ECAT_BP2_DRAWING_SET_-_03_TRANSFER_CENTER_Rev_1__26-11-13.pdf

PDF 9 MB Posted

Attached to
CDBG-DR HS004 New Escambia County Area Transit (ECAT) Facility
Solicitation number
PD 26-27.004
Issued by
Escambia County, Florida

About this file

ECAT Transfer Center Drawing Set Summary

This document is a comprehensive structural drawing set for Bid Package #2 of the Escambia County Area Transit (ECAT) Facility's Passenger Terminal Transfer Center, prepared by design firm KED bluestone and structural engineers RLG Consulting Engineers. The project, located at 41 Clarinda Lane in Pensacola, Florida, involves construction of a transfer center building with associated canopy structures. The drawing set includes general structural notes, roof framing plans, foundation details, wall and roof assembly specifications, exterior elevations, interior layouts, door schedules, plumbing underfloor plans, mechanical systems, electrical plans, and comprehensive details for steel, concrete, and masonry construction. The project must comply with the 8th Edition Florida Building Code as adopted by Escambia County, with design parameters including ASD wind speeds of 121 mph and basic wind speeds of 156 mph per ASCE 7-22, ground-face CMU masonry construction with integral water repellent, structural steel framing with galvanized connections, and composite metal deck roofing. The drawings are marked "NOT FOR CONSTRUCTION" with an effective date of November 12, 2026, and include multiple revisions (ADD 01, dated 11/12/2026), indicating this is part of an active bid package.

The drawing set specifies design and construction requirements across all building systems, including 5-inch reinforced concrete slabs on grade, steel joist roof framing with 1.5-inch metal deck, masonry walls with continuous reinforcement and grouted cells in designated areas, and comprehensive mechanical, plumbing, and electrical systems. Special construction considerations include trench safety design requirements prepared by qualified professional engineers, temporary shoring and bracing under licensed engineer supervision, deferred submittals for concrete formwork and steel connections, and shop drawing approvals required before fabrication. Foundation design is based on geotechnical report #26-162 from Larry M Jacobs & Associates, Inc., with allowable soil bearing values of 1.5 ksf for footings and native soil sliding resistance coefficients specified. The project incorporates Section 3 provisions, Davis-Bacon wage requirements, and federal compliance measures including E-Verify and suspension and debarment verification, with liquidated damages applicable and substantial completion timelines established based on individual lot specifications from Notice to Proceed.

View the file

Other files

File Type Posted
CDBG-DR_HS004_New_Escambia_County_Area_Transit_(ECAT)_Facility_(Addendum_#16_Revision).pdf PDF
ECAT_BP2_CONSTRUCTION_ADD-REV_1_WRITE-UP_Rev_1__26-11-13.pdf PDF
ECAT_BP2_PROJECT_MANUAL_Rev_1__26-11-13.pdf PDF
ECAT_BP2_DRAWING_SET_-_05_FUEL_STATION_Rev_1__26-11-13.pdf PDF
ECAT_BP2_DRAWING_SET_-_04_BUS_WASH_Rev_1__26-11-13.pdf PDF
ECAT_BP2_DRAWING_SET_-_02_MAINTENANCE_BUILDING_Rev_1_26-11-13.pdf PDF
ECAT_BP2_DRAWING_SET_-_01_ADMINISTRATION_BUILDING_Rev_1_26-11-13.pdf PDF
ECAT_BP2_DRAWING_SET_-_00_SITE_SITE_Rev_1_26-11-13.pdf PDF
CDBG-DR_HS004_New_Escambia_County_Area_Transit_(ECAT)_Facility_(Addendum_#10_Revision).pdf PDF
CDBG-DR_HS004_New_Escambia_County_Area_Transit_(ECAT)_Facility_(Addendum_#9_Revision).pdf PDF
CDBG-DR_HS004_New_Escambia_County_Area_Transit_(ECAT)_Facility_(Addendum_#8_Revision).pdf PDF
CDBG-DR_HS004_New_Escambia_County_Area_Transit_(ECAT)_Facility.pdf PDF
ECAT_BP2_PROJECT_MANUAL_-_VOLUME_TWO.pdf PDF
ECAT_BP2_PROJECT_MANUAL_-_VOLUME_ONE.pdf PDF
ECAT_BP2_DRAWING_SET_-_05_FUEL_STATION.pdf PDF
ECAT_BP2_DRAWING_SET_-_04_BUS_WASH.pdf PDF
ECAT_BP2_DRAWING_SET_-_03_TRANSFER_CENTER.pdf PDF
ECAT_BP2_DRAWING_SET_-_02_MAINTENANCE_BUILDING.pdf PDF
ECAT_BP2_DRAWING_SET_-_01_ADMINISTRATION_BUILDING.pdf PDF
ECAT_BP2_DRAWING_SET_-_00_SITE.pdf PDF
FDOT_Liquidated-Damages-2026-2027.pdf PDF
Building_Construction_Wage_Determination_5.18.26.pdf PDF
Exhibit.FederalContractProvisions.HUD_10.22.26.pdf PDF
Escambia_County_Section_3_Business_Application_CDBG-DR.pdf PDF
Section-3-project-implementation-plan-template---forms-0-8.pdf PDF
Escambia_County_Section_3_Contract_Clause_CDBG-DR.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

7. FLOOD DESIGN DATA:

THIS PROJECT IS NOT LOCATED WITHIN A FLOOD HAZARD AREA

8. SPECIAL LOADS:

VEHICULAR BARRIERS

AREA

AWNINGS & CANOPIES

UNIFORM

20 psf

6.0 ksf

CONCENTRATED

300 lbs.

IMPACT SECTION OF CODE

FBC 1607.9

FBC 1607.13.4

9. ROOF RAIN LOAD DATA:

RAIN INTENSITY (15-DURATION)

4.9 in/hr

DESIGN DATA

1. THE DESIGN OF THE STRUCTURE AND PARTS THEREOF IS IN ACCORDANCE WITH THE 8TH EDITION OF FLORIDA BUILDING

CODE, AS AMENDED AND ADOPTED BY ESCAMBIA COUNTY.

2. FLOOR LIVE LOADS.

AREA UNIFORM CONCENTRATED

OFFICES

IMPACT LIVE LOAD REDUCTION

50 psf 2.0 -kips

OFFICE CORRIDORS 1ST FLOOR 2.0 -kips

OFFICE CORRIDORS OTHER FLOORS -

- kipsASSEMBLY AREAS -

-STORAGE LIGHT - kips -

100 psf

80 psf

100 psf

125 psf

2.0 kips

3. ROOF LIVE LOADS:

AREA UNIFORM SPECIAL COMMENTS

ROOF, GENERAL

LIVE LOAD REDUCTION

20 psf -

ROOF, EQUIP LOADS SEE ROOF PLAN

4. SNOW LOADS: NOT APPLICABLE PER FBC

FACTORED COMPONENTS AND CLADDING WALL LOADS

POSITIVE PRESSURE (psf) NEGATIVE PRESSURE (psf)

AREA (SQ FT)

LESS THAN 10

GREATER THAN 500

INTERIOR & CORNER ZONE INTERIOR ZONE CORNER ZONE

50 -54

-49

-44

-41 -41

-47

-56

-65

CORNER ZONE IS A DISTANCE OF 3'-0" FROM WALL CORNERS

LINEAR INTERPOLATE FOR LOADS BETWEEN SPECIFIED AREAS

6. SEISMIC DESIGN DATA: NOT APPLICABLE PER FBC

PERIMETER ZONE, "B" IS A DISTANCE OF 21'-6" FROM EDGE OF BUILDING

CORNER ZONE, "5'-3" IS A DISTANCE OF 15'-6" FROM EDGE OF BUILDING

LINEAR INTERPOLATE FOR LOADS BETWEEN SPECIFIED AREAS

23 3

33 B

B

B

C

ROOF WIND LOAD LAYOUT

YES, PER FBC 1607.13.1

YES, PER FBC 1607.13.1

YES, PER FBC 1607.13.1

YES, PER FBC 1607.13.1

YES, PER FBC 1607.13.1.2

YES, PER FBC 1607.14

FACTORED COMPONENTS AND CLADDING ROOF LOADS

POSITIVE PRESSURE (psf) NEGATIVE PRESSURE (psf)

AREA (SQ FT)

LESS THAN 10

GREATER THAN 500

ALL ZONES 1, 2, & 3

ZONE 1

-95

-68

-59

ZONE 2

-125

-98

-90

-80

ZONE 3

-170

-117

-101

-80

-74

RAIN INTENSITY (60-DURATION)

9.12 in/hr

5. WIND DESIGN DATA:

ASD WIND SPEED Vasd 121 mph

RISK CATEGORY

BASIC WIND SPEED (3 SECOND GUST)

WIND EXPOSURE

INTERNAL PRESSURE COEFFICIENT

COMPONENTS AND CLADDING

156 mph

+/- 0.18

PER ASCE 7-22

N/A

N/A

TORNADO SPEED, Vt

EFFECTIVE PLAN AREA

II

C

SEISMIC IMPORTANCE FACTOR, Ie

MAPPED SPECTRAL RESPONSE ACCEL.

RISK CATEGORY

SITE CLASS

SPECTRAL RESPONSE COEFFICIENTS

SEISMIC DESIGN CATEGORY

Ss =

BASIC SEISMIC-FORCE-RESISTING SYSTEM

DESIGN BASE SHEAR

SEISMIC RESPONSE COEFFICIENT, Cs

RESPONSE MODIFICATION FACTOR, R

ANALYSIS PROCEDURE USED

SDS =

S1 =

SD1 =

0.11 0.063

0.090.1

0.07xW (R=1.5) 0.03W (R=3)

1.0

II

DEFAULT

B

ORDINARY PLAN MASONRY SHEAR

WALL AND STEEL SYSTEMS NOT

SPECIFICALLY DETAILED FOR

SEISMIC RESISTANCE

1.5 (SHEAR)

3 (STEEL)

EQUIVALENT LATERAL FORCE

0.07xW (R=1.5) 0.03W (R=3)

1. PROJECT SPECIFICATIONS ARE A PART OF THE CONTRACT DOCUMENTS. CONTRACTOR SHALL REVIEW THE SPECIFICATIONS AND NOTIFY ARCHITECT OF DISCREPANCIES BEFORE PROCEEDING WITH WORK.

2. STRUCTURAL DRAWINGS ARE AN INTEGRAL COMPONENT TO THE CONTRACT DOCUMENTS. CONTRACTOR SHALL

REVIEW AND COORDINATE ACCORDINGLY.

A. PRIOR TO FABRICATION OR INSTALLATION OF STRUCTURAL MEMBERS, CONTRACTOR SHALL COMPARE

STRUCTURAL DIMENSIONS AND SECTIONS WITH ARCHITECTURAL DIMENSIONS AND SECTIONS.

DISCREPANCIES ARE TO BE REPORTED IN WRITING TO THE ARCHITECT.

B. PRINCIPAL OPENINGS ARE SHOWN ON THESE DRAWINGS. REFER TO ARCHITECTURAL, MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR OTHER OPENINGS NOT SHOWN.

C. REFER TO ARCHITECTURAL DRAWINGS FOR ELEVATIONS AND LOCATIONS OF SLAB DEPRESSIONS AND

CURBS NOT SHOWN. PROVIDE POSITIVE SLOPE TO ALL DRAINS.

D. CONTRACTOR SHALL COORDINATE PENETRATIONS, SLEEVES, CURBS, AND INSERTS REQUIRED FOR THE

CONTRACT DOCUMENTS.

E. CONTRACTOR SHALL VERIFY SIZE, WEIGHT, LOCATION, AND SUPPORT CONDITIONS OF MECHANICAL

EQUIPMENT SUPPORTED ON OR SUSPENDED FROM THE ROOF OR FLOORS.

F. CONTRACTOR SHALL COORDINATE CONSTRUCTION WITH ADJACENT STRUCTURES AND UTILITIES.

G. CONTRACTOR SHALL NOTIFY IN WRITING THE ARCHITECT & ENGINEER OF ANY DISCREPANCIES BEFORE

PROCEEDING WITH WORK.

3. TEMPORARY SHORING AND BRACING DURING CONSTRUCTION

A. CONTRACTOR SHALL PROVIDE TEMPORARY BRACING OF COMPONENTS DURING CONSTRUCTION TO MEET

REGULATORY REQUIREMENTS FOR SAFETY.

B. CONTRACTOR SHALL PROVIDE TEMPORARY SHORING AND BRACING OF WALLS AND GRADE BEAMS DURING

CONSTRUCTION. SHORE WALLS AND GRADE BEAMS DURING THE BACKFILLING AND COMPACTION PROCESS.

C. CONTRACTOR SHALL PROVIDE NECESSARY TEMPORARY BRACING AND SHORING DURING CONSTRUCTION

UNTIL STRUCTURAL FRAMING AND DIAPHRAGMS ARE COMPLETED. TEMPORARY BRACING SHALL BE

DESIGNED UNDER THE SUPERVISION OF A LICENSED ENGINEER.

4. SELECTION OF CONSTRUCTION MEANS, METHODS, TECHNIQUES, AND PROCEDURES, AS WELL AS SAFETY PRECAUTIONS AND PROGRAMS, ARE SOLELY THE CONTRACTOR’S RESPONSIBILITIES. AS SUCH, CONSTRUCTION ENGINEERING AND DESIGN RESULTING FROM THESE SELECTIONS IS THE RESPONSIBILITY OF THE CONTRACTOR.

A. EXAMPLES INCLUDE, BUT ARE NOT LIMITED TO, ENGINEERING OF SHORING AND SCAFFOLDING SYSTEMS;

LOAD CHECKS AND STRUCTURAL MODIFICATIONS FOR STORAGE, STAGING, AND CONSTRUCTION

EQUIPMENT LOADING; MEANS OF EGRESS FOR HEAVY EQUIPMENT; CRANE SELECTION, LOCATION, SUPPORT

AND BRACING; TEMPORARY HOISTS, LIFTS AND PLATFORMS.

B. CONTRACTOR SHALL ENSURE THAT APPROPRIATE ENGINEERING IS PERFORMED BY A LICENSED ENGINEER FOR THE WORK, CONSULTED WITH ON FIELD MODIFICATIONS, SPECIFY APPROPRIATE LEVELS OF

INSPECTION OF THE WORK, AND TO REVIEW INSPECTION REPORTS.

C. CONSTRUCTION ENGINEERING FEES HAVE NOT BEEN INCLUDED IN THE BASE FEE TO THE

OWNER/ARCHITECT. IF REQUESTED, THE EOR MAY CONSIDER PERFORMING THESE SERVICES AS AN

ADDITIONAL SERVICE PAID BY THE CONTRACTOR.

5. PRE-CONSTRUCTION MEETINGS SHALL BE CONDUCTED TO DISCUSS SUBGRADE PREPARATION, FOUNDATION CONSTRUCTION, WALL BACKFILL, VOID FORM SYSTEMS, CONCRETE FORMING & PLACING, AND TESTING &

INSPECTION REQUIREMENTS.

6. CONTRACTOR SHALL COMPLY WITH REQUIREMENTS AS LISTED IN THE STATEMENT OF SPECIAL INSPECTIONS.

GENERAL NOTES

1. DEFERRED SUBMITTALS ARE PORTIONS OF THE OVERALL DESIGN WHICH ARE NOT SUBMITTED AT TIME OF PERMIT

APPLICATION AND ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL.

2. DEFERRED SUBMITTALS WILL BE REVIEWED FOR THE LIMITED PURPOSE OF CHECKING FOR CONFORMANCE WITH INFORMATION GIVEN IN THE CONTRACT DOCUMENTS. SUBMITTAL REVIEW WILL NOT BE CONDUCTED FOR THE PURPOSE OF DETERMINING THE ACCURACY AND COMPLETENESS OF OTHER DETAILED INFORMATION SUCH AS DIMENSIONS AND QUANTITIES, OR FOR SUBSTANTIATING INSTRUCTIONS FOR INSTALLATION OR SYSTEMS DESIGNED

BY THE CONTRACTOR WHICH REMAINS THE RESPONSIBILITY OF THE CONTRACTOR.

REVIEW SHALL NOT CONSTITUTE APPROVAL OF SAFETY PRECAUTIONS OR OF ANY CONSTRUCTION MEANS, METHODS, SEQUENCES OR PROCEDURES.

APPROVAL OF A SPECIFIC ITEM SHALL NOT INDICATE APPROVAL OF AN ASSEMBLY OF WHICH THE ITEM IS A

COMPONENT.

3. FOLLOWING DEFERRED SUBMITTALS ARE TO BE PROVIDED FOR REVIEW:

A. CONCRETE FORMWORK / RETENTION SYSTEMS

B. STEEL BEAM AND VERTICAL BRACING CONNECTIONS

C. STEEL FRAMING CONNECTION CALCULATIONS

SUPPLIER’S ENGINEERS SHALL PROVIDE SIGNED AND SEALED CALCULATIONS WITH THE SUBMITTAL FOR REVIEW.

REVIEW WILL BE LIMITED TO CONFORMANCE WITH DESIGN AND PERFORMANCE CRITERIA SPECIFIED IN THE CONSTRUCTION DOCUMENTS AND THE INTERFACE BETWEEN THESE ITEMS/SYSTEMS AND THE BUILDING STRUCTURE. THE MANUFACTURER/SUPPLIER AND ITS SPECIALTY STRUCTURAL ENGINEER REMAIN RESPONSIBLE FOR THE DESIGN OF THE ITEM/SYSTEM WILL RETAIN ALL RIGHTS AND RESPONSIBILITIES FOR THE DESIGN OF THE

PRODUCT AND THE CONNECTIONS TO THE BUILDING STRUCTURE.

NO WORK ON STRUCTURAL ELEMENTS SUPPORTING OR RELATED TO THESE ITEMS IS TO PROCEED UNLESS THE REVIEW STAMP CLEARLY INDICATES "REVIEWED" OR "REVIEWED, SEE COMMENTS" BY THE ENGINEER.

4. FOLLOWING SHOP DRAWINGS ARE TO BE PROVIDED FOR APPROVAL:

A. CONCRETE MIXES

B. REINFORCING STEEL

C. STRUCTURAL STEEL

D. STEEL JOISTS AND JOIST GIRDERS

E. METAL DECKING

F. MASONRY WALL REINFORCING

SHOP DRAWINGS ARE TO BE DISTRIBUTED ONLY FROM RETURNED SUBMITTALS BEARING AN INITIALED REVIEW STAMP AND WORK ON THESE ITEMS SHALL NOT PROCEED UNLESS THE STAMP CLEARLY INDICATES THE DRAWINGS

ARE "APPROVED" OR "APPROVED AS NOTED."

5. CONCRETE IS A MATERIAL DESIGNED BY THE SUPPLIER TO MEET THE STRENGTH AND PERFORMANCE CRITERIA SPECIFIED IN THE CONTRACT DOCUMENTS. CONCRETE MIX DESIGNS SHALL BE IN CONFORMANCE WITH ACI 318.

SUBMIT MIX DESIGNS AND THE TESTING LAB REVIEW TO THE ARCHITECT/ENGINEER FOR REVIEW.

MANY VARIABLES, INCLUDING ENVIRONMENTAL CONDITIONS AFFECT THE QUALITY OF CONCRETE. THE CONTRACTOR IS RESPONSIBLE FOR CONTROLLING VARIABLES AND REQUESTING MIX MODIFICATIONS AND SHALL BE

SOLELY RESPONSIBLE FOR THE QUALITY OF CONCRETE DELIVERED AND PLACED ON THE SITE.

6. BEFORE SUBMISSION FOR REVIEW, GENERAL CONTRACTOR SHALL PRE-CHECK SUBMITTALS. SUBMITTALS MUST BEAR AN INITIALED REVIEW STAMP OF THE GENERAL CONTRACTOR. SUBMITTALS WITHOUT REVIEW STAMPS WILL

BE RETURNED WITHOUT REVIEW AND SHALL NOT BE CAUSE FOR CLAIMS OF DELAY.

7. SCHEDULE SUBMITTALS SUFFICIENTLY IN ADVANCE OF THE DATE REQUIRED TO ALLOW REASONABLE TIME FOR PROCESSING AND REVIEW BY THE DESIGN TEAM. THIS SHALL INCLUDE A MINIMUM OF TEN WORKING DAYS FOR ENGINEER'S PROCESSING AND REVIEW. INCLUDE TIME FOR CONTRACTOR’S RESUBMISSION AND SUBSEQUENT

REVIEW IF NECESSARY.

SHORTER REVIEW PERIODS WILL ONLY BE HONORED WITH PRIOR WRITTEN CONSENT. THESE ACCELERATED SERVICES, AND APPROPRIATE COMPENSATION, MUST BE NEGOTIATED WITH THE ENGINEER AND ARCHITECT IN

ADVANCE.

TEN DAY REVIEW PERIODS CAN NOT BE HONORED WHEN LARGE QUANTITIES OF SHOP DRAWINGS ARE SUBMITTED AT ONE TIME. WHEN THIS HAPPENS, THE CONTRACTOR SHALL SUBMIT AN ITEMIZED LIST INDICATING PRIORITIES AND

REASONABLE RETURN DATES.

REVIEW OF RESUBMITTALS WILL BE LIMITED TO ONLY EARLIER COMMENTS AND IS NOT AN EXTENSIVE REVIEW.

8. USE OF REPRODUCTIONS OF THESE CONTRACT DRAWINGS, INCLUDING THE USE OF ELECTRONIC FILES, BY ANY CONTRACTOR IN LIEU OF THE INDEPENDENT PREPARATION OF SHOP DRAWINGS, SIGNIFIES THEIR ACCEPTANCE OF ALL INFORMATION SHOWN HEREON AS CORRECT AND OBLIGATES HIMSELF TO ANY JOB EXPENSE, REAL OR IMPLIED, ARISING DUE TO ANY ERRORS THAT MAY OCCUR HEREON.

9. NOT USED

DEFERRED SUBMITTALS NOTES

1. FOUNDATION DESIGN AND SUBSURFACE INFORMATION IS BASED ON GEOTECHNICAL REPORT #26-162 PREPARED FOR THIS PROJECT BY LARRY M JACOBS & ASSOCIATES, INC AND DATED MAY 1, 2026 & EMAIL RESPONSE DATED

SEPTEMBER 1, 2026.

2. GEOTECHNICAL ENGINEER OF RECORD (GER) IS SOLELY RESPONSIBLE FOR ESTABLISHING FOUNDATION, SLAB-ON- GRADE AND PAVEMENT DESIGN CRITERIA, AND FOR THE CONSTRUCTION RECOMMENDATIONS FOR EXCAVATION, SUBGRADE PREPARATION, BACKFILLING AND COMPACTION.

3. GEOTECHNICAL INFORMATION INDICATED IN THE STRUCTURAL CONSTRUCTION DOCUMENTS IS INTENDED TO REPLICATE THE RECOMMENDATIONS STATED IN THE GEOTECHNICAL ENGINEERING REPORT. PRESENTATION OF THIS INFORMATION IN THE STRUCTURAL DOCUMENTS DOES NOT DEMONSTRATE, STATE OR IMPLY GEOTECHNICAL EXPERTISE BY THE STRUCTURAL ENGINEER. CONTRACTOR SHALL OBTAIN A COPY OF THE REPORT AND COMPLY

WITH THE RECOMMENDATIONS INDICATED THEREIN.

4. IF DISCREPANCIES BETWEEN THE REPORT AND CONSTRUCTION DOCUMENTS ARE DISCOVERED, THE REPORT SHALL GOVERN. ALL CLARIFICATIONS AND INTERPRETATIONS OF THE REPORT SHALL BE MADE BY THE GER AND

REPORTED TO THE ARCHITECT FOR COORDINATION WITH THE DESIGN TEAM.

GEOTECHNICAL INFORMATION

1. BEARING STRATA SHOWN ON THE DETAILS IS COMPACTED NATIVE SOILS. PREPARE FOUNDATION BEARING

MATERIAL PER THE GEOTECHNICAL ENGINEER'S RECOMMENDATIONS.

2. FOUNDATION ALLOWABLE DESIGN SOIL VALUES:

CONTINUOUS FOOTING BEARING - 1.5ksf * ISOLATED FOOTING BEARING - 1.5ksf *

SOIL SLIDING RESISTANCE (NATIVE SOIL) 0.5

* IF CONTINUOUS FOOTING OR ISOLATED FOOTING WIDTH EXCESS 3FT IN DIMENSION, THE SOIL BENEATH FOOTING

SHALL HAVE ADDITIONAL 2FT OF SOIL COMPACTION PER GEOTECHNICAL REPORT.

RETAINING WALL DESIGN VALUES

SOIL DENSITY Yd- 95PCF (VERY LOOSE SLIGHTLY SILTY SAND) AT REST Ka- 0.4xYd PASSIVE PRESSURE Kp- 2.5XYd

3. ALL FOOTING EXCAVATIONS SHALL BE CLEANED TO REMOVE ALL LOOSE SOIL MATERIAL AND OTHER DEBRIS AND

SHOULD NOT BE ALLOWED TO DESICCATE PRIOR TO PLACEMENT OF CONCRETE.

4. CONCRETE FOR FOUNDATIONS SHALL BE FORMED ON THE SIDES (EARTH FORMED FOUNDATIONS WILL NOT BE

ALLOWED). PROPERLY PLACE AND COMPACT FILL MATERIAL AROUND SIDES OF FOOTINGS.

5. ALL FOUNDATION EXCAVATIONS SHALL BE INSPECTED BY THE TESTING AGENCY.

SHALLOW FOUNDATION NOTES

1. STRUCTURAL MASONRY SHALL CONFORM TO "BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES" ACI

530 / ASCE 5 - LATEST EDITION.

2. HOLLOW LOAD BEARING MASONRY UNITS SHALL CONFORM TO ASTM C90, LIGHTWEIGHT, TYPE N, WITH A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 2000 psi ON THE NET AREA OF THE BLOCK. DESIGN BASED ON AN ULTIMATE COMPRESSIVE STRENGTH f'm = 2500 psi.

3. MORTAR SHALL CONFORM TO ASTM C270, TYPE M OR S.

4. GROUT SHALL CONFORM TO ASTM A476 WITH A MINIMUM COMPRESSIVE STRENGTH OF 2500 psi. USE COARSE GROUT IN TYPICAL APPLICATION. USE FINE GROUT IN 4" AND 6" CMU WALLS AND IN ANY CELL REINFORCED WITH

MORE THAN ONE BAR.

5. REFER TO REINFORCING STEEL NOTES FOR REINFORCEMENT USED IN MASONRY CONSTRUCTION. ALL REINFORCING TO BE GRADE 60. PRIOR TO FABRICATION SUBMIT SHOP DRAWINGS FOR REVIEW, INCLUDING WALL

ELEVATIONS SHOWING ALL REINFORCING STEEL.

6. VERTICAL REINFORCING SHALL BE #6 BARS AT A MAXIMUM SPACING OF 40" O.C., UNLESS OTHERWISE NOTED ON DRAWINGS. THE FIRST CELL AT CORNERS AND ENDS OF WALLS SHALL BE REINFORCED WITH 1-#6 BAR AND GROUTED FULL. ON EACH SIDE OF WALL OPENINGS 1-#5 BAR EXTENDING 2'-0" BEYOND CORNERS OF OPENING SHALL BE PLACED. ALL REINFORCED CELLS SHALL BE FILLED SOLIDLY WITH GROUT. REFER TO DETAILS FOR

SPECIAL REINFORCEMENT AT SUPPORTS.

7. REINFORCING BARS SHALL BE STRAIGHT EXCEPT FOR BENDS AROUND CORNERS AND WHERE BENDS OR HOOKS

ARE DETAILED ON THE PLANS.

8. REINFORCING STEEL SHALL BE LAPPED 60 BAR DIAMETERS WHERE SPLICED AND SHALL BE WIRED TOGETHER.

9. HORIZONTAL WALL REINFORCING SHALL BE EXTRA HEAVY HOHMANN & BARNARD COMPANY (LADUR TYPE) AT 1'-4" O.C. FOR 12" CMU AND STANDARD HOHMANN & BARNARD COMPANY (LADUR TYPE) AT 1'-4" O.C. FOR 8" CMU. IN LIEU OF HOHMANN & BARNARD COMPANY REINFORCEMENT THE CONTRACTOR MAY PROVIDE HORIZONTAL BOND BEAMS

LOCATED 48" O.C. VERTICALLY AND REINFORCED WITH 2-#5 CONTINUOUS BARS.

10. ALL REINFORCING SHALL BE IN PLACE PRIOR TO GROUTING. VERTICAL REINFORCING BARS SHALL BE HELD IN POSITION AT TOP, BOTTOM, AND AT INTERVALS NOT FURTHER APART THAN 192 BAR DIAMETERS BY WALL-BRAC VERTICAL STEEL POSITIONER AS MANUFACTURED BY W.C.R. FABRICATORS, OR AN EQUIVALENT POSITIONER.

11. PROVIDE CONTINUOUS CMU BOND BEAMS (8" MIN. DEPTH) REINFORCED WITH 2-#5 CONTINUOUS BARS AT TOP OF PARAPETS AND AT ROOF FRAMING ELEVATION FOR FULL LENGTH OF ALL WALLS. WHERE BOND BEAMS REQUIRE SLOPES, PROVIDE 16" DEEP BOND BEAM AND CUT TO PROVIDE AN 8" MINIMUM DEPTH. CONTINUE HORIZONTAL

REINFORCEMENT THROUGH MASONRY COLUMNS AND PILASTERS.

12. PROVIDE 2-#5 CORNER BARS (2'-6"x2'-6"), LAP WITH CONTINUOUS BARS IN ALL BOND BEAMS AT CORNERS AND WALL

INTERSECTIONS.

13. PROVIDE VERTICAL CONTROL JOINTS IN ALL MASONRY WALLS WHERE SHOWN ON ARCHITECTURAL OR STRUCTURAL DRAWINGS, AND NOT TO EXCEED 30 FEET O.C. PROVIDE MATCHING CONTROL JOINTS IN FINISH MATERIALS (i.e. BRICK, STUCCO, etc.). VERTICAL CELLS ON EACH SIDE OF CONTROL JOINTS SHALL BE REINFORCED

AND GROUTED TO MATCH THE TYPICAL WALL REINFORCEMENT.

14. AT WALL CONTROL JOINTS, CONTINUE BOND BEAM REINFORCEMENT THROUGH JOINT AND DISCONTINUE ALL OTHER

HORIZONTAL WALL REINFORCING AT JOINT.

15. ALL UNITS SHALL BE LAID WITH FULL MORTAR BEDS ON THE FACE SHELLS. ALL HEAD JOINTS SHALL BE FILLED SOLIDLY WITH MORTAR FOR A DISTANCE IN FROM THE FACE OF THE UNIT NOT LESS THAN THE THICKNESS OF THE LONGITUDINAL FACE SHELLS. UNLESS THE WALL IS TO BE POURED SOLID, END WALLS AND CROSS WEBS FORMING

CELLS TO BE FILLED SHALL BE FULLBEDDED IN MORTAR TO PREVENT LEAKAGE OF GROUT.

16. ALL DOWELS, ANCHOR BOLTS, AND HEADED STUDS SHALL BE SET IN SOLID GROUTED CELLS.

17. GROUT ALL CELLS SOLID BELOW GRADE.

LOAD BEARING STRUCTURAL MASONRY

1. STRUCTURAL STEEL SHALL CONFORM TO AISC "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS," ANSI/AISC 360, LATEST EDITION.

2. BOLTS AND BOLTED CONNECTIONS SHALL CONFORM TO THE REQUIREMENTS OF THE "SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS," APPROVED BY THE RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS, LATEST EDITION. CONNECTIONS SHALL BE BEARING TYPE UNLESS NOTED OTHERWISE IN

DRAWINGS.

3. ALL W SHAPES SHALL CONFORM TO ASTM A992.

ALL OTHER STRUCTURAL STEEL SHAPES, PLATES, ETC., SHALL CONFORM TO ASTM A36, UNLESS NOTED

OTHERWISE.

4. ALL STRUCTURAL STEEL TUBE MEMBERS SHALL CONFORM TO ASTM A500, GRADE C.

5. ALL STRUCTURAL STEEL PIPE SHALL CONFORM TO ASTM A53, GRADE B.

6. ALL STRUCTURAL ROUND SHAPES SHALL CONFORM TO ASTM A53, GRADE B.

7. GALVANIZING OF STEEL MEMBERS SHALL CONFORM TO ASTM A123/A123M. ALL STEEL FRAMING THAT COMES IN CONTACT WITH PRESSURE TREATED WOOD SHALL BE COATED TO A G90 THICKNESS AND ALL BOLTS, HEADED STUDS AND CONNECTORS SHALL BE COATED TO A G185 THICKNESS. ALL EXPOSED STRUCTURAL STEEL FRAMING AND ACCESSORIES FOR MECHANICAL EQUIPMENT SUPPORTS SHALL BE HOT-DIP GALVANIZED AFTER FABRICATION.

CONTRACTOR TO PROVIDE BOLTS AND PUNCH BEAMS AS REQUIRED BY EQUIPMENT MANUFACTURER'S DETAILS.

8. ALL STRUCTURAL STEEL DETAILS AND CONNECTIONS SHALL CONFORM TO THE STANDARDS OF THE AISC.

9. STEEL MEMBERS SHALL NOT BE SPLICED EXCEPT WHERE SHOWN ON THE DRAWINGS.

10. ALL STEEL BEAMS SHALL BE ERECTED WITH NATURAL CAMBER UP.

11. WELDED CONSTRUCTION SHALL CONFORM TO THE AMERICAN WELDING SOCIETY "STRUCTURAL WELDING CODE", D1.1. ELECTRODES FOR FIELD AND SHOP WELDS SHALL BE E70XX, UNLESS NOTED OTHERWISE.

12. ALL WELDING SHALL BE PERFORMED BY CERTIFIED WELDERS.

13. FULL AND PARTIAL PENETRATION WELDS PERFORMED IN THE FIELD SHALL BE ULTRASONICALLY TESTED.

14. WHEN WELDS ARE NOT CALLED-OUT ON DRAWINGS, THEY ARE MINIMUM SIZE CONTINUOUS FILLET WELDS IN

ACCORDANCE WITH AWS D1.1.

15. THE STEEL FABRICATOR IS RESPONSIBLE FOR COORDINATION WITH THE MANUFACTURER OF STEEL JOISTS AND

JOIST GIRDERS.

16. TEMPORARY SUPPORTS, SUCH AS TEMPORARY GUYS, BRACES, FALSEWORK, CRIBBING OR OTHER ELEMENTS REQUIRED FOR THE ERECTION OPERATION WILL BE DETERMINED, FURNISHED, AND INSTALLED BY THE ERECTOR.

THESE TEMPORARY SUPPORTS SHALL BE CAPABLE OF SECURING THE STEEL FRAMING, OR ANY PARTLY ASSEMBLED STEEL FRAMING, AGAINST LOADS COMPARABLE IN INTENSITY TO THOSE FOR WHICH THE STRUCTURE

WAS DESIGNED, RESULTING FROM WIND, SEISMIC FORCES AND ERECTION OPERATIONS.

17. THE LIFTING AND ERECTION OF PRE-ASSEMBLED ELEMENTS SUCH AS TRUSSES OR PRE-FABRICATED FRAMING ARE CONSIDERED SPECIAL ERECTION CONDITIONS. THE SELECTION OF LIFT POINTS AND ERECTION TECHNIQUES ARE THE RESPONSIBILITY OF THE CONTRACTOR. LOCATE AND PROVIDE SUFFICIENT LIFT POINTS TO PREVENT OVERSTRESS AND/OR DISTORTION OF ANY COMPONENTS WITHIN THE ASSEMBLY. PROVIDE TEMPORARY STRONG-

BACKS, STIFFENERS AND/OR LIFTING DEVICES AS REQUIRED.

18. ALL GROUT BELOW ALL COLUMN BASE PLATES AND BEARING PLATES SHALL BE NON-SHRINK, NON-METALLIC GROUT

UNLESS NOTED OTHERWISE.

STRUCTURAL STEEL NOTES

1. FLOOR SLAB SHALL BE 5" THICK CONCRETE SLAB OVER A 15 MIL VAPOR RETARDER, OVER SUBGRADE PREPARED PER THE GEOTECHNICAL ENGINEER'S RECOMMENDATIONS. TAPE ALL SEAMS, PENETRATIONS AND TEARS IN

THE VAPOR RETARDER WITH A COMPATIBLE WATERPROOF TAPE.

2. REINFORCE SLAB WITH #3 @ 18" CTRS. EACH WAY PLACED AND SUPPORTED ON CHAIRS OR CONCRETE BRIQUETS, AT SLAB MID DEPTH.

3. PROVIDE ONE OF THE FOLLOWING JOINTS ON THE CENTERLINE OF ALL COLUMNS, AND @ 15' O.C. MAXIMUM.

A. CONSTRUCTION JOINTS WHERE DETAILED ON DRAWINGS.

B. SAW CUT CONTROL JOINTS ELSEWHERE 1 1/4" DEEP OR ONE QUARTER OF THE SLAB DEPTH DEEP, WHICHEVER IS GREATER.

4. A METAL CONTROL JOINT FORM MAY BE USED IN LIEU OF EITHER OF THE ABOVE.

5. CUT SAW CUT JOINTS WITHIN 8 HOURS OF POURING CONCRETE.

6. CONCRETE FINISHES AND SPRAY ON CURRING / SEALING COMPOUNDS SHALL BE COORDINATED WITH

ARCHITECTURAL FLOORING FINISHES FOR COMPATIBILITY.

SLAB-ON-GRADE NOTES

1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH ACI 318- PER GOVERNING BUILDING CODE.

2. CONCRETE IN THE FOLLOWING AREAS SHALL HAVE SAND AND GRAVEL OR CRUSHED STONE AGGREGATES AND THE DESIGNATED COMPRESSIVE STRENGTH IN 28 DAYS UNLESS NOTED OTHERWISE. NORMAL WEIGHT AGGREGATES

SHALL CONFORM TO ASTM C33.

FOOTING AND SLABS ON GRADE --------------------------- f'c = 4,000 psi ALL OTHER CONCRETE ---------------------------------------- f'c = 4,000 psi

3. CONCRETE PROTECTION FOR REINFORCEMENT SHALL BE AS FOLLOWS:

REFER TO ACI 318 - SECTION 7.7 FOR CONDITIONS NOT NOTED.

FOOTINGS ---------------------------------------- 3"

SLABS-ON-GRADE ----------------------------- CENTERED

4. MAXIMUM NOMINAL COARSE AGGREGATE SIZE SHALL BE 1 1/2" MAX FOR PIERS AND 1" MAX TYPICAL UNLESS NOTED

OTHERWISE.

5. CONCRETE SLUMPS SHALL BE AS FOLLOWS:

CONCRETE CONTAINING HRWR------ 10" MAX

ALL OTHER CONCRETE ---------------- 5" MAX, 2" MIN

6. CONCRETE EXPOSED TO WEATHER SHALL BE AIR-ENTRAINED AS FOLLOWS:

3/4" NOMINAL AGGREGATE SIZE 4% TO 8%

1" NOMINAL AGGREGATE SIZE 3.5% TO 6.5%

1 1/2" NOMINAL AGGREGATE SIZE 3% TO 6%

7. ALL FOUNDATION PIER CAPS SHALL BE FORMED ON SIDES. ALL ELEMENTS OF THE FORMS, FORMWORK, BRACING AND SHORING SHALL CONSIST OF WOOD, METAL OR OTHER MANUFACTURED PRODUCTS AS SPECIFIED. EARTH MAY NOT BE USED AS A FORM, EITHER DIRECTLY OR INDIRECTLY. NEITHER EARTH TRENCHES NOR EARTH TRENCHES

LINED WITH ANOTHER MATERIAL ARE ACCEPTABLE.

8. THERE SHALL BE NO HORIZONTAL CONSTRUCTION JOINTS IN CONCRETE POURS. ALL CONSTRUCTION JOINTS SHALL BE MADE IN THE CENTER OF SPANS WITH VERTICAL BULK HEADS. THE LOCATION OF CONSTRUCTION JOINTS SHALL

BE APPROVED BY THE STRUCTURAL ENGINEER.

9. ALL CONSTRUCTION JOINTS SHOWN ON THE DRAWINGS SHALL BE INCORPORATED IN THE STRUCTURE UNLESS OTHERWISE APPROVED BY THE ENGINEER OF RECORD. ADDITIONAL CONSTRUCTION JOINTS REQUIRED TO FACILITATE CONSTRUCTION SHALL BE LOCATED AND DETAILED ON SHOP DRAWINGS. WHEN CONSTRUCTION JOINTS OTHER THAN THOSE SHOWN ON THE CONSTRUCTION DOCUMENTS ARE REQUIRED, THE REINFORCEMENT SHALL PASS CONTINUOUSLY THROUGH JOINT AND A KEY SHALL BE PROVIDED FOR ADEQUATE SHEAR TRANSFER.

10. UNLESS OTHERWISE NOTED OR DETAILED, PROVIDE (2)#5, (1) EACH FACE AROUND UNFRAMED OPENINGS IN CONCRETE WALLS AND GRADE BEAMS. PLACE BARS PARALLEL TO SIDES OF OPENINGS AND EXTEND 24 INCHES

BEYOND CORNERS.

11. PROVIDE EQUIPMENT BASES AND SUPPORTS AS REQUIRED, COMPLYING WITH APPROVED MANUFACTURERS

CERTIFIED SHOP DRAWINGS AND DETAILS.

12. SIZE AND LOCATION OF BASES AND EMBEDDED ANCHORS FOR EQUIPMENT SHALL BE COORDINATED WITH

EQUIPMENT SUPPLIER AND ALL BE IN ACCORDANCE WITH APPROVED SHOP DRAWINGS.

13. NO ALUMINUM OF ANY TYPE SHALL BE ALLOWED IN THE CONCRETE WORK, UNLESS COATED AND APPROVED BY

THE ENGINEER OR RECORD.

14. NO ELECTRICAL CONDUIT SHALL BE PLACE ABOVE THE WELDED WIRE FABRIC IN THE SLAB-ON-GRADE OR CONCRETE PLACED ON COMPOSITE METAL DECK. MAXIMUM SIZE OF CONDUIT SHALL BE 1/3 THE SLAB THICKNESS (ABOVE DECK ON COMPOSITE SLAB) INCLUDING CROSSOVERS. CONDUIT SHALL NOT BE PLACED CLOSER THAN 3

DIAMETERS ON CENTER.

CONCRETE NOTES

1. ALL REINFORCING STEEL SHALL BE NEW DEFORMED BILLET STEEL CONFORMING TO ASTM A615, GRADE 60.

2. DETAILING OF REINFORCEMENT SHALL BE IN ACCORDANCE WITH THE ACI DETAILING MANUAL.

3. REINFORCING BARS MAY BE SPLICED ONLY AS SHOWN ON THE DRAWINGS EXCEPT THAT REINFORCING DESIGNATED AS "CONTINUOUS" MAY BE CONTACT LAP SPLICED WITH TENSION LAP PER ACI 318 CHAPTER 25.

4. FOR CONTINUOUS FOOTING REINFORCING, PER FOOTING REINFORCEMENT LAP SPLICES SCHEDULED ON S301.

5. PROVIDE CORNERS BARS OF SAME SIZE AND QUANTITY AS CONTINUOUS TOP AND BOTTOM REINFORCING OF

GRADE BEAMS AT ALL GRADE BEAM CORNERS AND INTERSECTIONS.

REINFORCING STEEL NOTES

1. THE CONTRACTOR SHALL PROVIDE TRENCH SAFETY DESIGN DOCUMENTS PREPARED AND SEALED BY A QUALIFIED REGISTERED PROFESSIONAL ENGINEER AS REQUIRED BY ALL LOCAL AND STATE LAWS. SAID ENGINEER SHALL ALSO BE RESPONSIBLE FOR ON SITE OBSERVATIONS. THE TRENCH SAFETY DESIGN DOCUMENTS SHALL BE FILED WITH THE APPROPRIATE GOVERNMENT AGENCY. THE CONTRACTOR SHALL FURNISH A SEPARATE AND DISTINCT PRICE FOR TRENCH SAFETY SYSTEM THAT MEETS OCCUPATIONAL SAFETY & HEALTH ADMINISTRATION STANDARDS.

TRENCH SAFETY

1. ALL SUBGRADE SHALL BE PREPARED IN STRICT CONFORMANCE TO THE GEOTECHNICAL ENGINEER’S RECOMMENDATIONS. REFER TO THE GEOTECHNICAL REPORT, SUPPLEMENTARY LETTERS AND SPECIFICATIONS

FOR ADDITIONAL INFORMATION.

THE SUBGRADE SHALL BE IMPROVED TO REDUCE THE POTENTIAL FOR SUBGRADE MOVEMENT TO LESS THAN OF ONE INCH TOTAL SETTLEMENT & 1/2 INCH OF DIFFERENTIAL SETTLEMENT BY RE-COMPACTING IN-SITU SOIL AS

APPROVED BY GEOTECH ENGINEER.

THE FOLLOWING IS A SUMMARY OF THE INFORMATION CONTAINED IN THE GEOTECHNICAL ENGINEER’S

RECOMMENDATIONS:

A. THE BUILDING EXCAVATION AREA SHALL EXTEND BEYOND THE BUILDING LINE A MINIMUM OF 5 FEET IN GENERAL. AT ALL ENTRANCES AND AT AREAS WITH SIDEWALKS/PAVING DIRECTLY ADJACENT TO THE

BUILDING.

B. WITHIN THE BUILDING AREA, EXCAVATE AND REMOVE ALL FILL MATERIAL. REFER TO THE GEOTECHNICAL REPORT FOR APPROXIMATE DEPTHS OF FILL. THE TESTING LAB SHALL DETERMINE THROUGH FIELD

OBSERVATION AND TESTING THAT ALL UNACCEPTABLE FILLS HAVE BEEN REMOVED.

C. WITHIN THE BUILDING AREA, RE-COMPACT NATIVE SOIL OR IMPORTED FILL AS REQUIRED TO PROVIDE A COMPACTED MATERIAL BENEATH BUILDING AREA. FOOTING THAT HAVE A WIDTH GREATER THAN 3FT IN

WIDTH WILL REQUIRE ADDITIONAL 2FT OF SOIL COMPACTION BENEATH FOOTING.

D. SCARIFY EXPOSED NATIVE SOILS TO A DEPTH OF 12 INCHES FOR FOOTING LESS THAN 3FT IN WIDTH AND RECOMPACT TO A MINIMUM OF 95% OF MODIFIED PROCTOR (ASTM D1557) AT A MINIMUM OF +2 PERCENTAGE POINTS ABOVE THE OPTIMUM MOISTURE CONTENT FOR THE SOIL AS DIRECTED IN THE

GEOTECHNICAL REPORT.

K. SELECT FILL SHALL CONSIST OF A SLIGHTLY SILTY SAND OR SILTY/CLAYEY SAND. ALL SELECT FILL SHALL BE

APPROVED BY THE GEOTECHNICAL ENGINEER.

L. SPREAD THE SELECT FILL IN THIN LOOSE LIFTS NOT EXCEEDING 10 TO 12 INCHES THICK FOR SLIGHTLY SILTY SAND OR LIFTS NOT EXCEEDING 6 TO 8 INCHES THICK FOR SILTY/CLAYEY SAND AND UNIFORMLY COMPACT TO A MINIMUM OF 95% OF ASTM D1557 WITHIN +2 OR –2 PERCENTAGE POINTS OF THE OPTIMUM MOISTURE

CONTENT FOR THE SOIL AS RECOMMENDED IN THE GEOTECHNICAL REPORT.

M. PLACE FIRST LIFT OF SELECT FILL WET OF OPTIMUM TO PREVENT DRYING OF THE UNDERLYING SUBGRADE.

N. PROTECT FILL TO PREVENT DESICCATION PRIOR TO PLACING A SUBSEQUENT LIFT.

2. CONTACT THE GEOTECHNICAL ENGINEER FOR ANY QUESTIONS REGARDING INTERPRETATION OR CLARIFICATION OF

THE ABOVE INFORMATION.

3. FOUNDATION AND SUBGRADE PREPARATION SHALL BE MONITORED AND TESTED BY THE SOILS ENGINEER. REFER

TO SPECIFICATIONS FOR QUALITY CONTROL REQUIREMENTS.

SUBGRADE PREPARATION

Architect of Record:

ADG

800 SW ADAMS STREET, SUITE 101

PEORIA, IL 61602

R e vi si o n s

P - 309.672.6948

Discipline:Discipline:Discipline:

P - P - P -

Discipline:

P -

PROJECT NO.

DATE

DRAWN BY

STATUS

Discipline: Owner Consultant

QSC SERVICES, LLC

PMB #69

545 BRENT LN. PENSACOLA, FL

P - 309.231.8272

OWNER ID:

Design and Construction Administration Division

ESCAMBIA COUNTY, FL

100 E. BLOUNT ST. PENSACOLA, FL 32501

ESCAMBIA COUNTY AREA TRANSIT - FACILITY:

03 - TRANSFER CENTER

41 CLARINDA LN

PENSACOLA, FL, 32505 S001GENERAL NOTES

KEDbluestone

707 NE JEFFERSON AVE,

PEORIA, IL 61602

RLG CONSULTING ENGINEERS

12001 N CENTRAL EXPY, STE 300

DALLAS, TX 75243

RLG CONSULTING ENGINEERS

12001 N CENTRAL EXPY, STE 300

DALLAS, TX 75243

214.739.8100 214.739.8100 515.727.0700

HODGSON DOUGLAS LANDSCAPE ARCHITECTS

12001 N CENTRAL EXPY, SUITE 1170

DALLAS, TX 75243

214.749.0333

BID PACKAGE #2 - NOT FOR CONSTRUCTION

10/22/2026

RLG

A D

D

.1

.1

ADD

ADD

A A

B B

T/STL EL =

110'-3 5/8"

T/STL EL =

110'-11 7/8"

T/STL EL =

113'-8"

T/STL EL =

112'-2 3/8"

32'-0" 32'-0" 32'-0" 32'-0" 32'-0" 32'-0" 32'-0" 32'-0"

LINE OF CANOPY

ROOF ABOVE

1 1/2" METAL

ROOF DECK

1 1/2" METAL

ROOF DECK

18K3 SP

18K3 SP

18K3 SP 18K3

18K3

18K3

W

X

W12X30

12K1

12K1SP

W

X

18K3

18K3

18K3

E

Q S

P A

/4

E

Q S

P A

/4

H S

S

X

X

/8

L

SLOPE SLOPE

S500

S302

TYP

S302

TYP

S302

12K1

E

Q S

P A

/8

/8

E

Q S

P A

/2

ARCH

REF

72'-0"

28'-0" 18'-8" 25'-4"

8'-0" 5'-4"

34'-8"

24'-0" 10'-8"

9'-4"

RTU

300 LBS

ROOF TIE BACK -

REF ARCH

S302

TYP AT

BEAM

S302

S302 TYP

TYP

S302

S302

S500

LOW

S500

E

Q S

P A

/4

8'-6" 5'-10"

ROOF HATCH OPNG -

SEE PLAN NOTE #5

S500

SEE 06/S303

FOR RTU

SUPPORT

NOTE #7

SEE PLAN

NOTE #7

SEE PLAN

EF-2

150LB

S500

SEE PLAN

NOTE #8

PLAN NOTES:

1. ALL ELEVATIONS ARE REFERENCED TO BUILDING 1 LEVEL 1 FINISHED FLOOR

EL = 100'-0" (79.30'). REFERENCE SITE PLAN FOR ABSOLUTE ELEVATIONS.

2. SEE S000 SERIES FOR ABBREVIATIONS, GENERAL NOTES, AND SPECIAL

3. SEE S300 SERIES SHEETS FOR TYPICAL DETAILS.

INSPECTIONS.

4. XXX'-X" - DENOTES TOP OF STEEL ELEVATION (METAL DECK BEARING).

5. SEE ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS OF ROOF HATCH OPENINGS.

PROVIDE FRAMING AROUND ROOF OPENINGS PER DETAIL 04 AND 07/S303.

6. JOIST DESIGNATED WITH THE "SP" IDENTIFIER SHALL BE ENGINEERED TO

ACCOMMODATE SUPPLEMENTAL LOADING CONDITIONS. CONTRACTOR TO

VERIFY/COORDINATE LOCATIONS WITH MEP DRAWINGS AND JOIST ENGINEER.

7. 8" CMU WALL SHALL BE GROUTED SOLID IN ALL CELLS. SEE PLAN FOR EXTENTS OF

FULLY GROUTED CMU.

8. INDICATES HANGING BATHROOM PARTITIONS. CONTRACTOR TO COORDINATE

PARTITION LOADING AND LOCATION WITH JOIST MANUFACTURER. REFER TO

DETAIL 06 & 07 ON S500.

Architect of Record:

ADG

800 SW ADAMS STREET, SUITE 101

PEORIA, IL 61602

R e vi si o n s

P - 309.672.6948

Discipline:Discipline:Discipline:

P - P - P -

Discipline:

P -

PROJECT NO.

DATE

DRAWN BY

STATUS

Discipline: Owner Consultant

QSC SERVICES, LLC

PMB #69

545 BRENT LN. PENSACOLA, FL

P - 309.231.8272

OWNER ID:

Design and Construction Administration Division

ESCAMBIA COUNTY, FL

100 E. BLOUNT ST. PENSACOLA, FL 32501

ESCAMBIA COUNTY AREA TRANSIT - FACILITY:

03 - TRANSFER CENTER

41 CLARINDA LN

PENSACOLA, FL, 32505 S200ROOF FRAMING PLAN

KEDbluestone

707 NE JEFFERSON AVE,

PEORIA, IL 61602

RLG CONSULTING ENGINEERS

12001 N CENTRAL EXPY, STE 300

DALLAS, TX 75243

RLG CONSULTING ENGINEERS

12001 N CENTRAL EXPY, STE 300

DALLAS, TX 75243

214.739.8100 214.739.8100 515.727.0700

HODGSON DOUGLAS LANDSCAPE ARCHITECTS

12001 N CENTRAL EXPY, SUITE 1170

DALLAS, TX 75243

214.749.0333

BID PACKAGE #2 - NOT FOR CONSTRUCTION

10/22/2026

RLG

1/8" = 1'-0"01 ROOF FRAMING PLAN

N

A D

D

.1

.1

ADD

T/STL EL

VARIES SEE PLAN

8" CMU WALL REINF -

SEE 11/S300

B/STL EL

107'-4"

FINISH - REF ARCH

6" 18 GA (MIN) @ 16"

OC (MAX) PER CFMF

ENGR

T/PARAPET EL

REF ARCH

VERT BYPASS CLIP

ANGLE PER CFMF ENGR

HSS BEAM (GALV) -

SEE PLAN

STEEL JOIST -

SEE PLAN

METAL ROOF

DECK - SEE

GEN NOTES

HSS 2 1/2X2 1/2X1/4 CONT BTWN JOIST

W/ 1/4" X 8" CONT PLATE. ATTACH DECK

TO PLATE PER PERIMETER

ATTACHMENT PATTERN.

JOIST TAIL EXTENSION - DESIGNER

TO DESIGN TAIL FOR:

DL = 15 PSF ASD

RL = 20 PSF ASD

WL = 46 PSF ASD

L3X3X1/4 CONT

3/16

3/16

3/16

EMBED PL & JOIST

CONNX - SEE 13/S302

3/16

3/16

B/STL EL

107'-4"

8" CMU WALL REINF -

SEE 11/S300

4" CMU SOAP

HSS BEAM (GALV) W/

#4 DBA X 16" -

SEE PLAN

1/4

1/4

S500

6"

8" CMU WALL REINF -

SEE 11/S300

B/STL EL

108'-0"

HSS BEAM (GALV) W/

1/4" CAP PL

5" MIN

2" CMU SOAP

#4 DBA - SEE 02/S500

EMBED PL & BM

CONNX - SEE 15/S302

METAL ROOF DECK -

SEE GEN NOTES

TIE-BACK ANCHOR /

HORIZONTAL LIFELINE

ANCHOR AND

CONNECTION BY

OTHERS

L6X6X3/8 CONT

DRAG STRUT -

ATTACH DECK TO

ANGLE @ 6" OC

CONNECTION BY

MFR

L2X2X1/4 KICKER

WIDE FLANGE W/

3/8" FULL HEIGHT

STIFF PL

3/16

3/16

TYP

3/16

TYP

T/STL EL

VARIES SEE PLAN

8" CMU WALL REINF -

SEE 11/S300

MTL ROOF DECK - SEE

PLAN & GEN NOTES

ATTACH ROOF DECK TO

CONT ANGLE @ 6" OC USING

PIN PER GEN NOTES

3/16

COPE ANGLE ENDS -

SEE 04/S500

WF BEAM - SEE PLAN

L6x6x3/8x1'-4" w/ (2)-5/8" DIA

F1554 GR 36 THREAD RODS

2" 1'-0" 2"

DRILL & EPOXY USING

HILTI-HY 270 SAFESET (5"

EMBED)

REFER TO S302 FOR

ADDL INFORMATION NOT

SHOWN FOR CLARITY

METAL ROOF

DECK - SEE PLAN

PL TO MATCH

THREADED ROD

DIAMETER

3/16

3/16

STEEL JOIST -

SEE PLAN

(2) L3X3X1/4

/2

1/2X4X4 PL

WASHER

NUT T&B OF

(2) L3X3

1/4 PL

3/16

TYP

3/16

3/16

TYP

THREADED ROD FOR

HANGING PARTITION BY

OTHERS - BTWN (2)L3X3

S500

TYPICAL HANGING TOILET

PARTITION SUPPORT DETAIL

FIELD VERIFY

T/STL EL

SEE PLAN

METAL ROOF DECK -

SEE GEN NOTES

L2X2X1/4 STRUT TO

TOP CHORD PANEL

POINT

3/16

TYP

STEEL JOIST -

SEE PLAN

(2) L3X3 FOR TOILET

PARTITION

Architect of Record:

ADG

800 SW ADAMS STREET, SUITE 101

PEORIA, IL 61602

R e vi si o n s

P - 309.672.6948

Discipline:Discipline:Discipline:

P - P - P -

Discipline:

P -

PROJECT NO.

DATE

DRAWN BY

STATUS

Discipline: Owner Consultant

QSC SERVICES, LLC

PMB #69

545 BRENT LN. PENSACOLA, FL

P - 309.231.8272

OWNER ID:

Design and Construction Administration Division

ESCAMBIA COUNTY, FL

100 E. BLOUNT ST. PENSACOLA, FL 32501

ESCAMBIA COUNTY AREA TRANSIT - FACILITY:

03 - TRANSFER CENTER

41 CLARINDA LN

PENSACOLA, FL, 32505 S500FRAMING DETAILS

KEDbluestone

707 NE JEFFERSON AVE,

PEORIA, IL 61602

RLG CONSULTING ENGINEERS

12001 N CENTRAL EXPY, STE 300

DALLAS, TX 75243

RLG CONSULTING ENGINEERS

12001 N CENTRAL EXPY, STE 300

DALLAS, TX 75243

214.739.8100 214.739.8100 515.727.0700

HODGSON DOUGLAS LANDSCAPE ARCHITECTS

12001 N CENTRAL EXPY, SUITE 1170

DALLAS, TX 75243

214.749.0333

BID PACKAGE #2 - NOT FOR CONSTRUCTION

10/22/2026

RLG

A D

D

.1

.1

ADD

WT2

WT1

WT1

WT1

WT2WT1 WT2 WT1

WT2

WT1

WT1

WT2

WT2

WT1

RT1

RT1

RT2

RT2

RT2

WT1

WT2

WT1WT1 WT2 WT1

WT1

WT2

WT1

WT2

WT2

WT1

WT1

WT1WT2

RT1

RT1

RT2

RT2

RT2

WT3

ROOF TYPE (RT) ASSEMBLIES

EXTERIOR WALL TYPE (WT) ASSEMBLIES

7 5/8" GROUND FACE CMU BLOCK.

PROVIDE FULL BED MORTAR JOINTS AND

TOOL ALL JOINTS TO A CONCAVE

PROFILE. (EB1, MT1)

EXTERIORINTERIOR

PROVIDE INJECTED FOAM INSULATION IN ALL NON-

GROUTED CMU CORES AFTER COMPLETION OF

MASONRY GROUTING OPERATIONS. INSULATION

MATERIAL SHALL BE INSTALLED IN ACCORDANCE WITH

MANUFACTURERS REQUIREMENTS AND SHALL COMPLY

WITH FBC ENERGY CONSERVATION CODE SECTION

C402.1.3, EXCEPTION C.

PROVIDE INTEGRAL WATER-REPELLENT ADMIXTURE IN ALL

EXPOSED GROUND-FACE CMU AND MORTAR AS PART OF

A SINGLE-SOURCE MASONRY WATER-REPELLENT SYSTEM.

AFTER MASONRY HAS CURED AND BEEN CLEANED, APPLY

MANUFACTURER'S RECOMMENDED CLEAR BREATHABLE

SILANE/SILOXANE PENETRATING WATER REPELLENT TO

THE EXTERIOR FACE OF THE WALL.

ROOF DECK - SEE STRUC

R-25 ROOF INSULATION BOARD

0'

1/

2" 1'

2"

BAR JOIST - SEE STRUC

ROOF MEMBRANE

1/4" / 12"

5/8" SUBSTRATE BOARD

7 5/8" GROUND FACE CMU BLOCK. PROVIDE FULL

BED MORTAR JOINTS AND TOOL ALL JOINTS TO A

CONCAVE PROFILE (EB4, MT1)

EXTERIORINTERIOR

PROVIDE INJECTED FOAM INSULATION IN ALL NON-

GROUTED CMU CORES AFTER COMPLETION OF MASONRY

GROUTING OPERATIONS. INSULATION MATERIAL SHALL BE

INSTALLED IN ACCORDANCE WITH MANUFACTURERS

REQUIREMENTS AND SHALL COMPLY WITH FBC ENERGY

CONSERVATION CODE SECTION C402.1.3, EXCEPTION C.

7/8'' VENTED HAT CHANNELS

@ 24'' O.C. & AT TOP AND

BOTTOM OF WALL

METAL PANELS W/ CONCEALED

FASTENERS (MP2)

WRB (FLUID APPLIED)

6'' GALVANIZED STEEL STUDS

THICKNESS & SPACING TO DETERMINED

BY COLD FORM ENGINEER

EXTERIORINTERIOR

7/8'' VENTED HAT CHANNELS

@ 24'' O.C. & AT TOP AND

BOTTOM OF WALL

METAL PANELS W/ CONCEALED

FASTENERS (MP2)

WRB (FLUID APPLIED)

5/8'' EXTERIOR GLASS-MAT

GYPSUM SHEATHING

METAL DECK - SEE STRUC

1'' INSULATION

ROOF MEMBRANE

1/2" / 12"

5/8'' ROOF COVER BOARD

A

B

4 5 6 7 8 9321

GWB

8' - 0" A.F.F.

24" x 24" ACT 9' - 0" A.F.F.

24" x 24" ACT 9' - 0" A.F.F.24" x 24" ACT

9' - 0" A.F.F.

24" x 24" ACT 9' - 0" A.F.F.

CUSTOMER SERVICE

C.S. OFFICE

ADA TOILET

JANITOR

VESTIBULE BREAK ROOM

JANITOR

HVAC GWB

8' - 0" A.F.F.

GWB

8' - 0" A.F.F.

SAFE MECH / IT

ADA TOILET

24" x 24" ACT 8' - 6" A.F.F.

NO CEILING

NO CEILING

NO CEILING

NO CEILING

WALL MOUNTED ROOF

ACCESS LADDER & 3'x3'

ROOF HATCH ABOVE

High-Impact Gypsum Board 8' - 0" A.F.F.

High-Impact Gypsum Board 8' - 0" A.F.F.

WOMEN RESTROOM

MEN RESTROOM

0'

7"

0'

7"

1'

4"

PAINT UNDERSIDE OF UPPER CANOPY AND ATTACHED COLUMNS PT3

PT3 PT3 PT3 PT3

PT3PT3PT3PT3

PAINT UNDERSIDE OF LOWER CANOPY AND ATTACHED COLUMNS PT2

PT2PT2

PT2 PT2

PT2 PT2 PT2

PT2PT2PT2

PAINT UNDERSIDE OF LOWER CANOPY AND ATTACHED COLUMNS PT2

Architect of Record:

ADG

800 SW ADAMS STREET, SUITE 101

PEORIA, IL 61602

Re vi sio ns

P - 309.672.6948

Discipline:Discipline:Discipline:

P - P - P -

Discipline:

P -

PROJECT NO.

DATE

DRAWN BY

STATUS

Discipline:Discipline: Owner Consultant

QSC SERVICES, LLC

PMB #69

545 BRENT LN. PENSACOLA, FL

P - 309.231.8272

OWNER ID:

Design and Construction Administration Division

ESCAMBIA COUNTY, FL

100 E. BLOUNT ST. PENSACOLA, FL 32501

ESCAMBIA COUNTY AREA TRANSIT - FACILITY:

03 - TRANSFER CENTER

41 CLARINDA LN

PENSACOLA, FL, 32505 X0013D VIEWS AND WALL / ROOF ASSEMBLIES

KEDbluestone 5518 NW 88th Street, JHONSTON, IA 50131

RLG CONSULTING ENGINEERS

12001 N CENTRAL,

DALLAS, TX 75243

RLG CONSULTING ENGINEERS

12001 N CENTRAL,

DALLAS, TX 75243

214.739.8100 214.739.8100 515.727.0700

HODGSON DOUGLAS LANDSCAPE ARCHITECTS

12001 N. CENTRAL EXPRESSWAY, SUITE 1170

DALLAS, TX 75243

214.749.0333

BID PACKAGE #2 - NOT FOR CONSTRUCTION

11/12/2026 Author

1 3D VIEW, ROOF AND EXTERIOR WALL ASSEMBLIES

2 3D VIEW, ROOF AND EXTERIOR WALL ASSEMBLIES

WT1

AD

D

.1

1.

RT1

WT2

WT3

RT2

1/8" = 1'-0"

9 REFLECTED CEILING PLAN

EB1 ECHELON MASONRY - STANDARD MASONRY - TRENWYTH HIGH POLISH

GROUND FACE BRICK - SIZE: 8" X 12" X 16" - COLOR: 5108 (DARK)

EB2 ECHELON MASONRY - STANDARD MASONRY - TRENWYTH HIGH POLISH

GROUND FACE BRICK - SIZE: 8" X 12" X 16" - COLOR: 5301 (LIGHT)

EB3 ECHELON MASONRY - STANDARD MASONRY - TRENWYTH HIGH POLISH

GROUND FACE BRICK - SIZE: 8" X 8" X 16" - COLOR: 5301 (LIGHT)

EB4 ECHELON MASONRY - STANDARD MASONRY - TRENWYTH HIGH POLISH

GROUND FACE BRICK - SIZE: 8" X 8" X 16" - COLOR: 5301 (DARK)

MP1 MBCI - CONCEALED FASTENING SYSTEM - FW-120-2 PANEL, 24 GAUGE, SMOOTH -

COLOR: BROWNSTONE

MP2 ARMSTRONG WALL & ROOF SYSTEMS - PBU PANEL - COLOR: POLAR WHITE

MT1 SOLOMON COLORS, INC., CONCENTRATED MORTAR - COLOR: 22X TAN

PT2 SHERWIN WILLIAMS - COLOR: QUIETUDE SW6212

PRIME: MACROPOXY 646 FC, 5-10 MILS DFT - TOPCOAT: ACROLON ULTRA, 2-3 MILS DFT

PT3 SHERWIN WILLIAMS - SURF GREEN SW6473

PRIME: MACROPOXY 646 FC, 5-10 MILS DFT - TOPCOAT: ACROLON ULTRA, 2-3 MILS DFT

EXTERIOR FINISH SCHEDULE

ADD

ADD

ADD

NOTE: A 20-YEAR NDL

MEMBRANE WARRANTY IS NOT

REQUIRED AT THIS ROOF TYPE

A

B

4 5 6 7 8 9321

FACE OF FDN TO FACE OF FDN

34' - 8" 12' - 0"

FACE OF FDN TO FACE OF FDN

24' - 0"

FACE OF FDN TO FACE OF FDN

10' - 8"

5'

8"

FA

CE

O

F

FD

N T

O F

AC

E

O F

FD

N

FA

CE

O F

FD

N

T O

F

AC

E O

F

FD

N 2'

8"

FA

CE

O F

FD

N

T O

F

AC

E O

F

FD

N

FA

CE

O F

FD

N

T O

F

AC

E O

F

FD

N 2'

8"

12' - 0"

FACE OF FDN TO FACE OF FDN

72' - 0"

FACE OF FDN TO FACE OF FDN

28' - 0"

FACE OF FDN TO FACE OF FDN

18' - 8"

FACE OF FDN TO FACE OF FDN

25' - 4"

5'

8"

FA

CE

O

F

FD

N T

O F

AC

E

O F

FD

N

FA

CE

O F

FD

N

T O

F

AC

E O

F

FD

N 1'

4"

FA

CE

O F

FD

N

T O

F

AC

E O

F

FD

N

FA

CE

O

F

FD

N T

O F

AC

E

O F

FD

N

1'

4"

CANOPY ROOF LINES

CANOPY ROOF LINES

CA

N

O

PY

R O

O F

LI

N

ES

CA

N

O

PY

R O

O F

LI

N

ES

32' - 0" 32' - 0" 32' - 0" 32' - 0" 32' - 0" 32' - 0" 32' - 0" 32' - 0"

BASE POINT COORDINATE:

N 538525' 46" E 1105818' 41"

SURVEY POINT COORDINATE:

N 538532' 02" E 1105801' 39"

INTERIOR SLAB ON

GRADE - SEE STRUC

PREFORMED JOINT FILLER W/

SELF LEVELING

POLYURETHANE SEALANT ON

TOP OF PJF

CONTINUOUS FOOTING - SEE

STRUC

FINISHED GRADE - SEE CIVIL

M

IN

0'

1"

ALIGN OUTSIDE FACE OF CMU

WITH FACE OF

FOOTING/FOUNDATION

WT1 WALL TYPE

INTERIOR SLAB ON

GRADE - SEE STRUC

PREFORMED JOINT FILLER W/

SELF LEVELING

POLYURETHANE SEALANT ON

TOP OF PJF

CONTINUOUS FOOTING - SEE

STRUC

FINISHED GRADE - SEE CIVIL

ALIGN OUTSIDE FACE OF CMU

WITH FACE OF

FOOTING/FOUNDATION

WT2 WALL TYPE

J-CHANNEL

PREFINISHED BASE FLASHING -

SEAL TOP EDGE WITH

TERMINATION BAR &

SEALANT AT TOP OF TERM

M

IN

0'

1"

Architect of Record:

ADG

800 SW ADAMS STREET, SUITE 101

PEORIA, IL 61602

Re vi sio ns

P - 309.672.6948

Discipline:Discipline:Discipline:

P - P - P -

Discipline:

P -

PROJECT NO.

DATE

DRAWN BY

STATUS

Discipline:Discipline: Owner Consultant

QSC SERVICES, LLC

PMB #69

545 BRENT LN. PENSACOLA, FL

P - 309.231.8272

OWNER ID:

Design and Construction Administration Division

ESCAMBIA COUNTY, FL

100 E. BLOUNT ST. PENSACOLA, FL 32501

ESCAMBIA COUNTY AREA TRANSIT - FACILITY:

03 - TRANSFER CENTER

41 CLARINDA LN

PENSACOLA, FL, 32505 X002LAYOUT PLAN

KEDbluestone 5518 NW 88th Street, JHONSTON, IA 50131

RLG CONSULTING ENGINEERS

12001 N CENTRAL,

DALLAS, TX 75243

RLG CONSULTING ENGINEERS

12001 N CENTRAL,

DALLAS, TX 75243

214.739.8100 214.739.8100 515.727.0700

HODGSON DOUGLAS LANDSCAPE ARCHITECTS

12001 N. CENTRAL EXPRESSWAY, SUITE 1170

DALLAS, TX 75243

214.749.0333

BID PACKAGE #2 - NOT FOR CONSTRUCTION

11/12/2026 Author

1/8" = 1'-0"

1 FIRST FLOOR LAYOUT PLAN

AD

D

.1

1.

N

1 1/2" = 1'-0"

2 TYP FOUNDATION DETAIL AT WT1

1 1/2" = 1'-0"

3 TYP FOUNDATION DETAIL AT WT2

T.O. SLAB BLDG 2

0' - 0"

4 5 6 7 8 9

T.O. PARAPET BLDG 2

12' - 0"

T.O. PARAPET BLDG 2

12' - 0"

PREFINISHED 8'' x 8'' METAL GUTTERS AND 4'' x 5'' DOWNSPOUTS.

PREFINISHED 8'' x 8'' METAL GUTTERS AND 4'' x 5'' DOWNSPOUTS.

PREFINISHED 8'' x 8'' METAL GUTTERS AND 4'' x 5'' DOWNSPOUTS.

4' - 0" R.O.

GL1

AL1

+14' - 9 1/2"

+12' - 0"

4'

0" R

.O

4' - 0" R.O.

TW

111113

100C

3' - 4" R.O.

3' - 4" R.O. 3' - 4" R.O.

5'

4" R

.O

GL2

A900

X200

T.O. SLAB BLDG 1

1' - 5 1/2"2'

8"

T.O. SLAB BLDG 2

0' - 0"

T.O. PARAPET BLDG 1

14' - 9 1/2"

T.O. LOW CANOPY

18' - 0 1/2"

T.O. HIGH CANOPY

26' - 8"

456789

T.O. PARAPET BLDG 2

12' - 0"

3 2 1

PREFINISHED 8'' x 8'' METAL GUTTERS AND 4'' x 5'' DOWNSPOUTS.

PREFINISHED 8'' x 8'' METAL GUTTERS AND 4'' x 5'' DOWNSPOUTS.

1/2" / 12"

1/2" / 12"

1/2" / 12"

32' - 0" 32' - 0" 32' - 0" 32' - 0" 32' - 0" 32' - 0" 32' - 0" 32' - 0" 0' - 5"

4' - 0" R.O.

5'

4" R

.O

GL1

AL1

PREFINISHED 8'' x 8'' METAL GUTTERS AND 4'' x 5'' DOWNSPOUTS.

3' - 4" R.O. 4' - 0" R.O.

TW

100A

110 112

3' - 4" R.O.3' - 4" R.O.

GL2

A900

T.O. SLAB BLDG 1

1' - 5 1/2"

7/ 8"

6'

4"

4'

0" R

.O

2'

8"

A B

T.O. PARAPET BLDG 2

12' - 0"

PREFINISHED 8'' x 8'' METAL GUTTERS AND 4'' x 5'' DOWNSPOUTS.

X200

X200

X200

X200

X200

T.O. SLAB BLDG 1

1' - 5 1/2"

T.O. PARAPET BLDG 1

14' - 9 1/2"

AB

T.O. PARAPET BLDG 2

12' - 0"

PREFINISHED 8'' x 8'' METAL GUTTERS AND 4'' x 5'' DOWNSPOUTS.

4' - 0" R.O. 4' - 0" R.O.

5'

8" R

.O

AL1 AL1

GL1 GL1

X200

X200

X200

X112

X200

X200

T.O. SLAB BLDG 1

1' - 5 1/2" T.O. SLAB BLDG 2

0' - 0"

AB

T.O. PARAPET BLDG 2

12' - 0"

X200

X200

T.O. PARAPET BLDG 1

14' - 9 1/2"

A B

TW TW

4' - 0" R.O.

4' - 0" R.O.

10' - 8"

X200

X200

X200

X112

GL2 GL2

X200

T.O. SLAB BLDG 1

1' - 5 1/2"

4'

0" R

.O

GLAZING SCHEDULE

GL1 1" CLEAR INSULATED

GL5 BULLETPROOF GLAZING

ADD

GENERAL ELEVATION NOTES

1.

2.

3.

4.

SEE X001 FOR EXTERIOR WALL TYPE ASSEMBLIES

SEE A900 FOR DOOR DETAILS

SEE X112 FOR WINDOW DETAILS

TICKET WINDOWS: READY ACCESS 4' x 4' TICKET

WINDOW WITH BULLET PROOF GLASS AND DEAL

TRAY

EXT WINDOW SCHEDULE

Architect of Record:

ADG

800 SW ADAMS STREET, SUITE 101

PEORIA, IL 61602

Re vi sio ns

P - 309.672.6948

PROJECT NO.

DATE

DRAWN BY

STATUS

Discipline:Discipline: Owner Consultant

QSC SERVICES, LLC

PMB #69

545 BRENT LN. PENSACOLA, FL

P - 309.231.8272

OWNER ID:

Design and Construction Administration Division

ESCAMBIA COUNTY, FL

100 E. BLOUNT ST. PENSACOLA, FL 32501

ESCAMBIA COUNTY AREA TRANSIT - FACILITY:

03 - TRANSFER CENTER

41 CLARINDA LN

PENSACOLA, FL, 32505 X300EXTERIOR ELEVATIONS

BID PACKAGE #2 - NOT FOR CONSTRUCTION

11/12/2026 Author

1/8" = 1'-0"

6 SOUTH ELEVATION

1/8" = 1'-0"

5 NORTH ELEVATION

1/8" = 1'-0"

1 WEST ELEVATION PUBLIC RESTROOM

1/8" = 1'-0"

2 EAST ELEVATION TICKET BUILDING

1/8" = 1'-0"

3 EAST ELEVATION PUBLIC RESTROOM

1/8" = 1'-0"

4 WEST ELEVATION TICKET BUILDING

AD

D

.1

1.

7 NORTHEAST AERIAL VIEW 8 SOUTHWEST AERIAL VIEW

TYPE MANUFACTURER MODEL NOTES

AL1 KAWNEER IR501T IMPACT STOREFRONT

TW READY ACCESS EXTERIOR TICKET WINDOW

WITH BULLETPROOF GLASS

AND DEAL TRAY

PROVIDE FACTORY-FABRICATED TRANSACTION WINDOW

ASSEMBLY, INCLUDING FRAMING, GLAZING, TRANSACTION

HARDWARE, AND ACCESSORIES. ASSEMBLY SHALL BE

DESIGNED FOR PROJECT-SPECIFIC ASCE 7-22 COMPONENT AND

CLADDING PRESSURES INDICATED ON THE DRAWINGS FOR

VULT = 154 MPH, EXPOSURE C, RISK CATEGORY II. ASSEMBLY

SHALL COMPLY WITH WIND-BORNE DEBRIS REGION

REQUIREMENTS AND BE TESTED IN ACCORDANCE WITH ASTM

E1886 AND ASTM E1996. PROVIDE COMPLETE ASSEMBLY WITH

UL 752 LEVEL 3 BALLISTIC RESISTANCE. THERMALLY BROKEN

FRAMING AND GLAZING SHALL PROVIDE NFRC-CERTIFIED

THERMAL PERFORMANCE OF U-FACTOR ≤ 0.50 AND SHGC ≤

0.25 FOR SOUTH/EAST/WEST EXPOSURES OR ≤ 0.33 FOR

NORTH EXPOSURES. SUBMIT STRUCTURAL, IMPACT, BALLISTIC,

AND THERMAL PERFORMANCE DOCUMENTATION SIGNED AND

SEALED AS REQUIRED BY THE AUTHORITY HAVING

JURISDICTION.

ADD

T.O. PARAPET BLDG 1

14' - 9 1/2"

L.O. HIGH CANOPY

22' - 0"

7 8

100A

T.O. SLAB BLDG 1

1' - 5 1/2"

T.O. SLAB BLDG 2

0' - 0"

T.O. PARAPET BLDG 2

12' - 0"

112 110

186 SF

MEN RESTROOM

39 SF

JANITOR

T.O. PARAPET BLDG 1

14' - 9 1/2"

A B

L.O. HIGH CANOPY

22' - 0"

T.O. PARAPET BLDG 2

12' - 0"

T.O. SLAB BLDG 1

1' - 5 1/2"

A600

T.O. SLAB BLDG 2

0' - 0"

A B

T.O. PARAPET BLDG 2

12' - 0"

BABY CHANGING STATION BABY CHANGING STATION

186 SF

MEN RESTROOM

186 SF

WOMEN RESTROOM

030201

4'

0" 4'

0"

005006 004

3'

0"

F 0' - 6"

2'

6" 1'

8"

2'

36B

07 05

2412001 008

33M 2' - 9"

30B 2' - 6"

42SB

3' - 6"

18DB

1' - 6"

F 0' - 5"

2' - 6" 3' - 6"

1' - 9"

F 0' - 3"

11 11

1'

7' - 3 1/4" 5' - 4 1/4" 7' - 6 7/8"

1' - 4 1/4"

3' - 0"

2'

0" 1'

0"

2'

1"

1'

ADA TOILET

ADA TOILET

A600

06 05

07 07

1'

0"

1' - 4"

3' - 0"

1' - 6"

0'

7"

A6007

BREAK ROOM

5'

9"

24' - 4 3/8"

/8

A600

A600

1'

0" 2'

0"

1' - 6" 1' - 6" 2' - 6"

2' - 7 3/8"

5' - 0" 0' - 1" 3' - 0" 0' - 1" 3' - 0" 0' - 1"

16' - 0 3/8"

9'

3/

8" 6'

3/ 8"

WOMEN RESTROOM

MEN RESTROOM

05 07

04 04 11 05 11 07

3'

0" 2'

0"

1'

0"

2' - 7 3/8"

1'

4"

11 11

HUNG PHENOLIC-CORE TOILET

PARTITIONS. IN SECOND FLOOR,

REFER TO STRUCTURAL DETAIL

DUPLEX RECEPTACLE

QUAD RECEPTACLE

LIGHT SWITCH

OXYGEN OUTLET

VACUUM OUTLET

MED AIR OUTLET

NITROUS OXIDE OUTLET

BOTTLE SLIDE

TELEPHONE / DATA OUTLET

WALL TELEPHONE OUTLET

NURSE CALL

V

A

N

BS

W

LS

NC

SYMBOLS LEGEND

2" TYP.

4'-0'' A.F.F. MAX

PAPER TOWEL

DISPENSER

DOOR

SIGNAGE

SOAP

DISPENSER

TOWEL

BAR

3'-6'' A.F.F. TYP

SANITARY

DISPOSAL UNIT

SINK &

MIRROR

SWITCH COAT

HOOK

CL

3'-4'' A.F.F. MAX

CL

GRAB

BARS

ACCESSIBLE

WATER CLOSET

1'-3'' A.F.F. MIN

TOILET PAPER

DISPENSER

2'-10'' A.F.F. MAX

M

IN

1'

6"CL

EA

R

2'

5"

1'-5" TYP.

16" -18"

" T

YP

. T

O T

/O S

EA

T

8" TYP.

7"-9" at highest operable control

2'-4" A.F.F. TYP

ADA GUIDELINES - TYPICAL MOUNTING HEIGHTS

3' - 4"

1' - 0"

MIRROR DIM. IS TO BOTTOM

OF REFLECTIVE SURFACE

1' - 0"

36" GRAB BAR

42" GRAB BAR

18-24" GRAB BAR

COVER/INSULATE

EXPOSED PIPING

HI

GH

ES

T

RA

IS

ED

C

HA

RA

CT

ER

" T

YP

O R

-6

0" T

O

3'-0'' A.F.F. MAX

3'-5'' A.F.F. MAX

0' - 6" MAX.

PAPER TOWEL

& TRASH UNIT

CHANGING

STATION

T/ O

W O

RK

S

U

RF

AC

E

" A

.F .F

. T O

1'

0" 1'

0"

1'

0" 1'

0"

1'

0" 1'

0"

1'

0" 1'

0"

1'

0"

0' - 0 3/8" 2' - 0" 0' - 0 3/8"

2' - 0 3/4"

4'

0" 4'

0"

1'

0" 1'

3/ 8"

1'

1/

2"

0'

3"

0' - 2 5/8" 0' - 0 3/8"

PL 3/8" X 2 1/2"

PL 3/8"

0'

1/

4"

0' - 3"

1/2" ø 4 1/2"

LAG SCREW

LOCATION OF THE ROOF LADDER FROM THE CORNER STUD

4' - 3 1/4"

0'

7/

8" 0'

3/ 8"

2X WOOD BLOCKING AT

FASTENER LOCATION

0' - 3" 2' - 0 3/4" 0' - 3"

PL 3/8" X 2 1/2"

PL 3/8"

STRUCTURAL SCREWS

THROUGH WOOD BLOCKING

3/4" ROD TYP

0'

7"

0301 02

3'

0" xxxxxxxx xxxxxxxx

STAFF SIDE PUBLIC SIDE

xxxxxxxx xxxxxxxx

TW

xxxxxxxx xxxxxxxx xxxxxxxx xxxxxxxx

Architect of Record:

ADG

800 SW ADAMS STREET, SUITE 101

PEORIA, IL 61602

Re vi sio ns

P - 309.672.6948

Discipline:Discipline:Discipline:

P - P - P -

Discipline:

P -

PROJECT NO.

DATE

DRAWN BY

STATUS

Discipline:Discipline: Owner Consultant

QSC SERVICES, LLC

PMB #69

545 BRENT LN. PENSACOLA, FL

P - 309.231.8272

OWNER ID:

Design and Construction Administration Division

ESCAMBIA COUNTY, FL

100 E. BLOUNT ST. PENSACOLA, FL 32501

ESCAMBIA COUNTY AREA TRANSIT - FACILITY:

03 - TRANSFER CENTER

41 CLARINDA LN

PENSACOLA, FL, 32505 A600LARGE SCALE PLANS

KEDbluestone 5518 NW 88th Street, JHONSTON, IA 50131

RLG CONSULTING ENGINEERS

12001 N CENTRAL,

DALLAS, TX 75243

RLG CONSULTING ENGINEERS

12001 N CENTRAL,

DALLAS, TX 75243

214.739.8100 214.739.8100 515.727.0700

HODGSON DOUGLAS LANDSCAPE ARCHITECTS

12001 N. CENTRAL EXPRESSWAY, SUITE 1170

DALLAS, TX 75243

214.749.0333

BID PACKAGE #2 - NOT FOR CONSTRUCTION

11/12/2026 Author

1/4" = 1'-0"

2 TRANSFER CENTER BLDG SECTION - A

1/4" = 1'-0"

1 TRANSFER CENTER BLDG SECTION B

1/4" = 1'-0"

4 TRANSFER CENTER BLDG SECTION - A1

1/4" = 1'-0"

3 TRANSFER CENTER BLDG SECTION B1

1/4" = 1'-0"

12 PUBLIC RESTROOM - ENLARGED

1/4" = 1'-0"

11 BREAK ROOM - ENLARGED 1/4" = 1'-0"

10 ADA TOILET - ENLARGED

1/4" = 1'-0"

8 MEN RESTROOM ELEV.

1/4" = 1'-0"

9 WOMEN RESTROOM ELEV.

1/4" = 1'-0"

5 ADA TOILET - ELEVATION A

1/4" = 1'-0"

6 BREAKROOM - N. ELEVATION

1/4" = 1'-0"

7 BREAKROOM - W. ELEVATION

AD

D

.1

1.

3/8" = 1'-0"

13 TYPICAL ADA DETAILS & EQUIPMENT MOUNTING HEIGHTS

SEE TYPICAL ADA DETAILS & EQUIPMENT MOUNTING HEIGHTS FOR MOUNTING

HEIGHTS

TOILET ACCESSORY SCHEDULE

MARK DESCRIPTION

01 36" HORIZONTAL GRAB BAR

02 42" HORIZONTAL GRAB BAR

03 18" VERTICAL GRAB BAR

04 TOILET PAPER DISPENSER

05 SOAP DISPENSER

06 SANITARY DISPOSAL UNIT

07 PAPER TOWEL DISPENSER

08 CHANGING STATION

10 Mirror - Frameless - LED Backlight - Plate Glass - Frosted - 36"W X 48"H (0640-4836)

11 Mirror - Stainless Steel Frame - Vandal Proof - 24"W X 36"H

3/4" = 1'-0"

14 JANITOR LADDER

3" = 1'-0"

15 JANITOR LADDER PLATE DETAIL

1" = 1'-0"

17 JANITOR LADDER PLAN

DT1 - MILESTONE TILE - NET-ZERO COLLECTION -

COLOR: IVORY - SIZE: 12"X24" - BRICK INSTALLATION

PATTERN - BRUSHED STAINLESS STEEL L-SHAPE TILE

TRIM ALONG UNFINISHED EDGES. (4'-00" HEIGTH)

PT2 - SHERWIN WILLIAMS - SATIN FINISH

QUIETUDE SW6212 (ACCENT).

1/4" = 1'-0"

18 ADA TOILET ELEV. B

EXPOSED CMU PAINTED WITH PT2 -

SHERWIN WILLIAMS - SATIN FINISH

QUIETUDE SW6212 (ACCENT).

1/4" = 1'-0"

19 BREAKROOM - S. ELEVATION

EXPOSED CMU PAINTED WITH PT-2 -

SHERWIN WILLIAMS - SATIN FINISH

QUIETUDE SW6212 (ACCENT).

DT2 - 23 FULL ROWS, 1/8" GROUT LINE (GT2) -

ALIGN GROUT LINE WITH CENTER OF FAUCET -

BRUSHED STAINLESS STEEL L-SHAPED TILE TRIM

ON UNFINISHED EDGES.

25" DEEP SOLID SURFACE (SSM2) MATERIAL

W/ 4" BACKSPLASH.

42" STAINLESS STEEL DOUBLE BOWL

DROP-IN SINK.

ALL BASE AND WALL CABINETS, PL2

25" DEEP SOLID SURFACE (SSM2) MATERIAL

W/ 4" BACKSPLASH - WORK SURFACE SUPPORT

@ 2'-10" MAX.

PT-2 - SHERWIN WILLIAMS - SATIN FINISH

QUIETUDE SW6212 (ACCENT).

24" DEEP PARTICLE BOARD COUNTER

TOP WITH PLASTIC LAMINATE (PL1) -

WORK SURFACE SUPPORT @3'00" MAX.

CASEWORK LEGEND

B BASE

DB DRAWER BASE

TB TRASH BASE

SB SINK BASE

TM TALL MICROWAVE

1/2" = 1'-0"

20 TRANSFER CENTER BLDG - TICKET WINDOW COUNTER

ADD

ADD

ADD

ADD

ADD

DO

O

R

SI

ZE

DOOR SIZE

FFT1

aa a

DOOR SIZE

DO

O

R

SI

ZE

HOLLOW METAL FRAME FLUSH

FT2

aa b

DOOR SIZE

DO

O

R

SI

ZE

HOLLOW METAL FRAME

0' - 2"

7/

8"

O

VE

RA

LL

W

AL

L

DE

PT

H

HOLLOW METAL

FRAME SECTION

a

0' - 4"

7/

8"

O

VE

RA

LL

W

AL

L

DE

PT

H

HOLLOW METAL

FRAME SECTION

b

HM HOLLOW METAL

F FLUSH

ABBREVIATIONS

GENERAL DOOR SCHEDULE NOTES

1.

2.

SEE A115 FOR FINISHES

SEE X300 FOR EXTERIOR ELEVATIONS

GLAZING SCHEDULE

GL1 1" INSULATED GLAZING UNIT

GL2 NOT USED

GL3 NOT USED

GL4 1/4" TEMPERED

MINIMUM (4) ANCHORS PER

JAMB

(2) 18 GAUGE STEEL STUDS, EXTEND

AND SECURE TO METAL

DECK ABOVE

CAULK

16 GAUGE HOLLOW

METAL FRAME

FOR WALL TYPE, SEE

X001

COILING DOOR MOUNTED

TO BACKSIDE OF WALL

ABOVE / BOTTOM OF BEAM

COILING DOOR JAMB BY MFR,

W/ WEATHERSTRIPPING

ANGLE ORIENTATION AS

SHOWN, TO HIDE FASTENERS

FROM VIEW. ANGLES TO BE

FACTORY PAINTED THE SAME

COLOR AS THE COILING DOOR

CURTAIN

HOLLOW METAL DOOR FRAME -

ALIGN OUTSIDE EDGE OF PRAME

WITH OUTSIDE FACE OF CMU

WALL

SHIM AS REQUIRED

BACKER ROD & SEALANT

BACKER ROD & SEALANT

OUTSIDE

HOLLOW METAL DOOR FRAME.

ALIGN OUTSIDE OF FRAME WITH

FACE OF CMU WALL

SHIM AS REQUIRED

BACKER ROD & SEALANT -

BOTH SIDES

12" CMU LINTEL W/

REINFORECEMT - SEE STRUC. OUTSIDE

AL

IG

N

WT2

HOLLOW METAL DOOR FRAME -

ALIGN OUTSIDE EDGE OF PRAME

WITH OUTSIDE FACE OF CMU

WALL

SHIM AS REQUIRED

BACKER ROD & SEALANT

BACKER ROD & SEALANT

OUTSIDE

NOTES

CARD READER: CR

DOOR CONTACT: DC

REQUEST EXIT (PIR): REXIT-PIR

ELECTRIC STRIKE: ES

LOCKDOWN: LD#

DOOR SWITCH: DS#

Architect of Record:

ADG

800 SW ADAMS STREET, SUITE 101

PEORIA, IL 61602

Re vi sio ns

P - 309.672.6948

Discipline:Discipline:Discipline:

P - P - P -

Discipline:

P -

PROJECT NO.

DATE

DRAWN BY

STATUS

Discipline:Discipline: Owner Consultant

QSC SERVICES, LLC

PMB #69

545 BRENT LN. PENSACOLA, FL

P - 309.231.8272

OWNER ID:

Desig…

This is the start of the file's text. The full file is on GovTribe.