ERV Schedule_TAFB B9001_O-212477.xlsx
XLSX spreadsheet 8 KB Posted
- Solicitation number
- FA813726R0026
About this file
This is an Energy Recovery Ventilator (ERV) Schedule specification document for Building 9001 at Tyndall Air Force Base. The document provides detailed technical specifications for a RenewAire HE05 indoor unit ERV system (designated ERV-1) located at elevation 1,299 feet. The unit is designed to supply 300 CFM of fresh air and exhaust 200 CFM of return air, each with 0.5 inches of static pressure and 0.5 HP motors operating without variable frequency drives. The system achieves a sensible effectiveness rating of 87.5% during summer cooling and 69.5% during winter heating, with total effectiveness of 86.1% for winter operations. Electrical specifications include 120V single-phase 60 Hz power supply with 6.1 MCA and 15 MOPD rating.
The ERV system utilizes pleated 2-inch MERV 10 filters for both supply and exhaust air streams. Performance data indicates cooling conditions with outdoor air at 99.5°F dry bulb and 73.9°F wet bulb, fresh air entering at 85.2°F dry bulb and 68.9°F wet bulb, and return air at 75°F dry bulb and 62.3°F wet bulb, with corresponding winter heating conditions detailed in the schedule. This specification document supports the REACT VII Facility installation project (Solicitation FA813726R0026) at Tyndall Air Force Base, which is set-aside exclusively for SBA Certified Women Owned Small Businesses (WOSB) with a mandatory initial site visit scheduled for July 20, 2026.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
html table
| Model Information | Fan Data | Energy Recovery Data | Unit Information | |||||||||||||||||||||||||||||||||||||||||||
| Unit | Basis of Design | Model | Location | Tag# | Elevation (ft) | Supply Air Airflow | Exhaust Air Airflow | Summer/Cooling | Winter/Heating | Performance Effectiveness | Electrical | Filters | Notes | |||||||||||||||||||||||||||||||||
| Outdoor Air | Fresh Air | Return Air | Outdoor Air | Fresh Air | Return Air | Outdoor Air | Return Air | |||||||||||||||||||||||||||||||||||||||
| Fresh Air CFM | ESP | Motor HP | VFD | FLA | Exhaust Air CFM | ESP | Motor HP | VFD | FLA | Dry Bulb | Wet Bulb | Grains/lb | Dry Bulb | Wet Bulb | Grains/lb | Dry Bulb | Wet Bulb | Grains/lb | Dry Bulb | Wet Bulb | Grains/lb | Dry Bulb | Wet Bulb | Grains/lb | Dry Bulb | Wet Bulb | Grains/lb | Sensible (%) | Summer Total (%) | Winter Total (%) | Voltage/Phase/HZ | MCA | MOPD | Type | Depth | Rating | Type | Depth | Rating | |||||||
| 1 | RenewAire | HE05 | Indoor Unit | ERV-1 | 1299 | 300 | 0.5 | 1 | NO | 2.7 | 200 | 0.5 | 1 | NO | 2.7 | 99.5 | 73.9 | 90.8 | 85.2 | 68.9 | 84.8 | 75 | 62.3 | 67.8 | 12.5 | 10 | 6.2 | 46.1 | 36.5 | 18.2 | 70 | 51.1 | 28.4 | 87.5 | 69.5 | 86.1 | 120V / 1 Phase / 60 HZ | 6.1 | 15 | Pleated | 2" | MERV 10 | Pleated | 2" | MERV 10 |