DESV_Submittal.pdf

PDF 457 KB Posted

Attached to
WWYK250063 - INSTALL REACT VII FACILITY, B9001, POST V19
Solicitation number
FA813726R0026
Issued by

About this file

This is a product submittal document for the DESV with Extended Casing, a single duct terminal unit manufactured by Titus Air Distribution Technologies, Inc.

The DESV is a digital, pressure-independent terminal unit available in seven sizes (5E through 4E) with CFM ranges from 0-350 to 0-3000. The unit features a heavy gauge G40 galvanized steel housing with mechanically sealed and gasketed, leak-resistant construction (less than 2% leakage at 1.5" static pressure). The extended casing design enables improved heating performance when paired with an optional matching hot water reheat coil, particularly when using low entering water temperature. All dimensions are provided in inches across multiple configurations, with discharge opening designed for slip and drive cleat duct connection. The unit is equipped with a multipoint center averaging inlet velocity sensor and can be installed horizontally, vertically, or at any angle. Rectangular discharge dimensions range from 4 7/8" to 13 7/8" (D dimension) depending on size, with corresponding casing dimensions varying accordingly.

Optional accessories include integral sound attenuators, hot water coil sections (available in 1-4 row configurations with aluminum ripple fins at 10 per inch), electric coil sections, and SCR or Lynergy controlled electric heaters. Control options include Titus I or Titus II velocity controllers with choice of direct/reverse acting and normally open/closed configurations. Available supply voltages range from 120V single phase to 480V three phase. Additional optional features include dust tight enclosure seals, various liner options (EcoShield, Fibre Free, SteriLoc, UltraLoc), disconnect switches, hanger brackets, and seismic certifications (OSP 0352-10). Only Titus Alpha controls are approved for seismic installation. The submittal date is February 14, 2025, and Titus reserves the right to make changes without written notice.

View the file

Other files

File Type Posted
250063_ATT 10_Submittal Register.xlsx XLSX spreadsheet
26 05 73 POWER STUDIES.pdf PDF
26 20 00.pdf PDF
09 90 00.pdf PDF
23 09 13.pdf PDF
23 36 00.00 40.pdf PDF
08 71 00.pdf PDF
05 40 00.pdf PDF
10 14 00.10.pdf PDF
08 33 23.pdf PDF
08 11 13.pdf PDF
07 92 00.pdf PDF
01 33 16.00 10.pdf PDF
01 32 16.00 20.pdf PDF
image.png PNG image
250063 React VII_Hardware schedule 25MAR26 JL.xlsx XLSX spreadsheet
JOIST SPECIAL INSPECTIONS.xlsx XLSX spreadsheet
ELECTRICAL PANEL SCHEDULE U18L.xlsx XLSX spreadsheet
esvEH_singledual_2023_V2.pdf PDF
lk406gn05t4_spec.pdf PDF
2_-_HE05-JINV-S11EE---GNT---L_001.pdf PDF
ERV Schedule_TAFB B9001_O-212477.xlsx XLSX spreadsheet
4500-CIVIL.pdf PDF
250063_ATT 10_Submittal Register.pdf PDF
250063_ATT 9_SOW.pdf PDF
250063_ATT 11_Drawings.pdf PDF
WWYK250063-04March2026.pdf PDF
2020 TAFB Facility Standard.pdf PDF
2026 TAFB Electrical Standard - Signed.pdf PDF
SOW Att 02a_Controlled Area Training.pptx PPTX presentation
SOW Att 02c_Controlled Area Training - Certificate.pdf PDF
22 00 00.pdf PDF
28 31 76.pdf PDF
23 09 23.02.pdf PDF
07 14 00.pdf PDF
08 51 23.pdf PDF
10 44 16.pdf PDF
07 21 16.pdf PDF
00 72 00.pdf PDF
00 71 00.pdf PDF
01 78 00.pdf PDF
01 33 00.pdf PDF
000_TABLE OF CONTENTS.pdf PDF
01 78 23.pdf PDF
esvperf_singledual_2023_V2.pdf PDF
lrad331965pd_spec.pdf PDF
REACT VII SA-01.pdf PDF
TAFB B9001 VAV Schedule.pdf PDF
ARCH-COMBINED.pdf PDF
4500-MUG.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DESV with Extended Casing Single Duct Terminal Unit Digital, Pressure Independent

Size CFM Range D (H x W) C F G H L M W CH CL CW

5E 0-350 4 7/8 6 2 1/8 7 3/8 10 15 1/2 3 3/8 12 12 1/4 18 6 1/2

6E 0-500 5 7/8 6 2 1/8 7 3/8 10 15 1/2 3 3/8 12 12 1/4 18 6 1/2

7E 0-650 6 7/8 7 1 1/8 5 3/8 12 1/2 15 1/2 3 3/8 14 12 1/4 18 6 1/2

8E 0-900 7 7/8 7 1 1/8 5 3/8 12 1/2 15 1/2 3 3/8 14 12 1/4 18 6 1/2

1E 0-1400 9 7/8 8 - 5 3/8 15 15 1/2 3 3/8 16 12 1/4 18 6 1/2

2E 0-2000 11 7/8 10 - 3 3/8 17 1/2 15 1/2 3 3/8 20 12 1/4 18 6 1/2

4E 0-3000 13 7/8 12 - 3 3/8 18 15 1/2 3 3/8 24 12 1/4 18 6 1/2

This submittal is meant to demonstrate general dimensions of this product. The drawings are not meant to detail every aspect of the product. Drawings are not to scale. Titus reserves the right to make changes without written notice.

All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system without permission in writing from Air Distribution Technologies, Inc.

Submittal DESV - 1.0 2-14-2025

CW

CL

Slip & Drive Cleat Connection

Control Enclosure (Optional on Cooling-only units)

LM

G

CH

D

C F

F W

H

Digital Control, DESV

Right hand unit shown. All dimensions are in inches.

This submittal is meant to demonstrate general dimensions of this product. The drawings are not meant to detail every aspect of the product. Drawings are not to scale. Titus reserves the right to make changes without written notice.

All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system without permission in writing from Air Distribution Technologies, Inc.

Accessories (Optional)

• The DESV with Extended Casing utilizes a larger casing than a standard DESV model. When accompanied with a matching hot water reheat coil, heating performance can be improved.

This is especially true when low entering water temperature is used.

• Heavy gauge G40 galvanized steel housing. Mechanically sealed and gasketed, leak resistant construction. Less than 2% of nominal cfm at 1.5” sp wg.

• Dual density internal insulation, treated to resist air erosion. Meets

24 V Control Transformer Dust Tight Enclosure Seal Fibre Free Liner ½” EcoShield Liner ½” Fibre Free Liner

Check if provided. 1” Fiberglass Liner 1” EcoShield Liner 1” Fibre Free Liner Low Leakage Seal/Test Certify SteriLoc Liner

UltraLoc Liner ½” EcoShield Liner (Foil Face) 1” EcoShield Liner (Foil Face) Disconnect Switch Hanger Brackets

Removable Air Flow Sensor Bottom Access Door OSP & IBC -S Seismic Certification Red List Compliant “Google” Gasketing Stainless Steel Construction requirements of NFPA 90A and UL 181.

• Units equipped with the Titus II velocity controller can either be direct acting or reverse acting, with the damper either normally open or normally closed. Controller maintains constant span and start point. (Span and start point are adjustable.)Rectangular discharge opening is designed for slip and drive cleat duct connection.

• Multipoint center averaging inlet velocity sensor.

• Control packages can be factory mounted by Titus.

• Choice of right hand or left hand control location.

• Units equipped with the Titus I velocity controller are available in both direct acting / normally open and reverse acting / normally closed operating modes.Model DESV without coils can be installed horizontally, vertically, or at any angle.

Operation is not affected by position. For units with coils, consult technical support.

•Gauge tees for cfm measurement.
•OSHPD Seismic Certification:

OSP 0352-10

• Only Titus Alpha controls approved for seismic installation.

Submittal DESV - 2.0 2-14-2025

General Description

39 1/2 6 1/2 W

12 1/4 H

Integral Sound Attenuator

DESV

Hot Water Coil Section

•Aluminum ripple fins, 10 per inch
•Coil pipe connections are male, sweat, type “L”
copper.
•Connection sizes: Unit sizes 04-08: 1/2” OD

on 1 row coils and 5/8” OD on 2 row coils. Unit sizes 09-40: 7/8” OD for all coils

•Coil is installed at discharge of unit.
•On units with attenuators, coil are installed at

the discharge of attenuator.

• Coils rated and certified to AHRI Standard 410

1 Row 2 Row 3 Row 4 Row

H

L W

This submittal is meant to demonstrate general dimensions of this product. The drawings are not meant to detail every aspect of the product. Drawings are not to scale. Titus reserves the right to make changes without written notice.

All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system without permission in writing from Air Distribution Technologies, Inc.

Accessories (Optional)

Submittal DESV - 3.0 2-14-2025

Standard Features

• Single side access to low voltage, high voltage, and electric heater controls.

• Automatic reset thermal cutouts, one per element.

•Manual reset secondary protection.
•Positive pressure flow switch.
•Magnetic contactor for each step.
•Slip and drive cleat discharge duct
connection.

Options Supply Voltage Fuse Block Disconnect switch, door interlock type Dust tight construction

120V, 1ph, 60Hz 208V, 1 ph, 60Hz 240V, 1 ph, 60Hz

277V, 1 ph, 60Hz 208V, 3 ph, 60Hz 480V, 3 ph, 60Hz (4 wire wye standard)

The total length of the DESV unit is the summation of the unit length (with or without attenuator) and the length of the optional water coil.

Size H W Water Coil

L 5E 8 12 7 1/4 6E 8 12 7 1/4 7E 10 12 7 1/4 8E 10 12 7 1/4 1E 12 1/2 14 7 1/4 2E 12 1/2 14 9 3/4 4E 12 1/2 20 9 3/4

Electric Coil Section Optional SCR Controlled Electric Heater Optional Lynergy Controlled Electric Heater

36 5/8”

39 1/2” 6 1/4” W

H12”

File details come from the government source that posted it. Updated .