This is an Electrical Site Plan drawing (E1.0) for the SVCLC at Rifle Resident Safety & Accessibility Improvements project located at 851 E. 5th Street, Rifle, Colorado 81650. The project involves the installation of new luminaires at five existing exterior lighting poles set at 20-foot intervals, with new conduit, wiring, and connections extending from existing site lighting poles to new bollards and relocated site lighting poles. The work includes relocating one existing site lighting pole, removing old luminaires and replacing them with new ones, and disconnecting and removing existing power, conduit, and associated wiring as designated for demolition. The electrical system will tie flag pole lighting into existing photo sensor controls for parking lot lighting and maintain existing exterior lighting controls for all new and relocated luminaires. The design document was prepared as 100% Construction Documents dated April 25, 2017, by Boulder Associates, Inc. with a project number of 152732.00.

The drawing specifies detailed pole mounting specifications including reinforced concrete pole bases with #4 vertical rebar, #3 ties at 12-inch on-center spacing, and a 3/4-inch by 10-foot copper clad ground rod with #6 AWG grounding conductor using a Burndy Type YGHR-C Hytail ground rod connector. Pole dimension tables indicate heights ranging from 10 to 35 feet with corresponding base dimensions and above-ground heights. General notes require compliance with state and federal regulations for disposal of fluorescent lamps and ballasts, and all existing work is indicated by lightweight lines while new work appears in dark weighted lines. The engineer's instruments of service remain the property of the engineer, and unauthorized reuse without written permission is prohibited.

View the file

Other files

File Type Posted
Drawings - 5p12-15.pdf PDF
Addendum #1 Narrative 152732.00 .pdf PDF
Addendum #1 - A1.1.pdf PDF
Drawings - 3p5-8.pdf PDF
Drawings - 7p20-23.pdf PDF
Part 1 - Project Manual .pdf PDF
Drawings - 6p16-19.pdf PDF
Part 3 - Project Manual.pdf PDF
Drawings - 4p9-11.pdf PDF
Drawings - Electrical E1.1.pdf PDF
Mandatory Walkthrough List- Rifle.pdf PDF
Addendum #1 -170512_Addendum1_LandscapeDwg_L1.0.pdf PDF
Drawings - Electrical E0 E.2.pdf PDF
Advertisement for Bid-Rifle 2017-04-26.docx DOCX document
Part 4 - Project Manual.pdf PDF
Drawings - 1p1.pdf PDF
Part 2 - Project Manual.pdf PDF
Drawings - Electrical E2.1 E2.2 E3.1.pdf PDF
Drawings - 2p2-4.pdf PDF
Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E1.1

E1 (TYP. OF 5)

D D

D

D

D

H

ER1

.(RR)

(R)

E E

E

E

E

E2

LP1A-(20,22)

ER2

E3

E4

(2#12 & 1#12G)3/4"C.

HAND HOLE WITH

COVER, 18" FROM

BASE OF POLE

BRANCH CIRCUIT

CONDUIT & WIRE.

RE: SITE PLAN.

3/4" x 10' LONG COPPER

CLAD GROUND ROD

#6 AWG GROUNDING CONDUCTOR

FROM GROUNDING LUG IN POLE

JUNCTION BOX. USE BURNDY

TYPE YGHR-C HYTAIL GROUND

ROD CONNECTOR.

REINFORCED CONCRETE POLE

BASE WITH 4 #4 VERTICAL REBAR,

AND #3 TIES AT 12" ON CENTER.

PROVIDE 3" CONCRETE ABOVE,

BELOW AND AROUND REBAR

ANCHOR BOLT BY POLE

MANUFACTURER (MIN. OF 4)

GROUNDING LUG IN POLE

GROUT POLE BASE

2" CHAMFER

FINISHED GRADE

18" MIN.

BASE/BOLT COVER

A

B

C

D

3"

E

B

5"x5" 5"x5" 5"x5" 5"x5" 6"x6"

SIZE

2'-6"

2'-6" 2'-6" 2'-6"

2'-6'

C

ABOVE GROUND

5'-0"

9'-0" 8'-0" 7'-0"

BELOW

4'-0"

D

2'-0"

3'-0" 3'-0" 2'-0"

2'-0"

DIAMETER

E

POLE

NOTES:

POLE DIMENSION TABLE

HEIGHT

A

15'

30' 25' 20'

10'

BASE

35' 6"x6" 2'-6" 9'-0" 3'-0"

1. WHEN POLE BASE TOP IS AT THE GROUND LEVEL,

BASE DEPTH TO BE EQUAL TO "D" + 2".

2. BASE DIMENSIONS ARE CALCULATED FOR

LUMINAIRE(S) WITH AN EPA OF 6.0.

3. REFER TO FIXTURE SCHEDULE FOR POLE HEIGHT.

OWNERSHIP OF DOCUMENTS:

ALL DRAWINGS, SPECIFICATIONS AND OTHER WORK PRODUCT OF THE ENGINEER FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE FOR THIS PROJECT ONLY AND SHALL REMAIN THE PROPERTY OF THE ENGINEER WHETHER THE PROJECT IS COMPLETED OR NOT. REUSE OF ANY OF THE INSTRUMENTS OF SERVICE OF THE ENGINEER BY THE OWNER OF EXTENSIONS OF THIS PROJECT WITHOUT WRITTEN PERMISSION OF THE ENGINEER SHALL BE AT THE OWNER'S RISK AND THE OWNER AGREES TO DEFEND, INDEMNIFY AND HOLD HARMLESS THE ENGINEER FROM ALL CLAIMS, DAMAGES, AND EXPENSES INCLUDING ATTORNEYS' FEES ARISING OUT OF UNAUTHORIZED REUSE OF THE ENGINEER'S INSTRUMENTS OF SERVICE BY THE OWNER OR BY OTHERS ACTING THROUGH THE OWNER.

PROJECT NUMBER

DRAWN BY

DATE

REVISIONS

SHEET TITLE

SHEET NUMBER

Boulder Associates, Inc.

www.boulderassociates.com

Architecture + Interior Design

1426 Pearl Street, Suite 300

Boulder , Colorado 80302

303.499.7795

PROJECT

REV

T T

L B v .2

T H

IS

L

IN

E

I S

I N

C H

L O

N G

W H

E N

P R

IN

T

E D

T O

F U

L L S

C A

L E

ADDRESS

851 E. 5th STREET

RIFLE, CO 81650

/2

/2

:3 :1

P

M C

U s e rs

\r le d fo rd \D o c u m e n ts

\L o c a l R e v it F ile s \1

S V

N H a t R if le

E le c

R rl e d fo rd .r v t

152732.00

RSL

February 1, 2017

ELECTRICAL SITE

PLAN

E1.0

SVCLC AT RIFLE

RESIDENT

SAFETY &

ACCESSIBILITY

IMPROVEMENTS

100%

CONSTRUCTION

DOCUMENTS

0'8' 4' 8' 16' 32'

1/16" = 1'-0"

ELECTRICAL SITE PLAN

WORK NOTES

E1 PROVIDE NEW LUMINAIRE (TYP. OF 5) TO EACH EXISTING EXTERIOR LIGHTING

POLE @ 20'-0". EACH EXISTING EXTERIOR LIGHTING POLE TO REMAIN UNLESS

NOTED OTHERWISE.

E2 PROVIDE NEW CONDUIT, WIRING, AND CONNECTIONS FROM EXISTING SITE

LIGHTING POLE TO EXTEND TO NEW BOLLARD.

E3 PROVIDE NEW CONDUIT, WIRING, AND CONNECTIONS FROM EXISTING SITE

LIGHTING POLE TO EXTEND TO NEW RELOCATED SITE LIGHTING POLE.

E4 SEE E2.2, FLOOR 2 - WALKWAY REFLECTIVE LIGHTING PLAN FOR DIMMER

SWITCHING LOCATION. CONTRACTOR SHALL TIE FLAG POLE LIGHTING INTO

EXISTING PHOTO SENSOR CONTROLS FOR PARKING LOT LIGHTING.

ER1 RELOCATE EXISTING SITE LIGHTING POLE. VERIFY WITH ARCHITECT FOR EXACT

LOCATION AND FURTHER REQUIREMENTS. REMOVE LUMINAIRE AND PROVIDE

NEW LUMINAIRE. SEE POLE FIXTURE MOUNTING DETAIL THIS SHEET.

ER2 REMOVE CONDUIT, WIRING, AND CONNECTIONS FROM RELOCATED EXISTING

SITE LIGHTING POLE.

NOT TO SCALE

POLE FIXTURE MOUNTING DETAIL

4. MAINTAIN EXISTING EXTERIOR LIGHTING CONTROLS FOR NEW AND RELOCATED

LUMINAIRES.

3. DISPOSE OF ALL FLUORESCENT LAMPS AND BALLASTS IN ACCORDANCE WITH STATE

AND FEDERAL REGULATION.

2. DISCONNECT AND REMOVE ALL EXISTING POWER ALONG WITH ALL ASSOCIATED

CONDUIT AND WIRE IF DASHED AS DEMOLISH, UNLESS SHOWN TO REMAIN.

1. ALL EXISTING WORK IS SHOWN IN LIGHT WEIGHT LINES AND ALL NEW WORK IS

SHOWN IN DARK WEIGHT LINES AND AS NOTED.

GENERAL NOTES

DESCRIPTION DATE

1 C-WEST COMMENTS 03.28.2017

A0.1 Cover Sheet 2017-04-25
CVCLC Rifle - Civil Set - 04252017
Rifle SVCLC_Landscape_L1.0
Rifle SVCLC_Landscape_L1.1
Architectural Bid Set 2017-04-25
Sheets
A0.0 - COVER SHEET
D1.1 - DEMO SITE PLAN
A1.0 - SITE PLAN
A1.1 - PORTE COCHERE - ENLARGED PLAN
A1.2 - PORTE COCHERE - ENLARGED PLANS & DETAILS
A2.01 - FLOOR 1 - LIFE SAFETY PLAN
A2.02 - FLOOR 2 - LIFE SAFETY PLAN
A2.1 - FLOOR PLAN - OVERALL - FIRST FLOOR
A2.2 - FLOOR PLAN - OVERALL - SECOND FLOOR
A3.1 - EXTERIOR ELEVATIONS
A4.1 - PORTE COCHERE - DETAILS
A6.1 - INTERIOR ELEVATION
A8.1 - DOOR & WINDOW TYPES, SCHEDULE & DETAILS
A9.1 - FLOOR 1 - REFLECTED CEILING PLAN
A9.2 - FLOOR 2 - REFLECTED CEILING PLAN
17794 042517
Sheets
S1.1 - PORTE COCHERE - GN & FRAMING
S1.2 - PORTE COCHERE - DETAILS

File details come from the government source that posted it. Updated .