This is a Fire Alarm Inspection and Test Report for the Fridley Groundwater Treatment Facility (Naval Facilities) located at 54 Northern Stacks Drive, Fridley, Minnesota 55421. The inspection was conducted on April 23, 2025, by Nardini Fire Equipment, with Inspector Josh Heller performing the service under Service Ticket No. ST00388326. The facility's fire alarm system received a "Pass" status with a white tag designation, indicating full compliance with inspection requirements.
The inspection covered a Notifier NFS2-640 fire alarm control panel with Class B circuit protection, two sealed lead-acid batteries (55 AH each, dated 05/01/2024) that both passed testing, and a 120V primary power supply with 20-amp circuit breaker protection. All system components passed functional and visual inspections, including two sealed lead-acid backup batteries, charger testing, and ground fault monitoring. The device inspection report documented 21 total devices inspected with zero failures: eight smoke detectors (Notifier FSP-951 model), two manual pull stations (Notifier NBG-12LOB model), two speakers (System Sensor SPRL model), seven speaker/strobes (System Sensor SPSRK model), and two relays to control panel (Notifier model). Emergency communications equipment including audible and visual notification systems, amplifiers, tone generators, and voice clarity all passed inspection. The system is monitored by Wright Hennepin (Account NFE9257) using DART transmission equipment, with all alarm signals, restores, trouble signals, and trouble restores confirmed as received. No deficiencies were identified, and both building management and the monitoring agency were notified of test completion on 4/23/2025.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
4/23/2025 xx
ZIP
SERVICE DATE:
Report Cover Page
BUILDING
54 Northern Stacks Drive MN
(651) 483-6631
Saint Paul MN 55126
763-572-3566
SERVICE TICKET:
STREET CITY STATE
405 County Road E W
Fridley Groundwater Trtmt Fac--naval Facilities
55421
Nardini Fire Equipment
PHONEBUILDING CONTACT
Fridley
ST00388326
System Status: Pass Tag Color: White
Please see the attached reports. If there are any questions, please reach out to the above office.
Download your Report at:
Signed Signed
Inspector: Building Contact:
Title:
4/23/2025 4/23/2025
Josh Heller xx https://customer.nardinifire.com
Service Ticket No. :ST00388326
0001436942
Equipment Location :
Frequency :
: 5542155421
Inspection Contract No. :
Phone
1133178
763-572-3566
54 Northern Stacks Drive
State
Address :
763-572-3566
Phone
State
Address
By entry door
Fridley Groundwater Trtmt Fac--navalOwner
Fire Alarm Inspection
Fridley Groundwater Trtmt Fac--naval
Zip
54 Northern Stacks Drive Property :
ST00388326
Fridley FridleyCity
Date :
Service Ticket No. :
4/23/2025
MN
Zip
MN
City
Annual
PO No. :
FIRE ALARM INSPECTION SUMMARY
8Smoke Detector: Manual Pull Station: 2
2Relay to Control Panel: Speaker: 2
7Speaker / Strobe:
None found at time of inspection.
DEFICIENCIES
SYSTEM DETAILS
Fire Alarm Control Panel Details Inspection Date 04/23/2025
Inspection Start Time 08:00am
Inspection End Time 09:00am
Panel Manufacturer Notifier
Panel Model NFS2-640
Circuit Class B
Over Current Type Circuit Breaker
Software/ Firmware Revision 27
Facp Battery Battery #1 Condition Pass
Battery #1 AH Rating 55
Battery #1 Type Sealed Lead-Acid
Battery #1 Date 05/01/2024
**Battery #1 Test Results Pass
Battery #2 Condition Pass
Battery #2 AH Rating 55
Battery #2 Type Sealed Lead-Acid
• 405 County Road E W • Saint Paul MN • 55126
Fire Alarm Inspection & Test Page 2 of 6
Battery #2 Date 05/01/2024
Battery #2 Test Results Pass
Charger Test Pass
SYSTEM POWER SUPPLY
Primary Normal Volts 120
Control Panel Amps 6
Over Current Type Circuit Breaker
Over Current Amps 20
Panel Location L1
Breaker # 27
SYSTEM TEST AND INSPECTIONS
Control Panel (FACP) Specify type of inspection Functional
Interface Equipment Specify type of inspection Visual
Lamps / Led Specify type of inspection Functional
Fuses Specify type of inspection Visual
Primary Power Supply Specify type of inspection Functional
Trouble Signals Specify type of inspection Functional
Disconnect Switches Specify type of inspection N/A
Ground Fault Monitoring Specify type of inspection Functional
Transiet Suppressors Specify type of inspection N/A
Remote Annuciators Specify type of inspection N/A
Door Holders Specify type of inspection N/A
Heat Detectors Were heat detectors tested with heat? N/A
FACP BATTERY TEST
Battery #1 AH Rating 55
Fire Alarm Inspection & Test Page 3 of 6
Battery #1 Type Sealed Lead-Acid
**Battery #1 Test Results Pass
Battery #2 AH Rating 55
Battery #2 Type Sealed Lead-Acid
**Battery #2 Test Results Pass
**Charger Test Pass
EMERG. COMM. EQUIP / NOTIFICATION APP.
System Performance **Visual Pass
**Functional Pass
Audible **Visual Pass
**Functional Pass
Visual **Visual Pass
**Functional Pass
Speakers **Visual Pass
**Functional Pass
Phone Set **Visual N/A
**Functional N/A
Phone Jack **Visual N/A
**Functional N/A
Off Hook Indicator **Visual N/A
**Functional N/A
Amplifiers **Visual Pass
**Functional Pass
Tone Generators **Visual Pass
**Functional Pass
Call In Signal **Visual N/A
**Functional N/A
Voice Clarity **Visual Pass
**Functional Pass
Fireman Phone
Fire Alarm Inspection & Test Page 4 of 6
**Visual N/A
**Functional N/A
Was dBA meter utilized? No
MONITORING & NOTIFICATION
On/off Premises Monitoring Panel Condition Normal On Arrival? Yes
Time Placed On Test 08:00am
Monitoring Agency Name Wright Hennepin
Monitoring Agency Phone # 18008587811
Account Number NFE9257
Account Password See FACP
Transmission Equipment Type DART
Alarm Signal - Received? Yes
Alarm Restore - Received? Yes
Trouble Signal - Received? Yes
Trouble Restored - Received? Yes
Notifications Of Testing Completion Building Management Notified? Yes
Monitoring Agency Notified? Yes
**Are There Any Monitoring Deficiencies To Report? No
Comments
DEVICE INSPECTION REPORT
Device Location
Total Inspected:21
Zone or Address
Pass / Fail
MakeType
Total Passed:21Total Failed:0
Model Sensitivity
Range Sensitivity
Alarm Point
Above Facp L1D101 PassNotifierSmoke Detector FSP-951
Nw Ceiling L1D102 PassNotifierSmoke Detector FSP-951
Bathroom L1D104 PassNotifierSmoke Detector FSP-951
Control Room L1D105 PassNotifierSmoke Detector FSP-951
Electrical Room PassNotifierSmoke Detector FSP-951
Se Ceiling L1D108 PassNotifierSmoke Detector FSP-951
Fire Alarm Inspection & Test Page 5 of 6
Sw Ceiling L1D109 PassNotifierSmoke Detector FSP-951
Nw Ceiling L1D110 PassNotifierSmoke Detector FSP-951
By North Entry Door L1M103 PassNotifier Manual Pull Station
NBG-12LOB
By South Door L1M107 PassNotifier Manual Pull Station
NBG-12LOB
Control Room Pass System Sensor
Speaker SPRL
Bathroom Pass System Sensor
Speaker SPRL
North Wall Pass System Sensor
Speaker / Strobe SPSRK
Outside North Entry Pass System Sensor
Speaker / Strobe SPSRK
Electrical Room Pass System Sensor
Speaker / Strobe SPSRK
South Entry Pass System Sensor
Speaker / Strobe SPSRK
South Wall Pass System Sensor
Speaker / Strobe SPSRK
West Wall Pass System Sensor
Speaker / Strobe SPSRK
Mezzannie Pass System Sensor
Speaker / Strobe SPSRK
Electrical Room L1M101 PassNotifier Relay to Control
Panel
Electrical Room L1M102 PassNotifier Relay to Control
Panel
SIGNATURE
This report was reviewed with: Nardini Fire Equipment xx
DateDate
Signature
4/23/2025
Josh Heller
4/23/2025:
:Technician
Signature
Print Name
Fire Alarm Inspection & Test Page 6 of 6