Drawings - Electrical E1.0.pdf
PDF 1 MB Posted
- Solicitation number
- IFB1 IHKA 2017000258 4
- Issued by
- Garfield County, Colorado
About this file
This is an Electrical Site Plan drawing (E1.0) for the SVCLC at Rifle Resident Safety & Accessibility Improvements project located at 851 E. 5th Street, Rifle, Colorado 81650. The project involves the installation of new luminaires at five existing exterior lighting poles set at 20-foot intervals, with new conduit, wiring, and connections extending from existing site lighting poles to new bollards and relocated site lighting poles. The work includes relocating one existing site lighting pole, removing old luminaires and replacing them with new ones, and disconnecting and removing existing power, conduit, and associated wiring as designated for demolition. The electrical system will tie flag pole lighting into existing photo sensor controls for parking lot lighting and maintain existing exterior lighting controls for all new and relocated luminaires. The design document was prepared as 100% Construction Documents dated April 25, 2017, by Boulder Associates, Inc. with a project number of 152732.00.
The drawing specifies detailed pole mounting specifications including reinforced concrete pole bases with #4 vertical rebar, #3 ties at 12-inch on-center spacing, and a 3/4-inch by 10-foot copper clad ground rod with #6 AWG grounding conductor using a Burndy Type YGHR-C Hytail ground rod connector. Pole dimension tables indicate heights ranging from 10 to 35 feet with corresponding base dimensions and above-ground heights. General notes require compliance with state and federal regulations for disposal of fluorescent lamps and ballasts, and all existing work is indicated by lightweight lines while new work appears in dark weighted lines. The engineer's instruments of service remain the property of the engineer, and unauthorized reuse without written permission is prohibited.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E1.1
E1 (TYP. OF 5)
D D
D
D
D
H
ER1
.(RR)
(R)
E E
E
E
E
E2
LP1A-(20,22)
ER2
E3
E4
(2#12 & 1#12G)3/4"C.
HAND HOLE WITH
COVER, 18" FROM
BASE OF POLE
BRANCH CIRCUIT
CONDUIT & WIRE.
RE: SITE PLAN.
3/4" x 10' LONG COPPER
CLAD GROUND ROD
#6 AWG GROUNDING CONDUCTOR
FROM GROUNDING LUG IN POLE
JUNCTION BOX. USE BURNDY
TYPE YGHR-C HYTAIL GROUND
ROD CONNECTOR.
REINFORCED CONCRETE POLE
BASE WITH 4 #4 VERTICAL REBAR,
AND #3 TIES AT 12" ON CENTER.
PROVIDE 3" CONCRETE ABOVE,
BELOW AND AROUND REBAR
ANCHOR BOLT BY POLE
MANUFACTURER (MIN. OF 4)
GROUNDING LUG IN POLE
GROUT POLE BASE
2" CHAMFER
FINISHED GRADE
18" MIN.
BASE/BOLT COVER
A
B
C
D
3"
E
B
5"x5" 5"x5" 5"x5" 5"x5" 6"x6"
SIZE
2'-6"
2'-6" 2'-6" 2'-6"
2'-6'
C
ABOVE GROUND
5'-0"
9'-0" 8'-0" 7'-0"
BELOW
4'-0"
D
2'-0"
3'-0" 3'-0" 2'-0"
2'-0"
DIAMETER
E
POLE
NOTES:
POLE DIMENSION TABLE
HEIGHT
A
15'
30' 25' 20'
10'
BASE
35' 6"x6" 2'-6" 9'-0" 3'-0"
1. WHEN POLE BASE TOP IS AT THE GROUND LEVEL,
BASE DEPTH TO BE EQUAL TO "D" + 2".
2. BASE DIMENSIONS ARE CALCULATED FOR
LUMINAIRE(S) WITH AN EPA OF 6.0.
3. REFER TO FIXTURE SCHEDULE FOR POLE HEIGHT.
OWNERSHIP OF DOCUMENTS:
ALL DRAWINGS, SPECIFICATIONS AND OTHER WORK PRODUCT OF THE ENGINEER FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE FOR THIS PROJECT ONLY AND SHALL REMAIN THE PROPERTY OF THE ENGINEER WHETHER THE PROJECT IS COMPLETED OR NOT. REUSE OF ANY OF THE INSTRUMENTS OF SERVICE OF THE ENGINEER BY THE OWNER OF EXTENSIONS OF THIS PROJECT WITHOUT WRITTEN PERMISSION OF THE ENGINEER SHALL BE AT THE OWNER'S RISK AND THE OWNER AGREES TO DEFEND, INDEMNIFY AND HOLD HARMLESS THE ENGINEER FROM ALL CLAIMS, DAMAGES, AND EXPENSES INCLUDING ATTORNEYS' FEES ARISING OUT OF UNAUTHORIZED REUSE OF THE ENGINEER'S INSTRUMENTS OF SERVICE BY THE OWNER OR BY OTHERS ACTING THROUGH THE OWNER.
PROJECT NUMBER
DRAWN BY
DATE
REVISIONS
SHEET TITLE
SHEET NUMBER
Boulder Associates, Inc.
www.boulderassociates.com
Architecture + Interior Design
1426 Pearl Street, Suite 300
Boulder , Colorado 80302
303.499.7795
PROJECT
REV
T T
L B v .2
T H
IS
L
IN
E
I S
I N
C H
L O
N G
W H
E N
P R
IN
T
E D
T O
F U
L L S
C A
L E
ADDRESS
851 E. 5th STREET
RIFLE, CO 81650
/2
/2
:3 :1
P
M C
U s e rs
\r le d fo rd \D o c u m e n ts
\L o c a l R e v it F ile s \1
S V
N H a t R if le
E le c
R rl e d fo rd .r v t
152732.00
RSL
February 1, 2017
ELECTRICAL SITE
PLAN
E1.0
SVCLC AT RIFLE
RESIDENT
SAFETY &
ACCESSIBILITY
IMPROVEMENTS
100%
CONSTRUCTION
DOCUMENTS
0'8' 4' 8' 16' 32'
1/16" = 1'-0"
ELECTRICAL SITE PLAN
WORK NOTES
E1 PROVIDE NEW LUMINAIRE (TYP. OF 5) TO EACH EXISTING EXTERIOR LIGHTING
POLE @ 20'-0". EACH EXISTING EXTERIOR LIGHTING POLE TO REMAIN UNLESS
NOTED OTHERWISE.
E2 PROVIDE NEW CONDUIT, WIRING, AND CONNECTIONS FROM EXISTING SITE
LIGHTING POLE TO EXTEND TO NEW BOLLARD.
E3 PROVIDE NEW CONDUIT, WIRING, AND CONNECTIONS FROM EXISTING SITE
LIGHTING POLE TO EXTEND TO NEW RELOCATED SITE LIGHTING POLE.
E4 SEE E2.2, FLOOR 2 - WALKWAY REFLECTIVE LIGHTING PLAN FOR DIMMER
SWITCHING LOCATION. CONTRACTOR SHALL TIE FLAG POLE LIGHTING INTO
EXISTING PHOTO SENSOR CONTROLS FOR PARKING LOT LIGHTING.
ER1 RELOCATE EXISTING SITE LIGHTING POLE. VERIFY WITH ARCHITECT FOR EXACT
LOCATION AND FURTHER REQUIREMENTS. REMOVE LUMINAIRE AND PROVIDE
NEW LUMINAIRE. SEE POLE FIXTURE MOUNTING DETAIL THIS SHEET.
ER2 REMOVE CONDUIT, WIRING, AND CONNECTIONS FROM RELOCATED EXISTING
SITE LIGHTING POLE.
NOT TO SCALE
POLE FIXTURE MOUNTING DETAIL
4. MAINTAIN EXISTING EXTERIOR LIGHTING CONTROLS FOR NEW AND RELOCATED
LUMINAIRES.
3. DISPOSE OF ALL FLUORESCENT LAMPS AND BALLASTS IN ACCORDANCE WITH STATE
AND FEDERAL REGULATION.
2. DISCONNECT AND REMOVE ALL EXISTING POWER ALONG WITH ALL ASSOCIATED
CONDUIT AND WIRE IF DASHED AS DEMOLISH, UNLESS SHOWN TO REMAIN.
1. ALL EXISTING WORK IS SHOWN IN LIGHT WEIGHT LINES AND ALL NEW WORK IS
SHOWN IN DARK WEIGHT LINES AND AS NOTED.
GENERAL NOTES
DESCRIPTION DATE
1 C-WEST COMMENTS 03.28.2017
| A0.1 Cover Sheet 2017-04-25 |
| CVCLC Rifle - Civil Set - 04252017 |
| Rifle SVCLC_Landscape_L1.0 |
| Rifle SVCLC_Landscape_L1.1 |
| Architectural Bid Set 2017-04-25 |
| Sheets |
| A0.0 - COVER SHEET |
| D1.1 - DEMO SITE PLAN |
| A1.0 - SITE PLAN |
| A1.1 - PORTE COCHERE - ENLARGED PLAN |
| A1.2 - PORTE COCHERE - ENLARGED PLANS & DETAILS |
| A2.01 - FLOOR 1 - LIFE SAFETY PLAN |
| A2.02 - FLOOR 2 - LIFE SAFETY PLAN |
| A2.1 - FLOOR PLAN - OVERALL - FIRST FLOOR |
| A2.2 - FLOOR PLAN - OVERALL - SECOND FLOOR |
| A3.1 - EXTERIOR ELEVATIONS |
| A4.1 - PORTE COCHERE - DETAILS |
| A6.1 - INTERIOR ELEVATION |
| A8.1 - DOOR & WINDOW TYPES, SCHEDULE & DETAILS |
| A9.1 - FLOOR 1 - REFLECTED CEILING PLAN |
| A9.2 - FLOOR 2 - REFLECTED CEILING PLAN |
| 17794 042517 |
| Sheets |
| S1.1 - PORTE COCHERE - GN & FRAMING |
| S1.2 - PORTE COCHERE - DETAILS |
File details come from the government source that posted it. Updated .