALL BE INCORPORATED IN THE STRUCTURE UNLESS OTHERWISE APPROVED BY THE ENGINEER OF RECORD. ADDITIONAL CONSTRUCTION JOINTS REQUIRED TO FACILITATE CONSTRUCTION SHALL BE LOCATED AND DETAILED ON SHOP DRAWINGS. WHEN CONSTRUCTION JOINTS OTHER THAN THOSE SHOWN ON THE CONSTRUCTION DOCUMENTS ARE REQUIRED, THE REINFORCEMENT SHALL PASS CONTINUOUSLY THROUGH JOINT AND A KEY SHALL BE PROVIDED FOR ADEQUATE SHEAR TRANSFER.
10. UNLESS OTHERWISE NOTED OR DETAILED, PROVIDE (2)#5, (1) EACH FACE AROUND UNFRAMED OPENINGS IN CONCRETE WALLS AND GRADE BEAMS. PLACE BARS PARALLEL TO SIDES OF OPENINGS AND EXTEND 24 INCHES
BEYOND CORNERS.
11. PROVIDE EQUIPMENT BASES AND SUPPORTS AS REQUIRED, COMPLYING WITH APPROVED MANUFACTURERS
CERTIFIED SHOP DRAWINGS AND DETAILS.
12. SIZE AND LOCATION OF BASES AND EMBEDDED ANCHORS FOR EQUIPMENT SHALL BE COORDINATED WITH
EQUIPMENT SUPPLIER AND ALL BE IN ACCORDANCE WITH APPROVED SHOP DRAWINGS.
13. NO ALUMINUM OF ANY TYPE SHALL BE ALLOWED IN THE CONCRETE WORK, UNLESS COATED AND APPROVED BY
THE ENGINEER OR RECORD.
14. NO ELECTRICAL CONDUIT SHALL BE PLACE ABOVE THE WELDED WIRE FABRIC IN THE SLAB-ON-GRADE OR CONCRETE PLACED ON COMPOSITE METAL DECK. MAXIMUM SIZE OF CONDUIT SHALL BE 1/3 THE SLAB THICKNESS (ABOVE DECK ON COMPOSITE SLAB) INCLUDING CROSSOVERS. CONDUIT SHALL NOT BE PLACED CLOSER THAN 3
DIAMETERS ON CENTER.
CONCRETE NOTES
1. THE DESIGN AND ERECTION OF PRECAST CONCRETE COMPONENTS SHALL BE THE RESPONSIBILITY OF THE PRECAST FABRICATOR. THE FABRICATOR'S SHOP DRAWINGS AND CALCULATIONS SHALL BE SUBMITTED FOR REVIEW AND SHALL BEAR THE SEAL OF A REGISTERED PROFESSIONAL ENGINEER IN THE STATE OF THE PROJECT, AND SHALL BE IN ACCORDANCE WITH ACI 318, AND PCI MNL 120 - PCI DESIGN HANDBOOK.
2. THE FABRICATOR SHALL DESIGN ALL PRECAST UNITS TO SUPPORT THE LIVE AND DEAD LOADS INDICATED ON PLANS AND DETAILS. REFER TO PLANS AND DETAILS FOR AREAS REQUIRING THICKER TOPPINGS. DESIGN ALL UNITS SUCH THAT NO SHORING WILL BE REQUIRED DURING CONSTRUCTION. LIMIT DEFLECTIONS TO THE STANDARDS SET FORTH IN ACI 318 FOR STRUCTURES SUPPORTING ELEMENTS LIKELY TO BE DAMAGED BY LARGE DEFLECTIONS.
3. THE FABRICATOR SHALL USE THE FOLLOWING WEIGHTS OF BUILDING MATERIALS TO DETERMINE ACTUAL LOADING
CONDITIONS:
NORMAL WEIGHT CONCRETE 150 pcf LIGHTWEIGHT CONCRETE 120 pcf
4. IN ADDITION TO THE LIVE AND DEAD LOADS INDICATED ON PLANS AND DETAILS, PRECAST COMPONENTS SHALL BE DESIGNED TO SUPPORT A 15 psf SUPERIMPOSED DEAD LOAD + MECHANICAL EQUIPMENT LOADING SHOWN ON PLAN
AND ROOF FALL PROTECTION SYSTEM.
5. NO ROOF LIVE LOAD REDUCTION SHALL BE ALLOWED.
6. TYPICAL ROOF UNITS SHALL BE 8" DEEP X 24" OR 48" WIDE SEE PLAN. UNITS SHALL BE FABRICATED FROM NORMAL WEIGHT CONCRETE WITH A 28 DAY COMPRESSIVE STRENGTH = 5000 psi AND A RELEASE STRENGTH OF 3500 psi.
7. UNITS HAVE BEEN LAID OUT USING THE 24" OR 48 " WIDTH AS TYPICAL. PROVIDE SPECIAL WIDTH UNITS AND FILLERS AS REQUIRED TO COMPLETE THE FLOOR AND ROOF SYSTEM. ALTERNATE UNIT WIDTHS WILL BE CONSIDERED PROVIDED THE CONTRACTOR COORDINATES REVISIONS TO THE SYSTEM WITH THE DESIGN TEAM AND ALL
APPROPRIATE SUB CONTRACTORS.
8. FABRICATOR SHALL DESIGN UNITS TO ACCOMMODATE OPENINGS SHOWN ON STRUCTURAL DRAWINGS AND SHALL REFER TO MECHANICAL, ELECTRICAL, ETC. FOR ADDITIONAL OPENINGS IN UNITS. FABRICATOR MAY PROPOSE
STEEL HEADERS WHERE APPROPRIATE, BUT SHALL COORDINATE THEM WITH ARCHITECT.
9. ALL TEMPORARY BRACING AND SHORING DURING ERECTION OF PRECAST ELEMENTS IS THE RESPONSIBILITY OF THE CONTRACTOR. ALL BRACING IS TO REMAIN IN PLACE UNTIL THE FLOOR AND ROOF DECKS HAVE ATTAINED
DESIGN STRENGTH AND DIAPHRAGM CONNECTIONS HAVE BEEN COMPLETED.
10. UNLESS NOTE OTHERWISE, ALL PRECAST/PRESTRESSED CONCRETE SHALL BE SUPPLIED BY A "PCI CERTIFIED
PLANT"
11. ALL PRECAST / PRESTRESSED MEMBERS SHALL BE OF SIZE, SHAPE, AND SPAN INDICATED ON THE DRAWINGS. ALL UNITS SHALL BE CAPABLE OF SUPPORTING THE SUPERIMPOSED DEAD AND LIVE LOADS AS SHOWN ON THE
DOCUMENTS, PLUE THE SELFWEIGHT OF THE PRECAST MEMBERS.
12. MANUFACTURER SHALL SUBMIT COMPLETE DESIGN CALCULATIONS FOR RECORD THAT ARE PREPARED B A LICENSED STRUCTURAL ENGINEER IN THE STATE OF FLORIDA FOR ALL PRECAST / PRESTRESSED CONCRETE
MEMBERS.
13. FIELD CUT HOLES FOR OPENINGS THAT DO NOT DISTURB PRESTRESSING STRANDS IN ACCORDANCE WITH THE PRESTRESSED UNIT MANUFACTURER'S INSTRUCTIONS. VERIFY SIZE AND LOCATION OF HOLES AND SLEEVES WITH
ALL APPLICABLE TRADES.
14. PRECAST MANUFACTURER SHALL COORDINATE WITH ARCHITECTURAL AND MECHANICAL DRAWINGS FOR REQUIRED
OPENINGS INCLUDING BUT NOT LIMITED TO OPENING SIZE AND LOCATIONS.
PRECAST CONCRETE NOTES
1. STRUCTURAL MASONRY SHALL CONFORM TO "BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES" ACI
530 / ASCE 5 - LATEST EDITION.
2. HOLLOW LOAD BEARING MASONRY UNITS SHALL CONFORM TO ASTM C90, LIGHTWEIGHT, TYPE N, WITH A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 1900 psi ON THE NET AREA OF THE BLOCK. DESIGN BASED ON AN ULTIMATE COMPRESSIVE STRENGTH f'm = 2500 psi.
3. MORTAR SHALL CONFORM TO ASTM C270, TYPE M OR S.
4. GROUT SHALL CONFORM TO ASTM A476 WITH A MINIMUM COMPRESSIVE STRENGTH OF 2500 psi. USE COARSE GROUT IN TYPICAL APPLICATION. USE FINE GROUT IN 4" AND 6" CMU WALLS AND IN ANY CELL REINFORCED WITH
MORE THAN ONE BAR.
5. REFER TO REINFORCING STEEL NOTES FOR REINFORCEMENT USED IN MASONRY CONSTRUCTION. ALL REINFORCING TO BE GRADE 60. PRIOR TO FABRICATION SUBMIT SHOP DRAWINGS FOR REVIEW, INCLUDING WALL
ELEVATIONS SHOWING ALL REINFORCING STEEL.
6. VERTICAL REINFORCING SHALL BE #6 BARS AT A MAXIMUM SPACING OF 40" O.C., UNLESS OTHERWISE NOTED ON DRAWINGS. THE FIRST CELL AT CORNERS AND ENDS OF WALLS SHALL BE REINFORCED WITH 1-#6 BAR AND GROUTED FULL. ON EACH SIDE OF WALL OPENINGS 2-#5 BAR EXTENDING 2'-0" BEYOND CORNERS OF OPENING SHALL BE PLACED. ALL REINFORCED CELLS SHALL BE FILLED SOLIDLY WITH GROUT. REFER TO DETAILS FOR
SPECIAL REINFORCEMENT AT SUPPORTS.
7. REINFORCING BARS SHALL BE STRAIGHT EXCEPT FOR BENDS AROUND CORNERS AND WHERE BENDS OR HOOKS
ARE DETAILED ON THE PLANS.
8. REINFORCING STEEL SHALL BE LAPPED 60 BAR DIAMETERS WHERE SPLICED AND SHALL BE WIRED TOGETHER.
9. HORIZONTAL WALL REINFORCING SHALL BE EXTRA HEAVY HOHMANN & BARNARD COMPANY (LADUR TYPE) AT 1'-4" O.C. FOR 12" CMU AND STANDARD HOHMANN & BARNARD COMPANY (LADUR TYPE) AT 1'-4" O.C. FOR 8" CMU. IN LIEU OF HOHMANN & BARNARD COMPANY REINFORCEMENT THE CONTRACTOR MAY PROVIDE HORIZONTAL BOND BEAMS
LOCATED 48" O.C. VERTICALLY AND REINFORCED WITH 2-#5 CONTINUOUS BARS.
10. ALL REINFORCING SHALL BE IN PLACE PRIOR TO GROUTING. VERTICAL REINFORCING BARS SHALL BE HELD IN POSITION AT TOP, BOTTOM, AND AT INTERVALS NOT FURTHER APART THAN 192 BAR DIAMETERS BY WALL-BRAC VERTICAL STEEL POSITIONER AS MANUFACTURED BY W.C.R. FABRICATORS, OR AN EQUIVALENT POSITIONER.
11. PROVIDE CONTINUOUS CMU BOND BEAMS (8" MIN. DEPTH) REINFORCED WITH 2-#5 CONTINUOUS BARS AT TOP OF PARAPETS AND AT ROOF FRAMING ELEVATION FOR FULL LENGTH OF ALL WALLS. WHERE BOND BEAMS REQUIRE SLOPES, PROVIDE 16" DEEP BOND BEAM AND CUT TO PROVIDE AN 8" MINIMUM DEPTH. CONTINUE HORIZONTAL
REINFORCEMENT THROUGH MASONRY COLUMNS AND PILASTERS.
12. PROVIDE 2-#5 CORNER BARS (2'-6"x2'-6"), LAP WITH CONTINUOUS BARS IN ALL BOND BEAMS AT CORNERS AND WALL
INTERSECTIONS.
13. PROVIDE VERTICAL CONTROL JOINTS IN ALL MASONRY WALLS WHERE SHOWN ON ARCHITECTURAL OR STRUCTURAL DRAWINGS, AND NOT TO EXCEED 30 FEET O.C. PROVIDE MATCHING CONTROL JOINTS IN FINISH MATERIALS (i.e. BRICK, STUCCO, etc.). VERTICAL CELLS ON EACH SIDE OF CONTROL JOINTS SHALL BE REINFORCED
AND GROUTED TO MATCH THE TYPICAL WALL REINFORCEMENT.
14. AT WALL CONTROL JOINTS, CONTINUE BOND BEAM REINFORCEMENT THROUGH JOINT AND DISCONTINUE ALL OTHER
HORIZONTAL WALL REINFORCING AT JOINT.
15. ALL UNITS SHALL BE LAID WITH FULL MORTAR BEDS ON THE FACE SHELLS. ALL HEAD JOINTS SHALL BE FILLED SOLIDLY WITH MORTAR FOR A DISTANCE IN FROM THE FACE OF THE UNIT NOT LESS THAN THE THICKNESS OF THE LONGITUDINAL FACE SHELLS. UNLESS THE WALL IS TO BE POURED SOLID, END WALLS AND CROSS WEBS FORMING
CELLS TO BE FILLED SHALL BE FULLBEDDED IN MORTAR TO PREVENT LEAKAGE OF GROUT.
16. ALL DOWELS, ANCHOR BOLTS, AND HEADED STUDS SHALL BE SET IN SOLID GROUTED CELLS.
17. GROUT ALL CELLS SOLID BELOW GRADE.
LOAD BEARING STRUCTURAL MASONRY
1. POST-INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED ON THE CONSTRUCTION DOCUMENTS. THE CONTRACTOR SHALL OBTAIN APPROVAL FROM THE ENGINEER-OF-RECORD PRIOR TO INSTALLING POST-INSTALLED ANCHORS IN PLACE OF MISSING OR MISPLACED CAST-IN-PLACE ANCHORS. CARE SHALL BE TAKEN IN PLACING POST-INSTALLED ANCHORS TO AVOID CONFLICTS WITH EXISTING REINFORCING OR POST-TENSIONING.
2. SUBSTITUTION REQUESTS, FOR PRODUCTS OTHER THAN THOSE SPECIFIED BELOW, SHALL BE SUBMITTED BY THE CONTRACTOR TO THE ENGINEER-OF-RECORD ALONG WITH CALCULATIONS THAT ARE PREPARED & SEALED BY A REGISTERED PROFESSIONAL ENGINEER. THE CALCULATIONS SHALL DEMONSTRATE THAT THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING EQUIVALENT PERFORMANCE VALUES (MINIMUM) OF THE SPECIFIED PRODUCT USING THE APPROPRIATE DESIGN PROCEDURE AND/OR STANDARD(S) AS REQUIRED BY THE BUILDING CODE.
3. POST-INSTALLED ANCHORS INCLUDE EXPANSION ANCHORS, UNDERCUT ANCHORS AND ADHESIVE ANCHORS.
ADHESIVE ANCHORS SHALL CONSIST OF A STRUCTURAL ADHESIVE AND STEEL INSERT. STEEL INSERTS SHALL BE EITHER ASTM F1554, GRADE 36 THREADED ROD OR ASTM A615, GRADE 60 REINFORCING STEEL UNLESS NOTED OTHERWISE ON THE DRAWINGS. PROVIDE, STORE AND INSTALL PRODUCTS IN STRICT CONFORMANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS.
4. EXPANSION ANCHORS FOR USE IN CRACKED AND UNCRACKED CONCRETE SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI 355.2 AND ICC-ES AC193. EXPANSION ANCHORS SHALL BE EITHER HILTI KWIK BOLT TZ ANCHORS OR SIMPSON STRONG-TIE STRONG-BOLT 2 ANCHORS, UNLESS NOTED OTHERWISE ON DRAWINGS. EXPANSION ANCHORS SHALL BE 3/4" DIAMETER WITH 4 3/4" EMBEDMENT UNLESS NOTED OTHERWISE
ON THE DRAWINGS.
5. EXPANSION ANCHORS FOR USE IN SOLID-GROUTED CONCRETE MASONRY SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC01. EXPANSION ANCHORS IN CMU SHALL BE EITHER HILTI KWIK
BOLT 3 ANCHORS OR SIMPSON STRONG-TIE WEDGE-ALL ANCHORS.
6. UNDERCUT ANCHORS FOR USE IN CRACKED AND UNCRACKED CONCRETE SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI 355.2 AND ICC-ES AC193. UNDERCUT ANCHORS SHALL BE EITHER
HILTI HDA ANCHORS OR SIMPSON STRONG-TIE TORQ-CUT ANCHORS, UNLESS NOTED OTHERWISE ON DRAWINGS.
7. STRUCTURAL ADHESIVES FOR USE IN CRACKED AND UNCRACKED CONCRETE SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI 355.4 AND ICC-ES AC308. STRUCTURAL ADHESIVES SHALL BE HITI HIT-RE 500-SD EPOXY, HILTI HIT-HY 200-A ADHESIVE, SIMPSON STRONG-TIE SET-XP ADHESIVE OR SIMPSON STRONG- TIE AT-XP ADHESIVE UNLESS NOTED OTHERWISE ON THE DRAWINGS. REFER TO DRAWINGS FOR SIZE AND EMBEDMENT REQUIREMENTS. ALL THREADED RODS USED IN EXTERIOR EXPOSURES SHALL BE GALVANIZED.
8. THE FOLLOWING PARAMETERS HAVE BEEN USED IN THE DESIGN OF ALL ADHESIVE ANCHORS UNLESS NOTED
OTHERWISE ON THE DRAWINGS:
A. MINIMUM AGE OF CONCRETE – 28 DAYS
B. CONCRETE TEMPERATURE RANGE FOR ANCHORS NOT EXPOSED TO THE ENVIRONMENT – MAXIMUM SHORT
TERM TEMPERATURE OF 104°F; MAXIMUM LONG TERM TEMPERATURE OF 75°F.
C. CONCRETE TEMPERATURE RANGE FOR ANCHORS EXPOSED TO THE ENVIRONMENT – MAXIMUM SHORT TERM
TEMPERATURE OF 150°F; MAXIMUM LONG TERM TEMPERATURE OF 110°F.
D. MOISTURE CONDITION OF CONCRETE AT THE TIME OF INSTALLATION – DRY CONCRETE
E. HOLE DRILLING AND PREPARATION – PER THE MANUFACTURER’S PRINTED INSTALLATION INSTRUCTIONS
9. STRUCTURAL ADHESIVES FOR USE IN SOLID-GROUTED CONCRETE MASONRY SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC58. STRUCTURAL ADHESIVES SHALL BE HILTI HIT-HY 70 ADHESIVE, SIMPSON STRONG-TIE SET ADHESIVE, OR SIMPSON STRONG-TIE AT ADHESIVE UNLESS NOTED OTHERWISE ON THE DRAWINGS. REFER TO DRAWINGS FOR SIZE AND EMBEDMENT REQUIREMENTS. ALL THREADED
RODS USED IN EXTERIOR EXPOSURES SHALL BE GALVANIZED.
10. ANCHOR CAPACITY IS DEPENDANT UPON THE SPACING BETWEEN ADJACENT ANCHORS AND THE PROXIMITY OF ANCHORS TO THE EDGE OF CONCRETE. INSTALL ANCHORS IN ACCORDANCE WITH THE SPACING AND EDGE
CLEARANCES INDICATED ON THE DRAWINGS.
11. PRIOR TO PLACEMENT, THE CONTRACTOR SHALL HAVE THE MANUFACTURER’S TECHNICAL REPRESENTATIVE VISIT THE SITE TO INSTRUCT THE CONSTRUCTION TEAM AND TESTING LAB ON PROPER STORAGE AND INSTALLATION TECHNIQUES. THE CONTRACTOR SHALL PROVIDE A LETTER FROM THE MANUFACTURER’S REPRESENTATIVE
STATING THAT SUCH A VISIT WAS CONDUCTED.
12. ALL EXPANSION ANCHORS SHALL BE INSPECTED BY AN INDEPENDENT TESTING LAB FOR THE FOLLOWING:
A. CORRECT LOCATION AND POSITION OF HOLE.
B. CORRECT HOLE DIAMETER
C. CORRECT EMBEDMENT DEPTH.
D. CORRECT BOLT TYPE AND FINISH.
E. CONDITION OF HOLE IN CONNECTION MATERIAL (NO BURNING OF HOLES ALLOWED).
F. SNUG TIGHT FIT.
13. ADHESIVE ANCHORS SHALL BE INSPECTED AND TESTED BY AN INDEPENDENT TESTING LAB AS FOLLOWS:
ALL ANCHORS SHALL BE INSPECTED FOR THE FOLLOWING:
A. CORRECT LOCATION AND POSITION OF HOLE.
B. CORRECT THREADED ROD OR REINFORCING BAR SIZE.
C. CORRECT THREADED ROD OR REINFORCING BAR TYPE AND FINISH.
D. CONDITION OF HOLE IN CONNECTION MATERIAL (NO BURNING OF HOLES ALLOWED).
E. SNUG TIGHT FIT.
F. CORRECT EMBEDMENT DEPTH.
G. HOLE PREPARATION (INCLUDING DRILL BIT TYPE WHERE CRITICAL TO MANUFACTURER) AND CLEANOUT PER
MANUFACTURER'S RECOMMENDATIONS.
H. ADHESIVE TYPE, EXPIRATION DATE AND METHOD OF STORAGE.
I. ADHESIVE AND ANCHOR INSTALLATION PER MANUFACTURER’S RECOMMENDATIONS.
14. THE TESTING LAB SHALL PREPARE AN INSPECTION REPORT SPECIFICALLY INDICATING DEGREE OF CONFORMANCE
IN ALL CATEGORIES LISTED ABOVE.
POST-INSTALLED ANCHOR NOTES
1. ALL SUBGRADE SHALL BE PREPARED IN STRICT CONFORMANCE TO THE GEOTECHNICAL ENGINEER’S RECOMMENDATIONS. REFER TO THE GEOTECHNICAL REPORT, SUPPLEMENTARY LETTERS AND SPECIFICATIONS
FOR ADDITIONAL INFORMATION.
THE SUBGRADE SHALL BE IMPROVED TO REDUCE THE POTENTIAL FOR SUBGRADE MOVEMENT TO LESS THAN OF ONE INCH TOTAL SETTLEMENT & 1/2 INCH OF DIFFERENTIAL SETTLEMENT BY RE-COMPACTING IN-SITU SOIL AS
APPROVED BY GEOTECH ENGINEER.
THE FOLLOWING IS A SUMMARY OF THE INFORMATION CONTAINED IN THE GEOTECHNICAL ENGINEER’S
RECOMMENDATIONS:
A. THE BUILDING EXCAVATION AREA SHALL EXTEND BEYOND THE BUILDING LINE A MINIMUM OF 5 FEET IN GENERAL. AT ALL ENTRANCES AND AT AREAS WITH SIDEWALKS/PAVING DIRECTLY ADJACENT TO THE
BUILDING.
B. WITHIN THE BUILDING AREA, EXCAVATE AND REMOVE ALL FILL MATERIAL. REFER TO THE GEOTECHNICAL REPORT FOR APPROXIMATE DEPTHS OF FILL. THE TESTING LAB SHALL DETERMINE THROUGH FIELD
OBSERVATION AND TESTING THAT ALL UNACCEPTABLE FILLS HAVE BEEN REMOVED.
C. WITHIN THE BUILDING AREA, RE-COMPACT NATIVE SOIL OR IMPORTED FILL AS REQUIRED TO PROVIDE A COMPACTED MATERIAL BENEATH BUILDING AREA. FOOTING THAT HAVE A WIDTH GREATER THAN 3FT IN
WIDTH WILL REQUIRE ADDITIONAL 2FT OF SOIL COMPACTION BENEATH FOOTING.
D. SCARIFY EXPOSED NATIVE SOILS TO A DEPTH OF 12 INCHES FOR FOOTING LESS THAN 3FT IN WIDTH AND RECOMPACT TO A MINIMUM OF 95% OF MODIFIED PROCTOR (ASTM D1557) AT A MINIMUM OF +2 PERCENTAGE POINTS ABOVE THE OPTIMUM MOISTURE CONTENT FOR THE SOIL AS DIRECTED IN THE
GEOTECHNICAL REPORT.
K. SELECT FILL SHALL CONSIST OF A SLIGHTLY SILTY SAND OR SILTY/CLAYEY SAND. ALL SELECT FILL SHALL BE
APPROVED BY THE GEOTECHNICAL ENGINEER.
L. SPREAD THE SELECT FILL IN THIN LOOSE LIFTS NOT EXCEEDING 10 TO 12 INCHES THICK FOR SLIGHTLY SILTY SAND OR LIFTS NOT EXCEEDING 6 TO 8 INCHES THICK FOR SILTY/CLAYEY SAND AND UNIFORMLY COMPACT TO A MINIMUM OF 95% OF ASTM D1557 WITHIN +2 OR –2 PERCENTAGE POINTS OF THE OPTIMUM MOISTURE
CONTENT FOR THE SOIL AS RECOMMENDED IN THE GEOTECHNICAL REPORT.
M. PLACE FIRST LIFT OF SELECT FILL WET OF OPTIMUM TO PREVENT DRYING OF THE UNDERLYING SUBGRADE.
N. PROTECT FILL TO PREVENT DESICCATION PRIOR TO PLACING A SUBSEQUENT LIFT.
2. CONTACT THE GEOTECHNICAL ENGINEER FOR ANY QUESTIONS REGARDING INTERPRETATION OR CLARIFICATION OF
THE ABOVE INFORMATION.
3. FOUNDATION AND SUBGRADE PREPARATION SHALL BE MONITORED AND TESTED BY THE SOILS ENGINEER. REFER
TO SPECIFICATIONS FOR QUALITY CONTROL REQUIREMENTS.
SUBGRADE PREPARATION
1. ALL REINFORCING STEEL SHALL BE NEW DEFORMED BILLET STEEL CONFORMING TO ASTM A615, GRADE 60.
2. DETAILING OF REINFORCEMENT SHALL BE IN ACCORDANCE WITH THE ACI DETAILING MANUAL.
3. REINFORCING BARS MAY BE SPLICED ONLY AS SHOWN ON THE DRAWINGS EXCEPT THAT REINFORCING DESIGNATED AS "CONTINUOUS" MAY BE CONTACT LAP SPLICED WITH TENSION LAP PER ACI 318 CHAPTER 25.
4. FOR CONTINUOUS GRADE BEAM REINFORCING, PER GRADE BEAM REINFORCEMENT LAP SPLICES SCHEDULED
ON S300.
5. PROVIDE CORNERS BARS OF SAME SIZE AND QUANTITY AS CONTINUOUS TOP AND BOTTOM REINFORCING OF
GRADE BEAMS AT ALL GRADE BEAM CORNERS AND INTERSECTIONS.
REINFORCING STEEL NOTES
Architect of Record:
ADG
800 SW ADAMS STREET, SUITE 101
PEORIA, IL 61602
R e vi si o n s
P - 309.672.6948
Discipline:Discipline:Discipline:
P - P - P -
Discipline:
P -
PROJECT NO.
DATE
DRAWN BY
STATUS
Discipline: Owner Consultant
QSC SERVICES, LLC
PMB #69
545 BRENT LN. PENSACOLA, FL
P - 309.231.8272
OWNER ID:
Design and Construction Administration Division
ESCAMBIA COUNTY, FL
100 E. BLOUNT ST. PENSACOLA, FL 32501
ESCAMBIA COUNTY AREA TRANSIT - FACILITY:
04 - BUS WASH
10 CLARINDA LN
PENSACOLA, FL 32505 S001GENERAL NOTES
KEDbluestone
707 NE JEFFERSON AVE,
PEORIA, IL 61602
RLG CONSULTING ENGINEERS
12001 N CENTRAL EXPY, STE 300
DALLAS, TX 75243
RLG CONSULTING ENGINEERS
12001 N CENTRAL, STE 300
DALLAS, TX 75243
214.739.8100 214.739.8100 515.259.5957
HODGSON DOUGLAS LANDSCAPE ARCHITECTS
12001 N CENTRAL EXPY, SUITE 1170
DALLAS, TX 75243
214.749.0333
BID PACKAGE #2 - NOT FOR CONSTRUCTION
10/22/2026
RLG
A D
D
.1
.1
ADD
ADD
T/CONC EL
SEE PLAN
CL OF CMU AND FTG
PAVING - REF CIVIL
12" CMU WALL REINF -
SEE PLAN
GROUT ALL CELLS
SOLID BELOW GRADE
DOWELS TO MATCH VERT
BAR SIZE AND SPACING W/
STD ACI HOOK
EQ EQ
4'-0" @ SIM
5'-0"
T/FTG EL
#5 @ 12" OC CONT
#5 @ 12" OC IN
TRANSVERSE DIR
1/2" EXPANSION JOINT
W/ BACKER ROD AND
SEALANT
PREPARED SOIL PER
GEOTECH REPORT
CONC SLAB-ON-GRADE
REINF -SEE PLAN & GEN
NOTES
VAPOR BARRIER -
SEE GEN NOTES
T/CONC EL
SEE PLAN
℄ OF CMU AND FTG
PAVING - REF CIVIL
GROUT ALL CELLS
SOLID BELOW GRADE
T/FTG EL
1/2" EXPANSION JOINT
W/ BACKER ROD AND
SEALANT
#4 X 18" SMOOTH
DWLS @ 18" OC -
GREASE ON END
CONC SLAB-ON-GRADE
REINF - SEE PLAN AND
GEN NOTES
#4 DWLS @ 16" OC W/
1- #5 CONT
24"
CONT FTG REINF -
SEE 01/S400
4'-0" @ SIM
5'-0"
EQ EQ
24"
T/CONC EL
SEE PLAN
℄ OF CMU AND FTG
12" CMU WALL REINF -
SEE PLAN
GROUT ALL CELLS
SOLID BELOW GRADE
DOWELS TO MATCH VERT
BAR SIZE AND SPACING W/
STD ACI HOOK
EQ EQ
4'-0" @ SIM
5'-0"
T/FTG EL
CONT FTG REINF -
SEE 01/S400
1/2" EXPANSION JOINT
W/ BACKER ROD AND
SEALANT
CONC SLAB REINF -SEE
PLAN AND GEN NOTES
VAPOR BARRIER -
SEE GEN NOTES
T/CONC EL
SEE PLAN
7'-2"
T/FTG EL
94'-0"
#5 @ 8" OC CONT
TOP AND BOT
#5 @ 8" OC IN TRANSVERSE
DIRECTION (TOP & BOT)
#4 CONT (TYP)
1 1/4" X 3/16" GALV STEEL
GRATING SYSTEM
CONT GALVANIZED BEARING
L2X2X1/4 W/ 1/2" DIA X 5" HS
@ 12" OC
1'-6" 8" w/ BUS WASH MFR
2'-10" GC TO VERIFY 8" 1'-6"
1/2" X 5" X5"X0'-6" (GALV)
EMBED PL w/ 1- 3/4" DIA
HS X0'-6" @ EA HSS
HSS4x4x1/4 @ 6'-0"
#4 DWL X 2'-0" @ 12" OC
℄ OF TRENCH
DRAIN
#5 VERT @ 12" OC
(CENTERED) w/ #5
CONT @ 10" OC
2X4 CONT KEYWAY w/
WATERSTOP -TYP
DRAIN TILE - REF
MEP DRAWINGS
VAPOR BARRIER - REF
PROJECT SPECS
CONC SLAB-ON-GRADE -
SEE PLAN & GEN NOTES
DOWELS TO MATCH
VERT BARS AND
SPACING
3/16
(GC TO
VERIFY
W/ MFR)
NOTE:
GC SHALL NOT BACKFILL BEHIND PIT
WALL UNTIL HSS BEAMS ARE INSTALLED.
REFER TO GEOTECH REPORT FOR
BACKFILLING REQUIREMENTS.
8" 8"
TOUCH UP W/
GALVANIC PAINT
ADD
T/CONC EL
SEE PLAN
T/FTG EL
94'-0"
℄ OF TRENCH
DRAIN
PVC SLEEVE
PER BUS WASH
MFR - TYP
S L E
E V
E E
L E
V A
T
IO
N
S E
E M
F R
F O
R
CONC PIT WALL
BEYOND
CONC PIT WALL
BEYOND
6" WIDE CONC WALL
REINF w/ #5 VERT @ 12" OC (CENTERED) w/ #5
@ 10" OC CONT
SEE 04/S400 FOR
ADDITIONAL INFORMATION
NOT SHOWN FOR CLARITY
DOWELS TO MATCH
VERT BARS AND
SPACING
(GC TO
VERIFY
W/ MFR)
SLEEVE LOCATION
SEE MFR FOR
SLEEVE LOCATION
SEE MFR FOR
ADD
T/CONC EL
SEE PLAN
CL OF CMU AND FTG
PAVING - REF CIVIL
12" CMU WALL REINF W/
#5 @ 32" OC VERT
2- #5 @ 48 HORIZ -
GROUT WALL SOLID
GROUT ALL CELLS
SOLID BELOW GRADE
DOWELS TO MATCH VERT
BAR SIZE AND SPACING W/
STD ACI HOOK
EQ EQ
4'-0"
T/FTG EL
#5 @ 12" OC CONT
TOP AND BOT
#5 @ 12" OC IN
TRANSVERSE
DIRECTION
1/2" EXPANSION JOINT
W/ BACKER ROD AND
SEALANT
PAVING - REF CIVIL
T/WALL EL
106'-0" (MAX)
MASONRY CAP -
REF ARCH
T/CONC EL
SEE PLAN
12" CMU WALL REINF -
SEE PLAN
T/FTG EL
CONC SLAB-ON-GRADE
REINF -SEE PLAN & GEN
NOTES
SEE 01/S400 FOR
ADDITIONAL INFORMATION
NOT SHOWN FOR CLARITY
LINE OF CONT FTG
BEYOND - SEE 01/S400
CANTILEVERED 12" CMU
WALL REINF - SEE 06/S400
CONT FTG REINF -
SEE 06/S400
1" EJ
12" CMU WALL REINF -
SEE PLAN NOTE
COILING DOOR GUIDE
RAIL AND CONNX PER
MFR
COILING DOOR SYSTEM -
REF ARCH
T/CONC EL
SEE PLAN
℄ OF CMU AND FTG
PAVING - REF CIVIL
GROUT ALL CELLS
SOLID BELOW GRADE
T/FTG EL
1/2" EXPANSION JOINT
W/ BACKER ROD AND
SEALANT
#4 X 18" SMOOTH
DWLS @ 18" OC -
GREASE ON END
CONC SLAB-ON-GRADE
REINF - SEE PLAN AND
GEN NOTES
#4 DWLS @ 16" OC W/
1- #5 CONT
24"
CONT FTG REINF -
SEE 01/S400
5'-0"
EQ EQ
24"
REF ARCH
COILING DOOR
SYSTEM - REF ARCH
/2
S
T E
P
1/2" SLOPE
Architect of Record:
ADG
800 SW ADAMS STREET, SUITE 101
PEORIA, IL 61602
R e vi si o n s
P - 309.672.6948
Discipline:Discipline:Discipline:
P - P - P -
Discipline:
P -
PROJECT NO.
DATE
DRAWN BY
STATUS
Discipline: Owner Consultant
QSC SERVICES, LLC
PMB #69
545 BRENT LN. PENSACOLA, FL
P - 309.231.8272
OWNER ID:
Design and Construction Administration Division
ESCAMBIA COUNTY, FL
100 E. BLOUNT ST. PENSACOLA, FL 32501
ESCAMBIA COUNTY AREA TRANSIT - FACILITY:
04 - BUS WASH
10 CLARINDA LN
PENSACOLA, FL 32505 S400FOUNDATION DETAILS
KEDbluestone
707 NE JEFFERSON AVE,
PEORIA, IL 61602
RLG CONSULTING ENGINEERS
12001 N CENTRAL EXPY, STE 300
DALLAS, TX 75243
RLG CONSULTING ENGINEERS
12001 N CENTRAL, STE 300
DALLAS, TX 75243
214.739.8100 214.739.8100 515.259.5957
HODGSON DOUGLAS LANDSCAPE ARCHITECTS
12001 N CENTRAL EXPY, SUITE 1170
DALLAS, TX 75243
214.749.0333
BID PACKAGE #2 - NOT FOR CONSTRUCTION
10/22/2026
RLG
A D
D
.1
.1
T/ WALL
REF ARCH
2" CMU SOAP
T/ PLANK
SEE PLAN
GROUT CMU CELLS
THAT HAVE DOWEL
FROM PRECAST PLANK
8X12 BOND BEAM W/
(2) - #5 CONT
12" CMU WALL
REINF - SEE PLAN
PROVIDE BEARING PAD OR
DRY PACK AS REQ'D FOR
CAMBER
4" MIN
PRECAST PLANK PER
PRECAST ENGR
L8x4x7/16 (LLV - GALV) CONT w/ 2" VERT SLOTTED HOLE w/ 5/8"
DIA F1554 GR 36 THREADED
ROD @ 16" OC USING HILTI
HY-270 (6" EMBED)
EMBED PL (GALV) @ 48" OC
MAX BY PRECAST MFR
DIAPHRAGM SHEAR = 0.150 KLF
(LRFD)
M
IN4
2"3/16
GC TO TOUCH UP WELD
WITH GALVANIC PAINT
GROUT WALL SOLID
ABOVE THE CONC
PLANK
METAL CAP -
REF ARCH
T/ WALL
REF ARCH
T/ PLANK
SEE PLAN
GROUT CMU CELLS
THAT HAVE DOWEL
FROM PRECAST PLANK
8X12 BOND BEAM W/
(2) - #5 CONT
12" CMU WALL
REINF - SEE PLAN
PRECAST PLANK PER
PRECAST ENGR
L8x4x7/16 (LLV - GALV) CONT w/ 2" VERT SLOTTED HOLE w/ 5/8"
DIA F1554 GR 36 THREADED
ROD @ 16" OC USING HILTI
HY-270 (6" EMBED)
2"3/16
GC TO TOUCH UP WELD
WITH GALVANIC PAINT
PROVIDE BEARING PAD OR
DRY PACK AS REQ'D FOR
CAMBER
EMBED PL (GALV) @ 48" OC
MAX BY PRECAST MFR
DIAPHRAGM SHEAR = 0.150 KLF
(LRFD)
GROUT WALL SOLID
ABOVE THE CONC
PLANK
4" MIN
METAL CAP -
REF ARCH
2" CMU SOAP
GUTTER SYSTEM & CONNX
PER GUTTER MFR
T/ PLANK
SEE PLAN
8X12 BOND BEAM W/
(2) - #5 CONT
12" CMU WALL
REINF - SEE PLAN
PRECAST PLANK PER
PRECAST ENGR
ROOFING - REF ARCH
ANGLE CONNECTION, SEE
01/S500 FOR DETAILS
EMBED PL (GALV) @ 48" OC
MAX BY PRECAST MFR
DIAPHRAGM SHEAR = 0.150 KLF
(LRFD)
2"3/16
2" CMU SOAP
#4 DWL X 24" @ KEYWAY
(2) - #5 CONT
HOLLOW CORE PLANK
IS ROTATED AT SIM.
T/ WALL
REF ARCH
2" CMU SOAP
T/ PLANK
SEE PLAN
GROUT CMU CELLS
THAT HAVE DOWEL
FROM PRECAST PLANK
8X12 BOND BEAM W/
(2) - #5 CONT
12" CMU WALL
REINF - SEE PLAN
AND PLAN NOTE
PRECAST PLANK PER
PRECAST ENGR
PROVIDE BEARING PAD OR
DRY PACK AS REQD FOR
CAMBER
4" MIN
12X32 CONT BOND
BEAM w/ 3-#5 TOP &
BOT
COIL DOOR SYSTEM
PER COIL DOOR MFR
EMBED PL @ 24" OC MAX BY
PRECAST MFR DIAPHRAGM
SHEAR = 1 KLF (LRFD)
L8x4x7/16 (LLV - GALV) CONT w/ 2" VERT SLOTTED HOLE w/ 5/8"
DIA F1554 GR 36 THREADED
ROD @ 16" OC USING HILTI
HY-270 (6" EMBED)
GROUT WALL SOLID
ABOVE THE CONC
PLANK
2"3/16
METAL CAP -
REF ARCH
COIL DOOR CONNX PER
COIL DOOR MFR
T/ PLANK
SEE PLAN
T/ PLANK
SEE PLAN
GUTTER SYSTEM & CONNX
PER GUTTER MFR
ROOFING REF ARCH
PRECAST PLANK PER
PRECAST ENGR
GROUT CMU CELLS
THAT HAVE DOWEL
FROM PRECAST PLANK
8X12 BOND BEAM W/
(2) - #5 CONT
12" CMU WALL
REINF - SEE PLAN
EMBED PL & ANGLE
CONNX - SEE 02/S500 FOR
DETAILS (TYP)
EMBED PL & ANGLE
CONNX - SEE 02/S500 FOR
DETAILS (TYP)
2" CMU SOAP
(2) - #5 CONT
#4 DWL X 24" @ KEYWAY
2" CMU SOAP
T/ PLANK
SEE PLAN
8X8 BOND BEAM W/
(2) - #5 CONT
8" CMU WALL REINF -
SEE PLAN
PROVIDE BEARING PAD OR
DRY PACK AS REQ'D FOR
CAMBER
PRECAST PLANK PER
PRECAST ENGR
PROVIDE BEARING PAD OR
DRY PACK AS REQD FOR
CAMBER
L8x4x7/16 (LLV - GALV) CONT w/ 2" VERT SLOTTED HOLE w/ 5/8"
DIA F1554 GR 36 THREADED
ROD @ 16" OC USING HILTI
HY-270 (6" EMBED) STAGGERED
CELLS
EMBED PL (GALV) @ 24" OC
MAX BY OTHERS DIAPHRAGM
SHEAR = 2.7 KLF (LRFD)
STAGGER EMBED PLATES
M
IN4
33/16
EA EMBED
GC TO TOUCH UP WELD
WITH GALVANIC PAINT
GROUT ALL CELLS
w/ (2) - #5 CONT
T/ WALL
REF ARCH
2" CMU SOAP
T/ PLANK
SEE PLAN
GROUT CMU CELLS
THAT HAVE DOWEL
FROM PRECAST PLANK
8X12 BOND BEAM W/
(2) - #5 CONT
12" CMU WALL
REINF - SEE PLAN
4" MIN
PRECAST PLANK PER
PRECAST ENGR
PROVIDE BEARING PAD OR
DRY PACK AS REQD FOR
CAMBER
L8x4x7/16 (LLV - GALV) CONT w/ 2" VERT SLOTTED HOLE w/ 5/8"
DIA F1554 GR 36 THREADED
ROD @ 16" OC USING HILTI
HY-270 (6" EMBED)
EMBED PL (GALV) @ 24" OC
MAX BY OTHERS
DIAPHRAGM SHEAR = 1 KLF
(LRFD)
M
IN4
GC TO TOUCH UP WELD
WITH GALVANIC PAINT
METAL CAP -
REF ARCH
T/ PLANK
SEE PLAN
EMBED PL PER
PRECAST ENGINEER
(4'-0" MAX SPACING)
8" HOLLOW CORE PLANK
PER PRECAST ENGR
GUARDRAIL SYSTEM -
REF ARCH (4'-0" MAX
SPACING)
GC TO COORDINATE GUARDRAIL
POST LOCATIONS FROM ARCH
DRAWINGS W/ PLANK DESIGNER
PLANK DESIGNER TO
DESIGN FOR ADDL LOAD:
H = 200 LB
M = 700 LB-FT
H
M
Architect of Record:
ADG
800 SW ADAMS STREET, SUITE 101
PEORIA, IL 61602
R e vi si o n s
P - 309.672.6948
Discipline:Discipline:Discipline:
P - P - P -
Discipline:
P -
PROJECT NO.
DATE
DRAWN BY
STATUS
Discipline: Owner Consultant
QSC SERVICES, LLC
PMB #69
545 BRENT LN. PENSACOLA, FL
P - 309.231.8272
OWNER ID:
Design and Construction Administration Division
ESCAMBIA COUNTY, FL
100 E. BLOUNT ST. PENSACOLA, FL 32501
ESCAMBIA COUNTY AREA TRANSIT - FACILITY:
04 - BUS WASH
10 CLARINDA LN
PENSACOLA, FL 32505 S500FRAMING DETAILS
KEDbluestone
707 NE JEFFERSON AVE,
PEORIA, IL 61602
RLG CONSULTING ENGINEERS
12001 N CENTRAL EXPY, STE 300
DALLAS, TX 75243
RLG CONSULTING ENGINEERS
12001 N CENTRAL, STE 300
DALLAS, TX 75243
214.739.8100 214.739.8100 515.259.5957
HODGSON DOUGLAS LANDSCAPE ARCHITECTS
12001 N CENTRAL EXPY, SUITE 1170
DALLAS, TX 75243
214.749.0333
BID PACKAGE #2 - NOT FOR CONSTRUCTION
10/22/2026
RLG
A D
D
.1
.1
ADD
ADD
ADD
ADD
ABC
WIDTH OF THE BUILDING FROM EDGE OF FDN TO EDGE OF FDN
32' - 8"
FA
CE
O F
FD
N
T O
F
AC
E O
F
FD
N
LE
N
GH
T O
F
TH
E
BU
IL
DI
N G
FR
O
M E
DG
E
O F
FD
N
T O
E
DG
E O
F
FD
N
FACE OF FDN TO FACE OF FDN
22' - 0"
FA
CE
O F
FD
N
T O
F
AC
E O
F
FD
N
FACE OF FDN TO FACE OF FDN
11' - 8''
FA
CE
O F F
DN
T
O
FA
CE
O
F F
DN
FA
CE
O F
FD
N
T O
F
AC
E O
F
FD
N
FA
CE
O F
FD
N
T O
F
AC
E O
F
FD
N
FACE OF FDN TO FACE OF FDN
23' - 4"
2' - 10"
BASE POINT COORDINATE:
N 538687' 98" E 1106574' 91"
SURVEY POINT COORDINATE:
N 538739' 66" E 1106572' 23"
AB
C
22' - 0"10' - 8"
32' - 8"
10' - 8"
FR
O
M G
RI
D
LI
N
E
TO
F .O
. T
HE
R O
O F
0'
/8
LE
N
GT
H
O F
TH
E
RO
O
F
/4
FR
O M
G
RI
D
LI
N E
TO
F
.O . T
HE
R
O O
F 0'
/8
FR
O
M G
RI
D
LI
N
E
TO
F .O
. T
HE
R O
O F
0'
/8
/8
/8
0'
/8
LE
N
GT
H
O F
TH
E
RO
O
F
/4
RO
O
F
TY
PE
: R
-3
RO
O
F
TY
PE
: R
-3
PREFINISHED METAL GUTTER
AND DOWNSPOUTS BY PEMB, TYP.
VERIFY QUANTITY AND SIZE.
PREFINISHED METAL GUTTER
AND DOWNSPOUTS BY PEMB, TYP.
VERIFY QUANTITY AND SIZE.
PREFINISHED METAL GUTTER
AND DOWNSPOUTS BY PEMB, TYP.
VERIFY QUANTITY AND SIZE.
RO
OF
T
YP
E:
R
PREFINISHED METAL GUTTER
AND DOWNSPOUTS BY PEMB, TYP.
VERIFY QUANTITY AND SIZE.
W
ID
TH
O
F T
HE
R
OO
F
9'
3/
4"
21' - 4 3/4"
0' - 11 5/8"
0'
0"
FIXED STEEL ROOF ACCESS LADDER.
PROVIDE LOCKABLE SECURITY GATE AT
LADDER BASE. EXTEND LADDER SIDE RAILS
OR SAFETY POSTS 42" MIN. ABOVE ROOF.
INSTALL IN ACCORDANCE WITH OSHA 29
CFR 1910.23. PROVIDE BILCO LADDERUP OR
APPROVED EQUAL SAFETY POST AT ROOF
ACCESS POINT.
PROVIDE PERMANENT GUARDRAIL
SYSTEM AT CONDENSING UNIT SERVICE
AREA WHERE REQUIRED FOR FALL
PROTECTION. GUARDRAIL SHALL COMPLY
WITH APPLICABLE OSHA REQUIREMENTS.
SEE STRUCTURAL DRAWINGS FOR DESIGN
AND DETAILS.
10' - 0"
8' - 3"
5'
5/
8"
ABC
FA
CE
O F
FD
N
T O
F
AC
E O
F
FD
N
FACE OF FDN TO FACE OF FDN
32' - 8"
FA
CE
O F
FD
N
T O
F
AC
E O
F
FD
N
FA
CE
O
F
FD
N T
O F
AC
E
O F
FD
N
FA
CE
O F
FD
N
T O
F
AC
E O
F
FD
N
FACE OF FDN TO FACE OF FDN
22' - 0"
FACE OF FDN TO FACE OF FDN
10' - 8"
EQUIPMENT
ROOM
ADA
RESTROOM
FARE
PROCESING
FARE
ENTRANCE
WASH
BAY
EDGE TO EDGE OF FDN
23' - 4"
ED
GE
T O
ED
GE
O F F
DN
2'
1/
4" 6'
0"
2'
5/
8"
17' - 5 3/8"
17' - 5 3/8"
VACUUM28
112.5°
112.5°
FA
CE
O F
FD
N
T O
F
AC
E O
F
FD
N
M.O.
3' - 4"2' - 0" 4' - 0"
M.O 14' - 0"
4' - 0"M.O 14' - 0"
M .O
3'
4"
6'
4"
3'
4"
3'
4"
2' - 8"
1'
5/
8"
/4
/8
4X5 DOWNSPOUT, CONNECT TO
UNDERGROUND STORM SYSTEM.
REFER TO CIVIL DWGS
4X5 DOWNSPOUT, CONNECT
TO UNDERGROUND STORM
SYSTEM. REFER TO CIVIL DWGS
4X5 DOWNSPOUT, CONNECT
TO UNDERGROUND STORM
SYSTEM. REFER TO CIVIL DWGS
21' - 4 3/4"
7'
4"
DUMPSTER WING WALLS:
TOP COURSE: BULLNOSE
CMU, NO EXPOSED CORES
WT1
WT2
R1
R1
WT2
R1
WT2
WT3WT3
WT3
WT2
WT1
WT1
R1
WT3WT2
WT2
WT3
R1
WT1
HOLLOW CORE
CONCRETE PLANK
R-35 AVG. INSULATION WITH
TAPERED INSULATION @ 1/4'':12''
ROOF MEMBRANE
11 5/8" GROUND FACE CMU.
PROVIDE FULL BED MORTAR JOINTS AND
TOOL ALL JOINTS TO A CONCAVE PROFILE
(WT1: EB1, MT1 - WT2: EP2, MT1)
INTERIOREXTERIOR
PROVIDE INTEGRAL WATER-REPELLENT
ADMIXTURE IN ALL EXPOSED GROUND-FACE
CMU AND MORTAR AS PART OF A SINGLE-
SOURCE MASONRY WATER-REPELLENT
SYSTEM. AFTER MASONRY HAS CURED AND
BEEN CLEANED, APPLY MANUFACTURER'S
RECOMMENDED CLEAR BREATHABLE
SILANE/SILOXANE PENETRATING WATER
REPELLENT TO THE EXTERIOR FACE OF THE
WALL
WT1 - DARK
WT2 - LIGHT
EB1 ECHELON MASONRY - STANDARD MASONRY - TRENWYTH HIGH POLISH
GROUND FACE BRICK - SIZE: 8" X 12" X 16" - COLOR: 5108 (DARK)
EB2 ECHELON MASONRY - STANDARD MASONRY - TRENWYTH HIGH POLISH
GROUND FACE BRICK - SIZE: 8" X 12" X 16" - COLOR: 5301 (LIGHT)
EB3 ECHELON MASONRY - STANDARD MASONRY - TRENWYTH HIGH POLISH
GROUND FACE BRICK - SIZE: 8" X 8" X 16" - COLOR: 5301 (LIGHT)
EB4 ECHELON MASONRY - STANDARD MASONRY - TRENWYTH HIGH POLISH
GROUND FACE BRICK - SIZE: 8" X 8" X 16" - COLOR: 5301 (DARK)
MP1 MBCI - CONCEALED FASTENING SYSTEM - FW-120-2 PANEL, 24 GAUGE, SMOOTH -
COLOR: BROWNSTONE
MP2 ARMSTRONG WALL & ROOF SYSTEMS - PBU PANEL - COLOR: POLAR WHITE
MT1 SOLOMON COLORS, INC., CONCENTRATED MORTAR - COLOR: 22X TAN
EXTERIOR FINISH SCHEDULE
WT1
WT1
WT2
WT2
WT3
WT3 WT2
WT2
FOR WALL TYPES - SEE
DETAILS 5, 6, & 7 ON
THIS SHEET
FINISHED GRADE - SEE
CIVIL
CONTINUOUS FOOTING -
SEE STRUC
M
IN
0'
1"
ALIGN CMU WITH
OUTSIDE FACE OF
FOUNDATION WALL
INTERIOR SLAB ON
GRADE - SEE STRUC
PREFORMED JOINT
FILLER W/ SELF LEVELING
POLYURETHANE SEALANT
ON TOP OF PJF
14"x4"x48" PRECAST
CAST STONE COPING
UNIT
11 5/8" GROUND FACE CMU (EB3, MT1)
DRIP EDGE ON BOTH
SIDES
1' - 2"
0'
4"
1" OVERHANG
SEE
ELEVATIONS
WT3 - LIGHT
0'
1"
Architect of Record:
ADG
800 SW ADAMS STREET, SUITE 101
PEORIA, IL 61602
Re vi sio ns
P - 309.672.6948
Discipline:Discipline:Discipline:
P - P - P -
Discipline:
P -
PROJECT NO.
DATE
DRAWN BY
STATUS
Discipline:Discipline: Owner Consultant
QSC SERVICES, LLC
PMB #69
545 BRENT LN. PENSACOLA, FL
P - 309.231.8272
OWNER ID:
Design and Construction Administration Division
ESCAMBIA COUNTY, FL
100 E. BLOUNT ST. PENSACOLA, FL 32501
ESCAMBIA COUNTY AREA TRANSIT - FACILITY:
04 - BUS WASH
10 CLARINDA LN
PENSACOLA, FL 32505 X001LAYOUT PLAN, 3D VIEWS AND WALL / ROOF
ASSEMBLIES
KEDbluestone
707 NE JEFFERSON AVE,
PEORIA, IL 61602
RLG CONSULTING ENGINEERS
12001 N CENTRAL, EXPY #300
DALLAS, TX 75243
RLG CONSULTING ENGINEERS
12001 N CENTRAL,
DALLAS, TX 75243
214.739.8100 214.739.8100 515.259.5957
HODGSON DOUGLAS LANDSCAPE ARCHITECTS
12001 N. CENTRAL EXPRESSWAY, SUITE 1170
DALLAS, TX 75243
214.749.0333
BID PACKAGE #2 - NOT FOR CONSTRUCTION
11/12/2026
ADG
5 3D VIEW, ROOF AND EXTERIOR WALL ASSEMBLIES
1/8" = 1'-0"
4 ROOF PLAN
6 3D VIEW, ROOF AND EXTERIOR WALL ASSEMBLIES
1" = 1'-0"
WT1 - GFB12 - DARKWT1 - GFB12 - DARK
R1
1/8" = 1'-0"
1 FIRST FLOOR LAYOUT PLAN
1/8" = 1'-0"
2 FIRST FLOOR DIMENSIONS AND WALL TYPE PLAN
N N N
AD
D
.1 0.
WT1 - DARK
WT2 - LIGHT
7 3D VIEW, ROOF AND EXTERIOR WALL ASSEMBLIES
1 1/2" = 1'-0"
3 TYP FOUNDATION DETAIL
WT3
PROVIDE UNDER SLAB AT VAPOR BARRIER
EXTERIOR WALL TYPE (WT) ASSEMBLIES
FIRST FLOOR
0' - 0"
T.O. EQUIPMENT ROOM
13' - 4"
1 2
B.O. WASH BAY
20' - 0"
B.O. EQUIPMENT ROOM
12' - 8"
T.O. WASH BAY
22' - 8"
3 4
PREFINISHED 8'' x 8'' METAL GUTTERS AND 4'' x
5'' DOWNSPOUTS.
PREFINISHED 8'' x 8'' METAL GUTTERS AND 4'' x
5'' DOWNSPOUTS.
PREFINISHED 8'' x 8''
METAL GUTTERS AND
4'' x 5'' DOWNSPOUTS.
102A103 101A
7'
4" R
.O
7'
4" R
.O
6' - 4" R.O.
7'
4" R
.O
3' - 4" R.O.
3' - 4" R.O.
A B C
PREFINISHED 8'' x 8'' METAL GUTTERS AND 4'' x 5'' DOWNSPOUTS.
" R
.O
101C
3' - 4" R.O.
7'
4" R
.O
PREFINISHED 8'' x 8'' METAL GUTTERS AND 4'' x
5'' DOWNSPOUTS.
FIRST FLOOR
0' - 0"
T.O. EQUIPMENT ROOM
13' - 4"
B.O. WASH BAY
20' - 0"
T.O. WASH BAY
22' - 8"
PAY TERMINAL - 26"W x 30"H OPENING
PROVIDE WOOD SHIMS AND .090" STAINLESS STEEL FLASHING ON ALL FOURS
SIDES OF THE OPENING. PROVIDE STAINLESS STEEL FACADE FROM VAULT
MANUFACTURER. SEAL ASSEMBLY AND FLASHING WEATHERTIGHT. PROVIDE
BOTTOM-HINGED SECURITY DOOR WITH STAPLE PLATE HASP LOCK AT TOP OF
DOOR. PROVIDE HARDWOOD SILL INSIDE STEEL FACADE TO PREVENT DAMAGE TO
CASHBOXES, PRE-DRILLED AND COUNTERSUNK ON BOTH SIDES FOR 10-32
FLATHEAD CAP SCREWS. PROVIDE AN L-ANGLE 2"X2"X32" PLACED AGAINST THE
FRONT LEGS OF THE VAULT AND BOLT TO THE FLOOR TO ENSURE THE VAULT
REMAINS TIGHT AGAINST THE WALL; L-ANGLE WITH FOUR 1/2" DIAMETER HOLES,
EQUALLY SPACED. REFER TO VAULT MANUFACTURER'S STANDARD INSTALLATION
RECOMMENDATIONS FOR MORE INFORMATION.
B.
O
. O F
O
PE
N
IN
G 2'
/2
" T O
2' - 2"
2'
6"
ABC
PREFINISHED 8'' x 8'' METAL GUTTERS AND 4'' x
5'' DOWNSPOUTS.
PREFINISHED 8'' x 8''
METAL GUTTERS AND 4''
x 5'' DOWNSPOUTS.
" R
.O
101B
FIRST FLOOR
0' - 0"
T.O. EQUIPMENT ROOM
13' - 4"
B.O. EQUIPMENT ROOM
12' - 8"
PREFINISHED 8'' x 8'' METAL GUTTERS AND 4'' x
5'' DOWNSPOUTS.
DU
M
PS
TE
R W
AL
L
HE
IG
HT
6'
0"
DUMPSTER WING WALLS
WT3: 14"x4"x48" PRECAST
CAST STONE COPING UNIT.
SEE WALL TYPE ON X001.
DUMPSTER WING WALLS
WT3: 14"x4"x48" PRECAST
CAST STONE COPING UNIT.
SEE WALL TYPE ON X001.
RO
U
GH
O
PE
N
IN
G
8'
0"
ROUGH OPENING
6' - 0"
FIRST FLOOR
0' - 0"
T.O. EQUIPMENT ROOM
13' - 4"B.O. EQUIPMENT ROOM
12' - 8"
GENERAL ELEVATION NOTES
SEE X001 FOR EXTERIOR WALL ASSEMBLIES & LAYOUT
SEE SHEET A900 FOR DOOR SCHEDULE, ELEVATIONS & DETAILS
SEE SHEET X800 FOR DETAILS
Architect of Record:
ADG
800 SW ADAMS STREET, SUITE 101
PEORIA, IL 61602
Re vi sio ns
P - 309.672.6948
PROJECT NO.
DATE
DRAWN BY
STATUS
Discipline:Discipline: Owner Consultant
QSC SERVICES, LLC
PMB #69
545 BRENT LN. PENSACOLA, FL
P - 309.231.8272
OWNER ID:
Design and Construction Administration Division
ESCAMBIA COUNTY, FL
100 E. BLOUNT ST. PENSACOLA, FL 32501
ESCAMBIA COUNTY AREA TRANSIT - FACILITY:
04 - BUS WASH
10 CLARINDA LN
PENSACOLA, FL 32505 X300EXTERIOR ELEVATIONS
BID PACKAGE #2 - NOT FOR CONSTRUCTION
11/12/2026 Author
1/4" = 1'-0"
4 WASH BLDG WEST ELEVATION
1/4" = 1'-0"
1 WASH BLDG NORTH ELEVATION
1/4" = 1'-0"
2 WASH BLDG EAST ELEVATION
1/4" = 1'-0"
3 WASH BLDG SOUTH ELEVATION
1/4" = 1'-0"
8 VACUUM/DUMPSTER WEST ELEVATION
1/4" = 1'-0"
7 VACUUM/DUMPSTER SOUTH ELEVATION
1/4" = 1'-0"
6 VACUUM/DUMPSTER EAST ELEVATION
1/4" = 1'-0"
5 VACUUM/DUMPSTER NORTH ELEVATION
AD
D
.1
0.
NORTHWEST AERIAL VIEW SOUTHEAST AERIAL VIEW
ADD
ADD
ABC
WASH
BAY
EQUIPMENT
ROOM
ADA
RESTROOM
FARE
PROCESING
FARE
ENTRANCE PAY TERMINAL - SEE
ELEVATION FOR OPENING
DIMENSIONS
DOWNSPOUT
DOWNSPOUT
BOLLARDBOLLARD
BOLLARD
BOLLARD
BOLLARD
BOLLARD
VACUUM
DUMPSTER B
DUMPSTER A
DOWNSPOUT
DOWNSPOUT
101C
102B
101B
A110
101A
23' - 4"
102A
BASIS OF DESIGN SELECTION FOR
FINISHES AND EQUIPMENT, OR
APPROVED EQUAL.
GENERAL SHEET NOTES
SEE G000 FOR CODE PLANS & GENERAL INFORMATION
SEE 'X' SHEETS FOR EXTERIOR ASSEMBLIES & ADDITIONAL INFORMATION
WALL LEGEND
NEW CONSTRUCTION WALL AND PARTITION
NEW CONSTRUCTION DOOR AND FRAME
ABC
EQUIPMENT
ROOM
ADA
RESTROOM
FARE
PROCESING
FARE
ENTRANCE
WASH
BAY
23' - 4"
9'
7/
8"
/8
8'
3/
4"
EQ
EQ
EQ2' - 10"EQ
--CMU12--
-- B-
--CMU8--
-- B-
--CMU8--
-- B-
--CMU8--
-- B-
--CMU8--
-- B-
--CMU12--
-- B-
5'
1/
2"
/8
7'
3/ 4"
1'
5/
8"
/2
11' - 7 5/8" 21' - 0 3/8"
NOTE: STANDARD PARTITION TYPE
--CMU8--
-- B-
--CMU12--
-- B-
PARTITION LEGEND
CMU
CMU CONCRETE MASONRY UNIT
PARTITION ABBREVIATIONS
TYPE MARK
X-M358-X
SHEATHING LAYER 02
SIZE OF CORE MATERIAL
SHEATHING LAYER 01
X-M358-X
INS UL FR P
TYPE MARK
WALL TYPE NOTES
FIRE RATING (IN HRS)
UL CODE
INSULATION
CORE MATERIAL
PARTITION TAG
CORE MATERIAL
- NO MATERIAL
SHEATHING MATERIAL
P
B
PARTITION WITH CORE MATERIAL TO DECK
ABOVE, SHEATHING TO 6" ABOVE CEILING
BARRIER WITH CORE MATERIAL AND SHEATHING
TO…
This is the start of the file's text. The full file is on GovTribe.