This document is a technical specification section for interior electrical distribution systems at Tinker Air Force Base, Oklahoma, dated April 2019.

The specification establishes comprehensive requirements for electrical materials, equipment, and installation practices. Key product requirements include rigid and nonmetallic conduit, busway systems with copper buses, cable trays (basket, trough, ladder, and channel types), surface raceways, outlet boxes, panelboards with circuit breakers, transformers (dry-type, self-cooled, ventilated), motors, motor controllers, enclosed circuit breakers, fuses, receptacles, switches, and telecommunications system components. All materials must comply with UL standards where established and NFPA 70 requirements. The specification mandates stranded copper conductors with specific color coding: black/red/blue for 208/120V three-phase; brown/orange/yellow for 480/277V three-phase; and green for grounding, white for neutral. Transformers rated 15 kVA and above require 220-degree Celsius insulation systems with 115-degree Celsius temperature rise. Panelboards must have circuit breaker-equipped designs with specific breaker placement matching indicated schedules, isolated neutral buses, and separate ground buses. Installation requirements specify rigid steel conduit as the primary wiring method, with minimum 1/2-inch diameter for low-voltage circuits, proper support intervals, grounding specifications not exceeding 5 ohms resistance, and telecommunications grounding per TIA-607 standards. The specification includes detailed field quality control testing procedures for 600-volt wiring, transformers, ground-fault receptacles, and grounding systems, with test results required in writing before equipment energization.

View the file

Other files

File Type Posted
Solicitation Amendment FA813726R00260001 - CANCELLATION.pdf PDF
Solicitation Amendment FA813726R00260001 SF 30.pdf PDF
250063_ATT 10_Submittal Register.pdf PDF
250063_ATT 9_SOW.pdf PDF
250063_ATT 11_Drawings.pdf PDF
WWYK250063-04March2026.pdf PDF
2020 TAFB Facility Standard.pdf PDF
2026 TAFB Electrical Standard - Signed.pdf PDF
SOW Att 02a_Controlled Area Training.pptx PPTX presentation
SOW Att 02c_Controlled Area Training - Certificate.pdf PDF
22 00 00.pdf PDF
28 31 76.pdf PDF
23 09 23.02.pdf PDF
07 14 00.pdf PDF
08 51 23.pdf PDF
10 44 16.pdf PDF
07 21 16.pdf PDF
00 72 00.pdf PDF
00 71 00.pdf PDF
01 78 00.pdf PDF
01 33 00.pdf PDF
000_TABLE OF CONTENTS.pdf PDF
01 78 23.pdf PDF
esvperf_singledual_2023_V2.pdf PDF
lrad331965pd_spec.pdf PDF
REACT VII SA-01.pdf PDF
TAFB B9001 VAV Schedule.pdf PDF
ARCH-COMBINED.pdf PDF
4500-MUG.pdf PDF
overall plan 04.15.2021.pdf PDF
250063_ATT 4_ODS.pdf PDF
WWYK250063-04March2026 1.docx DOCX document
250063_ATT 3_RMDF.pdf PDF
23 00 00.pdf PDF
23 07 00.pdf PDF
23 31 13.00 40.pdf PDF
23 08 00.pdf PDF
03 01 00.pdf PDF
23 64 26.pdf PDF
10 14 00.20.pdf PDF
23 05 48.00 40.pdf PDF
07 84 00.pdf PDF
23 03 00.pdf PDF
01 50 00.pdf PDF
00 80 00.pdf PDF
01 42 00.pdf PDF
UMRL.pdf PDF
PILE SCHEDULE.xlsx XLSX spreadsheet
HELICAL PILES NOTES.docx DOCX document
z400i.pdf_safe.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Ti nker AFB, OK TAFB Techni cal Spr ci f i cat i ons 2019

SECTI ON 26 20 00

I NTERI OR DI STRI BUTI ON SYSTEM

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o i n t he t ext by t he basi c desi gnat i on onl y.

ASTM I NTERNATI ONAL ( ASTM)

ASTM B1 ( 2013) St andar d Speci f i cat i on f or Har d- Dr awn Copper Wi r e

ASTM B8 ( 2011) St andar d Speci f i cat i on f or Concent r i c- Lay- St r anded Copper Conduct or s, Har d, Medi um- Har d, or Sof t

ASTM D709 ( 2016) Lami nat ed Ther moset t i ng Mat er i al s

I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)

I EEE 100 ( 2000; Ar chi ved) The Aut hor i t at i ve Di ct i onar y of I EEE St andar ds Ter ms

I EEE 81 ( 2012) Gui de f or Measur i ng Ear t h Resi st i v i t y, Gr ound I mpedance, and Ear t h Sur f ace Pot ent i al s of a Gr ound Syst em

I EEE C2 ( 2012; Er r at a 1 2012; I NT 1- 4 2012; Er r at a

2 2013; I NT 5- 7 2013; I NT 8- 10 2014; I NT

11 2015; I NT 12 2016) Nat i onal El ect r i cal Saf et y Code

I NTERNATI ONAL ELECTRI CAL TESTI NG ASSOCI ATI ON ( NETA)

NETA ATS ( 2013) St andar d f or Accept ance Test i ng Speci f i cat i ons f or El ect r i cal Power Equi pment and Syst ems

NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)

ANSI C12. 7 ( 2014) Requi r ement s f or Wat t hour Met er Sockets

ANSI C80. 1 ( 2005) Amer i can Nat i onal St andar d f or El ect r i cal Ri gi d St eel Condui t ( ERSC)

ANSI C80. 3 ( 2005) Amer i can Nat i onal St andar d f or El ect r i cal Met al l i c Tubi ng ( EMT)

ANSI C80. 5 ( 2005) Amer i can Nat i onal St andar d f or El ect r i cal Ri gi d Al umi num Condui t

Apr i l 2019 Page 1 SECTI ON 26 20 00

NEMA 250 ( 2014) Encl osur es f or El ect r i cal Equi pment ( 1000 Vol t s Maxi mum)

NEMA BU 1. 1 ( 2010) Gener al I nst r uct i ons f or Pr oper Handl i ng, I nst al l at i on, Oper at i on and Mai nt enance of Busway Rat ed 600 V or Less

NEMA FU 1 ( 2012) Low Vol t age Car t r i dge Fuses

NEMA I CS 1 ( 2000; R 2015) St andar d f or I ndust r i al Cont r ol and Syst ems: Gener al Requi r ement s

NEMA I CS 2 ( 2000; R 2005; Er r at a 2008) St andar d f or Cont r ol l er s, Cont act or s, and Over l oad Rel ays Rat ed 600 V

NEMA I CS 3 ( 2005; R 2010) Medi um- Vol t age Cont r ol l er s Rat ed 2001 t o 7200 V AC

NEMA I CS 4 ( 2015) Ter mi nal Bl ocks

NEMA I CS 6 ( 1993; R 2011) Encl osur es

NEMA KS 1 ( 2013) Encl osed and Mi scel l aneous Di st r i but i on Equi pment Swi t ches ( 600 V Maximum)

NEMA MG 1 ( 2014) Mot or s and Gener at or s

NEMA MG 10 ( 2013) Ener gy Management Gui de f or Sel ect i on and Use of Fi xed Fr equency Medi um AC Squi r r el - Cage Pol yphase I nduct i on Mot or s

NEMA MG 11 ( 1977; R 2012) Ener gy Management Gui de f or Sel ect i on and Use of Si ngl e Phase Mot or s

NEMA RN 1 ( 2005; R 2013) Pol yvi nyl - Chl or i de ( PVC) Ext er nal l y Coat ed Gal vani zed Ri gi d St eel Condui t and I nt er medi at e Met al Condui t

NEMA ST 20 ( 1992; R 1997) St andar d f or Dr y- Type Tr ansf or mer s f or Gener al Appl i cat i ons

NEMA TC 14 ( 2002) St andar d f or Rei nf or ced Ther moset t i ng Resi n Condui t ( RTRC) and Fittings

NEMA TC 2 ( 2013) St andar d f or El ect r i cal Pol yvi nyl Chl or i de ( PVC) Condui t

NEMA TC 3 ( 2015) St andar d f or Pol yvi nyl Chl or i de ( PVC) Fi t t i ngs f or Use Wi t h Ri gi d PVC Condui t and Tubi ng

NEMA TP 1 ( 2002) Gui de f or Det er mi ni ng Ener gy Ef f i c i ency f or Di st r i but i on Tr ansf or mer s

NEMA VE 1 ( 2009) St andar d f or Met al Cabl e Tr ay

Apr i l 2019 Page 2 SECTI ON 26 20 00

Systems

NEMA WD 1 ( 1999; R 2015) St andar d f or Gener al Col or Requi r ement s f or Wi r i ng Devi ces

NEMA WD 6 ( 2016) Wi r i ng Devi ces Di mensi ons Specifications

NEMA Z535. 4 ( 2011) Amer i can Nat i onal St andar d f or Pr oduct Saf et y Si gns and Label s

NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)

NFPA 70 ( 2014; AMD 1 2013; Er r at a 1 2013; AMD 2 2013; Er r at a 2 2013; AMD 3 2014; Er r at a 3- 4 2014; AMD 4- 6 2014) Nat i onal El ect r i cal Code

NFPA 70E ( 2015; ERTA 1 2015) St andar d f or El ect r i cal Saf et y i n t he Wor kpl ace

NFPA 780 ( 2014) St andar d f or t he I nst al l at i on of Li ght ni ng Pr ot ect i on Syst ems

TELECOMMUNI CATI ONS I NDUSTRY ASSOCI ATI ON ( TI A)

TIA-568-C.1 ( 2009; Add 2 2011; Add 1 2012) Commer ci al Bui l di ng Tel ecommuni cat i ons Cabl i ng Standard

TIA-569 ( 2015d) Commer ci al Bui l di ng St andar d f or Tel ecommuni cat i ons Pat hways and Spaces

TIA-607 ( 2011b) Gener i c Tel ecommuni cat i ons Bondi ng and Gr oundi ng ( Ear t hi ng) f or Cust omer Premises

U. S. NATI ONAL ARCHI VES AND RECORDS ADMI NI STRATI ON ( NARA)

29 CFR 1910. 147 Cont r ol of Hazar dous Ener gy ( Lock Out / Tag Out)

UNDERWRI TERS LABORATORI ES ( UL)

UL 1 ( 2005; Repr i nt Jul 2012) St andar d f or Fl exi bl e Met al Condui t

UL 1063 ( 2006; Repr i nt Jul 2012) Machi ne- Tool Wi r es and Cabl es

UL 1203 ( 2013; Repr i nt Apr 2015) UL St andar d f or Saf et y Expl osi on- Pr oof and Dust - I gni t i on- Pr oof El ect r i cal Equi pment f or Use i n Hazar dous ( Cl assi f i ed) Locat i ons

UL 1242 ( 2006; Repr i nt Mar 2014) St andar d f or El ect r i cal I nt er medi at e Met al Condui t - - Steel

Apr i l 2019 Page 3 SECTI ON 26 20 00

UL 1449 ( 2014; Repr i nt Mar 2015) Sur ge Pr ot ect i ve Devices

UL 1561 ( 2011; Repr i nt Jun 2015) Dr y- Type Gener al Pur pose and Power Tr ansf or mer s

UL 1569 ( 2014; Repr i nt Dec 2015) St andar d f or Met al - Cl ad Cabl es

UL 1660 ( 2014) Li qui d- Ti ght Fl exi bl e Nonmet al l i c Conduit

UL 1699 ( 2006; Repr i nt Nov 2013) Ar c- Faul t Circuit-Interrupters

UL 198M ( 2003; Repr i nt Feb 2013) St andar d f or Mi ne- Dut y Fuses

UL 20 ( 2010; Repr i nt Feb 2012) Gener al - Use Snap Switches

UL 2043 ( 2013) Fi r e Test f or Heat and Vi s i bl e Smoke Rel ease f or Di scr et e Pr oduct s and Thei r Accessor i es I nst al l ed i n Ai r - Handl i ng Spaces

UL 360 ( 2013; Repr i nt Jan 2015) Li qui d- Ti ght Fl exi bl e St eel Condui t

UL 4 ( 2004; Repr i nt Oct 2013) St andar d f or Ar mor ed Cabl e

UL 4248- 1 ( 2007; Repr i nt Oct 2013) UL St andar d f or Saf et y Fusehol der s - Par t 1: Gener al Requirements

UL 4248- 12 ( 2007; Repr i nt Dec 2012) UL St andar d f or Saf et y Fusehol der s - Par t 12: Cl ass R

UL 44 ( 2014; Repr i nt Feb 2015) Ther moset - I nsul at ed Wi r es and Cabl es

UL 467 ( 2013) Gr oundi ng and Bondi ng Equi pment

UL 486A- 486B ( 2013; Repr i nt Jan 2016) Wi r e Connect or s

UL 486C ( 2013; Repr i nt Jan 2016) Spl i c i ng Wi r e Connectors

UL 489 ( 2013; Repr i nt Mar 2014) Mol ded- Case Ci r cui t Br eaker s, Mol ded- Case Swi t ches, and Ci r cui t - Br eaker Encl osur es

UL 498 ( 2012; Repr i nt Jan 2016) At t achment Pl ugs and Recept acl es

UL 5 ( 2011) Sur f ace Met al Raceways and Fi t t i ngs

UL 50 ( 2007; Repr i nt Apr 2012) Encl osur es f or

Apr i l 2019 Page 4 SECTI ON 26 20 00

El ect r i cal Equi pment , Non- envi r onment al Considerations

UL 506 ( 2008; Repr i nt Oct 2013) Speci al t y Transformers

UL 508 ( 1999; Repr i nt Oct 2013) I ndust r i al Cont r ol Equi pment

UL 510 ( 2005; Repr i nt Jul 2013) Pol yvi nyl Chl or i de, Pol yet hyl ene and Rubber I nsul at i ng Tape

UL 514A ( 2013) Met al l i c Out l et Boxes

UL 514B ( 2012; Repr i nt Nov 2014) Condui t , Tubi ng and Cabl e Fi t t i ngs

UL 514C ( 2014; Repr i nt Dec 2014) Nonmet al l i c Out l et Boxes, Fl ush- Devi ce Boxes, and Covers

UL 5A ( 2015) Nonmet al l i c Sur f ace Raceways and Fittings

UL 6 ( 2007; Repr i nt Nov 2014) El ect r i cal Ri gi d Met al Condui t - St eel

UL 651 ( 2011; Repr i nt May 2014) St andar d f or Schedul e 40 and 80 Ri gi d PVC Condui t and Fittings

UL 67 ( 2009; Repr i nt Apr 2015) St andar d f or Panelboards

UL 674 ( 2011; Repr i nt Jul 2013) El ect r i c Mot or s and Gener at or s f or Use i n Di v i s i on 1 Hazar dous ( Cl assi f i ed) Locat i ons

UL 6A ( 2008; Repr i nt Nov 2014) El ect r i cal Ri gi d Met al Condui t - Al umi num, Red Br ass, and St ai nl ess St eel

UL 797 ( 2007; Repr i nt Dec 2012) El ect r i cal Met al l i c Tubi ng - - St eel

UL 817 ( 2015; Repr i nt Jan 2016) St andar d f or Cor d Set s and Power - Suppl y Cor ds

UL 83 ( 2014) Ther mopl ast i c- I nsul at ed Wi r es and Cables

UL 845 ( 2005; Repr i nt Jul 2011) Mot or Cont r ol Centers

UL 854 ( 2004; Repr i nt Nov 2014) St andar d f or Ser vi ce- Ent r ance Cabl es

UL 857 ( 2009; Repr i nt Dec 2011) Busways

Apr i l 2019 Page 5 SECTI ON 26 20 00

UL 869A ( 2006) Ref er ence St andar d f or Ser vi ce Equipment

UL 870 ( 2008; Repr i nt Feb 2013) St andar d f or Wi r eways, Auxi l i ar y Gut t er s, and Associ at ed Fi t t i ngs

UL 943 ( 2006; Repr i nt Jun 2012) Gr ound- Faul t Circuit-Interrupters

UL 984 ( 1996; Repr i nt Sep 2005) Her met i c Ref r i ger ant Mot or - Compr essor s

1. 2 DEFINITIONS

Unl ess ot her wi se speci f i ed or i ndi cat ed, el ect r i cal and el ect r oni cs t er ms used i n t hese speci f i cat i ons, and on t he dr awi ngs, ar e as def i ned i n

I EEE 100.

1. 3 SUBMITTALS

Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00, SUBMI TTAL

PROCEDURES.

SD- 02 Shop Dr awi ngs

Panelboards

Transformers

Busway

Cabl e t r ays

Mot or cont r ol cent er s

Wireways

Load cent er s f or housi ng uni t s

Mar ki ng st r i ps

SD- 03 Pr oduct Dat a

Receptacles

Ci r cui t br eaker s

Switches

Transformers

Encl osed ci r cui t br eaker s

Mot or cont r ol l er s

Combi nat i on mot or cont r ol l er s

Apr i l 2019 Page 6 SECTI ON 26 20 00

Load cent er s f or housi ng uni t s

Manual mot or st ar t er s

Met er base onl y

Gr oundi ng Busbar

Sur ge pr ot ect i ve devi ces

SD- 06 Test Repor t s

600- vol t wi r i ng t est

Gr oundi ng syst em t est

Tr ansf or mer t est s

Gr ound- f aul t r ecept acl e t est

SD- 07 Cer t i f i cat es

Fuses

SD- 10 Oper at i on and Mai nt enance Dat a

El ect r i cal Syst ems

1. 4 QUALI TY ASSURANCE

1. 4. 1 Regul at or y Requi r ement s

I n each of t he publ i cat i ons r ef er r ed t o her ei n, consi der t he advi sor y pr ovi s i ons t o be mandat or y, as t hough t he wor d, " shal l " or " must " had been subst i t ut ed f or " shoul d" wher ever i t appear s. I nt er pr et r ef er ences i n t hese publ i cat i ons t o t he " aut hor i t y havi ng j ur i sdi ct i on, " or wor ds of s i mi l ar meani ng, t o mean t he Cont r act i ng Of f i cer . Pr ovi de equi pment , mat er i al s, i nst al l at i on, and wor kmanshi p i n accor dance wi t h t he mandat or y and advi sor y pr ovi s i ons of NFPA 70 unl ess mor e st r i ngent r equi r ement s ar e speci f i ed or i ndi cat ed.

1. 4. 2 St andar d Pr oduct s

Pr ovi de mat er i al s and equi pment t hat ar e pr oduct s of manuf act ur er s r egul ar l y engaged i n t he pr oduct i on of such pr oduct s whi ch ar e of equal mat er i al , desi gn and wor kmanshi p and:

a. Have been i n sat i sf act or y commer ci al or i ndust r i al use f or 2 year s pr i or t o bi d openi ng i ncl udi ng appl i cat i ons of equi pment and mat er i al s under s i mi l ar c i r cumst ances and of s i mi l ar s i ze.

b. Have been on sal e on t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es dur i ng t he 2- year per i od.

c. Wher e t wo or mor e i t ems of t he same cl ass of equi pment ar e r equi r ed, pr ovi de pr oduct s of a s i ngl e manuf act ur er ; however , t he component par t s of t he i t em need not be t he pr oduct s of t he same manuf act ur er unl ess st at ed i n t hi s sect i on.

Apr i l 2019 Page 7 SECTI ON 26 20 00

1. 4. 2. 1 Al t er nat i ve Qual i f i cat i ons

Pr oduct s havi ng l ess t han a 2- year f i el d ser vi ce r ecor d wi l l be accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on f or not l ess t han 6000 hour s, excl usi ve of t he manuf act ur er s ' f act or y or l abor at or y t est s, i s f ur ni shed.

1. 4. 2. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e

Pr oduct s manuf act ur ed mor e t han 3 year s pr i or t o dat e of del i ver y t o s i t e ar e not accept abl e.

1. 5 MAINTENANCE

1. 5. 1 El ect r i cal Syst ems Dat a

Submi t Oper at i on and Mai nt enance Manual s i n accor dance wi t h Sect i on

01 78 23 OPERATI ON AND MAI NTENANCE DATA.

1. 5. 2 Assembl ed Oper at i on and Mai nt enance Manual s

Assembl e and secur el y bi nd manual s i n dur abl e, har d cover ed, wat er r esi st ant bi nder s. Assembl e and i ndex t he manual s i n t he f ol l owi ng or der wi t h a t abl e of cont ent s:

a. Manuf act ur er ' s O&M i nf or mat i on r equi r ed by t he par agr aph SD- 10, OPERATI ON AND MAI NTENANCE DATA.

b. Cat al og dat a r equi r ed by t he par agr aph SD- 03, PRODUCT DATA.

c. Dr awi ngs r equi r ed by t he par agr aph SD- 02, SHOP DRAWI NGS.

d. Spar e par t s and suppl y l i s t .

e. I nf or mat i on on met er i ng.

1. 6 WARRANTY

Pr ovi de equi pment i t ems suppor t ed by ser vi ce or gani zat i ons t hat ar e r easonabl y conveni ent t o t he equi pment i nst al l at i on i n or der t o r ender sat i sf act or y ser vi ce t o t he equi pment on a r egul ar and emer gency basi s dur i ng t he war r ant y per i od of t he cont r act .

1. 7 SEI SMI C REQUI REMENTS

Pr ovi de sei smi c det ai l s conf or mi ng t o Sect i on 13 48 00, SEI SMI C PROTECTI ON FOR MI SCELLANEOUS EQUI PMENT and t o Sect i on 26 05 48. 00 10, SEI SMI C

PROTECTI ON FOR ELECTRI CAL EQUI PMENT.

PART 2 PRODUCTS

2. 1 MATERI ALS AND EQUI PMENT

As a mi ni mum, meet r equi r ement s of UL, wher e UL st andar ds ar e est abl i shed f or t hose i t ems, and r equi r ement s of NFPA 70 f or al l mat er i al s, equi pment , and devi ces.

Apr i l 2019 Page 8 SECTI ON 26 20 00

2. 2 CONDUI T AND FI TTI NGS

Conf or m t o t he f ol l owi ng:

2. 2. 1 Ri gi d Met al l i c Condui t

2. 2. 1. 1 Ri gi d, Thr eaded Zi nc- Coat ed St eel Condui t

ANSI C80. 1, UL 6.

2. 2. 1. 2 Ri gi d Al umi num Condui t

ANSI C80. 5, UL 6A.

2. 2. 2 Ri gi d Nonmet al l i c Condui t

PVC Type EPC- 40, and EPC- 80 i n accor dance wi t h NEMA TC 2, UL 651, or f i ber gl ass condui t , i n accor dance wi t h NEMA TC 14.

2. 2. 3 I nt er medi at e Met al Condui t ( I MC)

UL 1242, z i nc- coat ed st eel onl y.

2. 2. 4 El ect r i cal , Zi nc- Coat ed St eel Met al l i c Tubi ng ( EMT)

UL 797, ANSI C80. 3.

2. 2. 5 Pl ast i c- Coat ed Ri gi d St eel and I MC Condui t

NEMA RN 1, Type 40( 40 mi l s t hi ck) .

2. 2. 6 Fl exi bl e Met al Condui t

UL 1.

2. 2. 6. 1 Li qui d- Ti ght Fl exi bl e Met al Condui t , St eel

UL 360.

2. 2. 7 Fi t t i ngs f or Met al Condui t , EMT, and Fl exi bl e Met al Condui t

UL 514B. Fer r ous f i t t i ngs: cadmi um- or z i nc- coat ed i n accor dance wi t h

UL 514B.

2. 2. 7. 1 Fi t t i ngs f or Ri gi d Met al Condui t and I MC

Thr eaded- t ype. Spl i t coupl i ngs unaccept abl e.

2. 2. 7. 2 Fi t t i ngs f or EMT

Di e Cast compr essi on t ype.

2. 2. 8 Fi t t i ngs f or Ri gi d Nonmet al l i c Condui t

NEMA TC 3 f or PVC and NEMA TC 14 f or f i ber gl ass, and UL 514B.

2. 2. 9 Li qui d- Ti ght Fl exi bl e Nonmet al l i c Condui t

UL 1660.

Apr i l 2019 Page 9 SECTI ON 26 20 00

2. 3 SURFACE RACEWAY

2. 3. 1 Sur f ace Met al Raceway

UL 5, t wo- pi ece pai nt ed st eel , t ot al l y encl osed, snap- cover t ype. Wi r e al t er nat e r ecept acl es on di f f er ent c i r cui t s.

2. 3. 2 Sur f ace Nonmet al l i c Raceway

UL 5A, nonmet al l i c t ot al l y encl osed, snap- cover t ype. Pr ovi de mul t i pl e out l et - t ype r aceway wi t h gr oundi ng- t ype r ecept acl e wher e i ndi cat ed.

Pr ovi de r ecept acl es as speci f i ed her ei n, spaced a mi ni mum of one ever y 18 i nches. Wi r e al t er nat e r ecept acl es on di f f er ent c i r cui t s.

2. 4 BUSWAY

NEMA BU 1. 1, UL 857. Pr ovi de t he f ol l owi ng:

a. Buses: copper .

b. Busways: vol t age and cont i nuous cur r ent amper age shal l be as i ndi cat ed i n t he cont r act document s. Thr ee- phase bus shal l be t hr ee-or f our - wi r e, as i ndi cat ed i n t he pr oj ect dr awi ngs or st at ement of wor k, and i ncl ude i nt egr al or i nt er nal gr ound bus.

c. Shor t c i r cui t r at i ng: r at i ng shal l be as i ndi cat ed i n t he pr oj ect dr awi ngs or st at ement of wor k.

d. Busway syst ems: sui t abl e f or use i ndoor s.

e. Encl osur es: met al l i c .

f . Har dwar e: pl at ed or ot her wi se pr ot ect ed t o r esi st cor r osi on.

g. Joi nt s: one- bol t t ype wi t h t hr ough- bol t s, whi ch can be checked f or t i ght ness wi t hout deener gi z i ng syst em.

h. Maxi mum hot spot t emper at ur e r i se at any poi nt i n busway at cont i nuous r at ed l oad: do not exceed 55 degr ees C above maxi mum ambi ent t emper at ur e of 40 degr ees C i n any posi t i on.

i . I nt er nal bar r i er s t o pr event movement of super heat ed gases.

j . Coor di nat e pr oper vol t age phasi ng of ent i r e bus duct syst em, f or exampl e wher e busway i nt er f aces wi t h t r ansf or mer s, swi t chgear , swi t chboar ds, mot or cont r ol cent er s, and ot her syst em component s.

2. 4. 1 Feeder Busways

Pr ovi de vent i l at ed, except t hat ver t i cal busways wi t hi n 6 f eet of f l oor s must be unvent i l at ed, l ow- i mpedance busway. Pr ovi de bus bar s f ul l y cover ed wi t h i nsul at i ng mat er i al , except at st abs. Pr ovi de an ent i r el y pol ar i zed busway syst em.

2. 4. 2 Pl ug- I n Busways

Unvent i l at ed t ype. Pr ovi de t he f ol l owi ng:

Apr i l 2019 Page 10 SECTI ON 26 20 00

a. Pl ug- i n uni t s: As i ndi cat ed i n cont r act document s: f usi bl e, handl e- oper at ed, swi t ch t ype, hor sepower - r at ed; c i r cui t br eaker - t ype;

or handl e- oper at ed, swi t ch t ype, equi pped wi t h hi gh i nt er r upt i ng- capaci t y, cur r ent - l i mi t i ng f uses.

b. Bus bar s: cover ed wi t h i nsul at i ng mat er i al t hr oughout , except at j oi nt s and ot her connect i on poi nt s.

c. As i ndi cat ed i n t he cont r act document s, a hook st i ck of sui t abl e l engt h shal l be pr ovi ded f or oper at i ng pl ug- i n uni t s f r om t he f l oor .

2. 5 CABLE TRAYS

NEMA VE 1. Pr ovi de t he f ol l owi ng:

a. Cabl e t r ays: f or m a wi r eway syst em, wi t h a nomi nal dept h as i ndi cat ed i n t he cont r act document s.

b. Cabl e t r ays: const r uct ed of al umi num, copper - f r ee al umi num, or st eel t hat has been zi nc- coat ed af t er f abr i cat i on.

c. Cabl e t r ays: i ncl ude spl i ce and end pl at es, dr opout s, and mi scel l aneous har dwar e.

d. Edges, f i t t i ngs, and har dwar e: f i ni shed f r ee f r om bur r s and shar p edges.

e. Fi t t i ngs: ensur e not l ess t han l oad- car r y i ng abi l i t y of st r ai ght t r ay sect i ons and have manuf act ur er ' s mi ni mum st andar d r adi us.

f . Radi us of bends: as i ndi cat ed.

2. 5. 1 Basket - Type Cabl e Tr ays

Pr ovi de si ze as i ndi cat ed wi t h maxi mum wi r e mesh spaci ng of 2 by 4 i nch.

2. 5. 2 Tr ough- Type Cabl e Tr ays

Pr ovi de si ze as i ndi cat ed.

2. 5. 3 Ladder - Type Cabl e Tr ays

Pr ovi de si ze as i ndi cat ed wi t h maxi mum r ung spaci ng of 9 i nches.

2. 5. 4 Channel - Type Cabl e Tr ays

Pr ovi de si ze as i ndi cat ed. Pr ovi de t r ays wi t h one- pi ece const r uct i on havi ng sl ot s spaced not mor e t han 4 1/ 2 i nches on cent er s.

2. 5. 5 Sol i d Bot t om- Type Cabl e Tr ays

Pr ovi de si ze as i ndi cat ed. Do not pr ovi de sol i d cover s.

2. 5. 6 Cantilever

Cant i l ever - t ype, cent er - hung cabl e t r ays may be pr ovi ded at t he Cont r act or ' s opt i on i n l i eu of ot her cabl e t r ay t ypes speci f i ed.

Apr i l 2019 Page 11 SECTI ON 26 20 00

2. 6 OPEN TELECOMMUNI CATI ONS CABLE SUPPORT

2. 6. 1 Open Top Cabl e Suppor t s

Pr ovi de open t op cabl e suppor t s i n accor dance wi t h UL 2043. Pr ovi de gal vani zed zi nc- coat ed st eel open t op cabl e suppor t s as i ndi cat ed.

2. 6. 2 Cl osed Ri ng Cabl e Suppor t s

Pr ovi de cl osed r i ng cabl e suppor t s i n accor dance wi t h UL 2043. Pr ovi de gal vani zed zi nc- coat ed st eel c l osed r i ng cabl e suppor t s as i ndi cat ed.

2. 7 OUTLET BOXES AND COVERS

UL 514A, cadmi um- or z i nc- coat ed, i f f er r ous met al . UL 514C, i f nonmetallic.

2. 7. 1 Fl oor Out l et Boxes

Pr ovi de t he f ol l owi ng:

a. Boxes: adj ust abl e and concr et e t i ght .

b. Each out l et : consi st i ng of nonmet al l i c or cast - met al body wi t h t hr eaded openi ngs, f or condui t s, adj ust abl e r i ng, and cover pl at e wi t h t hr eaded- pl ug si zed as i ndi cat ed n t he cont r act document s.

c. Tel ecommuni cat i ons out l et s: consi st i ng of f l ush, al umi num or st ai nl ess st eel housi ng wi t h a r ecept acl e as speci f i ed and 3/ 4 i nch t op openi ng.

d. Recept acl e out l et s: consi st i ng of f l ush al umi num or st ai nl ess st eel housi ng wi t h dupl ex- t ype r ecept acl e as speci f i ed her ei n.

e. Pr ovi de gasket s wher e necessar y t o ensur e wat er t i ght i nst al l at i on.

f . Pr ovi de pl ugs wi t h i nst al l at i on i nst r uct i ons t o t he Cont r act i ng Of f i cer f or 5 per cent of out l et boxes f or t he cappi ng of out l et s upon r emoval of ser vi ce f i t t i ngs.

2. 7. 2 Out l et Boxes f or Tel ecommuni cat i ons Syst em

Pr ovi de t he f ol l owi ng:

a. St andar d t ype 4 i nches squar e by 2 1/ 8 i nches deep.

b. Out l et boxes f or wal l - mount ed t el ecommuni cat i ons out l et s: 4 by 2 1/ 8 by 2 1/ 8 i nches deep.

c. Dept h of boxes: l ar ge enough t o al l ow manuf act ur er s ' r ecommended conduct or bend r adi i .

d. Out l et boxes f or f i ber opt i c t el ecommuni cat i on out l et s: i ncl ude a mi ni mum 3/ 8 i nch deep si ngl e or t wo gang pl ast er r i ng as shown and i nst al l ed usi ng a mi ni mum 1 i nch condui t syst em.

e. Out l et boxes f or handi capped t el ecommuni cat i ons st at i on: 4 by 2 1/ 8 by 2 1/ 8 i nches deep.

Apr i l 2019 Page 12 SECTI ON 26 20 00

2. 7. 3 Cl ock Out l et f or Use i n Ot her Than Wi r ed Cl ock Syst em

Pr ovi de t he f ol l owi ng:

a. Out l et box wi t h pl ast i c cover , wher e r equi r ed, and si ngl e r ecept acl e wi t h c l ock out l et pl at e.

b. Recept acl e: r ecessed suf f i c i ent l y wi t hi n box t o al l ow compl et e i nser t i on of st andar d cap, f l ush wi t h pl at e.

c. Sui t abl e c l i p or suppor t f or hangi ng cl ock: secur ed t o t op pl at e.

d. Mat er i al and f i ni sh of pl at e: as speci f i ed i n par agr aph DEVI CE PLATES of t hi s sect i on.

2. 8 CABI NETS, JUNCTI ON BOXES, AND PULL BOXES

Vol ume gr eat er t han 100 cubi c i nches, UL 50, hot - di p, z i nc- coat ed, i f sheet st eel .

2. 9 WI RES AND CABLES

Pr ovi de wi r es and cabl es i n accor dance appl i cabl e r equi r ement s of NFPA 70 and UL f or t ype of i nsul at i on, j acket , and conduct or speci f i ed or i ndi cat ed. Do not use wi r es and cabl es manuf act ur ed mor e t han 12 mont hs pr i or t o dat e of del i ver y t o s i t e.

2. 9. 1 Conductors

Pr ovi de t he f ol l owi ng:

a. Conduct or s i zes and capaci t i es shown ar e based on copper , unl ess i ndi cat ed ot her wi se.

b. Conduct or s No. 8 AWG and l ar ger di amet er : st r anded.

c. Conduct or s No. 10 AWG and smal l er di amet er : st r anded.

d. Conduct or s f or r emot e cont r ol , al ar m, and si gnal c i r cui t s, c l asses 1, 2, and 3: st r anded unl ess speci f i cal l y i ndi cat ed ot her wi se.

e. Al l conduct or s: copper .

2. 9. 1. 1 Mi ni mum Conduct or Si zes

Pr ovi de mi ni mum conduct or s i ze i n accor dance wi t h t he f ol l owi ng:

a. Br anch ci r cui t s: No. 12 AWG.

b. Cl ass 1 r emot e- cont r ol and si gnal c i r cui t s: No. 14 AWG.

c. Cl ass 2 l ow- ener gy, r emot e- cont r ol and si gnal c i r cui t s: No. 16 AWG.

d. Cl ass 3 l ow- ener gy, r emot e- cont r ol , al ar m and si gnal c i r cui t s: No. 22

AWG.

2. 9. 2 Col or Codi ng

Pr ovi de col or codi ng f or ser vi ce, f eeder , br anch, cont r ol , and si gnal i ng

Apr i l 2019 Page 13 SECTI ON 26 20 00 ci r cui t conduct or s.

2. 9. 2. 1 Gr ound and Neut r al Conduct or s

Pr ovi de col or codi ng of gr ound and neut r al conduct or s as f ol l ows:

a. Gr oundi ng conduct or s: Gr een.

b. Neut r al conduct or s: Whi t e.

c. Except i on, wher e neut r al s of mor e t han one syst em ar e i nst al l ed i n same r aceway or box, ot her neut r al s col or codi ng: whi t e wi t h a di f f er ent col or ed ( not gr een) st r i pe f or each.

2. 9. 2. 2 Ungr ounded Conduct or s

Pr ovi de col or codi ng of ungr ounded conduct or s i n di f f er ent vol t age syst ems as f ol l ows:

a. 208/ 120 vol t , t hr ee- phase

( 1) Phase A - bl ack

( 2) Phase B - r ed

( 3) Phase C - bl ue

b. 480/ 277 vol t , t hr ee- phase

( 1) Phase A - br own

( 2) Phase B - or ange

( 3) Phase C - yel l ow

c. 120/ 240 vol t , s i ngl e phase: Bl ack and r ed

2. 9. 3 Insulation

Unl ess speci f i ed or i ndi cat ed ot her wi se or r equi r ed by NFPA 70, pr ovi de power and l i ght i ng wi r es r at ed f or 600- vol t s, Type THWN/ THHN conf or mi ng t o UL 83, except t hat gr oundi ng wi r e may be t ype TW conf or mi ng t o UL 83;

r emot e- cont r ol and si gnal c i r cui t s: Type TW or TF, conf or mi ng t o UL 83.

Wher e l i ght i ng f i x t ur es r equi r e 90- degr ee Cent i gr ade ( C) conduct or s, pr ovi de onl y conduct or s wi t h 90- degr ee C i nsul at i on or bet t er .

2. 9. 4 Bondi ng Conduct or s

ASTM B1, sol i d bar e copper wi r e f or s i zes No. 8 AWG and smal l er di amet er ;

ASTM B8, Cl ass B, st r anded bar e copper wi r e f or s i zes No. 6 AWG and l ar ger diameter.

2. 9. 4. 1 Tel ecommuni cat i ons Bondi ng Backbone ( TBB)

Pr ovi de a copper conduct or TBB i n accor dance wi t h TIA-607 wi t h No. 6 AWG mi ni mum si ze, and si zed at 2 kcmi l per l i near f oot of conduct or l engt h up t o a maxi mum si ze of 3/ 0 AWG.

Apr i l 2019 Page 14 SECTI ON 26 20 00

2. 9. 4. 2 Bondi ng Conduct or f or Tel ecommuni cat i ons

Pr ovi de a copper conduct or Bondi ng Conduct or f or Tel ecommuni cat i ons bet ween t he t el ecommuni cat i ons mai n gr oundi ng busbar ( TMGB) and t he el ect r i cal ser vi ce gr ound i n accor dance wi t h TIA-607 . Si ze t he bondi ng conduct or f or t el ecommuni cat i ons t he same as t he TBB.

2. 9. 5 Ser vi ce Ent r ance Cabl es

Ser vi ce Ent r ance ( SE) and Under gr ound Ser vi ce Ent r ance ( USE) Cabl es, UL 854.

2. 9. 6 Met al - Cl ad Cabl e

UL 1569; NFPA 70, Type MC cabl e.

2. 9. 7 Ar mor ed Cabl e

UL 4; NFPA 70, Type AC cabl e.

2. 9. 8 Cabl e Tr ay Cabl e or Power Li mi t ed Tr ay Cabl e

UL l i s t ed; t ype TC or PLTC.

2. 9. 9 Cor d Set s and Power - Suppl y Cor ds

UL 817.

2. 10 SPLI CES AND TERMI NATI ON COMPONENTS

UL 486A- 486B f or wi r e connect or s and UL 510 f or i nsul at i ng t apes.

Connect or s f or No. 10 AWG and smal l er di amet er wi r es: i nsul at ed, pr essur e- t ype i n accor dance wi t h UL 486A- 486B or UL 486C ( t wi st - on spl i c i ng connect or ) . Pr ovi de sol der l ess t er mi nal l ugs on st r anded conductors.

2. 11 DEVI CE PLATES

Pr ovi de t he f ol l owi ng:

a. UL l i s t ed, one- pi ece devi ce pl at es f or out l et s t o sui t t he devi ces installed.

b. For met al out l et boxes, pl at es on unf i ni shed wal l s: z i nc- coat ed sheet st eel or cast met al havi ng r ound or bevel ed edges.

c. For nonmet al l i c boxes and f i t t i ngs, ot her sui t abl e pl at es may be provided.

d. Pl at es on f i ni shed wal l s ( as i ndi cat ed i n t he cont r act document s) :

nyl on or l exan, mi ni mum 0. 03 i nch wal l t hi ckness and same col or as r ecept acl e or t oggl e swi t ch wi t h whi ch t hey ar e mount ed.

e. Pl at es on f i ni shed wal l s ( as i ndi cat ed i n t he cont r act document s) :

sat i n f i ni sh st ai nl ess st eel or br ushed- f i ni sh al umi num, mi ni mum 0. 03 i nch t hi ck.

f . Scr ews: machi ne- t ype wi t h count er sunk heads i n col or t o mat ch f i ni sh of pl at e.

Apr i l 2019 Page 15 SECTI ON 26 20 00

g. Sect i onal t ype devi ce pl at es ar e not be per mi t t ed.

h. Pl at es i nst al l ed i n wet l ocat i ons: gasket ed and UL l i s t ed f or " wet locations."

2. 12 SWITCHES

2. 12. 1 Toggl e Swi t ches

NEMA WD 1, UL 20, s i ngl e pol e, doubl e pol e, t hr ee- way, or f our - way( as i ndi cat ed i n t he cont r act document s) , t ot al l y encl osed wi t h bodi es of t her mopl ast i c or t her moset pl ast i c and mount i ng st r ap wi t h gr oundi ng scr ew. I ncl ude t he f ol l owi ng:

a. Handl es: i vor y or br own t her mopl ast i c, as i ndi cat ed.

b. Wi r i ng t er mi nal s: scr ew- t ype, s i de- wi r ed.

c. Cont act s: s i l ver - cadmi um and cont act ar m - one- pi ece copper al l oy.

d. Swi t ches: r at ed qui et - t ype ac onl y, 120/ 277 vol t s, wi t h cur r ent r at i ng and number of pol es i ndi cat ed.

Mi ni mum 20 amp r at ed devi ces

2. 12. 2 Swi t ch wi t h Red Pi l ot Handl e

NEMA WD 1. Pr ovi de t he f ol l owi ng:

a. Pi l ot l i ght s t hat ar e i nt egr al l y const r uct ed as a par t of t he swi t ch' s handle.

b. Pi l ot l i ght col or : r ed and i l l umi nat e whenever t he swi t ch i s c l osed or " on" .

c. Pi l ot l i ght ed swi t ch: r at ed 20 amps and 120 vol t s or 277 vol t s as indicated.

d. The ci r cui t ' s neut r al conduct or t o each swi t ch wi t h a pi l ot l i ght .

2. 12. 3 Br eaker s Used as Swi t ches

For 120- and 277- Vol t f l uor escent f i x t ur es, mar k br eaker s " SWD" i n accor dance wi t h UL 489.

2. 12. 4 Di sconnect Swi t ches

NEMA KS 1. Pr ovi de heavy dut y- t ype swi t ches wher e i ndi cat ed, wher e swi t ches ar e r at ed hi gher t han 240 vol t s, and f or doubl e- t hr ow swi t ches.

Ut i l i ze Cl ass R f usehol der s and f uses f or f used swi t ches, unl ess i ndi cat ed ot her wi se. Pr ovi de hor sepower r at ed f or swi t ches ser vi ng as t he mot or - di sconnect means. Pr ovi de swi t ches i n NEMA , encl osur e as i ndi cat ed per NEMA I CS 6.

2. 13 FUSES

NEMA FU 1. Pr ovi de compl et e set of f uses f or each f usi bl e swi t ch, panel and cont r ol cent er . Coor di nat e t i me- cur r ent char act er i st i cs cur ves of f uses ser vi ng mot or s or connect ed i n ser i es wi t h c i r cui t br eaker s f or

Apr i l 2019 Page 16 SECTI ON 26 20 00 pr oper oper at i on. Submi t coor di nat i on dat a f or appr oval . Pr ovi de f uses wi t h a vol t age r at i ng not l ess t han ci r cui t vol t age.

2. 13. 1 Fuseholders

Pr ovi de i n accor dance wi t h UL 4248- 1.

2. 13. 2 Car t r i dge Fuses, Cur r ent Li mi t i ng Type ( Cl ass R)

UL 198M, Cl ass RK- 1 or RK- 5. Pr ovi de onl y Cl ass R associ at ed f usehol der s i n accor dance wi t h UL 4248- 12.

2. 13. 3 Car t r i dge Fuses, Hi gh- I nt er r upt i ng Capaci t y, Cur r ent Li mi t i ng Type ( Cl asses J, L, and CC)

UL 198M, Cl ass J f or zer o t o 600 amper es, Cl ass L f or 601 t o 6, 000 amper es, and Cl ass CC f or zer o t o 30 amper es.

2. 13. 4 Car t r i dge Fuses, Cur r ent Li mi t i ng Type ( Cl ass T)

UL 198M, Cl ass T f or zer o t o 1, 200 amper es, 300 vol t s; and zer o t o 800 amper es, 600 vol t s.

2. 14 RECEPTACLES

Pr ovi de t he f ol l owi ng:

a. UL 498, har d use ( al so desi gnat ed heavy- dut y) , gr oundi ng- t ype.

b. Rat i ngs and conf i gur at i ons: as i ndi cat ed.

c. Bodi es: i vor y or br own ( as i ndi cat ed) as per NEMA WD 1.

d. Face and body: t her mopl ast i c suppor t ed on a met al mount i ng st r ap.

e. Di mensi onal r equi r ement s: per NEMA WD 6.

f . Scr ew- t ype, s i de- wi r ed wi r i ng t er mi nal s or of t he sol der l ess pr essur e t ype havi ng sui t abl e conduct or - r el ease ar r angement .

g. Gr oundi ng pol e connect ed t o mount i ng st r ap.

h. The r ecept acl e: cont ai ni ng t r i pl e- wi pe power cont act s and doubl e or t r i pl e- wi pe gr ound cont act s.

Mi ni mum 20 amp r at ed devi ces

2. 14. 1 Swi t ched Dupl ex Recept acl es

Pr ovi de separ at e t er mi nal s f or each ungr ounded pol e. Top r ecept acl e:

swi t ched when i nst al l ed.

2. 14. 2 Weat her pr oof Recept acl es

Pr ovi de r ecept acl es, UL l i s t ed f or use i n " wet l ocat i ons" . I ncl ude cast met al box wi t h gasket ed, hi nged, l ockabl e and weat her pr oof whi l e- i n- use, di e- cast met al / al umi num cover pl at e.

Apr i l 2019 Page 17 SECTI ON 26 20 00

2. 14. 3 Gr ound- Faul t Ci r cui t I nt er r upt er Recept acl es

UL 943, dupl ex t ype f or mount i ng i n st andar d out l et box. Pr ovi de devi ce capabl e of det ect i ng cur r ent l eak of 6 mi l l i amper es or gr eat er and t r i ppi ng per r equi r ement s of UL 943 f or Cl ass A gr ound- f aul t c i r cui t i nt er r upt er devi ces. Pr ovi de scr ew- t ype, s i de- wi r ed wi r i ng t er mi nal s or pr e- wi r ed ( pi gt ai l ) l eads.

2. 14. 4 Speci al Pur pose Recept acl es

Recept acl es ser vi ng 20 amps ar e speci al pur pose. pr ovi de r ecept acl es i n NEMA conf i gur at i on, r at ed amper es, and vol t s as i ndi cat ed i n t he cont r act document s. Fur ni sh one mat chi ng pl ug wi t h each r ecept acl e ( unl ess i ndi cat ed ot her wi se) .

2. 14. 5 Plugs

Pr ovi de heavy- dut y, r ubber - cover ed t hr ee- , f our - , or f i ve- wi r e cor d of r equi r ed si ze ( as i ndi cat ed i n t he cont r act document s) , i nst al l pl ugs t her eon, and at t ach t o equi pment . Pr ovi de UL l i s t ed pl ugs wi t h r ecept acl es, compl et e wi t h gr oundi ng bl ades. Wher e equi pment i s not avai l abl e, t ur n over pl ugs and cor d assembl i es t o t he Gover nment .

2. 14. 6 Range Recept acl es

NEMA 14- 50 conf i gur at i on, r at ed 50 amper es, 125/ 250 vol t s. Fur ni sh one mat chi ng pl ug wi t h each r ecept acl e.

2. 14. 7 Dr yer Recept acl es

NEMA 14- 30 conf i gur at i on, r at ed 30 amper es, 125/ 250 vol t s. Fur ni sh one mat chi ng pl ug wi t h each r ecept acl e.

2. 14. 8 Tamper - Resi st ant Recept acl es

Pr ovi de dupl ex r ecept acl e wi t h mechani cal s l i di ng shut t er s t hat pr event t he i nser t i on of smal l obj ect s i nt o i t s cont act s l ot s.

2. 15 PANELBOARDS

Pr ovi de panel boar ds i n accor dance wi t h t he f ol l owi ng:

a. UL 67 and UL 50 havi ng a shor t - c i r cui t cur r ent r at i ng as i ndi cat ed.

b. Panel boar ds f or use as ser vi ce di sconnect i ng means: addi t i onal l y conf or m t o UL 869A.

c. Panel boar ds: c i r cui t br eaker - equi pped.

d. Desi gned such t hat i ndi v i dual br eaker s can be r emoved wi t hout di st ur bi ng adj acent uni t s or wi t hout l ooseni ng or r emovi ng suppl ement al i nsul at i on suppl i ed as means of obt ai ni ng cl ear ances as r equi r ed by UL.

e. " Speci f i c br eaker pl acement " i s r equi r ed i n panel boar ds t o mat ch t he br eaker pl acement i ndi cat ed i n t he panel boar d schedul e on t he dr awi ngs.

f . Use of " Subf eed Br eaker s" i s not accept abl e unl ess speci f i cal l y i ndi cat ed ot her wi se.

Apr i l 2019 Page 18 SECTI ON 26 20 00

g. Mai n br eaker : " separ at el y" mount ed " above" or " bel ow" br anch br eaker s.

h. Wher e " space onl y" i s i ndi cat ed, make pr ovi s i ons f or f ut ur e i nst al l at i on of br eaker s.

i . Di r ect or i es: i ndi cat e l oad ser ved by each ci r cui t i n panel boar d.

j . Di r ect or i es: i ndi cat e sour ce of ser vi ce t o panel boar d ( e. g. , Panel PA ser ved f r om Panel MDP) .

k. Pr ovi de new di r ect or i es f or exi st i ng panel s modi f i ed by t hi s pr oj ect as i ndi cat ed.

l . Type di r ect or i es and mount i n hol der behi nd t r anspar ent pr ot ect i ve covering.

m. Panel boar ds: l i s t ed and l abel ed f or t hei r i nt ended use.

n. Panel boar d namepl at es: pr ovi ded i n accor dance wi t h par agr aph FI ELD

FABRI CATED NAMEPLATES.

2. 15. 1 Enclosure

Pr ovi de panel boar d encl osur e i n accor dance wi t h t he f ol l owi ng:

a. UL 50.

b. Cabi net s mount ed out door s or f l ush- mount ed: hot - di pped gal vani zed af t er f abr i cat i on.

c. Cabi net s: pai nt ed i n accor dance wi t h par agr aph PAI NTI NG.

d. Out door cabi net s: NEMA 3R r ai nt i ght wi t h a r emovabl e st eel pl at e 1/ 4 i nch t hi ck i n t he bot t om f or f i el d dr i l l i ng f or condui t connect i ons.

e. Fr ont edges of cabi net s: f or m- f l anged or f i t t ed wi t h st r uct ur al shapes wel ded or r i vet ed t o t he sheet st eel , f or suppor t i ng t he panel boar d f r ont .

f . Al l cabi net s: f abr i cat ed such t hat no par t of any sur f ace on t he f i ni shed cabi net devi at es f r om a t r ue pl ane by mor e t han 1/ 8 i nch.

g. Hol es: pr ovi ded i n t he back of i ndoor sur f ace- mount ed cabi net s, wi t h out si de spacer s and i nsi de st i f f ener s, f or mount i ng t he cabi net s wi t h a 1/ 2 i nch cl ear space bet ween t he back of t he cabi net and t he wal l surface.

h. Fl ush door s: mount ed on hi nges t hat expose onl y t he hi nge r ol l t o v i ew when t he door i s c l osed.

i . Each door : f i t t ed wi t h a combi ned cat ch and l ock, except t hat door s over 24 i nches l ong pr ovi ded wi t h a t hr ee- poi nt l at ch havi ng a knob wi t h a T- handl e, and a cyl i nder l ock.

j . Keys: t wo pr ovi ded wi t h each l ock, wi t h al l l ocks keyed al i ke.

k. Fi ni shed- head cap scr ews: pr ovi ded f or mount i ng t he panel boar d f r ont s

Apr i l 2019 Page 19 SECTI ON 26 20 00 on t he cabi net s.

2. 15. 2 Panel boar d Buses

Suppor t bus bar s on bases i ndependent of c i r cui t br eaker s. Desi gn mai n buses and back pans so t hat br eaker s may be changed wi t hout machi ni ng, dr i l l i ng, or t appi ng. Pr ovi de i sol at ed neut r al bus i n each panel f or connect i on of c i r cui t neut r al conduct or s. Pr ovi de separ at e gr ound bus i dent i f i ed as equi pment gr oundi ng bus per UL 67 f or connect i ng gr oundi ng conduct or s; bond t o st eel cabi net . I n addi t i on t o equi pment gr oundi ng bus, pr ovi de second " i sol at ed" gr ound bus, wher e i ndi cat ed.

2. 15. 2. 1 Panel boar d Neut r al s f or Non- Li near Loads

Pr ovi de i n accor dance wi t h t he f ol l owi ng:

a. UL l i s t ed, wi t h panel boar d t ype speci f i cal l y UL heat r i se t est ed f or use on non- l i near l oads.

b. Panel boar d: heat r i se t est ed i n accor dance wi t h UL 67, except wi t h t he neut r al assembl y i nst al l ed and car r y i ng 200 per cent of t he phase bus cur r ent dur i ng t est i ng.

c. Ver i f i cat i on of t he t est i ng pr ocedur e: pr ovi ded upon r equest .

d. Two neut r al assembl i es par al l el ed t oget her wi t h cabl e i s not acceptable.

e. Namepl at es f or panel boar d r at ed f or use on non- l i near l oads: mar ked " SUI TABLE FOR NON- LI NEAR LOADS" and i n accor dance wi t h par agr aph FI ELD

FABRI CATED NAMEPLATES.

f . Pr ovi de a neut r al l abel wi t h i nst r uct i ons f or wi r i ng t he neut r al of panel boar ds r at ed f or use on non- l i near l oads.

2. 15. 3 Ci r cui t Br eaker s

UL 489, t her mal magnet i c- t ype or sol i d st at e- t ype ( as i ndi cat ed i n t he cont r act document s) havi ng a mi ni mum shor t - c i r cui t cur r ent r at i ng equal t o t he shor t - c i r cui t cur r ent r at i ng of t he panel boar d i n whi ch t he ci r cui t br eaker wi l l be mount ed. Br eaker t er mi nal s: UL l i s t ed as sui t abl e f or t ype of conduct or pr ovi ded. Wher e i ndi cat ed on t he dr awi ngs, pr ovi de ci r cui t br eaker s wi t h shunt t r i p devi ces. Ser i es r at ed ci r cui t br eaker s and pl ug- i n c i r cui t br eaker s ar e unaccept abl e.

2. 15. 3. 1 Mul t i pol e Br eaker s

Pr ovi de common t r i p- t ype wi t h s i ngl e oper at i ng handl e. Desi gn br eaker such t hat over l oad i n one pol e aut omat i cal l y causes al l pol es t o open.

Mai nt ai n phase sequence t hr oughout each panel so t hat any t hr ee adj acent br eaker pol es ar e connect ed t o Phases A, B, and C, r espect i vel y.

2. 15. 3. 2 Ci r cui t Br eaker Wi t h Gr ound- Faul t Ci r cui t I nt er r upt er

UL 943 and NFPA 70. Pr ovi de wi t h " push- t o- t est " but t on, v i s i bl e i ndi cat i on of t r i pped condi t i on, and abi l i t y t o det ect and t r i p on cur r ent i mbal ance of 6 mi l l i amper es or gr eat er per r equi r ement s of UL 943 f or Cl ass A gr ound- f aul t c i r cui t i nt er r upt er .

Apr i l 2019 Page 20 SECTI ON 26 20 00

2. 15. 3. 3 Ci r cui t Br eaker s f or HVAC Equi pment

Pr ovi de ci r cui t br eaker s f or HVAC equi pment havi ng mot or s ( gr oup or i ndi v i dual ) mar ked f or use wi t h HACR t ype and UL l i s t ed as HACR t ype.

2. 15. 3. 4 Ar c- Faul t Ci r cui t I nt er r upt er s

UL 489, UL 1699 and NFPA 70. Mol ded case ci r cui t br eaker s: r at ed as i ndi cat ed. Two pol e ar c- f aul t c i r cui t - i nt er r upt er s: r at ed 120/ 240 vol t s. The pr ovi s i on of ( t wo) one pol e c i r cui t br eaker s f or shar ed neut r al c i r cui t s i n l i eu of ( one) t wo pol e c i r cui t br eaker i s unaccept abl e.

Pr ovi de wi t h " push- t o- t est " but t on.

2. 16 LOAD CENTERS FOR HOUSI NG UNI TS

Pr ovi de si ngl e- phase panel boar ds f or housi ng uni t s on t hi s pr oj ect i n accor dance wi t h t he f ol l owi ng:

a. Load cent er t ype, c i r cui t br eaker equi pped, conf or mi ng t o UL 67 and

UL 50.

b. Panel boar ds ser i es shor t - c i r cui t cur r ent r at i ng: 22, 000 amper es symmet r i cal mi ni mum f or t he mai n br eaker and t he br anch br eaker s.

c. Panel boar ds f or use as ser vi ce di sconnect i ng means: addi t i onal l y conf or m t o UL 869A.

d. Desi gned such t hat i ndi v i dual br eaker s can be r emoved wi t hout di st ur bi ng adj acent uni t s or wi t hout l ooseni ng or r emovi ng suppl ement al i nsul at i on suppl i ed as means of obt ai ni ng cl ear ances as r equi r ed by UL.

e. " Speci f i c br eaker pl acement " i s r equi r ed i n panel boar ds t o mat ch t he br eaker pl acement i ndi cat ed i n t he panel boar d schedul e on t he dr awi ngs.

f . Wher e " space onl y" i s i ndi cat ed, make pr ovi s i ons f or f ut ur e i nst al l at i on of br eaker s.

g. Pr ovi de cover wi t h l at chi ng door .

h. Di r ect or i es: i ndi cat e l oad ser ved by each ci r cui t i n panel boar d.

i . Di r ect or i es: i ndi cat e sour ce of ser vi ce t o panel boar d ( e. g. , Panel PA ser ved f r om panel MDP) .

j . Type di r ect or i es and mount behi nd i n hol der wi t h t r anspar ent pr ot ect i ve cover i ng on i nsi de of panel door .

2. 16. 1 Panel boar d Buses

Suppor t bus bar s on bases i ndependent of c i r cui t br eaker s. Desi gn mai n buses and back pans so t hat br eaker s may be changed wi t hout machi ni ng, dr i l l i ng, or t appi ng. Pr ovi de copper or al umi num bus bar s, ei t her t i n pl at ed or s i l ver pl at ed. Pr ovi de i sol at ed neut r al bus i n each panel f or connect i on of c i r cui t neut r al conduct or s. Pr ovi de separ at e gr ound bus i dent i f i ed as equi pment gr oundi ng bus per UL 67 f or connect i ng gr oundi ng conduct or s; bond t o st eel cabi net .

Apr i l 2019 Page 21 SECTI ON 26 20 00

2. 16. 2 Ci r cui t Br eaker s

UL 489 t her mal magnet i c t ype havi ng a mi ni mum shor t - c i r cui t cur r ent r at i ng equal t o t he shor t - c i r cui t cur r ent r at i ng of t he panel boar d i n whi ch t he ci r cui t br eaker wi l l be mount ed. Br eaker t er mi nal s: UL l i s t ed as sui t abl e f or t ype of conduct or pr ovi ded. Hal f - s i ze and t andem br eaker s ar e not accept abl e. Pr ovi de swi t ch dut y r at ed 15 and 20 amper e br eaker s.

Br eaker s must not r equi r e use of panel t r i m t o secur e t hem t o t he bus.

2. 16. 2. 1 Mul t i pol e Br eaker s

Pr ovi de common t r i p- t ype wi t h s i ngl e oper at i ng handl e. Desi gn br eaker such t hat over l oad i n one pol e aut omat i cal l y causes al l pol es t o open.

Mai nt ai n phase sequence t hr oughout each panel so t hat any t wo adj acent br eaker pol es ar e connect ed t o Phases A and B r espect i vel y.

2. 16. 2. 2 Ar c- Faul t Ci r cui t - I nt er r upt er s

UL 489, UL 1699 and NFPA 70. Mol ded case ci r cui t br eaker s: r at ed as i ndi cat ed. Two pol e ar c- f aul t c i r cui t - i nt er r upt er s: r at ed 120/ 240 vol t s. The pr ovi s i on of ( t wo) one pol e c i r cui t br eaker s f or shar ed neut r al c i r cui t s i n l i eu of ( one) t wo pol e c i r cui t br eaker i s unaccept abl e.

Pr ovi de wi t h " push- t o- t est " but t on.

2. 17 ENCLOSED CI RCUI T BREAKERS

UL 489. I ndi v i dual mol ded case ci r cui t br eaker s wi t h vol t age and cont i nuous cur r ent r at i ngs, number of pol es, over l oad t r i p set t i ng, and shor t c i r cui t cur r ent i nt er r upt i ng r at i ng as i ndi cat ed. Encl osur e t ype as i ndi cat ed. Pr ovi de sol i d neut r al .

2. 18 TRANSFORMERS

Pr ovi de t r ansf or mer s i n accor dance wi t h t he f ol l owi ng:

a. NEMA ST 20, gener al pur pose, dr y- t ype, sel f - cool ed, vent i l at ed.

b. Pr ovi de t r ansf or mer s i n NEMA encl osur e sui t abl e t o t he envi r onment , or as i ndi cat ed i n t he cont r act document s.

c. Tr ansf or mer i nsul at i on syst em:

( 1) 220 degr ees C i nsul at i on syst em f or t r ansf or mer s 15 kVA and gr eat er , wi t h t emper at ur e r i se not exceedi ng 115 degr ees C under f ul l - r at ed l oad i n maxi mum ambi ent of 40 degr ees C.

( 2) 180 degr ees C i nsul at i on f or t r ansf or mer s r at ed 10 kVA and l ess, wi t h t emper at ur e r i se not exceedi ng 115 degr ees C under f ul l - r at ed l oad i n maxi mum ambi ent of 40 degr ees C.

e. Tr ansf or mer of 115 degr ees C t emper at ur e r i se: capabl e of car r y i ng cont i nuousl y 115 per cent of namepl at e kVA wi t hout exceedi ng i nsul at i on rating.

g. Tr ansf or mer s: qui et t ype wi t h maxi mum sound l evel at l east 3 deci bel s l ess t han NEMA st andar d l evel f or t r ansf or mer r at i ngs i ndi cat ed.

Apr i l 2019 Page 22 SECTI ON 26 20 00

2. 18. 1 Speci f i ed Tr ansf or mer Ef f i c i ency

Tr ansf or mer s, i ndi cat ed and speci f i ed wi t h: 480V pr i mar y, 115 degr ees C t emper at ur e r i se, kVA r at i ngs of 37. 5 t o 100 f or s i ngl e phase or 30 t o 500 f or t hr ee phase, ener gy ef f i c i ent t ype. Mi ni mum ef f i c i ency, based on f act or y t est r esul t s: not be l ess t han NEMA Cl ass 1 ef f i c i ency as def i ned by NEMA TP 1.

2. 18. 2 Tr ansf or mer s Wi t h Non- Li near Loads

Pr ovi de t r ansf or mer s f or non- l i near l oads i n accor dance wi t h t he f ol l owi ng:

a. Tr ansf or mer i nsul at i on: UL r ecogni zed 220 degr ees C syst em. Nei t her t he pr i mar y nor t he secondar y t emper at ur e i s al l owed t o exceed 220 degr ees C at any poi nt i n t he coi l s whi l e car r y i ng t hei r f ul l r at i ng of non- si nusoi dal l oad.

b. Tr ansf or mer s ar e t o be UL l i s t ed and l abel ed f or K- Fact or r at i ng as i ndi cat ed i n accor dance wi t h UL 1561.

c. Tr ansf or mer s eval uat ed by t he UL K- Fact or eval uat i on: l i s t ed f or 115 degr ees C aver age t emper at ur e r i se onl y.

d. Tr ansf or mer s wi t h K- Fact or r at i ngs wi t h t emper at ur e r i se of 150 degr ees C r i se ar e not accept abl e.

e. K- Fact or r at ed t r ansf or mer s i mpedance: al l owed r ange of 3 per cent t o 5 per cent , wi t h a mi ni mum r eact ance of 2 per cent t o pr event excessi ve neut r al cur r ent when suppl y i ng l oads wi t h l ar ge amount s of t hi r d harmonic.

2. 19 MOTORS

Pr ovi de mot or s i n accor dance wi t h t he f ol l owi ng:

a. NEMA MG 1.

b. Her met i c- t ype seal ed mot or compr essor s: Al so compl y wi t h UL 984.

c. Pr ovi de t he si ze i n t er ms of HP, or kVA, or f ul l - l oad cur r ent , or a combi nat i on of t hese char act er i st i cs, and ot her char act er i st i cs, of each mot or as i ndi cat ed or speci f i ed.

d. Det er mi ne speci f i c mot or char act er i st i cs t o ensur e pr ovi s i on of cor r ect l y s i zed st ar t er s and over l oad heat er s.

e. Rat e mot or s f or oper at i on on 208- vol t , 3- phase ci r cui t s wi t h a t er mi nal vol t age r at i ng of 200 vol t s, and t hose f or oper at i on on 480- vol t , 3- phase ci r cui t s wi t h a t er mi nal vol t age r at i ng of 460 vol t s.

f . Use mot or s desi gned t o oper at e at f ul l capaci t y wi t h vol t age var i at i on of pl us or mi nus 10 per cent of mot or vol t age r at i ng.

g. Unl ess ot her wi se i ndi cat ed, use cont i nuous dut y t ype mot or s i f r at ed 1 HP and above.

h. Wher e f use pr ot ect i on i s speci f i cal l y r ecommended by t he equi pment manuf act ur er , pr ovi de f used swi t ches i n l i eu of non- f used swi t ches

Apr i l 2019 Page 23 SECTI ON 26 20 00 indicated.

2. 19. 1 Hi gh Ef f i c i ency Si ngl e- Phase Mot or s

Si ngl e- phase f r act i onal - hor sepower al t er nat i ng- cur r ent mot or s: hi gh ef f i c i ency t ypes cor r espondi ng t o t he appl i cat i ons l i s t ed i n NEMA MG 11.

I n except i on, f or mot or - dr i ven equi pment wi t h a mi ni mum seasonal or over al l ef f i c i ency r at i ng, such as a SEER r at i ng, pr ovi de equi pment wi t h mot or t o meet t he over al l syst em r at i ng i ndi cat ed.

2. 19. 2 Pr emi um Ef f i c i ency Pol yphase Mot or s

Sel ect pol yphase mot or s based on hi gh ef f i c i ency char act er i st i cs r el at i ve t o t ypi cal char act er i st i cs and appl i cat i ons as l i s t ed i n NEMA MG 10. I n addi t i on, cont i nuous r at ed, pol yphase squi r r el - cage medi um i nduct i on mot or s must meet t he r equi r ement s f or pr emi um ef f i c i ency el ect r i c mot or s i n accor dance wi t h NEMA MG 1, i ncl udi ng t he NEMA f ul l l oad ef f i c i ency r at i ngs. I n except i on, f or mot or - dr i ven equi pment wi t h a mi ni mum seasonal or over al l ef f i c i ency r at i ng, such as a SEER r at i ng, pr ovi de equi pment wi t h mot or t o meet t he over al l syst em r at i ng i ndi cat ed.

2. 19. 3 Mot or Si zes

Pr ovi de si ze f or dut y t o be per f or med, not exceedi ng t he f ul l - l oad namepl at e cur r ent r at i ng when dr i ven equi pment i s oper at ed at speci f i ed capaci t y under most sever e condi t i ons l i kel y t o be encount er ed. When mot or s i ze pr ovi ded di f f er s f r om si ze i ndi cat ed or speci f i ed, make adj ust ment s t o wi r i ng, di sconnect devi ces, and br anch ci r cui t pr ot ect i on t o accommodat e equi pment act ual l y pr ovi ded.