EV32 NIROP Fridley Site 5 O M
Solicitation number
N4008526R0103
Issued by

About this file

This is a Fire Alarm Inspection and Test Report for the Fridley Groundwater Treatment Facility (Naval Facilities) located at 54 Northern Stacks Drive, Fridley, Minnesota 55421. The inspection was conducted on April 23, 2025, by Nardini Fire Equipment, with Inspector Josh Heller performing the service under Service Ticket No. ST00388326. The facility's fire alarm system received a "Pass" status with a white tag designation, indicating full compliance with inspection requirements.

The inspection covered a Notifier NFS2-640 fire alarm control panel with Class B circuit protection, two sealed lead-acid batteries (55 AH each, dated 05/01/2024) that both passed testing, and a 120V primary power supply with 20-amp circuit breaker protection. All system components passed functional and visual inspections, including two sealed lead-acid backup batteries, charger testing, and ground fault monitoring. The device inspection report documented 21 total devices inspected with zero failures: eight smoke detectors (Notifier FSP-951 model), two manual pull stations (Notifier NBG-12LOB model), two speakers (System Sensor SPRL model), seven speaker/strobes (System Sensor SPSRK model), and two relays to control panel (Notifier model). Emergency communications equipment including audible and visual notification systems, amplifiers, tone generators, and voice clarity all passed inspection. The system is monitored by Wright Hennepin (Account NFE9257) using DART transmission equipment, with all alarm signals, restores, trouble signals, and trouble restores confirmed as received. No deficiencies were identified, and both building management and the monitoring agency were notified of test completion on 4/23/2025.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

4/23/2025 xx

ZIP

SERVICE DATE:

Report Cover Page

BUILDING

54 Northern Stacks Drive MN

(651) 483-6631

Saint Paul MN 55126

763-572-3566

SERVICE TICKET:

STREET CITY STATE

405 County Road E W

Fridley Groundwater Trtmt Fac--naval Facilities

55421

Nardini Fire Equipment

PHONEBUILDING CONTACT

Fridley

ST00388326

System Status: Pass Tag Color: White

Please see the attached reports. If there are any questions, please reach out to the above office.

Download your Report at:

Signed Signed

Inspector: Building Contact:

Title:

4/23/2025 4/23/2025

Josh Heller xx https://customer.nardinifire.com

Service Ticket No. :ST00388326

0001436942

Equipment Location :

Frequency :

: 5542155421

Inspection Contract No. :

Phone

1133178

763-572-3566

54 Northern Stacks Drive

State

Address :

763-572-3566

Phone

State

Address

By entry door

Fridley Groundwater Trtmt Fac--navalOwner

Fire Alarm Inspection

Fridley Groundwater Trtmt Fac--naval

Zip

54 Northern Stacks Drive Property :

ST00388326

Fridley FridleyCity

Date :

Service Ticket No. :

4/23/2025

MN

Zip

MN

City

Annual

PO No. :

FIRE ALARM INSPECTION SUMMARY

8Smoke Detector: Manual Pull Station: 2

2Relay to Control Panel: Speaker: 2

7Speaker / Strobe:

None found at time of inspection.

DEFICIENCIES

SYSTEM DETAILS

Fire Alarm Control Panel Details Inspection Date 04/23/2025

Inspection Start Time 08:00am

Inspection End Time 09:00am

Panel Manufacturer Notifier

Panel Model NFS2-640

Circuit Class B

Over Current Type Circuit Breaker

Software/ Firmware Revision 27

Facp Battery Battery #1 Condition Pass

Battery #1 AH Rating 55

Battery #1 Type Sealed Lead-Acid

Battery #1 Date 05/01/2024

**Battery #1 Test Results Pass

Battery #2 Condition Pass

Battery #2 AH Rating 55

Battery #2 Type Sealed Lead-Acid

• 405 County Road E W • Saint Paul MN • 55126

Fire Alarm Inspection & Test Page 2 of 6

Battery #2 Date 05/01/2024

Battery #2 Test Results Pass

Charger Test Pass

SYSTEM POWER SUPPLY

Primary Normal Volts 120

Control Panel Amps 6

Over Current Type Circuit Breaker

Over Current Amps 20

Panel Location L1

Breaker # 27

SYSTEM TEST AND INSPECTIONS

Control Panel (FACP) Specify type of inspection Functional

Interface Equipment Specify type of inspection Visual

Lamps / Led Specify type of inspection Functional

Fuses Specify type of inspection Visual

Primary Power Supply Specify type of inspection Functional

Trouble Signals Specify type of inspection Functional

Disconnect Switches Specify type of inspection N/A

Ground Fault Monitoring Specify type of inspection Functional

Transiet Suppressors Specify type of inspection N/A

Remote Annuciators Specify type of inspection N/A

Door Holders Specify type of inspection N/A

Heat Detectors Were heat detectors tested with heat? N/A

FACP BATTERY TEST

Battery #1 AH Rating 55

Fire Alarm Inspection & Test Page 3 of 6

Battery #1 Type Sealed Lead-Acid

**Battery #1 Test Results Pass

Battery #2 AH Rating 55

Battery #2 Type Sealed Lead-Acid

**Battery #2 Test Results Pass

**Charger Test Pass

EMERG. COMM. EQUIP / NOTIFICATION APP.

System Performance **Visual Pass

**Functional Pass

Audible **Visual Pass

**Functional Pass

Visual **Visual Pass

**Functional Pass

Speakers **Visual Pass

**Functional Pass

Phone Set **Visual N/A

**Functional N/A

Phone Jack **Visual N/A

**Functional N/A

Off Hook Indicator **Visual N/A

**Functional N/A

Amplifiers **Visual Pass

**Functional Pass

Tone Generators **Visual Pass

**Functional Pass

Call In Signal **Visual N/A

**Functional N/A

Voice Clarity **Visual Pass

**Functional Pass

Fireman Phone

Fire Alarm Inspection & Test Page 4 of 6

**Visual N/A

**Functional N/A

Was dBA meter utilized? No

MONITORING & NOTIFICATION

On/off Premises Monitoring Panel Condition Normal On Arrival? Yes

Time Placed On Test 08:00am

Monitoring Agency Name Wright Hennepin

Monitoring Agency Phone # 18008587811

Account Number NFE9257

Account Password See FACP

Transmission Equipment Type DART

Alarm Signal - Received? Yes

Alarm Restore - Received? Yes

Trouble Signal - Received? Yes

Trouble Restored - Received? Yes

Notifications Of Testing Completion Building Management Notified? Yes

Monitoring Agency Notified? Yes

**Are There Any Monitoring Deficiencies To Report? No

Comments

DEVICE INSPECTION REPORT

Device Location

Total Inspected:21

Zone or Address

Pass / Fail

MakeType

Total Passed:21Total Failed:0

Model Sensitivity

Range Sensitivity

Alarm Point

Above Facp L1D101 PassNotifierSmoke Detector FSP-951

Nw Ceiling L1D102 PassNotifierSmoke Detector FSP-951

Bathroom L1D104 PassNotifierSmoke Detector FSP-951

Control Room L1D105 PassNotifierSmoke Detector FSP-951

Electrical Room PassNotifierSmoke Detector FSP-951

Se Ceiling L1D108 PassNotifierSmoke Detector FSP-951

Fire Alarm Inspection & Test Page 5 of 6

Sw Ceiling L1D109 PassNotifierSmoke Detector FSP-951

Nw Ceiling L1D110 PassNotifierSmoke Detector FSP-951

By North Entry Door L1M103 PassNotifier Manual Pull Station

NBG-12LOB

By South Door L1M107 PassNotifier Manual Pull Station

NBG-12LOB

Control Room Pass System Sensor

Speaker SPRL

Bathroom Pass System Sensor

Speaker SPRL

North Wall Pass System Sensor

Speaker / Strobe SPSRK

Outside North Entry Pass System Sensor

Speaker / Strobe SPSRK

Electrical Room Pass System Sensor

Speaker / Strobe SPSRK

South Entry Pass System Sensor

Speaker / Strobe SPSRK

South Wall Pass System Sensor

Speaker / Strobe SPSRK

West Wall Pass System Sensor

Speaker / Strobe SPSRK

Mezzannie Pass System Sensor

Speaker / Strobe SPSRK

Electrical Room L1M101 PassNotifier Relay to Control

Panel

Electrical Room L1M102 PassNotifier Relay to Control

Panel

SIGNATURE

This report was reviewed with: Nardini Fire Equipment xx

DateDate

Signature

4/23/2025

Josh Heller

4/23/2025:

:Technician

Signature

Print Name

Fire Alarm Inspection & Test Page 6 of 6