Drawings - Electrical E0 E.2.pdf

PDF 351 KB Posted

Attached to
Rifle Vets Living Center-Resident Safety&Accessibility Impro
Solicitation number
IFB1 IHKA 2017000258 4
Issued by
Garfield County, Colorado

About this file

This electrical drawing document is part of construction specifications for the SVCLC at Rifle Resident Safety & Accessibility Improvements project located at 851 E. 5th Street, Rifle, Colorado 81650, prepared by Boulder Associates, Inc. The project involves removing and replacing existing interior lighting with LED fixtures on both floors at corridors and nursing stations (excluding nursing station downlights), adding new LED lighting at the porte cochere, walkway, bollards, and below a new flagpole location, and replacing exterior lighting at site poles with LED units. The electrical work includes installation of conduit systems with pull cords/tape in all conduits, communication cabling that is self-supported and not resting on ceiling tiles, back boxes measuring 4-11/16" square by 2 1/8" deep, and various luminaires specified in the fixture schedule including H.E. Williams LED 2x2 and 2x4 recessed fixtures, Finelite LED pendant fixtures, Hubbell street lighting and bollard fixtures, and Lumascape in-grade flagpole uplights. The construction documents are dated February 1, 2017, with revisions through April 25, 2017, and were prepared by project engineer Ricky Ledford and project manager David Hughes.

The one-line electrical diagram indicates a total load of 2.4 kVA being added to the existing 120/208V, three-phase electrical system, which equates to 7 amps at 208V. The existing facility is supplied by a 2000 kVA pad-mounted transformer with a 200-amp main distribution panel featuring 30 circuits and 99,136 AIC capacity. New panelboards include LP1B (600 VA), LP2A (900 VA), and LP2B (capacity not specified), while loads are distributed across existing panels EL1 (200 VA) and LP1A (1.4 kVA). All existing gear and feeders remain in place with no new equipment or feeders being added; the project scope is limited to lighting fixture replacement and new installations. The electrical contractor is responsible for providing conduit and backboxes, while communications cabling and outlets are supplied by others. New panel directory cards with as-built circuit information must be provided upon project completion.

View the file

Other files

File Type Posted
Drawings - 5p12-15.pdf PDF
Addendum #1 Narrative 152732.00 .pdf PDF
Addendum #1 - A1.1.pdf PDF
Drawings - 3p5-8.pdf PDF
Drawings - 7p20-23.pdf PDF
Part 1 - Project Manual .pdf PDF
Drawings - 6p16-19.pdf PDF
Part 3 - Project Manual.pdf PDF
Drawings - 4p9-11.pdf PDF
Drawings - Electrical E1.1.pdf PDF
Mandatory Walkthrough List- Rifle.pdf PDF
Addendum #1 -170512_Addendum1_LandscapeDwg_L1.0.pdf PDF
Advertisement for Bid-Rifle 2017-04-26.docx DOCX document
Part 4 - Project Manual.pdf PDF
Drawings - 1p1.pdf PDF
Drawings - Electrical E1.0.pdf PDF
Part 2 - Project Manual.pdf PDF
Drawings - Electrical E2.1 E2.2 E3.1.pdf PDF
Drawings - 2p2-4.pdf PDF
Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

J

ROUTE CONDUIT TO CABLE TRAY OR

STUB CONDUIT INTO ACCESSIBLE

CEILING SPACE. PROVIDE BUSHING

AND SWEEP ELBOW. TYPICAL.

ACCESSIBLE CEILING

1 1/4" FLEXIBLE CONDUIT

TO PARTITION

(FURNITURE) RACEWAY

1 1/4"C.1"C.

6" MIN.

NOTES:

1. CONDUIT AND BACKBOXES PROVIDED BY ELECTRICAL

CONTRACTOR. INSTALL PULL CORD/TAPE IN ALL CONDUITS.

2. COMMUNICATION CABLING SHALL BE SELF SUPPORTED. DO

NOT REST ON CEILING TILES, OR CEILING SUSPENSION WIRES.

3. COMMUNICATIONS CABLES AND OUTLETS SUPPLIED BY

OTHERS.

4. ALL BACK BOXES SHALL BE A 4-11/16" SQUARE BY 2 1/8" DEEP.

B

T

D

J P

J C

P

TOP OF EQUIPMENT

TOP OF PANEL

M

IN

TYPICAL 8'-0" CEILING

FLOOR

NOTES:

1. HEIGHTS SHOWN ARE TYPICAL TO CENTERLINE.

2. DEVICES ABOVE DOORS SHALL BE CENTERED.

3. MOUNTING HEIGHTS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL GOVERN

OVER THOSE SHOWN ABOVE.

4. FOR CEILING HEIGHTS HIGHER THAN 7'-2", INSTALL FIRE ALARM NOTIFICATION AUDIO

AND VISUAL APPLIANCES SO THAT BOTTOM OF STROBE LENS NOT LESS THAN 80"

A.F.F., OTHERWISE INSTALL WITHIN 6" BELOW CEILING.

FACP

FAA

FARP

FSCP

FFCP

ASFP

MM

CM

RM

M

V

RTS

A

H

J

P

R

FABP

P

S

FF

VS

WF

PS

AA

FS

CO

CO

B

ABBREVIATIONS AND DESCRIPTIONS

ALL SYMBOLS IN LEGEND MAY NOT NECESSARILY BE USED ON THIS PROJECT

ELECTRICAL LEGEND

LIGHTING

POWER

ONE-LINE DIAGRAMS

SYSTEMS

GROUNDING/LIGHTNING

I

TO

A

A

T1

K KEYLESS FIXTURE

600/100

100/5

TTB

30/3 30A

30/3

POLE MOUNTED FIXTURE

FLUORESCENT STRIP

CEILING FIXTURE

WALL MOUNTED FIXTURE

EXIT SIGN W/ARROW

BATTERY PACK

LANDSCAPE FIXTURE

SINGLE-POLE SWITCH

b

P PHOTOCELL

C

POWER/TELEPHONE POLE

IG

DUPLEX RECEPTACLE

SPECIAL PURPOSE OUTLET

SINGLE RECEPTACLE

L

RACEWAY TURNED DOWN

RACEWAY TURNED UP

TC

B

S

R

T

BUZZER

HORN

BELL

PUSH BUTTON

SOLENOID (LOW VOLTAGE)

RELAY (LOW VOLTAGE)

TIME CLOCK

THERMOSTAT (LINE VOLTAGE)

PB

T2

CB

J

M

JUNCTION BOX

METER

MOTOR

BLANKED OUTLET

PULL BOX

B

M

D ELECTRIC DAMPER

THERMAL OVERLOAD SWITCH

LP

EXOTHERMIC CONNECTION

VS

AS

V

A

AMMETER SELECTOR SWITCH

AMMETER

VOLTMETER

FUSE AND SWITCH < 600V

FUSE < 600V

CIRCUIT BREAKER < 600V

CAPACITOR

SWITCH AIR BREAK

FUSE > 600V

CABLE TERMINATION

ST

G ENGINE-GENERATOR UNIT

C

R G

DIFFERENTIAL RELAY

LOCKOUT RELAY

PRESSURE SWITCH

OVER VOLTAGE RELAY

AC CIRCUIT BREAKER

TIME OVER CURRENT RELAY

MANUAL SELECTOR SWITCH

UNDER VOLTAGE RELAY27

OVERHEAD GUY

OVERHEAD LINE

DOWN GUY AND ANCHOR

A

S

INTERCOM MASTER UNIT

VOLUME CONTROL

TELEVISION OUTLET

INTERCOM OUTLET

M

MICROPHONE OUTLET

SPEAKER CALL-IN SWITCH

SPEAKER

SPEAKER HORN

AMPLIFIER

TELEPHONE/DATA OUTLET

A

M

S

S

V

WORK NOTE SYMBOL

ROOM NUMBER

REVISION SYMBOL

E-5

(2#12 & 1#12G)3/4"C.

(4#12 & 1#12G)3/4"C.

(6#12 & 1#12G)3/4"C.

(8#12 & 1#12G)3/4"C.

M

L1

J

J

WALL WASH

BATTERY

PAD MOUNTED TRANSFORMER

6M12

OS

T

GFP

J

(R) (RELOCATED)

J

J

P

C

POWER JUNCTION BOX

COMMUNICATION JUNCTION BOX

4WG100

AHU-1

FLUORESCENT FIXTURES

MONITOR MODULE

CONTROL MODULE

RELEASE MODULE

STROBE

HORN/SPEAKER (RE: SPEC)

HORN/SPEAKER/STROBE

(RE: SPEC)

MINI HORN

MAGNETIC DOOR HOLD

REMOTE LIGHT/TEST SWITCH

FIRE OR EMERGENCY PHONE

MANUAL PULL STATION HEAT DETECTOR - THERMAL

R/C = RATE COMPENSATION

HEAT DETECTOR -

LINE TYPE (CABLE)

SMOKE DETECTOR

VALVE SUPERVISORY SWITCH

PRESSURE SWITCH

LOW AIR PRESSURE ALARM

FIRE/SMOKE DAMPER

CARBON MONOXIDE

DETECTOR

AUDIBLE ALARM

ABORT SWITCH

JLT

GROUNDING CONDUCTORG

GROUND BUS ON WALLGROUND ROD

GROUND

PATIENT GROUNDING POINTG

XXcd

XXcd

CARD READERCR

(RR)

ISOLATED GROUND

RECEPTACLE

DOUBLE DUPLEX

RECEPTACLE

DUPLEX RECEPTACLE

SPLIT WIRED

NUMBER DESIGNATES DETAIL

PRIMARY FUSE CUTOUT

OIL TYPE

CURRENT TRANSFORMER

W/RATIO

POTENTIAL

TRANSFORMER W/RATIO

VOLTMETER SELECTOR SWITCH

AUTOMATIC TRANSFER SWITCH

MANUAL TRANSFER SWITCH

END OF LINE RESISTOR (EOL)

RED AND GREEN PILOT LIGHTS

PUSH-BUTTON-NORMALLY OPEN

CONTACT NORMALLY

OPEN (N.O.)

CONTACT NORMALLY

CLOSED (N.C.)

AMP TRIPAT

MANUAL TRANSFER SWITCHMTS

HORSE POWERHP

RELOCATED(R)

BKR BREAKER

DP

(D)

CKT

C

DISTRIBUTION PANEL

DEDICATED

CIRCUIT

CONDUIT

ATS

AIC

AF

AFG

AHU

AFF

+4'-6"

A

AMPERE INTERRUPTING

CAPACITY

AMP FRAME

AUTO. TRANSFER SWITCH

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLING UNIT

MOUNTING HEIGHT AFF

AMPS

G

GFCI

FDR

FA

FCU

GROUND

FAN COIL UNIT

FEEDER

FIRE ALARM

EPO

EX

F

EWC

EM

EMT

EOL

EF

(E)

EMERGENCY POWER OFF

EXPLOSION-PROOF

ELECTRIC WATER COOLER

FUSE OR FIRE

END OF LINE RESISTOR

ELEC. METALLIC TUBING

EMERGENCY

EXHAUST FAN

EXISTING

MDS

MH

MG

MDP

MTD

MCC

MAIN DIST. SWITCHBOARD

MOTOR GENERATOR UNIT

MANHOLE

MAIN DISTRIBUTION PANEL

MOTOR CONTROL CENTER

MOUNTED

KW

L

KVAR

KV

KVA

IG

GRC

H

KILOWATT

KILOVAR

ISOLATED GROUND

KILO VOLT-AMPERE

KILOVOLT

GALVANIZED RIGID CONDUIT

PT POTENTIAL TRANSFORMER

RTU

RM

RT

PVC

ROOF TOP UNIT

POLYVINYL CHLORIDE

ROOM

RAINTIGHT

PF

ø OR PH

PDU

NO

NC

NIC

N

POWER FACTOR

POWER DISTRIBUTION UNIT

PHASE

NORMALLY CLOSED

NORMALLY OPEN

NOT IN CONTRACT

NEUTRAL

UPS

V

UG

VOLTS

UNDERGROUND

TTC

TTB

SW

TS

SRG

ST

SCA

TELEPHONE

TERMINAL CABINET

TELEPHONE

TERMINAL BOARD

SIGNAL REFERENCE GRID

TEST SWITCH

SWITCH

SHUNT TRIP

WP

WHM

VFD

VDC

VAC

WEATHERPROOF

WATTHOUR METER

VARIABLE FREQUENCY DRIVE

VOLTS DIRECT CURRENT

AC ALTERNATING CURRENT

B BATTERY

CP CONTROL PANEL

EC ELECTRICAL CONTRACTOR

FS

FI

FIRE SUPPRESSION

FILM ILLUMINATOR

MONITOR

LOW VOLTAGE

M

LV

MECHANICAL CONTRACTORMC

PREACTION SYSTEMPA

ac ABOVE COUNTER

REMOVE & RELOCATE(RR)

CURRENT TRANSFORMERCT

UC UNDERCABINET

UF UNDERFLOOR

ARC FAULT CIRCUIT

INTERRUPTER

AFCI

UON UNLESS OTHERWISE NOTED

LOW VOLTAGE SWITCH

b

S

SEAL OFF

CAP

FEEDER BUS DUCT

6(C)18

UG

W

EXTENSION WHIP

MCC MOTOR CONTROL CENTER

CP CONTROL PANEL

OH

OHG

PRESENCE STATION

MASTER STATION

DUTY STATION

STAFF STATION

PATIENT STATION - 2 BED

PATIENT STATION - 1 BED

M

S

D

P

EMERGENCY STATION

DOME LIGHT WITH BUZZER

E

E

S

B

Z

ZONE DOME LIGHT

C

M C

C

MASTER CLOCK

CLOCK AND SPEAKER UNIT

CLOCK OUTLET & CLOCK

C

C

C 24 HOUR CLOCK

ET

R

ELAPSED TIME CLOCK

GROUND FAULT

CIRCUIT INTERRUPTER

PREFIX DENOTING

277/480 PANEL

PREFIX DENOTING

120/208V PANEL

SHORT CIRCUIT

CURRENT AVAILABLE

VOLTS ALTERNATING

CURRENT

UNINTERRUPTIBLE

POWER SUPPLY

NUMBER REFERS

TO FEEDER

SCHEDULE

REFERS TO

EQUIPMENT SCHEDULE

SHEET ON WHICH

DETAIL IS LOCATED

DASHED SYMBOLS

DENOTE REMOVAL WORK

LIGHT LINE WEIGHT

SYMBOLS DENOTE

EXISTING (REMOVE &

RELOCATE)

LIGHTING CONTACTOR

W/ NO OF POLES

LETTER REFERS TO

FIXTURE SCHEDULE

ALL FIXTURES IN ROOM

ARE THIS TYPE UNLESS

NOTED OTHERWISE

LOWER CASE LETTER

INDICATES SWITCHING

SWITCHES GANGED

IN SAME BOX

OS = OCCUPANCY SENSOR

MD = MOTION DETECTOR

TC = TIME CLOCK

2 = DOUBLE-POLE SWITCH

3 = THREE-WAY SWITCH

4 = FOUR-WAY SWITCH

P = SWITCH AND PILOT LIGHT

K = KEY OPERATED SWITCH

D = DIMMER SWITCH

RECESSED

FLUORESCENT

FIXTURES

LIGHT TRACK

WITH FIXTURE

HEADS

FIXTURE(S) ON

EMERGENCY

CIRCUIT

GROUND FAULT CIRCUIT

INTERRUPTER RECEPTACLE

COMBINATION SWITCH

AND DUPLEX RECEPTACLE

CEILING SPECIAL

PURPOSE OUTLET

CEILING DUPLEX

RECEPTACLE

FLOOR MOUNTED

DUPLEX RECEPTACLE

MULTI-OUTLET ASSEMBLY (NO.

INDICATES RECEPTACLES AND

SPACING IN INCHES O.C.)

FLOOR MOUNTED

JUNCTION BOX

TRANSFORMER (SEE

TRANSFORMER SCHEDULE)

TOGGLE DISCONNECT

SWITCH 30 AMP

CIRCUIT BREAKER

DISCONNECT W/SIZE

NON-FUSED DISCONNECT

SWITCH W/SIZE

FUSED DISCONNECT

SWITCH W/SIZE

MOTOR STARTER

OR CONTACTOR

COMBINATION MOTOR

STARTER/DISCONNECT SWITCH BASEBOARD HEATING

STRIP (ELECTRICAL)

BRANCH CIRCUIT

PANELBOARD

MAIN DISTRIBUTION

PANEL OR SWITCHBOARD

CABLE TRAY WITH

DEPTH/LOAD/WIDTH

CONCEALED RACEWAY

HOME RUN INDICATES NUMBER OF CIRCUITS,

WIRES AND CONDUIT SIZE UNLESS OTHERWISE

NOTED:

WEATHER HEAD

SERVICE ENTRANCE

SINGLE PHASE

TRANSFORMER: NUMERAL

INDICATES RATING IN KVA

PRIMARY FUSE

CUTOUT AIR TYPE

SWITCH AIR BREAK,

GANG OPERATED

UNDERGROUND DUCTS:

NUMERAL INDICATES

QUANTITY OF DUCTS

LETTER INDICATES

SYSTEM

MANHOLE: NUMERAL

INDICATES THE

ASSIGNED NUMBER

AND THE LETTER

INDICATES THE TYPE

PUSH-BUTTON-

NORMALLY CLOSED

OPERATING COIL

(LADDER DIAGRAM)

OPERATING COIL

(SCHEMATIC DIAGRAM)

INSTANTANEOUS

OVER CURRENT

RELAY

LOAD BREAK ELBOW

SEPARABLE CONNECTION

PANEL BOARD

DESIGNATION INSIDE

TRANSFORMER (SEE

TRANFORMER SCHEDULE)

CIRCUIT BREAKER WITH

GROUND FAULT PROTECTION

BREAKER WITH DRAWOUT

FEATURE < 600V

BREAKER WITH DRAWOUT

FEATURE > 600V

FUSED DISCONNECT

SWITCH > 600V

CIRCUIT BREAKER WITH:

ST = SHUNT TRIP

K = KEY INTERLOCKED

E = ELECTRIC OPERATED

TELEPHONE TERMINAL

CABINET "TTC" TELEPHONE

TERMINAL BACKBOARD

TELEPHONE OUTLET

FLOOR MOUNTED

TELEPHONE OUTLET

W = WALL MOUNTED

P = PAY PHONE

F = FIREMAN PHONE

CCTV

AIR SAMPLING CONTROL

DETECTION PANEL

FIRE ALARM ANNUNCIATOR

FIRE ALARM BOOSTER PANEL

FIRE ALARM RELEASE PANEL

FIREFIGHTER SMOKE

CONTROL PANEL

FIRE FIGHTER CONTROL PANEL

V = BELL

VS = BELL/STROBE

C = CHIME

CS =

CHIME/STROBE

FIRE OR EMERGENCY

PHONE - HANDSET

FIRE OR EMERGENCY

PHONE - ACCESSIBLE

FIRE OR EMERGENCY

PHONE - JACK

R = RATE OF RISE ONLY

F = FIXED TEMPERATURE

R/F = R OF R & FIXED

TEMPERATURE

FLAME DETECTOR

F = FLAME

UV = ULTRAVIOLET

IR = INFRARED

VR = VISIBLE

RADIATION

DUCT SMOKE

DETECTOR S =

SUPPLY AIR

R = RETURN AIR

C = COMBINATION SMOKE/HEAT

DETECTOR

P = PHOTOELECTRIC

I = IONIZATION

BT = BEAM TRANSMITTER

BR = BEAM RECIEVER

ASD = AIR SAMPLING

EMERGENCY STATION

S = SHOWER

T = TOILET DOME LIGHT

MASTER CLOCK

AND PROGRAM CONTROL

RESET SWITCH FOR

ELAPSED TIME CLOCK

LIGHTNING

PROTECTION BARE

CONDUCTOR

SURGE ARRESTER

PLUS GROUND

LIGHTNING

PROTECTION AIR

TERMINAL

GROUND ROD WITH

INSPECTION WELL

FIRE ALARM CONTROL PANEL

NUMBER INDICATES

LAMPS

WR WEATHER RESISTANT

SPD

SURGE PROTECTIVE

DEVICE

S = SURFACE

UG = UNDERGROUND

W = WIREWAY

UF UF = UNDERFLOOR

NL NIGHT LIGHT

TR TAMPER RESISTANT

WATER FLOW SWITCH

OWNERSHIP OF DOCUMENTS:

ALL DRAWINGS, SPECIFICATIONS AND OTHER WORK PRODUCT OF THE ENGINEER FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE FOR THIS PROJECT ONLY AND SHALL REMAIN THE PROPERTY OF THE ENGINEER WHETHER THE PROJECT IS COMPLETED OR NOT. REUSE OF ANY OF THE INSTRUMENTS OF SERVICE OF THE ENGINEER BY THE OWNER OF EXTENSIONS OF THIS PROJECT WITHOUT WRITTEN PERMISSION OF THE ENGINEER SHALL BE AT THE OWNER'S RISK AND THE OWNER AGREES TO DEFEND, INDEMNIFY AND HOLD HARMLESS THE ENGINEER FROM ALL CLAIMS, DAMAGES, AND EXPENSES INCLUDING ATTORNEYS' FEES ARISING OUT OF UNAUTHORIZED REUSE OF THE ENGINEER'S INSTRUMENTS OF SERVICE BY THE OWNER OR BY OTHERS ACTING THROUGH THE OWNER.

PROJECT NUMBER

DRAWN BY

DATE

REVISIONS

SHEET TITLE

SHEET NUMBER

Boulder Associates, Inc.

www.boulderassociates.com

Architecture + Interior Design

1426 Pearl Street, Suite 300

Boulder , Colorado 80302

303.499.7795

PROJECT

REV

T T

L B v .2

T H

IS

L

IN

E

I S

I N

C H

L O

N G

W H

E N

P R

IN

T

E D

T O

F U

L L S

C A

L E

ADDRESS

851 E. 5th STREET

RIFLE, CO 81650

/2

/2

:3 :1

P

M C

U s e rs

\r le d fo rd \D o c u m e n ts

\L o c a l R e v it F ile s \1

S V

N H a t R if le

E le c

R rl e d fo rd .r v t

152732.00

RSL

February 1, 2017

ELECTRICAL

GENERAL

INFORMATION

E0.0

SVCLC AT RIFLE

RESIDENT

SAFETY &

ACCESSIBILITY

IMPROVEMENTS

100%

CONSTRUCTION

DOCUMENTS

ARVADA OFFICE COLORADO SPRINGS OFFICE

10807 NEW ALLEGIANCE DRIVE

SUITE 400

COLORADO SPRINGS, CO 80921

719.533.1112

5420 WARD ROAD

SUITE 200

ARVADA, CO 80002

303.422.7400

PROJECT ENGINEER PROJECT MANAGER

RICKY LEDFORD

rledford@BCER.COM (303)422-7400 X. 270

DAVID HUGHES

dhughes@BCER.COM (303)422-7400 Ext. 228

CONTACT LIST

LUMINAIRE SCHEDULE

KEY

LAMP

BALLAST QTY. DESCRIPTION VOLT FINISH

MOUNTING

MFR. MODEL VA REMARKSQTY. TYPE TYPE DEPTH

A1 1 LED - LED 2x2 120 V WHITE BAKED

ENAMEL

RECESSED 2-3/8" H.E. WILLIAMS PT-22-L38/835-RA-F358L-DIM-BD-UNV 37

A1E 1 LED - LED 2x2 120 V WHITE BAKED

ENAMEL

RECESSED 2-3/8" H.E. WILLIAMS PT-22-L38/835-RA-EM-DIM-BD-UNV 37 (3)

A2 1 LED - LED 2x2 120 V WHITE BAKED

ENAMEL

RECESSED 2-3/8" H.E. WILLIAMS PT-22-L29/835-RA-F358L-DIM-BD-UNV 31

A2E 1 LED - LED 2x2 120 V WHITE BAKED

ENAMEL

RECESSED 2-3/8" H.E. WILLIAMS PT-22-L38/835-RA-EM-DIM-BD-UNV 37 (3)

B 1 LED - LED 2x4 120 V WHITE BAKED

ENAMEL

RECESSED 2-3/8" H.E. WILLIAMS PT-24-L58/835-RA-F358L-DIM-BD-UNV 54

BE 1 LED - LED 2x4 120 V WHITE BAKED

ENAMEL

RECESSED 2-3/8" H.E. WILLIAMS PT-24-L58/835-RA-EM-DIM-BD-UNV 54 (3)

C 1 LED - FLOOR 2 - HALLWAY - 4' LED PENDANT 120 V WHITE POWDER

COAT

PENDANT -MIN. 24"

FROM CEILING

4 3/4" FINELITE HP4-ID-4'-S-H-8-35-F-F-FA-SC-C4 107

CE 1 LED - FLOOR 2 - HALLWAY - 4' LED PENDANT 120 V WHITE POWDER

COAT

PENDANT -MIN. 24"

FROM CEILING

4 3/4" FINELITE HP4-ID-4'-S-H-8-35-F-F-FA-SC-C4 107 (3)

D 1 LED - LED DIRECT STREET LIGHTING 208 V MATCH EXISTING - 5 3/4" HUBBELL ASL-A-16L3K-210-3-2-BL-RPA 123

E LED - LED BOLLARD 208 V THERMOSET

POLYESTER

POWDER COAT

SURFACE 42" POLE, 2"

BASE

HUBBELL #FN2-24LU-3K-DO-Q-BL- 46

F 1 LED - 4' LINEAR LED - PORTE COCHERE 120 V SILVER WALL 7-7/8" ELLIPTIPAR S171-L424-H-02-8-00-0-35-00 27 NO BLUETOOTH

G 1 LED - 6" ROUND LED DOWNLIGHT 120 V CLEAR RECESSED 6-3/4" WILALIGHTING WILA

621-6-XTM19-13LM-30K-83-DA60-120

GE 1 LED - 6" ROUND LED DOWNLIGHT 120 V CLEAR RECESSED 6-3/4" WILALIGHTING WILA

621-6-XTM19-13LM-30K-83-DA60-120

21 (3)

H LED - LED INGRADE FLAGPOLE UPLIGHT 208 V STAINLESS STEEL SURFACE 12.5" BELOW LUMASCAPE LS853LED-20W4-A-M-85-NM-29-Q-09 21

VERIFY ALL LUMINAIRE REQUIREMENTS WITH ARCHITECT PRIOR TO ORDERING.

(5) VERIFY ARROW DIRECTION.

(4) EMERGENCY BALLAST: 90 MIN, 1100 - 1400 LUMENS, 2-LAMP, TEST SWITCH, BODINE B-50 OR SIMILAR.

(3) CONNECT TO EMERGENCY CIRCUIT.

(2) ALL BALLAST AND FLUORESCENT LAMPS SHALL BE RAPID START TYPE.

(1) PROVIDE ELECTRONIC BALLAST WITH LESS THAN 10% THD.

NOT TO SCALE

TELEPHONE (VOICE/DATA) DIAGRAM

NOT TO SCALE

TYPICAL DEVICE MOUNTING HEIGHTS

ELECTRICAL DRAWING LIST

E0.0 ELECTRICAL GENERAL INFORMATION

E0.2 ELECTRICAL ONE-LINE DIAGRAM

E1.0 ELECTRICAL SITE PLAN

E1.1 PORTE COCHERE - ENLARGED PLANS & DETAILS

E1.2 START VIEW

E2.1 FLOOR 1 - LIGHTING PLAN

E2.2 FLOOR 2 - LIGHTING PLAN

E3.1 PANEL SCHEDULES

REMOVE AND REPLACE EXISTING INTERIOR LIGHTING WITH LED ON BOTH FLOORS AT

CORRIDORS AND NURSING STATIONS, EXCLUDE NURSING STATION DOWNLIGHTS. ADD NEW

LED LIGHTING AT PORTE COCHERE, WALKWAY, BOLLARDS, FLUSH MOUNTED SURFACE BELOW

NEW FLAG POLE LOCATION AND REPLACE EXTERIOR LIGHTING AT SITE POLES WITH LED...

ELECTRICAL NARRATIVE

DESCRIPTION DATE

1 C-WEST COMMENTS 03.28.2017

EXISTING ELECTRICAL ONE LINE DIAGRAM

LOAD SUMMARY

T

UG

CT CAN

UG

N

G

EXISTING PAD

MOUNTED

TRANSFORMER

2000 MAIN BUSS

EPP

200A MLO

30 CKT

120/208

100A

99,136 AIC

2000A

MAIN DISC.

SECTION

BRANCH

SECTION(S)

X-50,457 AIC

200A 200A 200A 150A 200/3 150A

200/3 100A

200/3 150A

200/3 150A

100/3 100A

CT1

225A MLO

8 CKT

120/208

PP1

225A MLO

120/208

EL1

100A MB

30 CKT

120/208

GDP

500A MLO

120/208

SPACE

100A

200A

GENERATOR

125 kW/156.25 KVA

120/208V

3 PHASE

100A

3 POLE

TRANSFER

SWITCH

200A

3 POLE

TRANSFER

SWITCH

EL2

50A MB

24 CKT

120/208

4#4/0

THHN, CU

+#4GND

2 1/2"C

LP1A

150A MB

42 CKT

120/208

RP1A

200A MB

42 CKT

120/208

LP1B

100A MB

42 CKT

120/208

RP1B

200A MB

42 CKT

120/208

KP1

200A MB

120/208

LP2A

100A MB

42 CKT

120/208

RP2A

200A MLO

42 CKT

120/208

LP2B

100A MLO

42 CKT

120/208

RP2B

200A MB

42 CKT

120/208

KP2

50A MB

24 CKT

120/208

PRP

400A MLO

60 CKT

120/208

PP2

125A MLO

42 CKT

120/208

MAINTENANCE

BUILDING

K1

125A MLO

30 CKT

120/208

X-5011 AICX-9117 AIC

4 #3+#6 G 1 1/2"C

200/3 150A

100/3 100A

200/3 150A

100/3 100A

400/3 400A

100/3 100A

100/3 100A

FRNR

100/3 100A

FRNR

EXISTING

SPARE

DISCONNECT

4 #3+#6 G

1 1/2"C

ITE VACU-BREAK

FUSED SWITCH

#V7E3233 INTO THE

GEAR

M

E G 500A

50A

NOT TO SCALE

LOAD ADDED TO PANEL "EL1"

(INCLUDES PANEL "EL2") = 0.2 kVA

LOAD ADDED TO PANEL "LP1A" = 1.4 kVA

LOAD ADDED NEW PANEL "LP1B" = 0.6 kVA

LOAD ADDED NEW PANEL "LP2A" = 0.9 kVA

LOAD ADDED NEW PANEL "LP2B" = <0.7> kVA

TOTAL LOAD ADDED = 2.4 kVA

(2.4 kVA @ 208V,3Ø = 7A)

OWNERSHIP OF DOCUMENTS:

ALL DRAWINGS, SPECIFICATIONS AND OTHER WORK PRODUCT OF THE ENGINEER FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE FOR THIS PROJECT ONLY AND SHALL REMAIN THE PROPERTY OF THE ENGINEER WHETHER THE PROJECT IS COMPLETED OR NOT. REUSE OF ANY OF THE INSTRUMENTS OF SERVICE OF THE ENGINEER BY THE OWNER OF EXTENSIONS OF THIS PROJECT WITHOUT WRITTEN PERMISSION OF THE ENGINEER SHALL BE AT THE OWNER'S RISK AND THE OWNER AGREES TO DEFEND, INDEMNIFY AND HOLD HARMLESS THE ENGINEER FROM ALL CLAIMS, DAMAGES, AND EXPENSES INCLUDING ATTORNEYS' FEES ARISING OUT OF UNAUTHORIZED REUSE OF THE ENGINEER'S INSTRUMENTS OF SERVICE BY THE OWNER OR BY OTHERS ACTING THROUGH THE OWNER.

PROJECT NUMBER

DRAWN BY

DATE

REVISIONS

SHEET TITLE

SHEET NUMBER

Boulder Associates, Inc.

www.boulderassociates.com

Architecture + Interior Design

1426 Pearl Street, Suite 300

Boulder , Colorado 80302

303.499.7795

PROJECT

REV

T T

L B v .2

T H

IS

L

IN

E

I S

I N

C H

L O

N G

W H

E N

P R

IN

T

E D

T O

F U

L L S

C A

L E

ADDRESS

851 E. 5th STREET

RIFLE, CO 81650

/2

/2

:3 :1

P

M C

U s e rs

\r le d fo rd \D o c u m e n ts

\L o c a l R e v it F ile s \1

S V

N H a t R if le

E le c

R rl e d fo rd .r v t

152732.00

RSL

February 1, 2017

ELECTRICAL

ONE-LINE

DIAGRAM

E0.2

SVCLC AT RIFLE

RESIDENT

SAFETY &

ACCESSIBILITY

IMPROVEMENTS

100%

CONSTRUCTION

DOCUMENTS

3. ALL GEAR AND FEEDERS ARE EXISTING, NO NEW EQUIPMENT OR FEEDERS ARE

BEING ADDED IN THIS PROJECT. THIS DIAGRAM IS PROVIDED FOR INFORMATION

ONLY.

2. PROVIDE NEW TYPEWRITTEN PANEL DIRECTORY CARDS FOR ALL PANELBOARDS IN

THIS PROJECT. DIRECTORIES ARE TO INDICATE THE AS-BUILT CIRCUIT INFORMATION

AT THE COMPLETION OF THE PROJECT.

1. ALL WORK SHOWN IN LIGHT LINE WEIGHTS IS EXISTING TO REMAIN AND ALL WORK

SHOWN IN DARK LINE WEIGHTS IS NEW.

GENERAL NOTES

DESCRIPTION DATE

A0.1 Cover Sheet 2017-04-25
CVCLC Rifle - Civil Set - 04252017
Rifle SVCLC_Landscape_L1.0
Rifle SVCLC_Landscape_L1.1
Architectural Bid Set 2017-04-25
Sheets
A0.0 - COVER SHEET
D1.1 - DEMO SITE PLAN
A1.0 - SITE PLAN
A1.1 - PORTE COCHERE - ENLARGED PLAN
A1.2 - PORTE COCHERE - ENLARGED PLANS & DETAILS
A2.01 - FLOOR 1 - LIFE SAFETY PLAN
A2.02 - FLOOR 2 - LIFE SAFETY PLAN
A2.1 - FLOOR PLAN - OVERALL - FIRST FLOOR
A2.2 - FLOOR PLAN - OVERALL - SECOND FLOOR
A3.1 - EXTERIOR ELEVATIONS
A4.1 - PORTE COCHERE - DETAILS
A6.1 - INTERIOR ELEVATION
A8.1 - DOOR & WINDOW TYPES, SCHEDULE & DETAILS
A9.1 - FLOOR 1 - REFLECTED CEILING PLAN
A9.2 - FLOOR 2 - REFLECTED CEILING PLAN
17794 042517
Sheets
S1.1 - PORTE COCHERE - GN & FRAMING
S1.2 - PORTE COCHERE - DETAILS